You are on page 1of 11

711

ARTICLE
Compression failure of thin concrete walls during 2010 Chile
earthquake: lessons for Canadian design practice1
Can. J. Civ. Eng. Downloaded from www.nrcresearchpress.com by MEMORIAL UNIV OF NEWFOUNDLAND on 09/04/13

P. Adebar

Abstract: Numerous thin concrete walls failed in compression during the 2010 Chile earthquake. Experiments on small wall
elements indicate that thin concrete walls without tied vertical reinforcement may fail very suddenly at uniform compression
strains as low as 0.001 due to the thin layer of concrete between two layers of reinforcement becoming unstable. A test on a wall
subjected to axial compression and strong-axis bending demonstrated that unlike a tied column, a thin concrete wall can
suddenly lose all axial load-carrying capacity. Nonlinear response history analysis of a typical Chilean high-rise shear wall
building indicates small global drift demands and correspondingly small curvature and compression strain demands when
subjected to the ground motions measured in Santiago, which explains why most buildings were not damaged. Nonlinear finite
element analysis of a typical wall step-back irregularity indicates the increase in maximum compression strains due to a
reduction in wall length is much larger than predicted by a sectional analysis. Based on all the results of the current study, a
number of significant changes are proposed for the 2014 edition of CSA A23.3 to avoid compression failures of thin concrete
walls, including limiting the axial compression force applied to thin bearing walls, accounting for unexpected strong-axis
bending of thin bearing walls, and limiting the compression strain demands on thin concrete shear walls.

Key words: building codes, compression, concrete walls, earthquake damage, high-rise buildings, nonlinear analysis, seismic
design, testing.
For personal use only.

Résumé : Plusieurs murs minces en béton ont défailli par rupture en compression lors du séisme de 2010 au Chili. Des
expériences sur des petits échantillons de mur indiquent que les murs minces en béton sans renforcement vertical attaché
pouvaient défaillir très soudainement à des contraintes uniformes en compression aussi faibles que 0,001 en raison de la mince
couche de béton entre deux couches d’armature qui devenait instable. Un essai sur un mur soumis à une compression axiale et
en flexion dans l’axe principal a démontré qu’un mur mince en béton, contrairement à une colonne attachée, peut soudaine-
ment perdre toute sa capacité de charge axiale. Une analyse historique de la réponse non linéaire d’un immeuble de grande
hauteur typique au Chili, bâti en utilisant des murs de contreventement, indique des petites demandes de glissement globales
et des petites demandes correspondantes de contraintes en courbure et en compression lorsque ces murs sont soumis aux
mouvements de sol mesurés à Santiago. C’est ce qui explique pourquoi la majorité des immeubles n’a pas été endommagé. Une
analyse non linéaire par éléments finis de l’irrégularité typique de retrait d’un mur souligne que l’augmentation des contraintes
maximales en compression causée par une réduction dans la longueur du mur est beaucoup plus grande que celle prévue lors de
l’analyse sectionnelle. En se basant sur tous les résultats de cette étude, plusieurs changements importants sont proposés pour
l’édition 2014 de la norme CSA A23.3 afin d’éviter les défaillances en compression des murs minces en béton, incluant la
limitation de la force axiale en compression appliquée à de minces murs porteurs, tenant compte d’une forte flexion inattendue
de l’axe principal des murs porteurs minces et limitant les demandes de contraintes en compression des murs de contrevente-
ment minces en béton. [Traduit par la Rédaction]

Mots-clés : codes du bâtiment, compression, murs de béton, dommage de séisme, immeubles de grande hauteur, analyse non
linéaire, conception sismique, essais.

Introduction having thinner walls. Most of the damage occurred in newer shear
Although only a few buildings completely collapsed during the wall buildings with thinner walls.
magnitude M8.8 earthquake that occurred in the Maule region of High-rise residential buildings with numerous thin shear walls
Chile on 27 February 2010, many buildings were badly damaged are a more common form of construction in lower seismic regions
and subsequently had to be demolished. A common type of dam- of Canada such as in Toronto. The numerous thin walls between
age to high-rise concrete buildings was compression failure of rooms support the floor slabs and control lateral drifts due to
shear walls. Figure 1 shows some examples. A description of the wind or earthquake. Such buildings have also been constructed
damage in one of these buildings is provided by Sherstobitoff et al. on the west coast of Canada — mostly prior to the development of
(2012). modern seismic design requirements; but some new buildings
A common form of high-rise residential construction in Chile is have also been constructed this way. It is interesting to note that
to make every partition between rooms a concrete shear wall. The the Pyne Gould Building in Christchurch, New Zealand collapsed
thickness of these walls typically ranges from 120 to 200 mm, with during the February 2011 earthquake in part because “the east
older buildings having thicker walls and newer buildings often core wall failed catastrophically in compression” (Beca 2011). The

Received 19 July 2012. Accepted 22 March 2013.


P. Adebar. Department of Civil Engineering, The University of British Columbia, Vancouver, BC V6T 1Z4, Canada.
E-mail for correspondence: adebar@civil.ubc.ca.
1This paper is one of a selection of papers in this Special Issue on Lessons Learned from Recent Earthquakes.

Can. J. Civ. Eng. 40: 711–721 (2013) dx.doi.org/10.1139/cjce-2012-0315 Published at www.nrcresearchpress.com/cjce on 25 March 2013.
712 Can. J. Civ. Eng. Vol. 40, 2013

Fig. 1. Compression failures of thin shear walls during 2010 Chile earthquake.

(a) (b)
Can. J. Civ. Eng. Downloaded from www.nrcresearchpress.com by MEMORIAL UNIV OF NEWFOUNDLAND on 09/04/13

(c) (d)
For personal use only.

(e)

wall was 200 mm thick and had a single layer of reinforcement. provided). These walls are very similar to the thin walls that failed
Although it is difficult to establish a simple definition, a wall with in compression during the 2010 Chile earthquake. Conventional
a 200 mm thickness or less could be considered to be thin. (Rd = 1.5) shear walls are commonly used for buildings in lower
Most of the thin shear walls that failed in compression during seismic regions and are permitted in buildings up to 30 m high
the 2010 Chile earthquake did not have boundary zones (concen- (about 12 stories) in the highest seismic regions in Canada. In
trated vertical reinforcement with column ties) at the ends of the addition, the current requirements are such that a very tall build-
wall. The horizontal reinforcement placed outside the vertical ing in the highest seismic regions in Canada can have thin walls
reinforcement was typically terminated with 90-degree hooks that have been designated as bearing walls even though these walls
around the two vertical reinforcing bars at the end of the wall (see may be subjected to significant strong-axis bending due to the
Fig. 1b, 1c, and 1d). The failed wall shown in Fig. 1a did contain seismic deformations of the designated seismic-force resisting
concentrated reinforcing bars with nominal column ties; but this walls.
was because the wall above cantilevered over the wall below The current study was undertaken to better understand com-
(Sherstobitoff et al. 2012). The additional demands due to this type pression failures of thin concrete walls. An experimental investi-
of irregularity are examined in the current study. gation was undertaken on concrete wall elements with a variety
Walls designed according to Clause 14 of CSA A23.3-04, whether of reinforcement and subjected to a variety of load histories. The
conventional (Rd = 1.5) seismic-force resisting shear walls, wind- experimental results provide new information on the compres-
force resisting shear walls or bearing walls can be as thin as 150 mm sion strain capacity of thin concrete walls. To investigate the
and are not required to have “boundary zones” of tied vertical compression strain demands on shear walls in typical high-rise
reinforcement at the ends of the walls (ties are only required residential buildings in Chile, nonlinear response history analysis
when concentrated reinforcement in excess of two 20M bars is was done on an example 18-story building using ground motions

