DIESEL GENERATOR SET

MTU 20V4000 DS3600


3.3 - 11 kV/50 Hz/Prime Power/NEA (ORDE) + Tier 2 Optimized
MTU 20V4000G44F/Water Charge Air Cooling

Optional equipment and finishing shown. Standard may vary.

Product Highlights
//  Benefits //  Performance Assurance Certification (PAC)
- Low fuel consumption - Engine-generator set tested to ISO 8528-5 for transient
- Optimized system integration ability response
- High reliability - 75% load factor
- High availability of power - Verified product design, quality and performance integrity
- Long maintenance intervals - All engine systems are prototype and factory tested

//  MTU Onsite Energy is a single-source supplier //  Complete range of accessories available
- Control panel
//  Support - Power panel
- Global product support offered - Fuel system
- Fuel connections with shut-off valve mounted to base frame
//  Standards - Starting/charging system
- Engine-generator set is designed and manufactured in - Exhaust system
facilities certified to standards ISO 2008:9001 and - Electrical driven radiators
ISO 2004:14001 - Medium and oversized voltage alternators
- Generator set complies to ISO 8528
- Generator meets NEMA MG1, BS5000, ISO, DIN EN and //  Emissions
IEC standards - Tier 2 optimized engine
- NFPA 110 - NEA (ORDE) optimized

//  Power
Rating //  Certifications
- System ratings: 3380 kVA - 3390 kVA - CE certification option
- Accepts rated load in one step per NFPA 110 - Unit certificate acc. to BDEW (German Grid-Code)
- Generator set complies to G3 according to ISO 8528-5 on request
- Generator set exceeds load steps according to ISO 8528-5
2 / //  / MTU 20V4000 DS3300 / 50 Hz / 3.3 - 11 kV

Application data➀
//  Engine //   Liquid Capacity (Lubrication)

Manufacturer MTU Total oil system capacity: l 390


Model 20V4000G44F Engine jacket water capacity: l 260
Type 4-cycle Intercooler coolant capacity: l 50
Arrangement 20V
Displacement: l 95.4 //  
Combustion Air Requirements
Bore: mm 170
Stroke: mm 210 Combustion air volume: m3/s 4.3
Compression ratio 16.4 Max. air intake restriction: mbar 30
Rated speed: rpm 1500
Engine governor ADEC (ECU 9) //  
Cooling/Radiator System
Max power: kWm 2807
Air cleaner Dry Coolant flow rate (HT circuit): m3/h 80
Coolant flow rate (LT circuit): m3/h 44
//   Fuel System Heat rejection to coolant: kW (100/110%) 1010/1140
Heat radiated to charge air cooling: kW (100/110%) 780/890
Maximum fuel lift: m 5 Heat radiated to ambient: kW 105
Total fuel flow: l/min 27 Fan power for electr. radiator (40°C): kW 105

//   Fuel Consumption➁ //  
Exhaust System
l/hr g/kwh
At 100% of power rating: 674 199 Exhaust gas temp. (after engine, max.): °C 550
At 75% of power rating: 523 206 Exhaust gas temp. (before turbocharger): °C 605
At 50% of power rating: 369 218 Exhaust gas volume: m3/s 10.0
Maximum allowable back pressure: mbar 50
Minimum allowable back pressure: mbar –

➀ All data refers only to the engine and is based on ISO standard conditions (25°C and 100m above sea level).
➁ Values referenced are in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml.
All fuel consumption values refer to rated engine power and are approximate values.
3 / //  / MTU 20V4000 DS3300 / 50 Hz / 3.3 - 11 kV

Standard and Optional Features


//  System Ratings (kW/kVA)

Generator model Voltage NEA (ORDE) optimized 40°C/1000m


without radiator
kWel kVA* AMPS
Leroy Somer LSA54.2 XL11 11 kV 2704 3380 177
(Medium volt. Leroy Somer)
Marathon 1040FDH7103 11 kV 2712 3390 178
(Medium volt. marathon)
Leroy Somer LSA54.2 ZL12 11 kV 2704 3380 177
(MV Leroy Somer oversized)
Marathon 1040FDH7105 11 kV 2712 3390 178
(MV marathon oversized)

* cos phi = 0,8

//  Engine

■ 4-Cycle ■ Closed crankcase ventilation ■ Tier 2 optimized engine


■ Standard single stage air filter ■ Governor-electronic isochronous ■ NEA (ORDE) optimized engine
■ Oil drain extension & shut-off valve ■ Common rail fuel injection

