You are on page 1of 4

DATA SHEET

Rectifier Board for CS4000 Part no: 921767-0 Rev. no: 0


part of Item 201

Type: RB Item no: 202 Page 1 of 4

Description
The printed circuit board RB, Rectifier
Board, is a system module in the Salwico
CS4000 fire alarm system.
The Rectifier Board together with the
transformer forms the power supply unit for
the CS4000 central, including battery-
charging function for the internal batteries.
The transformer is adjustable for both
115VAC and 230VAC power supply.
For more information about how to connect
the different CS4000 system boards
together, please refer to the CS4000 Service
& Maintenance manual.

Data
Input voltage: 115VAC or 230 VAC
Output voltage: 27 VDC
Working current: 70 mA
Max output: 27.5 VDC, 4 A
2
Cable terminals P1-P2: 4 mm
2
Cable terminals P5-P7: 2.5 mm
Temperature range: +5°C to +55°C
Weight RB: ~475 g
Dimensions RB:
Weight transformer:
175x100x72 mm
~1850 g
Address switch
Dimensions transformer: Ø110, height 43 mm
The 8-pole DIP switch is used to
Charge capacity: 1.6A
set the address for RB Rectifier
(battery size 2.3-18Ah)
Board. Each board in a system
has its own unique address.
For more data, see under Terminals.
The address no. can be set from
1 to 255.

This documentation (datasheets, drawings, descriptions, specifications etc.) is the intellectual property of NOVENCO Fire Fighting A/S and
must neither be passed on to any person or company not authorized by NOVENCO Fire Fighting A/S to receive it, nor be copied or otherwise
made use of by anybody without NOVENCO Fire Fighting A/S’s written permission.

Novenco Fire Fighting A/S · Industrivej 22 · 4700 Naestved · Denmark · Tel. +45 70 12 07 00 · Fax +45 55 75 65 41 · VAT No. DK 29 42 19 51
DATA SHEET
Rectifier Board for CS4000 Part no: 921767-0 Rev. no: 0
part of Item 201

Type: RB Item no: 202 Page 2 of 4

Block diagram

Component & Terminal


layout

Jumpers LEDs
JP1 D7 Relay 1. Green.
Programming mode. Fitted during D10 System fault. Yellow.
programming of RB. Move to JP4 when D11 Relay 2. Green.
programming is completed. D23 TX data port 1. Green.
JP2-JP3 D24 RX data port 1. Green.
Not used D27 TX data port 2. Green.
JP4 D28 RX data port 2. Green.
Run mode, fitted during normal D31 Power to board OK. Green.
operation. Move to JP1 during D33 Battery fault. Yellow.
programming of RB. D34 Forced battery charge. Green.
JP5 D35 Battery circuit OK. Green.
Battery charging current. Fitted if D36 Indicates battery test. Yellow.
batteries larger than 10 Ah is connected.

This documentation (datasheets, drawings, descriptions, specifications etc.) is the intellectual property of NOVENCO Fire Fighting A/S and
must neither be passed on to any person or company not authorized by NOVENCO Fire Fighting A/S to receive it, nor be copied or otherwise
made use of by anybody without NOVENCO Fire Fighting A/S’s written permission.

Novenco Fire Fighting A/S · Industrivej 22 · 4700 Naestved · Denmark · Tel. +45 70 12 07 00 · Fax +45 55 75 65 41 · VAT No. DK 29 42 19 51
DATA SHEET
Rectifier Board for CS4000 Part no: 921767-0 Rev. no: 0
part of Item 201

Type: RB Item no: 202 Page 3 of 4

Connectors Transformer connection


P1 Power in- and output.
P2 To transformer
P3 Internal system channel A to LB3/ZB.
P4 Internal system channel A to Base
Boards + separate power to bell outputs
on Base Board.
P5 From transformer.
P6 Programmable relay output 1.
P7 Programmable relay output 2.
P8 Batteries
P9 Contact for download of software to
RB.
P12 Internal system channel B

Fuses Change over function


F3-F4 3.15AF To transformer The rectifier board has an in-built change
F5-F6 3.15AF To external over function between the two
230VAC 115/230VAC inputs (main and emergency).
F8-F9 4 AF Battery If there is only one 115/230VAC power
F10-F11 6 AF From supply available, it shall always be
Transformer connected to “emergency”.
Note: The rectifier board will not start up if
Fuse type: 5 x 20 mm 115/230VAC is connected to “main” unless
the batteries are connected first.

This documentation (datasheets, drawings, descriptions, specifications etc.) is the intellectual property of NOVENCO Fire Fighting A/S and
must neither be passed on to any person or company not authorized by NOVENCO Fire Fighting A/S to receive it, nor be copied or otherwise
made use of by anybody without NOVENCO Fire Fighting A/S’s written permission.

Novenco Fire Fighting A/S · Industrivej 22 · 4700 Naestved · Denmark · Tel. +45 70 12 07 00 · Fax +45 55 75 65 41 · VAT No. DK 29 42 19 51
DATA SHEET
Rectifier Board for CS4000 Part no: 921767-0 Rev. no: 0
part of Item 201

Type: RB Item no: 202 Page 4 of 4

Terminal data

TERMINAL NO. FUNCTION DATA


DESCRIPTION

1 ~ 24 VAC
From transformer
lmin=0.1A, lmax=5A
2 ~
3 a RS485
Internal system channel
A 4 b
11 NC Max 230 VAC, 5A

Programmable output 1 12 C
14 NO
21 NC

Programmable output 2 22 C
24 NO
101 ~ 115 VAC/230 VAC
+10%/-15%, 50-60 Hz
Power in, main 102 ~
103 ~ 115 VAC/230 VAC
Power in, emergency +10%/-15%, 50-60 Hz
104 ~
105 ~ Output 115VAC / 230 VDC
Power out max=1A
106 ~
107 ~ Output 115VAC/230 VDC
lmin= 1.0A
To transformer 108
109 ~
P8 + 24 VDC. Max changing
Battery current to battery is 1.6A
P8 -
P3 + Vmin=18.5VDC
Power to LB3/ZB (c.i.e) Vmax=27.5VDC
P3 - Vripple=200mV RMS
P4 + Lmax=4A (total P3+P4)
Power to base board
P4 -
(c.i.e)

 If only one 115/220VAC power supply is provided, it shall be connected to “power in, emergency”.
 When replacing the batteries, make sure to use batteries with the same specification as the
original.

This documentation (datasheets, drawings, descriptions, specifications etc.) is the intellectual property of NOVENCO Fire Fighting A/S and
must neither be passed on to any person or company not authorized by NOVENCO Fire Fighting A/S to receive it, nor be copied or otherwise
made use of by anybody without NOVENCO Fire Fighting A/S’s written permission.

Novenco Fire Fighting A/S · Industrivej 22 · 4700 Naestved · Denmark · Tel. +45 70 12 07 00 · Fax +45 55 75 65 41 · VAT No. DK 29 42 19 51