Published by NRC Research Press


Adebar 713

Fig. 2. Small wall element test specimens: (a) cross sections straight horizontal reinforcement as shown in Fig. 2a. Type 2
showing arrangement of reinforcement in the four types of specimens had two layers of horizontal reinforcement and two or
specimens, (b) elevation of specimen during testing showing end four vertical reinforcing bars. Type 3 specimens also had two lay-
plates and displacement transducers used to measure axial strain. ers of horizontal reinforcing bars; but these bars were hooked
around the ends of the walls. Specimens 1 to 4 and 22 (called Type
3-SH) had seismic hooks embedded into the core as shown in
Fig. 2a, while Specimens 5 and 6 (called Type 3-H) had 90-degree
hooks in the cover similar to the walls shown in Fig. 1. Specimen
Can. J. Civ. Eng. Downloaded from www.nrcresearchpress.com by MEMORIAL UNIV OF NEWFOUNDLAND on 09/04/13

21 is a unique Type 3 element that had U-shaped horizontal rein-


forcement that went around three sides of the specimen to simu-
late an element from the end of a wall. Finally, two Type 4
specimens did not contain any horizontal reinforcement.
All specimens were cast in wooden forms in the same position
as they were tested — vertical bars in vertical position. Two
batches of ready-mix concrete were used to cast the specimens.
Specimens 1 to 11 were cast and tested in 2010, while the remain-
ing specimens were cast in 2011. The 28-day cylinder compression
strength of the concrete determined from moist-cured cylinders
was found to be 30.3 MPa and 30.5 MPa for the two batches of
concrete cast one year apart. The 28-day compression strength
determined from field-cured specimens was 25 MPa. The wall el-
ements were tested between one and 6 months after casting. At
6 months, the concrete compression strength had only increased
to 32 MPa based on moist-cured cylinders and 26 MPa based on
field-cured cylinders.
The specimens were loaded under pseudo strain control, i.e.,
the load was increased until the target average strain was
reached. The standard protocol involved five cycles to each strain
level. The first target strain level was 0.0005 and the subsequent
For personal use only.

strain targets were 0.00025 higher than the previous one. Thus a
recorded in Chile during the February 2010 earthquake. Some of
specimen loaded using the standard protocol to a maximum
the damaged shear wall buildings had irregularities in the lower
strain of 0.0035 was loaded a total of 65 cycles — five cycles to each
levels such as step-back walls (wall above overhangs wall below).
of 13 strain levels between 0.0005 and 0.0035. Two of the speci-
Nonlinear finite element (NLFE) analysis was used to investigate
mens (1 and 4) were subjected to different protocols to study the
how much such irregularities magnify the compression demands.
influence of additional cycles at high strain.
Based on the results of the current study, a number of significant
The wall elements were subjected to concentric axial compres-
changes are recommended for the 2014 edition of CSA A23.3 to
sion in a universal testing machine. To prevent failure at the top
avoid compression failures of thin concrete walls.
and bottom and ensure uniform stress, the concrete elements
Experimental study were grouted within confining steel angles attached to thick load-
ing plates (see Fig. 2b). Four displacement transducers were used
A two-phase experimental study was conducted to understand to measure the average strain over a gauge length of 46 cm on the
compression failures in thin concrete walls. In the first phase, 61 cm high specimens and 76 cm on the 91 cm high specimens. In
many small wall elements were subjected to cyclic axial compres-
three tests, no effort was made to ensure the specimens were
sion. The main parameters were wall thickness (which varied
subjected to uniform strain and the strain gradients were re-
from 140 to 250 mm), number of layers of horizontal wall rein-
corded. During all other tests, the position of the specimen was
forcement (no horizontal reinforcement, one layer or two layers),
shifted slightly in the test frame after each loading cycle to ensure
clear cover to horizontal reinforcement, whether the wall had any
concentric loading and uniform compression strain.
cross ties (out-of-plane reinforcement), and the height (slender-
ness) of the wall elements. In the second phase, a 140 mm thick Results of compression tests on small wall
wall, reinforced similar to a typical Chilean shear wall, was sub-
jected to axial compression combined with reverse cyclic lateral elements
load. Significant details will be presented from the Phase 1 tests, The last four columns in Table 1 summarize the experimental
while only a brief summary will be presented from Phase 2. results. The measured vertical strains were used to estimate the
The Phase 1 wall elements were either 610 or 910 mm high. A compression force resisted by the vertical reinforcement. The net
schematic diagram of the four basic types of specimen cross sec- compression force resisted by concrete and net cross-sectional
tions are shown in Fig. 2a, while the details of the specimens are area of concrete were used to calculate the maximum concrete
summarized in Table 1. All vertical reinforcing bars, which were compression stress (fc-max in Table 1). The ratio of maximum com-
welded to small steel plates at the top and bottom of the speci- pression stress to the 28-day compression strength based on
mens to ensure full development, had a nominal diameter of moist-cured cylinders is also shown. The strain capacity shown in
10 mm. The horizontal reinforcing bars had a diameter of 9.5, 10, 15 Table 1 is the largest compression strain level that the specimen
or 20 mm as given in Table 1. In Canada, walls up to 210 mm thick resisted 5 times without crushing. The strain at failure is the
can have a single layer of reinforcement, while the 140 mm thick maximum recorded compression strain prior to the specimen
walls that failed in Chile typically had two layers of small diame- losing load carrying capacity.
ter reinforcing bars. Type 1 specimens had a single layer of hori- When the wall elements were subjected to a significant varia-
zontal reinforcement and usually a single vertical reinforcing bar. tion of compression strain, the results were very different than
Specimens 10 and 11 had 180 hooks on the two ends of the hori- when the elements were subjected to uniform compression
zontal reinforcement and two vertical bars within each hook strain. Specimens 7 and 8 were identical except for the compres-
(called Type 1-H). All other specimens had the single layer of sion strain gradient. Specimen 7 failed when the maximum com-

Published by NRC Research Press


714 Can. J. Civ. Eng. Vol. 40, 2013

Table 1. Summary of small wall element test specimens.


