Batteries - VRLA

Valve Regulated Lead Acid Batteries

User Manual
User Manual
Series: Sealed Batteries

Language: English

Document: 10005922959 / 01

Publication Date: 08/2019


Summary of the Revisions

The information below describes the revisions made to this manual.

Version Revision Description


- R00 First edition
- R01 General Revision
Summary

1 SAFETY INSTRUCTIONS........................................................................ 1-1


1.1 QUALIFIED PERSONNEL.................................................................................................................1-1
1.2 SAFETY WARNINGS IN THE MANUAL...........................................................................................1-1

2 GENERAL INFORMATION...................................................................... 2-1


2.1 CONSTRUCTION FEATURES..........................................................................................................2-1
2.2 RECEIVING AND STORAGE........................................................................................................... 2-2
2.3 DISPOSAL........................................................................................................................................ 2-3

3 INSTALLATION AND OPERATION..........................................................3-1


3.1 INSTALLATION PRECAUTIONS...................................................................................................... 3-1
3.2 INSTALLATION METHOD............................................................................................................... 3-1
3.3 WORKING PRINCIPLE.................................................................................................................... 3-2
3.3.1 Electrochemical..................................................................................................................... 3-2
3.3.2 Oxygen Recombination......................................................................................................... 3-2
3.4 BATTERY CHARGE, DISCHARGE & SERVICE LIFE..................................................................... 3-3
3.4.1 Charge Characteristics......................................................................................................... 3-3
3.4.2 Charge Curve on Float Duty................................................................................................. 3-3
3.4.3 Relation Between Float Voltage and Ambient Temperature ........................................... 3-3
3.4.4 Equalizing Charge.................................................................................................................. 3-4
3.4.5 Charge Curve for Cyclic Use................................................................................................ 3-4
3.4.6 Supplementary Charge......................................................................................................... 3-5
3.4.7 Discharge Characteristic...................................................................................................... 3-6
3.4.8 Life Characteristic on Float Duty......................................................................................... 3-7
3.5 RECORDS......................................................................................................................................... 3-8

4 TROUBLESHOOTING..............................................................................4-1

5 MAINTENANCE........................................................................................5-1

6 TECHNICAL SPECIFICATIONS...............................................................6-1
Summary
Safety Instructions

1 SAFETY INSTRUCTIONS
This manual contains the information necessary for the correct use of the VRLA Battery. The following instructions
are extremely important for a good performance of your VRLA Battery and should be thoroughly observed during
the storage, maintenance and operation of the system. Failure to comply with the product instructions may cause
operating accidents, damages to the environment, to the battery and to the devices connected to it, in addition
to voiding the warranty.

1.1 QUALIFIED PERSONNEL


All the installation, commissioning, operation and maintenance procedures must be performed by trained and 1
qualified personnel. During the execution of maintenance jobs, the legal provisions in force in the country of
installation must be respected.

Maintenance and operation must be carried out exclusively by qualified personnel familiarized with the characteristics
of the panel, in compliance with all applicable IEC safety directions and standards of other technical entities, also
observing other paramount instructions. The procedures of NR-10 must also be followed. It is recommended to
request the intervention of personnel from WEG technical assistance to perform maintenance and repair jobs.

1.2 SAFETY WARNINGS IN THE MANUAL

DANGER!
Not following the procedures recommended in this warning can lead to death, serious injuries and
considerable material damages.

ATTENTION!
It identifies the risks of unsafe operations that may cause minor injuries or material damages.

NOTE!
The text aims at providing important information for the full understanding and proper operation of
the product.

ATTENTION!
Make sure the power is disconnected before installation. Otherwise, electric shock may cause serious
injury or death.
Always work with the equipment disconnected.
When performing any tests, maintenance or repairs, first remove the power supply and then
disassemble the equipment.

NOTE!
In case of doubt about this product / manual, contact our Technical Assistance department. Capital
cities and metropolitan areas: +055 4003-8201 / Other locations: +055 0800 701 0701.

