ECB Priority IV

1. General information

Hot Gas Bypass Valve (HGBV)


SETTING
ECB Number : CTSC 0042
Priority : IV
Applicable to : F5-130 (AII)
FX5-300 and FX9N-270N (AII), FX17-22 (AIF)
FX HT15-60 (AII)
FD5-95 and FD100-300VSD, FD310-1010 and FD310-510 VSD / FD760-1010 VSD
(AIF)
ID6-370+ (AII), ID365-525 (AIF)
PGC : -
Responsible person : Filippo Faccio

2. Document overview
This document describes the following:
1. General information .................................................................................................................................................. 1
2. Document overview .................................................................................................................................................. 1
3. Safety first ................................................................................................................................................................ 2
4. Document Information and History ........................................................................................................................... 3
5. Subject ..................................................................................................................................................................... 3
6. Reason for this ECB ................................................................................................................................................. 3
7. Application ................................................................................................................................................................ 3
7.1. In case of dryers with ONE Hot gas By-pass Valve ........................................................................................... 4
7.2. In case of dryers with TWO Hot gas By-pass Valves......................................................................................... 5
7.2.1. Both HGBV in parallel ........................................................................................................................................ 5
7.2.2. One HGBV with solenoid valve .......................................................................................................................... 5
8. Required parts .......................................................................................................................................................... 7
9. Planning ordering parts at ASC ................................................................................................................................ 7
10. Reimbursement criteria ............................................................................................................................................ 7
11. Reporting .................................................................................................................................................................. 7
12. Safety precautions .................................................................................................................................................... 7

28/01//2022
CTSC 0042 - FF Page 1 of 7
3. Safety first

Identify the hazard Evaluate the risk

Take action Start work safely

KNOW THE SAFETY KNOW THE SAFETY


RULES OF YOUR INSTRUCTIONS OF
CUSTOMER YOUR MACHINE

LOCK OUT / TAG OUT


PERSONAL PROTECTION KEEPS YOU SAFE TAKE AWAY THE RISKS

28/01//2022
CTSC 0042 - FF Page 2 of 7
4. Document Information and History
Edition Date Description Author
00 28/01/2022 First Edition Filippo Faccio

5. Subject
This Engineering Change Bulletin (ECB) informs you about the Hot gas Bypass SET UP for the dryers produced by PC
Brendola.

6. Reason for this ECB


This overview will clarify the correct HGBV setting for different dryers.
We strongly recommend verifying this SET UP in case of:

• HGBV REPLACEMENT

• SERVICE on refrigerant circuit

• If at commissioning is after 30min in unload condition at rated temperature of 20°C÷25°C (68°F÷77°F) the PDP
is not according to the value reported in the technical specification available in Business Portal

• Refrigerant circuit ANOMALIES like freezing and overheating.


o Please be aware that PDP values different from expected ones, mostly have an external root cause that
is not related to HGBV itself (i.e. bad ventilation, bad ducting, less refrigerant filling and too high
superheat/discharge temperature).

7. Application
Here a simple procedure to reset the HGBV setting:
• This operation must be done in UNLOAD condition at rated temperature of 20°C÷25°C (68°F÷77°F). For precise
setting the machine must be turned ON for at least 30 minutes. The operator has to remove the closing cap (ref.
1) and to adjust the screw (ref.2)

• Verify the dryer and the refrigerant gas TYPES on unit dataplate:

28/01//2022
CTSC 0042 - FF Page 3 of 7
7.1. In case of dryers with ONE HGBV
This operation must be done in UNLOAD condition at rated temperature of 20°C÷25°C (68°F÷77°F). For precise setting
the machine must be turned ON for at least 30 minutes.