Horizontal bars
Thickness Diameter Vertical Cover No. of vertical Height fc-max fc-max/ Strain Strain
Specimen Type (mm) (mm) spacing (mm) (mm) bars (mm) (MPa) fc' capacity at failure
1 3 140 9.5 140 20 4 610 31.7 1.05 0.0035 0.0043
2 3 140 9.5 140 20 4 610 33.4 1.10 0.0035 0.0043
3 3 140 9.5 140 20 4 610 31.3 1.03 0.0035 0.0044
Can. J. Civ. Eng. Downloaded from www.nrcresearchpress.com by MEMORIAL UNIV OF NEWFOUNDLAND on 09/04/13

4 3 140 9.5 140 20 4 610 30.0 0.99 0.0035 0.0046


5 3 140 9.5 140 20 4 610 32.2 1.06 0.0035 0.0039
6 3 140 9.5 140 20 4 610 30.8 1.02 0.0035 0.0039
7 2 140 10 140 20 4 610 26.4 0.87 0.0015 0.0017
8 2 140 10 140 20 4 610 26.9 0.89 0.0010 0.0013
9 4 140 — — 30 4 610 33.4 1.10 0.0033 0.0033
10 1 140 10 140 60 4 610 30.8 1.02 0.0035 0.0037
11 1 140 10 140 60 4 610 32.3 1.07 0.0020 0.0023
12 1 152 15 150 20 1 610 33.6 1.10 0.0028 0.0029
13 1 152 15 150 60 1 610 33.8 1.11 0.0030 0.0031
14 1 203 20 150 20 1 610 33.5 1.10 0.0035 0.0039
15 1 203 20 150 50 1 610 33.7 1.11 0.0033 0.0034
16 1 203 20 150 80 1 610 33.9 1.11 0.0028 0.0030
17 2 203 15 150 20 2 610 33.2 1.09 0.0035 0.0039
18 2 203 15 300 20 2 910 30.0 0.98 0.0015 0.0016
19 2 203 15 150 40 2 610 31.8 1.04 0.0025 0.0026
20 2 203 15 300 40 2 910 33.1 1.09 0.0023 0.0026
21 3 203 10 200 20 2 910 30.1 0.99 0.0035 0.0038
22 3 203 10 200 20 4 910 31.6 1.04 0.0030 0.0031
23 2 254 15 150 20 2 610 32.9 1.08 0.0030 0.0032
24 2 254 15 300 20 2 910 31.6 1.04 0.0018 0.0020
25 2 254 15 150 40 2 610 32.4 1.06 0.0035 0.0038
For personal use only.

26 2 254 15 300 40 2 910 33.1 1.08 0.0020 0.0023


27 4 203 — — 40 4 910 26.8 0.88 0.0015 0.0017

pression strain at one end was 0.0023, while the minimum 0.0013. Figure 4 shows photographs of two specimens that failed
compression strain at the other end was only 0.0011 (average of at low compression strains. The failures were clearly influenced
0.0017). Specimen 8 failed when subjected to a uniform compres- by the horizontal reinforcement in the wall. These failures are
sion strain of 0.0013. Specimens 10 and 11 were also identical reminiscent of failures observed in thin concrete walls in Chile
except for the variation of compression strain. Specimen 10 failed after the 2010 earthquake.
when the compression strain was 0.006 at one end and 0.0015 at Figure 5 examines the relationship between height-to-thickness
the other end (average of 0.0037), while Specimen 11 failed at a ratio of the wall elements and the minimum compression strain
uniform compression strain of 0.0023. The compression strains capacity of concrete. As the compression stress applied to con-
reported in Table 1 are the average values. crete approaches the compression strength, the concrete be-
The specimens with significant strain variation behaved simi- comes unstable. The concrete in the more slender wall elements is
larly. The end subjected to higher compression strains had visible less influenced by the restraint at the top and bottom of the ele-
damage prior to failure, whereas the end that was subjected to ments and therefore becomes unstable at lower compression
lower compression strains had no visible damage prior to failure. strain values. The wall element with the lowest strain capacity
Failure occurred when the end subjected to lower compression was 140 mm thick and had two layers of 10 mm diameter horizon-
strains became damaged. This behavior explains why concrete tal reinforcement. This is very similar to many of the walls that
subjected to significant strain gradient is able to tolerate larger failed during the earthquake in Chile.
maximum compression strains — the concrete subjected to The most important conclusion from the compression tests on
lower compression strain stabilizes the concrete subjected to wall elements is that concrete walls subjected to uniform compres-
higher compression strain. In all subsequent tests, the compres- sion strain and not containing any tied vertical reinforcement may
sion strains were kept uniform as the specimens were meant to have a compression strain capacity as low as 0.001. Long concrete
represent small elements of long thin walls. walls will have a low strain gradient and thus almost uniform strains.
Figure 3 shows two typical recorded load–deformation relation- For example, typical shear walls in high-rise residential buildings in
ships. The load is expressed as the compression stress P/Ag and the Chile are from 6 to 8 m long. A transverse wall that acts as a com-
deformation is expressed as the average compression strain mea- pression flange for a shear wall will also be subjected to uniform
sured by the four displacement transducers. Specimen 6 shown in strain.
Fig. 3a is typical of many specimens that had a strain capacity of Specimens 2 and 3 were identical to Specimens 5 and 6 except
0.0035, which is the maximum target strain. The maximum com- that 2 and 3 had seismic hooks on the horizontal reinforcement
pression force was applied to the specimen at a strain of about (Type 3-SH), whereas 5 and 6 had 90-degree hooks similar to walls
0.002. As the specimen was pushed to higher compression strains, in Chile (Type 3-H). All four specimens had a compression strain
the maximum compression force during each load cycle reduced capacity of 0.0035 indicating the 90-degree hooks provided ade-
and increasing damage was observed. quate anchorage in these wall elements. It is important to note
Specimen 8 shown in Fig. 3b is a good example of a specimen that the cover did not spall on the widely spaced horizontal rein-
with low compression strain capacity. After cycling to a compres- forcement. It is expected that if the element had been subjected to
sion strain demand of 0.0010 with no visible damage, the speci- numerous cycles after cover spalling, significant difference would
men suddenly “exploded” when pushed to a compression strain of be seen between the two types of hooks.

Published by NRC Research Press


Adebar 715

Fig. 3. Example results from wall element tests — axial compression Fig. 4. Photographs of Specimen 7 (left) and Specimen 8 (right) after
stress P/Ag versus average compression strain: (a) Specimen 6 with the test. Note red circles highlight locations of horizontal wall steel.
nominal column ties, (b) Specimen 8 with horizontal wall
reinforcement but no through-the-thickness reinforcement.