VRLA Batteries | 1-1


Safety Instructions

1-2 | VRLA Batteries


General Information

2 GENERAL INFORMATION
In order to correct and safely install and use the VRLA Batteries, it is necessary to read this technical manual
carefully.

Pay attention to safety during installation so as to avoid accidents.

In case of any questions concerning this Technical Manual or technical problems, please contact WEG or our
nearest Authorized Service.

DANGER!
Do not touch any uninsulated terminal or connectors to avoid electric shock. Gases generated from
explosion may cause eye injury or even blindness. It is prohibited smoking or producing sparks and
flames near VRLA Batteries.
Vitriol acid can cause blindness or serious burns. Do not loosen the safety valves.
Keep batteries in a well-ventilated environment when in operation.
Maintenance and repair of VRLA Batteries should be performed by specialized technicians.

2.1 CONSTRUCTION FEATURES


2
1. Service life time.
The robust lead-calcium grids ensure moderate corrosion, providing a service life time of 15 years on stand-by
duty and under optimal conditions of floating charge and operating temperature.

2. Excellent characteristics of high-efficiency discharge.


VRLA batteries are equipped with low electrical resistivity plates and conductive parts, which reduce the
internal ohmic resistance, ensuring high discharge efficiency.

3. Construction with Triplex sealing.


The valve-regulated sealed construction with triplex reinforcement in the sealing of the terminals and poles
inhibits the electrolyte leakage and ensures the tightness of the batteries under normal operating conditions,
preventing the ingress of external air.

4. Low self-discharge.
Due to the use of lead-calcium alloy grids, VRLA batteries provide low self-discharge and high reliability
performance. At ambient temperature, the monthly self-discharge of the batteries is approximately 3 % of its
rated capacity.

5. High Safety.
VRLA batteries are provided with explosion-proof safety valves to inhibit gas production. They are also
manufactured to inhibit internal flame in the presence of sparks.

6. High efficiency in the Recharge.


Exclusive formulas are used in the lead paste composition of the positive plates to ensure that the batteries
can be easily recharged.

7. Absence of Electrolyte Stratification.


Special additives are used in the electrolyte to provide a gelatinous consistency without drainage, leakage or
stratification, allowing homogeneous reactions on the surface of the plates.

VRLA Batteries | 2-1


General Information

Positive pole

Intercell connector

Valve

Negative pole

Sealing washer

Ring

Cover

Negative plate

Separator

Positive plate

2 ABS container case

Figure 2.1: Sealed VRLA battery construction

2.2 RECEIVING AND STORAGE

Visually inspect the package when opening it, looking for signs of tampering or damage to the VRLA Batteries
during transportation.

Check that the information on the product nameplate corresponds to the purchased model. If any problem is
detected, immediately notify the carrier.

Open the packaging near the installation site and check the accessories accompanying the product.

Check carefully to ensure that there is no damage or leaks in the battery container cases.

If any battery falls or if any container case suffers an abnormal impact, please report it to WEG Technical Assistance
or the nearest Authorized Service.

If batteries are not immediately installed after the delivery, it is necessary to store them in a clean, ventilated, dark
location, with temperature between 5 °C and 30 °C (41 °F and 86 °F).

When stored, the battery capacity will gradually decrease due to the self-discharge. Do not store the batteries
for more than twelve months, as this will affect their performance and service life. If the storage time exceeds 4
months, the batteries must be charged with a voltage of 2.35 V to 2.40 V per element for 24 hours and recharged
at least every 4 months.

A relatively high temperature will accelerate the battery self-discharge. From 25 °C (77 °F), for each temperature
increase of 10 °C (50 °F), the recharge interval shall be reduced by half. For example, if the battery is stored at
35 °C (95 °F), its initial charge or recharge interval shall be 2 months. If the batteries are not properly charged,
their performance and service life will be affected, voiding the warranty.

2-2 | VRLA Batteries


General Information

ATTENTION!
Batteries (internal or external) stored for more than 120 days (at 25 °C (77 °F)) without a 24-hour
recharge lose their warranty.