Refr Evap. Temp Evap. Press


Dryer range Comments
gas °C (°F) bar (psi)
1°C ÷ 2°C 2,02bar ÷ 2,13 bar
F5-70 R134a
(33,8°F ÷ 35,6°F) (29,3psi ÷ 30,89psi)

1°C÷2°C 2,35bar ÷ 2,47 bar Interchangeable 1:1 for


F5-70 R513A
(33,8°F ÷ 35,6°F) (34,08psi ÷ 35,82psi) R134a

0.5°C÷1,5°C 7,1bar ÷ 7,36 bar


F90-130 R410A
(32,9°F ÷ 34,7°F) (103psi ÷ 106,75psi)

FX5-50 1°C ÷ 2°C 2,02bar ÷ 2,1 bar


R134a
(old FX1-7) (33,8°F ÷ 35,6°F) (29,3psi ÷ 30,89psi)

FX5-50 1°C÷2°C 2,35bar ÷ 2,4 bar Interchangeable 1:1 for


R513A
(old FX1-7) (33,8°F ÷ 35,6°F) (34,08psi ÷ 35,82psi) R134a

FX60-130 1°C÷2°C 7,2bar ÷ 7,49 bar


R410A
(old FX8-12) (33,8°F ÷ 35,6°F) (104,4psi ÷ 108,6psi)

FX170-300 0,5°C÷1,5°C 7,1bar ÷ 7,36 bar


R410A
(old FX13-16) (32,9°F ÷ 34,7°F) (103psi ÷ 106,7psi)

0,5°C÷1°C 7,1bar ÷ 7,2 bar


FX17-19 R410A
(32,9°F ÷ 33,8°F) (103psi ÷ 104,4psi)

2°C÷3°C 5,38bar ÷ 5,58 bar


FX19.5-22 R404A
(35,6°F ÷ 37,4°F) (78psi ÷ 80,9psi)

2°C÷3°C 4,99bar ÷ 5,19 bar


FX19.5-22 R452A
(35,6°F ÷ 37,4°F) (72,38psi ÷ 75,3psi)

-0,5°C÷0,5°C 2,18bar ÷ 2,29 bar


FX9N-31N R513A
(31,1°F ÷ 32,9°F) (31,6psi ÷ 33,21psi)

-0,5°C÷0,5°C 6,84bar ÷ 7,1 bar


FX41N-270N R410A
(31,1°F ÷ 32,9°F) (99.2psi ÷ 103psi)

1°C ÷ 2°C 2,02bar ÷ 2,13 bar


FX HT15 R134a
(33,8°F ÷ 35,6°F) (29,3psi ÷ 30,89psi)

1°C÷2°C 2,35bar ÷ 2,47 bar Interchangeable 1:1 for


FX HT15 R513A
(33,8°F ÷ 35,6°F) (34,08psi ÷ 35,82psi) R134a

1°C÷2°C 5,18bar ÷ 5,38 bar


FX HT25-60 R404A
(33,8°F ÷ 35,6°F) (75,1psi ÷ 78psi)

ID6 / ID15-21 / ID30-46 and 0,5°C÷1,5°C 1,97bar ÷ 2,08 bar


R134a
FD5-50 (32,9°F ÷ 34,7°F) (28,57psi ÷ 30,17psi)

0,5°C÷1,5°C 2,29bar ÷ 2,41 bar Interchangeable 1:1 for


ID6 / ID15-21 / ID30-46 and FD5-50 R513A
(32,9°F ÷ 34,7°F) (33,21psi ÷ 34,95psi) R134a

ID75-115VSD+ / FD60-95 / ID100- 0,5°C÷1,5°C 7,1bar ÷ 7,36 bar Valid also for old ID73-
R410A
286 / ID180-340 / ID190-370+ (32,9°F ÷ 34,7°F) (103psi ÷ 106,7psi) 96VSD+ / ID/FD95-285

28/01//2022
CTSC 0042 - FF Page 4 of 7
0 °C ÷ 1 °C 6,97bar ÷ 7,23 bar
ID 365 A/W FS R410A
(32 °F ÷ 33,8°F) (101,1psi÷104,86psi)

-0,5°C÷0,5°C 6,84bar ÷ 7,1 bar


FD100-260VSD R410A At rpm=1800
(31,1°F ÷ 32,9°F) (99.2psi ÷ 103psi)