(a) 35 Average (LP1,LP2)


Specimen 6
30
Can. J. Civ. Eng. Downloaded from www.nrcresearchpress.com by MEMORIAL UNIV OF NEWFOUNDLAND on 09/04/13

25
Stress (MPa)

20

15

10

0
0 0.5 1 1.5 2 2.5 3 3.5 4
Strain x 10
-3

(b) Average Value (LP1,LP2)


30

25 Specimen 8
For personal use only.

Fig. 5. Relationship between compression strain capacity of


Stress (MPa)

20
concrete and height-to-thickness of wall elements.

15

10

0
0 0.5 1 1.5 2 2.5 3 3.5 4
Strain x 10
-3

Specimen 1 was subjected to the standard protocol until reach-


ing a compression strain of 0.002 and then was subjected to 30
cycles at 0.002 and 10 cycles at every strain level beyond that until
failure (total of 60 cycles at a compression strain ≥0.002). Speci-
men 4 was subjected to one cycle of loading to standard target
strains and then was subjected to 55 cycles at a strain of 0.003.
Although both specimens degraded somewhat due to the addi- Results from wall subjected to reverse cyclic
tional loading cycles, the amount of degradation was surprisingly bending
small suggesting that the large number of cycles that occurred In the second phase of testing (Chin 2012), a 140 mm thick wall
during the Maule Earthquake — accelerations exceeding 5% g that was 1.1 m long was subjected to an axial compression of
lasted up to two minutes in some regions of Chile — may not have 1500 kN (0.33fc Ag) combined with reverse cyclic lateral load ap-
been a significant factor in the compression failures of thin walls. plied 1.41 m above the base causing a significant reverse cyclic
Specimen 11 had a single layer of horizontal reinforcement at strain gradient in the wall. The thin wall was reinforced similar to
the middle of the wall and was subjected to uniform compression a typical Chilean shear wall — two layers of 10M vertical and
strain. At a maximum compression strain of 0.0023, the speci- horizontal reinforcement except the two vertical bars at the end
of the wall were 15M bars. There were a total of 8 vertical bars
men, with no prior indication of damage, suddenly split into two
(4 pairs) and the horizontal reinforcement was spaced at 135 mm.
along the central layer of horizontal reinforcement. This brittle
The horizontal reinforcement was terminated with 90-degree
failure is important because of the compression failure of a simi- hooks around the vertical reinforcing bars at the ends of the wall
lar wall in the Pyne Gould Building in Christchurch, New Zealand as is the typical detail in Chile. The wall specimen was similar to a
and because of the many such walls that exist in older Canadian 140 mm thick Type 3 wall element.
buildings. Additional results from the wall element tests are re- Because the wall was subjected to a very significant strain gra-
ported by Adebar and Lorzadeh 2012. dient (due to the short wall length) and the horizontal reinforce-

Published by NRC Research Press


716 Can. J. Civ. Eng. Vol. 40, 2013

Fig. 6. Photograph of thin concrete wall specimen (140 mm × Fig. 7. Description of simplified example building: (a) partial floor
1100 mm) subjected to 35% of fc Ag after complete collapse. plan, (b) close-up of one T-shaped wall within the 5 m wide analysis
strip. The second wall is a mirror image of this wall.

6m 1.6 m 6m
Can. J. Civ. Eng. Downloaded from www.nrcresearchpress.com by MEMORIAL UNIV OF NEWFOUNDLAND on 09/04/13

5m

5 m analysis strip

5m

(a)

200 mm
4 – 22 mm φ bars (each end)

5m

8 mm φ bars E.W. & E.F.

(b) 6m
For personal use only.

ment bent around the end of the wall acted as cross ties, concrete remainder wall area has 8 mm diameter bars (cross-sectional area
crushing occurred at a large compression strain at the edge of the of 50 mm2) spaced at 200 mm each way (horizontal and vertical)
wall. The most notable result from the test is that the wall com- and on each face of the wall (two layers).
pletely collapsed after a small portion of concrete at the end of the The lateral force resisting system is two back-to-back T-shaped
wall crushed in compression. Figure 6 shows how the wall looked cantilever shear walls. For any direction of loading, the 5.0 m wide
after the failure. Unlike the tied columns with square cross sec- “flange” on one wall will be in tension, while the 5.0 m wide
tions that were tested, which have a significant core of undam- “flange” on the other wall will be in compression. Frame action
aged concrete within the tied vertical reinforcement, thin created by the two corridor walls interconnected by the 120 mm
concrete walls can suddenly lose all axial load carrying capacity thick corridor slab spanning 1.6 m between the walls was ignored
because the undamaged concrete between the two layers of rein- as nonlinear analysis indicated the contribution was small
forcement is very thin. This is an important issue that must be (Sherstobitoff et al. 2012). The slabs were 150 mm thick every-
accounted for in the design of thin walls. Another observation is where but in the corridor. The concrete compression strength was
the 90-degree bends on the horizontal reinforcement did not open 30 MPa, and reinforcement yield strength was 400 MPa.
(see bottom right corner of wall in Fig. 6) as was observed in the The mass per floor for the 5.0 m “slice” of building, which is 13.6 m
small element tests. wide, is 31 200 kg. This includes self-weight of concrete slabs and
walls, tile finishes on floors, plaster finishes on walls and ceilings,
Analysis of example building and an exterior curtain wall. For the 18 floors plus roof, the total
To investigate the compression strain demands on typical high- mass creates an axial compression force of 5500 kN at the base of
rise residential shear wall buildings in Chile, an analytical study each of the two walls. Using a modulus of elasticity E of concrete
was done on an example 18-story building. The example building equal to 24 650 MPa, the gross (uncracked) section flexural rigidity
was modeled after an actual building in Santiago that suffered EI of the two cantilever walls is equal to 400 × 106 kNm2. Assuming
significant damage in the earthquake (Sherstobitoff et al. 2012); the mass is uniformly distributed over the 46.8 m height of can-
however the details were simplified to make the results applicable tilever walls, and neglecting shear deformations results in an es-
to typical buildings in Chile rather than one specific building. timate for the fundamental period T1 equal to 0.68 s. A computer
Figure 7 shows a partial plan of the example building. As in analysis determined the first three periods of the building to be
many shear wall buildings in Chile, two corridor shear walls exist T1 = 0.72 s, T2 = 0.11 s, and T3 = 0.04 s. The ratio of wall height to
over the entire length of building in the long direction. Transverse fundamental period H/T1 is equal to 65 m/s, which is in the middle
shear walls spaced regularly at 5.0 m on centre are attached to the of the range for typical Chilean shear wall buildings.
corridor walls. A 5.0 m wide strip of the building with one pair of
transverse shear walls in the centre is the structure that was ana- Bending moment – curvature response of walls
lyzed in the current study. As the T-shaped shear walls had very thin wide flanges (0.2 m ×
All walls are 200 mm thick. The 6.0 m long transverse shear 5.0 m), a nonlinear FE analysis using program VecTor2 (Wong and
walls had four 22 mm diameter bars (cross-sectional area of Vecchio 2002) was done to investigate whether the flexural com-
390 mm2 per bar) at each end of the wall (outer edge of building pression strains and flexural tension strains are uniform across
and intersection of transverse shear wall and corridor wall). The the width of the flange. The three-dimensional analysis was done

Published by NRC Research Press


Adebar 717

Fig. 8. Bending moment – curvature relationships for T-shaped wall with maximum axial compression P = 5500 kN at base of wall and zero
axial compression at top of wall; for both case of “flange” of wall in tension and “flange” of wall in compression. Nonlinear curves and
trilinear approximations.