2.3 DISPOSAL

In accordance with Resolution 401/08 of the Brazilian Environmental Council (CONAMA), WEG Critical Power is
capable and properly registered with the competent authorities to promote the correct disposal of the batteries
it sells.

When the battery life ends, contact WEG through the e-mail wcp-contato@weg.net or the phone 48.3202-8358.

We will inform you of the correct procedure for the environmentally friendly disposal.

Capital cities and metropolitan areas in Brazil: 4003-8201.

Other cities in Brazil: 0800 701 0701.

DANGER! 2
Do not dispose of batteries in the garbage!
The battery has toxic components that may cause damages to health and the environment if not
properly disposed of.
Composition: lead, sulphuric acid and plastic.

VRLA Batteries | 2-3


General Information

2-4 | VRLA Batteries


Installation and Precautions

3 INSTALLATION AND OPERATION

3.1 INSTALLATION PRECAUTIONS

„„ Use the following protective equipment when moving, installing and handling the VRLA Batteries:
1. Safety goggles or protective face masks.
2. Safety shoes.
3. Proper handling instruments.
4. Do not wear metal objects such as jewelry and the like.

„„ Due to the VRLA Batteries weight, take care to avoid impacts during handling.

„„ It is strictly prohibited smoking or using lighters, matches, among others, near VRLA Batteries. Keep the batteries
away from any kind of electric arc.

„„ VRLA Batteries are pre-charged, so avoid short-circuiting in order to prevent damages or injuries.

„„ Install
the batteries in a ventilated location and at ambient temperature (25 °C (77 °F)). Do not install them in
locations where there is a risk of flood or where water may reach.

„„ Tighten the screws and nuts on the connection terminals to the specified torque.

„„ Cleanthe battery container cases and covers with a damp cloth to prevent static electricity and sparks. It is
prohibited using organic solvents or detergents, which could damage the battery container cases.

„„ In
normal operation, there should be no electrolyte leakage into the container cases after the perfect battery
sealing. However, if the container case is damaged, vitriol acid may leak. If electrolyte comes into contact with
skin or clothing, flush with large amounts of water. If eyes are affected, wash quickly with large amounts of water
and seek immediate medical assistance.
3
„„ Make sure that the positive (+ / red) and negative (- / black) terminals are connected correctly.

„„ Connectors, terminals and interconnections of the battery contain lead or lead compounds and other chemicals
that are also harmful to health. Therefore when handling the battery, always use protective equipment.

„„ Wash the hands after handling batteries.

3.2 INSTALLATION METHOD

1. Batteries.
Keep a side clearance of at least 20 mm for ventilation and 150 mm on top for maintenance.

2. Connectors.
If there is oxidation on the battery terminals, clean them until they have metallic shine, apply vaseline to inhibit
the formation of high-strength oxide, and then install the connectors.
Make sure that all terminals, positive (+ / red) and negative (- / black), are connected correctly. The cables
must be installed according to the technical drawing or according to the instruction of a qualified professional.
Tighten the connection screws with a proper torque wrench. The recommended torque values are indicated
in Table 3.1 on page 3-1:

Table 3.1: Screw tightening torque


Screw Torque
M5 6 to 7 N*m
M6 8 to 10 N*m
M8 10 to 12 N*m

VRLA Batteries | 3-1


Installation and Precautions

3. Measure the electric voltage.


After installing the connectors, measure the total electric voltage of the bank, which should be the total voltage
of all the cells. If there is inconsistency, check the polarities of every monobloc and every terminal connection.

4. Numbering of the cells.


Stick the self-adhesive labels with the cell numbers and the bank polarity signal on top of the first and last
cells. The first cell at the bank positive terminal must be marked as No.1, and the other cells must be marked
sequentially.

5. Install the VRLA Battery protections.


After checking the electric voltage and the cell number arrangement, place the protections on top of the
batteries.

3.3 WORKING PRINCIPLE

3.3.1 Electrochemical

A lead-acid battery is an electric energy storage device that converts electric energy into chemical energy. When
required, the stored chemical energy can be converted again into electric energy to feed external systems.