-0,5°C÷0,5°C 6,84bar ÷ 7,1 bar


FD300VSD R410A At rpm=1200
(31,1°F ÷ 32,9°F) (99.2psi ÷ 103psi)

1,5 °C ÷ 2 °C 7,36bar ÷ 7,49 bar


FD310-1010 VSD R410A At rpm=1200
(34,7 °F ÷ 35,56°F) (106,75psi÷108,6psi)

7.2. In case of dryers with TWO HGBV’s

7.2.1.If both HGBV’s in parallel


This operation must be done in UNLOAD condition at rated temperature of 20°C÷25°C (68°F÷77°F). For precise setting
the machine must be turned ON for at least 30 minutes.
Here please follow the procedure:
1) Remove the safety cap from the HGBV’s

Safety CAP

2) Completely open the HGBV’s (screw counter clockwise)

Set VALVE

3) Set the two HGBV’s as per those recommended values turning the screw (screw clockwise, see setting chart):
Evap. Temp Evap. Press
Dryer range Refr gas
°C (°F) bar (psi)
0 °C ÷ 1 °C 6,97bar ÷ 7,23bar
ID440 / ID565 A FS R410A
(32 °F ÷ 33,8°F) (101,1psi÷104,86psi)
0 °C ÷ 1 °C 6,97bar ÷ 7,23bar
ID440 / ID565 W FS R410A
(32 °F ÷ 33,8°F) (101,1psi÷104,86psi)

4) Close with the safety caps

7.2.2.If one HGBV with solenoid valve


This operation must be done in UNLOAD condition at rated temperature of 20°C (68°F). For precise setting the machine
must be turned ON for at least 30 minutes
Here please follow the procedure:

28/01//2022
CTSC 0042 - FF Page 5 of 7
1. Verify the dryer and the refrigerant gas TYPES on unit dataplate;
2. Connect the manometer to the Schrader port to read the evaporating pressure and convert this value to the
evaporating temperature;
3. Remove the PDP temperature sensor by the heat exchanger
4. Set the “HGBV without solenoid” upstream as per those recommended values:

Lowest evaporating Higher evaporating


Dryer range Frequency Temperature Temperature
(when fan switch-off) (when fan switch-on)
50Hz -3,5°C (25,7°F) -1,5°C (29,3°F)
FD310 A FS 40°C
60Hz -3,5°C (25,7°F) -1,5°C (29,3°F)
50Hz -4,5°C (23,9°F) -1,5°C (29,3°F)
FD310 A FS 46°C
60Hz -4,8°C (23,36°F) -1,5°C (29,3°F)
50Hz -3,2°C (26,24°F) -0,5°C (31,1°F)
FD310 A FS 50°C
60Hz -3,9°C (24,98°F) -2,9°C (26,78°F)
50Hz -6,0°C (21,2°F) -3,5°C (25,7°F)
FD310 W FS 50°C
60Hz -4,8°C (23,36°F) -2,8°C (26,96°F)
50Hz -7,5°C (18,5°F) -5,5°C (22,1°F)
FD410 A FS 40°C
60Hz -3,5°C (25,7°F) -1,5°C (29,3°F)
50Hz -4,5°C (23,9°F) -2,0°C (28,4°F)
FD410 A FS 46°C
60Hz -4,5°C (23,9°F) -2,0°C (28,4°F)
50Hz -3,0°C (26,6°F) -0,5°C (31,1°F)
FD410 A FS 50°C
60Hz -3,0°C (26,6°F) -0,5°C (31,1°F)
50Hz -7,0°C (19,4°F) -5,0°C (23°F)
FD410 W FS 50°C
60Hz -7,0°C (19,4°F) -6,0°C (21,2°F)
50Hz -6,5°C (20,3°F) -3,5°C (25,7°F)
FD510 A FS 40°C
60Hz -6,0°C (21,2°F) -3,5°C (25,7°F)
50Hz -4,5°C (23,9°F) -2,0°C (28,4°F)
FD510 A FS 46°C
60Hz -4,5°C (23,9°F) -1,5°C (29,3°F)
50Hz -3,1°C (26,42°F) -0,8°C (30,56°F)
FD510 A FS 50°C
60Hz -3,0°C (26,6°F) -0,5°C (31,1°F)
50Hz -7,0°C (19,4°F) -5,0°C (23°F)
FD510 W FS 50°C
60Hz -6,5°C (20,3°F) -4,5°C (23,9°F)
50Hz -7,6°C (18,32°F) -5,7°C (21,74°F)
FD610 A FS
60Hz -6,8°C (19,76°F) -4,4°C (24,08°F)
50Hz -8,4°C (16,88°F) -6,6°C (20,12°F)
FD610 W FS
60Hz -10,3°C (14°F) -4,7°C (23,54°F)
50Hz -7,0°C (19,4°F) -5,0°C (23°F)
FD760 A FS
60Hz -7,0°C (19,4°F) -5,6°C (21,92°F)
50Hz -5,1°C (22,82°F) -2,7°C (27,14°F)
FD760 W FS
60Hz -12,1°C (10,4°F) -10,8°C (14°F)
50Hz -9,0°C (15,8°F) -7,0°C (19,4°F)
FD870 A FS
60Hz -9,5°C (14,9°F) -6,8°C (19,76°F)
50Hz -9,0°C (15,8°F) -7,0°C (19,4°F)
FD870 W FS
60Hz -11,2°C (12,2°F) -9,4°C (15,08°F)
50Hz -4,5°C (23,9°F) -2,0°C (28,4°F)
FD1010 A FS
60Hz -4,0°C (24,8°F) -1,0°C (30,2°F)
50Hz -9,7°C (14,54°F) -8,7°C (16,34°F)
FD1010 W FS
60Hz -11,7°C (12,2°F) -9,8°C (14,36°F)