35000
Flange in tension; P = 5500 kN
30000
Can. J. Civ. Eng. Downloaded from www.nrcresearchpress.com by MEMORIAL UNIV OF NEWFOUNDLAND on 09/04/13

max. fibre strain = 0.003


25000
Bending Moment (kNm)

max. fibre strain = 0.001


20000
Flange in comp.; P = 5500 kN
15000
Flange in tension; P = 0

10000
Flange in comp.; P = 0

5000

0
0.0 0.5 1.0 1.5 2.0
Curvature (rad/km)

using a two-dimensional program by using a pseudo-3 D approach Nonlinear response history analysis of example
developed by Mercer (2012). It is expected that if there is a large
For personal use only.

building
amount of vertical reinforcement in the flange, the strains would
The recorded ground motion from the City of Santiago that was
not be uniform in tension, i.e., there would be significant shear
selected for the study was recorded at station Colegio Las Americas
lag. The results indicated that for the current walls, the strains are
(The Americas School) located at −33.45 and −70.53. The PGA for the
uniform in both tension and compression, and thus a simple
horizontal motion is 0.31g for North-South (N-S) direction and 0.23g
plane sections analysis, where the stresses are assumed to be uni-
for the East-West (E-W) direction. The record sampling rate was 100
form across the section, can be done.
per second and thus a time step of 0.01 s was used in the analysis.
Program Response 2000 (Bentz 2000) was used to develop the
Program OpenSees was used to do the nonlinear response history
bending moment – curvature relationships for the walls. Four analysis of the example building. A hysteretic bending moment –
cases were analyzed: flange in compression, flange in tension, and curvature model was developed for OpenSees as part of a project on
for each of these P = 5500 kN (at base of wall) and P = 0 (at top of estimating flexural demands in high-rise cantilever shear walls
wall). The results from the analysis are summarized in Fig. 8. For (Dezhdar 2012). The input to the model includes the trilinear upper-
each case, the actual nonlinear relationship is shown along with a bound bending moment curvature relationships shown in Fig. 8, as
trilinear approximation. As noted by Adebar and Ibrahim (2002), a well as the lower-bound trilinear relationships that are appropriate
trilinear relationship can be used as a very good approximation to after significant cracking in the wall has occurred and there is no
the bending moment – curvature relationship for typical concrete concrete tension stiffening. The parameters that define the trilinear
shear walls. The bending moment – curvature relationships relationships vary linearly over the building height as vertical rein-
shown in Fig. 8 are the upper-bound response including the effect forcement is uniform and axial compression varies linearly.
of concrete tension stiffening. Figure 9 presents a portion of the time history of maximum
As expected, concrete reaches a compression strain of 0.003 curvatures at base of building due to the N-S direction ground
first in the wall with the “flange” in tension (narrow “web” in motion. Approximately 80 cycles of maximum curvature occur
compression) and largest axial compression (P = 5500 kN at base of during the 60 s time period. The maximum curvature demand
building). Crushing of concrete due to excessive curvature de- is 0.36 rad/km at a time of 62 s, which is much less than the
mand would occur first at the outside edge of the building where 1.8 rad/km curvature at which the concrete reaches a compres-
the wall is narrow. The curvature when concrete reaches a com- sion strain of 0.003. As discussed above, the maximum compres-
pression strain of 0.003 is 1.8 rad/km and this point is indicated as sion strain demand is 0.001 at a curvature of 0.36 rad/km. As the
a round data point in Fig. 8. The compression strain of 0.003 was end of the wall has cross ties, a maximum compression strain of
selected because it is the assumed compression strain capacity of 0.001 is not expected to cause any significant damage.
unconfined concrete in walls according to ACI 318, which is refer- The low curvature demands in the shear walls are consistent
enced by the Chilean building code NCh433.Of96. with the observation that few high-rise shear wall buildings in
The curvature at which the walls reach a compression strain of Santiago were damaged, and those that were damaged generally
0.001 is indicated by solid triangles. The curvature at which the had features such as irregularities that increased the compression
critical wall (flange in tension; P = 5500 kN) reaches a maximum strain demands. The magnification of compression strains due to
compression strain of 0.001 is 0.36 rad/km. Note that while the the irregularity that existed in the example building are investi-
compression strain is reduced by a factor of 3 from 0.003 to 0.001, gated below using nonlinear finite element analysis.
the curvature capacity is reduced by a factor of 5 from 1.8 to 0.36. While the ratio of wall height to fundamental period H/T1 =
The reason is the larger compression strain depth when the max- 65 m/s for the example building is very typical of Chilean shear wall
imum compression strain is smaller. buildings, it is very different than what is common practice in

Published by NRC Research Press


718 Can. J. Civ. Eng. Vol. 40, 2013

Fig. 9. Partial time history of maximum curvature at base of Fig. 10. Results from NLTHA of example 18-story shear wall
example 18-story shear wall due to N-S direction ground motion. building (T1 = 0.72 s), as well as for same building with increased
fundamental period (increased mass): (a) displacement envelopes,
0.4 (b) curvature envelopes.
0.3
(a) 50
0.2 45
Curvature (rad/km)

0.1 40
Can. J. Civ. Eng. Downloaded from www.nrcresearchpress.com by MEMORIAL UNIV OF NEWFOUNDLAND on 09/04/13

35
0.0

Height (m)
40 50 60 70 80 90 100 30
-0.1 25
-0.2 20
-0.3 15
10
-0.4
Time (s) 5
0
0.00 0.10 0.20 0.30 0.40
Canada where the fundamental period of an 18-story shear wall
building would probably be about 1.8 s. This corresponds to a ratio Displacement (m)
of wall height to fundamental period H/T1 less than 30 m/s. As
ground motions similar to that recorded in Santiago are expected (b) 50
to occur on the west coast of Canada due to a subduction earth- 45
quake centred in the Cascadia subduction zone, it is interesting to 40
investigate how the curvature demands would increase if the ex-
ample building had a longer fundamental period. In Canada, the 35
Height (m)
buildings are more flexible because fewer shear walls are pro- 30
For personal use only.