In the discharge state, part of the PbO2 of the positive plates becomes PbSO4 and part of the lead of the negative
plates also becomes PbSO4. In this electrochemical reaction, both positive and negative electrodes generate
PbSO4. In the charge state the lead sulfate (PbSO4) on the positive and negative plates become PbO2 and Pb
respectively. At the discharge, the concentration and density of the electrolyte H2SO4 decreases gradually, while
during the charge it increases. The charge and discharge processes are carried out by electrochemical reactions.

Charge
Positive: PbSO4 + 2HO2 PbO2 + H2SO4 + 2H+ + 2e+
Discharge
3
Charge
Secondary reaction: HO2 1/2O2 + 2H- + 2e

Charge
Negative: PbSO4 + 2H + 2e+ Pb + H2SO4
Discharge

Charge
Secondary reaction: 2H + 2e H2

Figure 3.1: Electrochemical reaction

3.3.2 Oxygen Recombination

Positive plates generate oxygen in the final stage of the charge process. With the condition of sufficient additives
in the negative, the oxygen propagates to the negative plates through the separators and reacts with the spongy
lead, forming lead oxide and then lead sulfate and water.

Negative plates must be maintained slightly depolarized or in a state slightly lower than the full charge state, so
that the battery does not reach the potential for oxygen gasification. Therefore, the gasification and loss of water
will be inhibited, making the battery sealed and maintenance free.

Positive Overcharge
Charge
PbSO4 PbO2 O2
Negative
Charge
PbSO4 Pb O2

H 2O

H2SO4 + PbO

Figure 3.2: Oxygen recombination

3-2 | VRLA Batteries


Installation and Precautions

3.4 BATTERY CHARGE, DISCHARGE & SERVICE LIFE

3.4.1 Charge Characteristics

The charge condition is one of the most important factors in the use of VRLA Battery. The battery performance
and service life are directly related to the charge methods and charge parameters used. It is recommended
that the battery be charged at a temperature between 5 ºC and 30 ºC (41 °F and 86 °F). At any temperature
below 5 °C (41 °F) or above 30 °C (86 °F), there will be an incomplete charge or overheating, and consequently
the service life will decrease.

3.4.2 Charge Curve on Float Duty

140 0.28 2.4

Charge voltage
120 0.24 2.3

Charge volume
100 0.20 2.2
Charge volume (%)

Charge voltage (V)


Charge current (A)

80 0.16 2.1
1 Discharge
2 Charge with constant voltage
60 0.12 2.0 and limited current:
- Charge voltage: 2.30 V / Cell
- Charge current: 0,2 C10 A
40 0.08 1.9
3 Temperature: 25 ºC (77 °F)

20 0.04

Charge current
0 0 0
0 4 8 12 16 20 24 28 32 36
3
Charge time (Hr)

Figure 3.3: Characteristic charge curve on float duty

DANGER!
Do not dispose of batteries in the garbage!
The battery has toxic components that may cause damages to health and the environment if not
properly disposed of.
Composition: lead, sulphuric acid and plastic.

3.4.3 Relation Between Float Voltage and Ambient Temperature

In the normal temperature range of 5 °C to 30 °C (41 °F and 86 °F), the float voltage per element is from 2.25 V
to 2.29 V. For battery charge on float duty, normally, a constant voltage is adopted , but with limited current. The
initial current should be limited to 0.1 C10 A and not exceeding 0.2 C10 A.

1. At 25 °C (77 °F) the float voltage should be 2.27 V per element.

2. The float voltage should be adjusted when the ambient temperature changes. The compensation coefficient
is - 3 mV / °C, i.e., float = [2.27 - 0.003 (t-25)] x n.

VRLA Batteries | 3-3


Installation and Precautions

3.4.4 Equalizing Charge

An equalizing charge is required when the operation, for a long time on float duty, causes a voltage unbalance in
some elements of the battery bank. The equalizing charge can prevent stratification and reduce plate sulfation,
providing the return of all cells to similar voltage levels.

