Professional Documents
Culture Documents
HTX75C Series
FEATURES HUMITRON® HTX75C series is an economical model for the general climate controlling
circumstance and makes it possible to measure the exact temperature and humidity.
Also, HTX75C series can maintain longterm durability in the circumstance where is dusty
- RS485 Communication
and occurs constant air flow by applying stainless steel mesh filter.You can choose either
- Up to 100 nodes can be connected duct mount type or wall mount type according to installed place or method.
- High Accuracy & Safety
• Water-Proof & Independent Structure • Operational with Low Voltage (6 volts)
- Water-Proof Housing
- Minimizing outside influences at high humid place - Superior to long-distance transmission
- Compact & Slim Size - Removing self-heating error by isolation - Usable at high impedance
- Easy Instrallation of fine heat at circuit part
• Choosing Metal Mesh Filter • Basic for Humidity Measuring, Option for
- Excellence in sensor protection & high response speed Temperature Measuring
APPLICATIONS - Cost Saving Effect
- Removable structure for easy installation & maintenance
- Minimization
- HVAC
- Clenroom
- Dehumidifier
- Humidifier
- Precision Air-Conditionor
- Building Automation
- Garden(Farm)
- Lab/Test Room
- Museum / Show Room
SPECIFICATIONS
- Industrial (Production / Storage)
- Semi-Conductor Model
Item HTX75C
- Subway / Train
Range 0 ~ 100 %RH (Non-Condensation)
- Pharmacy, Food
- Factory Automation Accuracy ±2.0 %RH (@25℃, 20~80%RH)
DOTECH INC. http://www.dotech21.com 6F, JOONGANG-ILBO B/D, 30, Dongsan-ro, Danwon-gu, Ansan-si, Gyeonggi-do, KOREA
1
business@dotech21.com TEL : +82-31-495-3767 FAX : +82-31-495-3917
Housing Dimension(mm)
Φ
12
.7
42
30
6
25
83
HTX75C-W
<WALL MOUNT>
83
.7
42
83
83
HTX75C-D
<DUCT MOUNT >
41
83
.7
42
30
Φ12
83
170
20
HTX75C-R
<REMOTE MOUNT>
Φ12
58
42
Φ4.2
Φ3.2
58
42
<Wall & Duct Mount> <Duct Mount Bracket>
Connection Diagram
TXD RXD
Ex) ID set 15
SW2 SW1
TRX-
RS485
TRX+
- DC Power Supply
+ 6 ... 30Vdc Tens digits Ones digits
HTX75C - ① - ② Description
T Temperature
Communications
Protocol
40001 Humidity correction values %RH Analog INT16 -10.0 ~ 10.0 -100 ~ 100 X10
40005 Temp. correction values ℃ Analog INT16 -10.0 ~ 10.0 -100 ~ 100 X10
40022 Current Humidity(PV) %RH Analog INT16 0.0 ~ 100.0 0 ~ 1000 X10
40023 Current Temperature(PV) ℃ Analog INT16 -30.0 ~ 80.0 -300 ~ 800 X10
40024 Current Dew point Temp.(PV) ℃ Analog INT16 -40.0 ~ 60.0 -400 ~ 600 X10
40027 Current Enthalpy(PV) kJ/kg Analog INT16 0 ~ 2200 0 ~ 22000 X10
Ex) ID set 15
SW2 SW1
Recommendations for communication line
Use of industrial communication cables is recommended and wire communication
line with equivalent in LG LIREV-AMESB AWG22, BELDEN 9841(2), FTP, UTP (in case
of installing a number of channels at the same time).