vided. Thus the mass attributed to the pair of shear walls in the 25
analysis was increased to achieve higher fundamental periods.
20
The mass was increased by factors of 2, 4, 6, 9, and 12, resulting in
initial fundamental periods of the buildings (based on uncracked 15
flexural rigidity) equal to 1.0, 1.4, 1.8, 2.2, and 2.5 s. 10
Figure 10 presents the displacement envelopes and curvature en-
5
velopes for the N-S direction ground motion. The envelope with the
smallest displacements and envelope with the smallest curvatures 0
are from the example building with the actual mass. The other en- 0 0.5 1 1.5 2
velopes are from buildings with longer initial fundamental periods. Curvature (rad/km)
While the concrete shear walls crack in the example building, the
vertical reinforcement does not yield. When the building period is Table 2. Results from nonlinear response history analysis (NRHA) of
increased (mass increased), the bending moment demand at base of example building.
building is increased and vertical reinforcement yields. When the
initial fundamental period is increased to 2.2 and 2.5 s, significant Maximum
Initial Top wall curvature
yielding occurs at mid-height of the building; however the curvature
fundamental Ground displacement Global drift from NRHA
is still maximum at the base of the wall.
period (s) motions from NRHA (cm) from NRHA (rad/km)
The results from the nonlinear response history analysis for the
example building, including maximum displacements at top of wall, 0.72 N-S 18.0 0.004 0.37
corresponding global drift and maximum curvatures at base of wall E-W 18.0 0.004 0.35
are summarized for both the N-S and E-W ground motions in Table 2. 1.0 N-S 34.1 0.007 1.30
Because of the irregular shape of the displacement spectra, the top E-W 21.1 0.005 0.39
wall displacements do not increase steadily as the periods increase. 1.4 N-S 26.8 0.006 1.56
Figure 11 summarizes the relationship between maximum top wall E-W 30.0 0.006 1.25
displacement and maximum curvature demand. Also shown is the 1.8 N-S 37.3 0.008 1.75
E-W 25.8 0.006 0.95
estimate from the following simple expression:
2.2 N-S 28.1 0.006 1.41

共 兲
E-W 22.0 0.005 1.57
␣ ⌬t 2.5 N-S 28.0 0.006 1.31
(1) ␾d ⫽
lw hw E-W 26.2 0.006 2.13

where ␣ is a constant, lw is the wall length, and ⌬t/hw is the ratio of


maximum displacement at top of wall to height of wall (maximum ␣ = 2.0. As shown in Fig. 11, this simple expression does a remarkably
global drift). Based on the results of response history analysis of the good job of estimating maximum curvature demands.
cantilever direction of 13 different Canadian core wall buildings
from 10 to 50 stories high (Dezhdar 2012), an estimate of mean cur- NLFE analysis of wall step-back irregularity
vature demand can be made from mean displacement demand using Many shear walls that failed in compression during the 2010
␣ = 1.25 and an estimate of mean plus one standard deviation curva- Chile earthquake had irregularities that caused increased com-
ture demand can be made from mean displacement demand using pression strain demands at the ends of the wall. A common exam-

Published by NRC Research Press


Adebar 719

Fig. 11. Relationship between top wall displacement and maximum Fig. 12. Results from NLFE analysis of wall irregularity (reduction of
curvature demand at base of wall: comparison of results from NRHA wall length from 6.0 m to 5.0 m): (a) vertical strain profiles across
with prediction of eq. (1). 2.0 m wide flexural compression zone of wall immediately below
irregularity for two levels of lateral loading, (b) comparison of
maximum compression strains determine from plane sections
analysis, which are similar to the strains away from the irregularity,
and maximum compression strains determine from NLFE analysis in
four elements.
Can. J. Civ. Eng. Downloaded from www.nrcresearchpress.com by MEMORIAL UNIV OF NEWFOUNDLAND on 09/04/13

ple is a reduction in the transverse shear wall lengths in the lower


levels. The inside ends of the transverse wall are aligned at the
For personal use only.

central corridor wall in the building; but the transverse shear wall
no longer extends the full distance to the edge of the building.
Thus the transverse shear wall above overhangs the wall below.
The damage in the 18-story condominium building in Santiago
(Sherstobitoff et al. 2012) was located exactly where the shear wall
length decreased in the first level below grade — see Fig. 1a. To
investigate the increase in compression strain demands due to
this wall step-back irregularity, a study was conducted using non-
linear finite element program VecTor2 (Wong and Vecchio 2002).
The transverse shear wall length of 6.0 m shown in Fig. 7 was
reduced to 5.0 m in the first level below grade in the example
building. All of the reinforcement in the 6.0 m wall above was
continued into the 5.0 m wall below plus eight 22 mm diameter
bars were added at the end of the wall supporting the overhang
above (see Fig. 1a). The response history analysis indicates the
elastic bending moment demand at the base of the example build-
ing due to the measured ground motion in Santiago is 38 000 kNm.
Plane sections analysis of the reduced-length wall subjected
to an axial compression force of 5500 kN indicates a bending
resistance of 25 400 kNm when the web is in compression and the
axial compression is applied at the gross section centroid. Ac-
counting for the 0.5 m eccentricity of the 5500 kN gravity load
due to the 1.0 m step-back, the bending resistance reduces to
17 000 kNm. Thus the combined bending resistance of the 6.0 m
wall with flange in compression (16 200 kNm) and reduced-length
wall with web in compression equals 33 200 kNm (only one wall
has a step-back). The ratio of total elastic bending moment de- to a constant axial load of 5500 kN (at the centre of the upper
mand to total bending resistance is 1.14. It is interesting to note wall), and increasing bending moment until failure.
that since Update 3, CSA A23.3-04 does not require designs to meet Figure 12 summarizes the NLFE results for two levels of lateral
ductility or capacity design requirements if the structure has suf- load, and compares these with the results of a plane sections
ficient strength to resist loads calculated using Rd Ro equal to 1.3. analysis, which is the analysis a designer would likely use.
Nonlinear finite element analysis of the critical portion of wall Figure 12a presents the horizontal profile of vertical strain across
(reduction from 6.0 m length to 5.0 m length) was conducted to a portion of wall just below the step-back. The dashed lines show
determine the magnification of compression strains due to the the predicted vertical strains from a plane sections analysis. The
sudden change in wall length. Four stories of the wall (two below NLFE analysis results (solid lines) indicate there are very large
the change in wall length and two above) were modeled using magnifications of compression strains below the wall step-back.
250 mm square elements. The critical zone where strain concen- Figure 12b shows how the magnification of compression strain
tration is expected (where wall length is reduced) was further changes as the loading is increased. The horizontal axis is the
discretized into 100 mm square elements. The wall was subjected maximum compression strain predicted by a plane sections anal-