Uneven distribution of voltages of the elements is the main cause of failure of the VRLA Battery. Requirements for
VRLA Batteries equalizing charge:

„„ Equalizing charge every three months or every 20 discharge cycles.

„„ Equalizing charge method: with equalizing charge voltage from 2.42 to 2.45 Vpc @ 25 °C (77 °F), maximum
current of 0.3 C10 A and charge time from 12 to 24 hours. When the charge current is stable for approximately
2 to 3 hours, stop the equalizing and return to the float duty.

„„ Before the equalizing charge, leave the battery 100 % discharged.

3.4.5 Charge Curve for Cyclic Use

Batteries for cyclic service should be charged at a constant voltage, but with a limited current. From 20 °C to 25 °C
(68 °F and 77 °F), the battery charge voltage is 2.40 V per element. The initial current should not be higher than 0.2
C10 A, and the battery will be fully charged in approximately 24 hours.

In the final stage of the charge, if the current value remains stable for 3 hours, it indicates that the battery is
fully charged. Charge curves are shown in Figure 3.4 on page 3-4:

140 2.42 2.60

Charge voltage
120 2.36 2.40
3 Charge volume

100 0.30 2.20


Charge volume (%)

Charge current (A)

Charge voltage (V)

1 Discharge
80 0.24 2.0 100 % (0.2 C10 A X 10h)
50 % (0.2 C10 A X 5h)
2 Charge with constant voltage
60 0.18 1.8 and limited current:
- Charge voltage: 2.40 V / Cell
- Charge current: 0.2 C10 A
40 0.12 1.6
3 Temperature: 25 ºC (77 ºF)

20 0.06
Charge current
0 0 0
0 5 10 15 20 25
Charge time (Hr)

Figure 3.4: Characteristic charge curve for cyclic use

3-4 | VRLA Batteries


Installation and Precautions

3.4.6 Supplementary Charge

Due to the self-discharge in batteries stored for a long time, the remaining capacity will be shortened gradually.
The relation between the remaining capacity, temperature and storage time is shown on Figure 3.5 on page 3-5.

For Supplementary Charge, the charge method with constant voltage should be adopted, but with limited current.

The charge current should be from 0.05 C10 to 0.10 C10, the charge voltage 2.35-2.4 ± 0.05 V / element and the
duration of the charge from 24 to 36 hours. After long storage time, the batteries must be recharged before use.

110

100 Supplementary charge


is not required. Used on
90 floating charge.

80 5 ºC (41 °F)
Supplementary charge is
Excess of capacity (%)

70 required
60
Supplementary charge
50 performance will be
affected
40

30
40 ºC (104 °F) 30 ºC (86 °F) 20 ºC (68 °F)
It is prohibited reaching
20 this state

10

0
0 2 4 6 8 10 12 14 16 18 20 22 24
Storage time (Month)

Figure 3.5: Remaining capacity, temperature and storage time 3


Table 3.2: Storage time, charge voltage, current and time
Storage Charge Voltage Maximum Maximum Charge
Time (Month) (V / Cell) Charge Current Time (Hr)
3-6 2.35 0.2 C10 36
6 - 12 2.4 0.2 C10 48
12 - 20 2.4 0.2 C10 60

VRLA Batteries | 3-5


Installation and Precautions

3.4.7 Discharge Characteristic

If the discharge speed is different, the final discharge voltage will also be different. The higher the discharge
currents, the lower the final discharge voltages; inversely, lower discharge currents will produce higher final
discharge voltages. Typically, the final discharge voltage of the elements is in the range between 1.8 V and 1.6 V.
The capacity of the batteries in AH is lower with high discharge currents.

Characteristic discharge curves are shown on Figure 3.6 on page 3-6.