28/01//2022
CTSC 0042 - FF Page 6 of 7
5. Reconnect the PDP temperature sensor using silicon grease that must be a dielectric, heat dissipater. PC
Brendola suggests:
o Compound Greasil MS12
6. Use a Service-magnet solenoid to open the solenoid valve to set the second “HGBV with solenoid valve” as
per those recommended values:

Lowest evaporating Temperature Highest evaporating Temperature


(when fan switch-off) (when fan switch-on)

1,5 °C (34,7 °F) 2 °C (35,56 °F)

8. Required parts
N.A.

9. Planning ordering parts at ASC


N.A.

10. Reimbursement criteria


N.A.

11. Reporting
N.A.

12. Safety precautions


The operator must employ safe working practices and observe all related local work safety requirements and regulations.
• Maintenance must only be performed by authorized, trained and specialized personnel.
• Before maintenance, repair work, adjustment or any other non-routine checks, stop the compressor, switch off the
voltage, press the emergency button and depressurize the compressor. In addition, the power insolating switch
must be opened and locked.
• Use only the correct tools for maintenance and repair work.
• All maintenance work shall only be undertaken when the machine has cooled down.
• A warning sign bearing a legend such as ‘Work in progress; do not start’ shall be attached to the starting
equipment.
• Persons switching on remotely controlled machines shall take adequate precautions to ensure that there is no
one checking or working on the machine. To this end, a suitable notice shall be affixed to the remote start
equipment.
• Close the compressor air outlet valve before connecting or disconnecting a pipe.
• Before removing any pressurized component, effectively isolate the machine from all sources of pressure and
relieve the entire system of pressure.
• Scrupulously observe cleanliness during maintenance and repair. Keep dirt away by covering the parts and
exposed openings with a clean cloth, paper or tape.
• Make sure that no tools, loose parts or rags are left in or on the machine.
• All regulating and safety devices shall be maintained with due care to ensure that they function properly. They
may not be put out of action.
• Always wear the following personal protective equipment: Work clothing, safety shoes, safety goggles, ear
protection and safety gloves when there is a cutting risk or a risk for a head injury.

28/01//2022
CTSC 0042 - FF Page 7 of 7