//  Generator

■ 4 pole three-phase synchronous ■ Short circuit capability 3xIn for 10sec ■ Leroy Somer medium voltage
generator ■ Winding and bearing RTDs generator
■ Brushless, self-excited, self-regulating, (without monitoring)  Marathon medium voltage generator
self-ventilated ■ Excitation by AREP + PMI  Oversized generator
■ Digital voltage regulator ■ Mounting of CT´s: 3x 2 core CT´s
■ Anti condensation heater ■ Winding pitch: 5/6 winding
■ Stator winding Y-connected, ■ Voltage setpoint adjustment ± 5%
accessible neutral (brought out) ■ Meets NEMA MG-1, BS 5000,
■ Protection IP23 IEC 60034-1, VDE 0530,
■ Insulation class H, utilization acc. to H DIN EN 12601, AS1359 and ISO 8528
■ Radio suppression EN55011, requirements
group 1, cl. B

//  Cooling System

■ Jacket water pump  Electrical driven front-end cooler


■ Thermostat(s)  Jacket water heater
■ Water charge air cooling  Pulley for fan drive

■ Represents standard features  Represents optional features


4 / //  / MTU 20V4000 DS3300 / 50 Hz / 3.3 - 11 kV

Standard and Optional Features, continuation


//  Control Panel

■ Pre-wired control cabinet for easy  Basler controller  Remote annunciator


application of customized controller  Deif controller  Daytank control
(V1+) ■ Complete system metering  Generator winding temperature
 Island operation (V2) ■ Digital metering and bearing temperature monitoring
 Automatic mains failure operation ■ Engine parameters  Modbus TCP-IP
with ATS (V3a) ■ Generator Protection Functions
 Automatic mains failure operation ■ Engine protection
incl. control of generator and mains ■ SAE J1939 engine ECU
breaker (V3b) communications
 Island parallel operation of multiple ■ Parametrization software
gensets (V4) ■ Multilingual capability
 Automatic mains failure operation ■ Multiple programmable contact inputs
with short (< 10s) mains parallel ■ Multiple contact outputs
overlap synchronization (V5) ■ Event recording
 Mains parallel operation of ■ IP 54 front panel rating with
a single genset (V6) integrated gasket
 Mains parallel operation of
multiple gensets (V7)

//  Power Panel

 Available in 600x600 mm  Supply for anti condensation heating


 Phase monitoring relay 230V/400V  Plug socket cabinet for 230V
 Supply for battery charger compatible Euro/USA
 Supply for jacket water heater

//  Fuel System

■ Flexible fuel connectors mounted to  Switchable fuel filter with  Fuel cooler integrated into
base frame water separator cooling equipment
 Fuel filter with water separator  Switchable fuel filter with
 Fuel filter with water separator water separator heavy-duty
heavy-duty  Separate fuel cooler

//  Starting/Charging System

■ 24V starter  Starter batteries, cables, rack,  Battery charger


disconnect switch  Redundant starter 2x 15kW

■ Represents standard features  Represents optional features


5 / //  / MTU 20V4000 DS3300 / 50 Hz / 3.3 - 11 kV

Standard and Optional Features, continuation


//  Mounting System

■ Welded base frame ■ Resilient engine and generator ■ Modular base frame design
mounting

//  Exhaust System

■ Exhaust bellows with connection  Exhaust silencer with 30 dB(A) sound  Y-connection-pipe
flange attenuation
 Exhaust silencer with 10 dB(A) sound  Exhaust silencer with 40 dB(A) sound
attenuation attenuation

■ Represents standard features  Represents optional features


6 / //  / MTU 20V4000 DS3300 / 50 Hz / 3.3 - 11 kV

Weights and dimensions

Drawing above for illustration purposes only, based an standard open power 11 kV engine-generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.

System Dimensions (L x W x H) Weight (dry/less tank)


Open Power Unit (OPU) 6249 x 1887 x 2412 mm 18420 kg
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific engine-generator set.

Sound data
//  Consult your local MTU Onsite Energy distributor for sound data.

Emissions data
//  Consult your local MTU Onsite Energy distributor for emissions data.

Rating Definitions and conditions


//  Prime power ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of
generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance
with ISO 8528-1, ISO 3046-1, BS 5514 and AS 2789. Average load factor: ≤ 75%.
//  Derating factor:
Altitude: Consult your local MTU Onsite Energy Power Generation distributor for altitude derating.
Subject to change. | 32310671 | Edition 02/17 | EPC 2017-11.
Temperature: Consult your local MTU Onsite Energy Power Generation distributor for temperature derating.

Rated power is available up to 40°C and 1000m above sea level.

Materials and specifications subject to change without notice.

MTU Onsite Energy


Part of the Rolls-Royce Group