2.10
2.05

2.00

1.95
1.90
1.85
Voltage (V)

1.80 0.1 10 A

1.75 0.165 10 A
1.70 0.25 C10 A
1.65
0.55 C10 A
1.60
1 C10 A
1.55
1.50
1 2 3 5 10 20 30 60 2 3 5 10 20
Min Hr

Note: C10 = Capacity rate 10h


3
Figure 3.6: Characteristic discharge curve

Discharge Capacity X Temperature:

The discharge capacity of the batteries depends on temperature. The lower the temperature, the lower the capacity
of the batteries. The battery discharge capacity increases with the temperature. However, very high temperatures
will dramatically reduce the battery service life. The best operating temperature for the batteries is between 20 °C
and 25 °C (68 °F and 77 °F).

The following equation provides the battery capacity at a Ct temperature with capacity at 25 °C (77 °F):

Ct
C25
1 + K(t - 25)

Where:
C25 = Discharge capacity at 25 °C (77 °F) (AH).
Ct = Discharge capacity at t °C (AH).
t = The environmental temperature at the time of discharge (°C)
K = Coefficient of temperature compensation.
Discharge in 10 h: K = 0.006 / ºC Discharge in 5 h: K = 0.007 / ºC.
Discharge in 3 h: K = 0.008 / ºC Discharge in 1 h: K = 0.010 / ºC.

3-6 | VRLA Batteries


Installation and Precautions

Temperature X Capacity Curves according to Figure 3.7 on page 3-7:

120

110

100
Effective capacity (%)

80

60

40

Temperature
ºC
0
-40 -30 -20 -10 -0 10 20 30 40 50

Figure 3.7: Temperature x capacity curve

3.4.8 Life Characteristic on Float Duty

In the recommended situation of charge on float duty at 25 °C (77 °F), the battery is designed for a service life
of around 15 years. This battery service life time is related to ambient temperature, discharge depth, discharge
speed and float voltage. Discharge depth, discharge frequency, inadequate float voltage are factors that will
directly affect the operational life of the batteries. The characteristic curves of the life time on float duty are shown
on Figure 3.8 on page 3-7: 3
20

16
14

10
8
Service life (year)

6
5
4

3
Float voltage charge: 2.26 V / Cell
2

1.4

1
20 30 40 50 ºC Temperature
ºC

Figure 3.8: Life characteristic curve on float duty

VRLA Batteries | 3-7


Installation and Precautions

Life time on Float Duty X Temperature:

According to the Arrhenius equation, the battery life time varies with the temperature, and it's reduced by 50%
for each 10 degree increase in ambient temperature.

K1 Ea 1 1
1n
K2 R T2 T1

Where:
K1: equal. constant at temperature T1.
K2: 1 (equal. constant at temperature T2).
Ea: activation energy.
R: constant of air, 8.3143J·mol·K-1.
T1: absolute ambient temperature during discharge (Kelvin).
T2: reference temperature 293 K.

Table 3.3: Service life time on Float Duty x Temperature


Float Voltage Battery Service Life at Different Temperatures (Year)
Charge (V) 20 ºC (68 °F) 25 ºC (77 °F) 30 ºC (86 °F) 40 ºC (104 °F) 50 ºC (122 °F)
2.26 15.0 10.6 7.5 3.7 1.9

3.5 RECORDS

Operation records are very important for the protection and maintenance of VRLA batteries. The corresponding
information is useful for confirming battery service life and for adjusting their longevity.

Batteries can operate at temperatures lower than 25 °C (77 °F); however, the charge time will be relatively long. After
battery installation and one week of operation in float duty, you are requested to record the following information:

3 1. Total voltage of the batteries.

2. Charge voltage.

3. Float voltage of each monobloc.

4. Internal resistance of each monobloc. For each monobloc, position the probes of the internal resistance meter
on the two most distant terminals diagonally.

5. Ambient temperature.

6. Check that all connections have been tightened to the correct torque. Use a multimeter to test the internal
resistance of each interconnection cable. Perform the tests according to the position of the probes indicated in
the instruction manual. If the figures are 20 % above the figures obtained during installation, check the torque
of the connections again. If the data remains high, clean the terminals and interfaces between terminals and
interconnection cables.