Published by NRC Research Press


720 Can. J. Civ. Eng. Vol. 40, 2013

ysis, which compare well with the maximum compression strain by the increased number of cycles that occur in a typical sub-
lower down in the wall away from the influence of the step-back. duction earthquake such as the 2010 Chile earthquake.
The vertical axis of Fig. 12b is the maximum compression strain 6. The 90-degree hooks around the end vertical reinforcing bars
determined from NLFE analysis. If there was no magnification of were never observed to open, as has occurred in column tests
compression strains, all data points would lie along the solid di- when the concrete is subjected to significant compression
agonal line where the horizontal and vertical axes have equal strains after cover spalling. Thus the 90-degree hooks pro-
value. The amount the data points are above this line indicates the vided adequate anchorage of the horizontal wall reinforce-
magnification of strain. The dashed diagonal lines indicate the ment.
Can. J. Civ. Eng. Downloaded from www.nrcresearchpress.com by MEMORIAL UNIV OF NEWFOUNDLAND on 09/04/13

magnification of compression strains when the structure is in the 7. Unlike tied columns with square cross sections, which have a
linear elastic range. These magnifications can be predicted using significant core of undamaged concrete within the tied verti-
a linear FE analysis. As the concrete response becomes more non- cal reinforcement, thin concrete walls can suddenly lose all
linear, the magnification of compression strains increases. axial load carrying capacity because the undamaged concrete
The element with the largest compression strain reaches a within the vertical reinforcement is very thin.
compression strain of 0.003 when the predicted maximum The conclusions from the nonlinear response history anal-
compression strain from a plane sections analysis is only 0.001 ysis of an example Chile high-rise residential shear wall build-
(magnification factor of 3.0). If the average strains from the four ing can be summarized as follows:
elements are used, the compression strain limit reaches 0.003 8. The example 18-story residential shear wall building with a
when the predicted maximum strain from a plane sections anal- height-to-fundamental period ratio of 65 m/s, which is very
ysis is 0.0013 (magnification factor of 2.3). This magnification fac- typical of Chilean buildings, was found to have very small
tor can be reasonably estimated using a linear FE analysis. A global drift demands (0.4%) when subjected to the ground
refined linear analysis could be made by reducing the modulus of motions measured in Santiago during the 2010 Chile earth-
elasticity in the elements that are subjected to higher stresses. The quake. As a result, the maximum curvature demands in the
strain magnification is very significant and must be accounted for walls were found to be small.
when determining whether the maximum compression strains in 9. The shear walls in the example building are such that the
concrete will exceed the compression strain capacity of concrete axial compression strain is small when the flexural tension
in a wall below a step-back irregularity. reinforcement first yields, including the walls with large ten-
sion flange and no compression flange. The curvature de-
Conclusions mand on the walls has to increase significantly beyond first
For personal use only.

The conclusions from the three parts of the current study are yielding before the concrete will fail in compression. This
summarized below beginning with the conclusions from experi- explains why most high-rise residential shear wall buildings
ments on thin concrete walls: in Santiago were not damaged during the 2010 earthquake.
10. Typical high-rise residential shear wall buildings in western
1. When subjected to a significant strain gradient, the maxi-
Canada have fewer thicker shear walls and as a result, have a
mum compression strain that concrete can tolerate is greatly
longer fundamental period than a typical building of the
increased because the undamaged concrete subjected to
same height in Chile. As a result, the Canadian buildings
lower compression strains stabilizes the damaged concrete
would experience larger displacements, larger curvatures,
subjected to the maximum compression strain. This observa-
and larger compression strain demands.
tion, which has been made in many previous studies, was
reaffirmed by the current tests. Conversely, when concrete is The conclusions from the nonlinear finite element anal-
subjected to uniform compression strain, it may become un- ysis of a typical wall step-back irregularity can be summa-
stable at lower compression strains — the slenderness of the rized as follows:
concrete element influences the strain at which concrete may 11. When a shear wall suddenly reduces in length going down the
become unstable. structure, there is significant magnification of concrete com-
2. Thin concrete walls without any cross ties were found to fail pression strain demands at the compression edge of the
at uniform compression strains as low as 0.001. Concrete shorter length shear wall that supports the overhanging
crushing occurs very suddenly with little prior damage. A shear wall above. Plane-sections analysis, which can be used
140 mm thick wall with two layers of horizontal reinforce- to calculate the flexural capacity of the shorter length wall,
ment had the lowest compression strain capacity, while cannot be used to estimate the maximum compression
200 mm and 250 mm thick walls with two layers of horizon- strains in the shorter length wall.
tal reinforcement had compression strain capacities as low as 12. The magnification of compression strains is larger than what
0.0015 and 0.0018, respectively. Failure occurs when the thin is determined from a linear FE analysis; but a reasonable
layer of undamaged concrete between the two cages of rein- estimate can be made using linear FE analysis.
forcement becomes unstable. 13. If the critical section for bending moment occurs at a wall
3. Thin walls with a single layer of reinforcement where found step-back, as was the case in the example building, failure
to fail in a very brittle manner; but at higher compression may result from a concentration of inelastic demands over a
strains than thin walls with two layers of reinforcement, pre- small height of wall. This can be avoided by ensuring that
sumably because the total thickness of undamaged concrete yielding of the wall (the critical section) occurs above the
is larger in walls with a single layer of reinforcement. irregularity.
4. A light cage of reinforcement with widely-spaced transverse In most concrete buildings, there are additional concrete shear
reinforcement as required in gravity-load columns is suffi- walls below grade and a linear analysis assuming the floor dia-
cient to stabilize the concrete in a thin wall subjected to phragms are rigid will indicate that the bending moments in the
uniform compression strains so that it will not become un- tower shear walls reduce very quickly below grade (large negative
stable prematurely and the compression response of the con- shear forces in tower walls below grade). Caution is needed when
crete will be similar to a standard cylinder. applying the results of such an analysis to determine the critical
5. When walls contain cross ties or boundary zone reinforcement section in the shear wall as the calculated bending moments are
that stabilizes the damaged concrete, the compression strain very sensitive to the stiffness assumptions. A complete methodol-
capacity of the walls do not appear to be significantly influenced ogy for designing shear walls below grade, including recommen-

