You are on page 1of 2

CS4000 System boards

IPLC, Loop Board


Part no. 462013

System: Salwico CS4000 fire alarm

Description Data
The printed circuit board IPLC is a system module in the Nominal voltage 24 VDC
Salwico CS4000 fire alarm system. Working voltage 19-30 VDC
Working current 240 mA
The IPLC Board is a connection board for 1 analogue Cable terminals 2.5 mm2
addressable detector loop. The analogue addressable loop Temperature range +5°C to +55°C
can have up to 50 IDA/NOSE loop units. IPLC Weight ~300 g
communicates with the CS4000 central using Ethernet Dimensions (bxhxd) 137x128x50
and UDP protocol.
For more information about how to connect the different
CS4000 system boards together, please refer to the
CS4000 Service & Maintenance manual.

Address switch Example address switch setting:


The 8-pole DIP switch is used to set the MAC-address for O
IPLC. Each board in a system has its own unique address. N

The address no. can be set from 1 to 255. 1 2 3 4 5 6 7 8


IP address is received from DHCP server.
1 2 4 8 16 32 64 128

Board adress no.

1+4+64=69

Block diagram

DHCP server IPLC


CS4000
Base Board
Ethernet / UDP
Network switch IPLC

IPLC

Specifications may be subject to change for improvement without prior notice Data sheet no: 462013 IPLC 06 1 E
Page 1 of 2
Consilium Marine AB
ÇConsilium P.O. Box 8763, SE-402 76 Göteborg
Phone +46 31 7107700 Fax +46 31 7107800
www.consilium.se
CS4000 System boards
IPLC, Loop Board
Component layout

Jumpers Switches
JP1 – JP6 Spare SW1 Address switch
SW2 Reset switch
Connectors
LEDs
P1 Power supply and loop connection.
P2 Internal use D3 Ethernet, TX data, Green.
P3 Ethernet connector D4 Ethernet, RX data, Green.
P4 RS485 D11 Loop communication indication, Green
P5 Outputs D13 Not used. Green.
D14 TX RS485. Green.
D17 RX RS485. Green.
D26 Power indication. Green.

Terminals
DESCRIPTION CONNECTOR TERMINAL FUNCTION DATA
1 CHASSIE
Power supply 2 + 24VDC
3 -
P1 4 +
Fire loop 1 A side
5 - 35VDC,
6 + max 300mA/loop
Fire loop 1 B side
7 -
11 a
Interface output P4 12 b RS485, isolated
13 GND
21
Fire. Normally inactive Open collector,
22
Outputs P5 transistor output
23 max 50mA
Fault. Normally active.
24
Specifications may be subject to change for improvement without prior notice Data sheet no: 462013 IPLC 06 1 E
Page 2 of 2
Consilium Marine AB
ÇConsilium P.O. Box 8763, SE-402 76 Göteborg
Phone +46 31 7107700 Fax +46 31 7107800
www.consilium.se