3-8 | VRLA Batteries


Troubleshooting

4 TROUBLESHOOTING
Table 4.1: Troubleshooting
Nº. Common Failures Solution
1 Leakage Contact the supplier for replacements
2 Cracks Contact the supplier for replacements
3 Low float voltage If it continues after 24 to 48 hours of equalizing charge, contact the supplier
4 Reduced battery capacity If it continues after 24 to 48 hours of equalizing charge, contact the supplier
5 High pole temperature Inspect connection points, ventilation, charger and charge current
6 Abnormal appearance Contact the supplier for replacements
7 Ground Fault Check leaks or ground fault detector
8 Abnormal resistance Check connections and charge method

NOTE!
For measurements on battery banks containing several elements connected in series and/or in parallel,
whenever any element presents an individual voltage 10 % above or below the average voltage of
the other elements in the bank, such element should be replaced immediately.
The replacement must be performed in accordance with the Safety and Maintenance Instructions
contained in this manual.
If you have any questions, please contact WEG or the Authorized Service.

VRLA Batteries | 4-1


Troubleshooting

4-2 | VRLA Batteries


Maintenance

5 MAINTENANCE
Wear a protective mask or safety goggles when approaching batteries and be sure they are far away from locations
with smokers or any kind of fire.

The battery service life can be extended by means of proper maintenance. Every maintenance procedure requires
experienced professionals to perform them.

1. Check.
Try to perform all checks of charge condition on float duty. The measurements must be made according to
the supplier’s specifications and the records must be made for occasional comparisons.

1.1 Quarterly check:


1.1.1 Record all float voltages of the monoblocs.
1.1.2 Record the voltage and current supplied by the rectifier/charger.
1.1.3 Record the temperature and the situation of the ventilation and monitoring devices.
1.1.4 Record the visual inspection of the monobloc unit:

„„ Appearance of the batteries: terminals, connectors, any corrosion in the batteries.

„„ Distance between monoblocs.

„„ Any cracks or leaks in the batteries.

„„ Any monobloc deformation.

1.2 Semiannual Check:


In addition to the quarterly checks indicated above, record:

„„ Internal resistance of each monobloc.

„„ Temperature of the negative terminal of each monobloc.

„„ Check the resistance of connections by sampling (at least 10 % or 6 connections). If the resistance is
greater than the initial resistance, it is necessary to check all the connections and find out why. (Check
different connections at each inspection).

1.3 Annual check and initial check:


In addition to the checks indicated in items 1.1 and 1.2, check the following points and keep the records
to compare with the previous records:

„„ Check all the resistances of the connections.

„„ Check the input voltage and AC current of the rectifier.

„„ Check the torque of all battery connections.

1.4 Special checks:


Batteries should be inspected for damages in special situations e.g., excessive discharges, excessive
loads caused by excessive voltage supplied by the rectifier, etc. The inspection must include all annual 5
checks and the corresponding records must be provided.

2. Residual ripple voltage of the rectifier:


It is recommended that the residual ripple rms voltage of the rectifier be at most 0.5% of the charge voltage
and that the period of ripple be shorter than 8 milliseconds.

VRLA Batteries | 5-1


Maintenance

3. Battery cleaning.
Use normal water or carbonated water to clean the monoblocs and covers.

4. Capacity test.
If the batteries are working properly there is no need to carry out a capacity test. This test must only be done
when you are not sure about the battery capacity. The final discharge voltage should not be less than the
value specified for the discharge duty used. Before testing the capacity, make sure that the batteries are fully
charged for more than 48 hours on float duty. Alternatively, provide an equalizing charge for 24 hours and
then leave the batteries resting from 8 to 24 hours.