Published by NRC Research Press


Adebar 721

dations on appropriate effective stiffness for shear walls and floor tied vertical reinforcement or limits on compression strains in
diaphragms is given by Rad and Adebar (2009). shear walls designed to resist wind loads according to Clause 14.
Higher mode bending moments can cause yielding of shear walls
Proposed changes for CSA A23.3- 2014 near mid-height and therefore the compression strains need to be
Based on the results of the current study and a review of the limited to prevent crushing of concrete near mid-height of all thin
requirements for concrete walls in the 2004 edition of CSA A23.3, shear walls. While conventional construction shear walls are not
the following changes are recommended for the 2014 edition of expected to be subjected to large curvature demands, tied vertical
CSA A23.3 to avoid compression failures of thin concrete walls. reinforcement should be provided at the compression ends of
Can. J. Civ. Eng. Downloaded from www.nrcresearchpress.com by MEMORIAL UNIV OF NEWFOUNDLAND on 09/04/13

walls near the base, and a compression strain limit is required to


Limit axial compression applied to thin bearing prevent crushing of thin conventional construction shear walls.
The compression strain demands are expected to be lowest in
walls
shear walls designed for wind loads; however unexpected crush-
A literal reading of CSA A23.3-04 suggests a bearing wall de- ing could occur at the compression end of thin concrete shear
signed for concentric loading by Clause 10 can have Pr,max equal to walls that are subjected to the factored wind loads and have no
Pro, i.e., the wall does not have to be designed for any minimum tied vertical reinforcement. An investigation has shown that if
eccentricity. This is not the intent; but Clause 10.10, which defines wind-resisting shear walls are designed conservatively for out-of-
Pr,max as a portion of Pro, refers specifically to columns and not plane slenderness, crushing of concrete is unlikely to occur. Thus
general compression members that includes bearing walls. This is such a requirement should be added to Clause 14.
an obvious error that needs to be corrected. To ensure the compression strain demands do not exceed the
Analogous to the way spirally-reinforced columns have a larger compression strain capacity of thin concrete shear walls, design-
maximum factored axial load resistance Pr,max as a portion of the ers need a methodolgy to estimate the magnification of compres-
factored axial load resistance at zero eccentricity Pro than tied sion strain demands due to irregularities such as a step back (wall
columns because they have increased toughness due to enhanced above overhangs wall below) or when a perpendicular wall acting
confinement of the core, concrete walls — particularly thin con- as a compression flange is suddenly terminated. Additional work
crete walls — should have a lower Pr,max to account for the limited is currently being done to develop such a methodolgy.
toughness and increased likelihood of a complete collapse of
these members as occurred in the Phase 2 wall test. Acknowledgements
The current definition of bearing walls in CSA A23.3-04 — walls The author is grateful to his graduate students who made im-
that support in-plane vertical loads, weak-axis bending moments portant contributions to the work reported in this paper. Amir
For personal use only.

and the corresponding shear forces — implies that a wall desig- Lorzadeh conducted the small wall element tests under cyclic
nated as a bearing wall does not have to be designed for any compression, while Helen Chin conducted the large shear wall
strong-axis bending moments. Strong-axis bending moments will test. Ehsan Dezhdar conducted the NRHA using OpenSees. Ste-
be induced in bearing walls due to the deformations of the lateral phen Mercer conducted pseudo three-dimensional analysis with
force resisting system subjected to the factored lateral forces due VecTor2 to investigate shear lag in the thin wall flanges. Funding
to wind or earthquake. The calculation of the factored axial load to undertake the research was provided by the Natural Sciences
resistance of bearing walls must account for unintended strong- and Engineering Research Council of Canada (NSERC) to the
axis bending moments. The simplest way to accomplish this is to Canadian Seismic Research Network (CSRN).
limit the maximum compression strain depth in a bearing wall to
a portion of the length of the shear wall that controls strong-axis References
Adebar, P., and Ibrahim, A.M.M. 2002. Simple non-linear flexural stiffness model
bending of the bearing wall. This is consistent with what was for concrete shear walls. Earthquake Spectra, 18: 407–426. doi:10.1193/1.
proposed by Adebar et al. (2010) for the design of elongated 1503343.
gravity-load columns. If the length of a bearing wall is much less Adebar, P., and Lorzadeh, A. 2012. Compression failure of concrete walls, 15th
than the length of the shear walls in a building, the capacity of World Conference on Earthquake Engineering, Lisbon, Portugal.
Adebar, P., Mutrie, J., and DeVall, R. 2005. Ductility of concrete walls: the Cana-
the bearing wall can be calculated based on the total area of the dian seismic design provisions 1984 to 2004. Canadian Journal of Civil Engi-
bearing wall, whereas if a bearing wall is long compared to the neering, 32(6): 1124–1137. doi:10.1139/l05-070.
shear walls, only a portion of the bearing wall length can be used Adebar, P., Bazargani, P., Mutrie, J., and Mitchell, D. 2010. Safety of gravity-load
to calculate the factored axial load resistance. columns in shear wall buildings designed to Canadian standard CSA A23.3.
Canadian Journal of Civil Engineering, 37(11): 1451–1461. doi:10.1139/L10-075.
Beca Carter Hollings & Ferner Ltd. (Beca). 2011. Investigation into the collapse of
Limit compression strain demands in shear walls the Pyne Gould Corporation Building on 22nd February 2011, Report. 46 pp.
For ductile and moderately ductile shear walls designed accord- Bentz, E.C. 2000. Sectional analysis of reinforced concrete members. Ph.D. the-
ing to Clause 21, the ends of all walls are required to contain tied sis, Department of Civil Engineering, University of Toronto, Toronto, Ont.
Chin, H. 2012. Bending displacement capacity of elongated reinforced concrete
vertical reinforcement, and a check is made to ensure the com- columns, M.A.Sc. thesis, Department of Civil Engineering, University of Brit-
pression strain demands are less than the compression strain ca- ish Columbia, Vancouver, BC. 441 pp.
pacity within the plastic hinge region. The compression strain CSA. 2004. Design of concrete structures. Standard CSA-A23.3-04, Canadian Stan-
depth must be limited to a portion of the shear wall length de- dards Association, Mississauga, Ont.
Dezhdar, E. 2012. Seismic response of cantilever shear wall buildings. Ph.D.
pending on the drift demands. For shear walls without confine- thesis, Dept. of Civil Engineering, University of British Columbia, Vancouver,
ment reinforcement (strain capacity assumed to be 0.0035) in a BC. 309 pp.
building with low drift demands, the compression strain depths Mercer, S. 2012. Nonlinear shear response of cantilever reinforced concrete
must be limited to 29% and 35% of the shear wall length for ductile shear walls with floor slabs. M.A.Sc. thesis, Department of Civil Engineering,
University of British Columbia, Vancouver, BC. 180 pp.
and moderately ductile shear walls, respectively (Adebar et al. Rad, B.R., and Adebar, P. 2009. Seismic design of high-rise concrete walls: reverse
2005). shear due to diaphragms below flexural hinge. Journal of Structural Engi-
Currently, there are no limits on the compression strain de- neering, 135: 916–924. doi:10.1061/(ASCE)0733-9445(2009)135:8(916).
mands above the plastic hinge regions in ductile shear walls, Sherstobitoff, J., Cajiao, P., and Adebar, P. 2012. Repair of an 18-story shear wall
building damaged in the 2010 Chile earthquake. Earthquake Spectra, 28(S1):
there are no requirements for tied vertical reinforcement or lim- S335–S348. doi:10.1193/1.4000028.
its on the compression strains anywhere in conventional con- Wong, P.S., and Vecchio, F.J. 2002. VecTor2 and FormWorks user's manual.
struction (Rd = 1.5) shear walls, and there are no requirements for Department of Civil Engineering, University of Toronto, Toronto, Ont.

Published by NRC Research Press

You might also like