5-2 | VRLA Batteries


Rated Capacity 7 Ah 9 Ah 18 Ah 40 Ah 60 Ah 80 Ah 100 Ah 120 Ah 150 Ah
Model (Part
BAT2120071E BAT2120091 BAT2120181 BAT2120401 BAT2120601 BAT2120801 BAT2121001 BAT2121201 BAT2121501
Number)
SAP Code 13293745 13714063 13714064 13714065 13714066 13714067 13714238 13714239 13714240
Composition Lead acid
Type VRLA
Technology AGM
Number of Cells 6
Rated Voltage 12 V
Capacity @ 25 °C 7 Ah @ 20 hr 9 Ah @ 20 hr 18 Ah @ 20 hr to 40 Ah @ 10 hr to 60 Ah @ 10 hr to 80 Ah @ 10 hr to 100 Ah @ 10 hr to 120 Ah @ 10 hr to 150 Ah @ 10 hr to
(77 °F) to 1.75 V/cel até 1.75 V/cel 1.75 V/cel 1.80 V/cel 1.80 V/cel 1.80 V/cel 1.80 V/cel 1.80 V/cel 1.80 V/cel
100.0 mm (3.93 in) 167.0 mm (6.57 in) 169.0 mm (6.65 in) 217.0 mm (8.54 in) 181.0 mm (7.12 in) 220.5 mm (8.68 in) 225.0 mm (8.85 in) 241.0 mm (9.48 in)
Height
± 1.5 mm (0.05 in) ± 1.5 mm (0.05 in) ± 3.0 mm (0.12 in) ± 3.0 mm (0.12 in) ± 3.0 mm (0.12 in) ± 3.0 mm (0.12 in) ± 3.0 mm (0.12 in) ± 3.0 mm (0.12 in)
151.0 mm (5.94 in) 181.0 mm (7.12 in) 198.0 mm (7.79 in) 260.0 mm (10.23 in) 350.0 mm (13.77 in) 328.5 mm (12,93 in) 408.0 mm (16.06 in) 483.0 mm (19,01 in)
6 TECHNICAL SPECIFICATIONS

Width
± 1.5mm (0.05 in) ± 1.5 mm (0.05 in) ± 3.0 mm (0.12 in) ± 3.0 mm (0.12 in) ± 3.0 mm (0.12 in) ± 3.0 mm (0,12 in) ± 3.0 mm (0.12 in) ± 2.0 mm (0.07 in)
65.0 mm (2.55 in) 77.0 mm (3.03 in) 166.0 mm (6.53 in) 168.0 mm (6.61 in) 167.0 mm (6.57 in) 172.0 mm (6,77 in) 177.0 mm (6.96 in) 170.0 mm (6.69 in)
Depth
± 1.5 mm (0.05 in) ± 1.5 mm (0.05 in) ± 3.0 mm (0.12 in) ± 3.0 mm (0.12 in) ± 3.0 mm (0.12 in) ± 3.0 mm (0.12 in) ± 3.0 mm (0.12 in) ± 3.0 mm (0.12 in)
Weight 2.13 kg ± 10 % 2.47 kg ± 10 % 5.29 kg ± 10 % 13.12 kg ± 10 % 21.12 kg ± 10 % 22.50 kg ± 10 % 28.9 kg ± 10 % 33.5 kg ± 10 % 44.70 kg ± 10 %
Color Preta
Terminal Faston 250 (F2) Faston 250 (F2) F3 F11 F12
Screw Não aplicavel M5 x 12 M6 x 16 M8 x 16
Housing ABS
29.0 mOhm 16.5 mOhm 15.0 mOhm 8.85 mOhm 6.5 mOhm 6.0 mOhm 5.35 mOhm 4.90 mOhm 3.95 mOhm
Internal Resistance
± 10 % ± 10 % ± 10 % ± 10 % ± 10 % ± 10 % ± 10 % ± 10 % ± 10 %
Rated Operating
25 °C
Temperature
Floating Voltage
13.5 V - 13.7 V
@ 25 °C (77 °F)
Equalization Voltage
14.5 V - 14.7 V
@ 25 °C (77 °F)
Maximum Charge
2.1 A 2.7 A 5.4 A 12.0 A 18.0 A 24.0 A 30.0 A 36.0 A 40.0 A
Current
Maximum
70 A / 5 s 90 A / 5 s 180 A / 5 s 400 A / 5 s 600 A / 5 s 750 A / 5 s 900 A / 5 s 950 A / 5 s 970 A / 5 s
Discharge Current
Technical Specifications

VRLA Batteries | 6-1


6
Technical Specifications