PREFACE
Dear customers,
Thank you for your buying our series of products. In
order tomake you fully utilize the functions and features of
the product,please read this manual carefully before
installation,and keep it well so as to use in the future.please
contact us if you have any question and we will exclude the
difficulty and anxiety for you with best service and quick
speed.
Brief Introduction and
Structural Characteristic
SF Series Refrigeration Equipment is developed by
Wenzhou Shuangfeng Refrigeration Equipmet Co.,Ltd.in
accordance with year's technical experience and follow-up
and investigati on of customers.[t has such features such as
stable operation,strong adaptability,high energy
efficiency.saving power expenditure and convenience in
washing and transportation.tt is applicable for supported
products such as suction molding machine,injection
molding machine,chemical industry,clectro
Plating,hospital,printing,mold,aquiculture high-tech
experiment ete. The products are trusted by vast users for
their excellent performance.+ Don't install it in the following sitesOperating instruction and
precautions of installation
and transportation
[Transportation
(1)prevent the water cooling machine from raining or
knocking in transit.
(2)Handle with care and prevent from knocking
in transit or during un/loading.
I.Installation
()The equipment shall be placed on firm and level
place where shall be ventilated,dry and no air pollution.
The ambient temperature shall not exceed 45°C indoors-
(2)The in/outlet pipe and circulating cooling pipe of
water cooling machine shall be correctly connected
without leakage.
(3)The distance between machine unit and hamper
around walls shallbe not less than 45ems
IILPower supply connection
(1) The equipment adopts three-phase four-wire,electric
power line,(R,S,T)according to 380Vlive
wire(N)connection to zero line.Pay attention to correct
connection of “earth wire” =
(2)Main power supply of machine unit:supply voltage:
380VL10%
supply frequency:
S0Hz+2%
(3)Don't start equipment if supply voltage fluctuation
exceeds designated range. We will not take any
responsibility for the damage due to starting the machine
forcibly.(4)Do not modify the interlock control circuit and
electric appliance without permission. Please contact us if
you want to change it. We will inform the customers after
checking and confirming the wiring to be changed.
Otherwise, we will not take the consequences after
change.
WV.Operation
(Before starting the machine,please check whether
there are any foreign objects around ,whether the wires are
connected correctly,whether the fastening water pipe is
installed correctly and whether voltage is normal.
(2)Turn on the automtic wate compensation valve to
check whether the water tank of water cooling machine is
full of water (For water cooling type,please check whether
the outside circulation system such as cooling tower,pump
and condenser is full of water. Operating without water or
lower water level is prohibited. )
(3)Tum on the power supply and observe the indicator
light and heat indicator on the panel. At this time,the
water pump is working, while the dot in the heat in dicator
is stil blinking. Do not turn the host machine until delay
of four minutes.
V.Temperature control
Operation instruction
The functions of thermometer indicator light are listed
from top down as follows:
[Indicator ight Bright Blinding
Temp upper limit] Seting upper limit emp |
[Temp lower limit] Setting lower limit temp
Empty
Compressor isin delay
Protection state upon start
Refigerion | Refigeming
|How to set the upper and lower limit of temp?
Pressdand V keys at the seme time to enter into temp.
upper limit setting state. Atthis time, the temp. shown on
the digital display is the upper limit temp, (0.5 will
increase or decrease by pressing A or ¥ key once,fast
increase or decrease if pressing and holding more than
0.Ssecond). After finishing the setting of temp.upper
limit,press A.andW keys at the same time to set temp.
lower limit. Notice that the controller shall obey the rules
of “upper limit bigger than lower limit” .
Notes:
1.The setting state will quit automatically if not pressing
any key for continuousS seconds during the setting state.
2.The settingvalue won't be storesd until the setting
state quits. If power off before quitting the setting state. the
setting value won't be stored.
Temp. control
The temp control will operate according to two parameters
of “upper limit temp. " and “lower limit temp.” It is
supposed that the “temp upper limit” is20°C and the
“temp love limit” is 18°C,refrigeration will start when the
temp. control probe detects the temp. higher than 20°C
and stop when the temp. lower than 18°C and the temp.
will be controlled between 18Cand 20°C .
Delay protect of compressor starting
There is 2 “compressor stop timer” in the controllers
start timing when the compressor stops,first check the
timer befor starting the compressor next time. Do not
start the compressor until the timer reaches 3 minutes.Thus it can guarantee above 3minutes interval to prevent
the damage of comprssor from frequent starting.
Upon powering on the controller within 3 minutes the
compressor will not start,thus the compressor will be
protected in case of powering off suddenly and powering
on again.
(Note: The delay guard time of starting-up the compressor
is adjustable, suppose the above is set at 4 minutes. )
VL.Troubleshooting
(1)The state of panel indicator light
Description | State Solution
Jay the voltage of main power supply is
oss 1. [sbnormalor
Taiture | BEM |(2yTye order of R.S.T of main power isnot
‘crreetjexchange the positionef to lines.
p
Novbright| Indicate that input circuit isin order
i [inde poor bat cliinaon ad vetaton,
| Sec nesarondingencronment machine
sonemtaiere| |“Sottforwatrcosing ype check wheter |
Brigh_| schestrmlcnclaion gems coong
| {owes pnp tnd conser wo somal) |
Frosh pest wich no oa To sp) |
Hersosbesootng. |
Notbright] —indiete hatsyseminimorder
Tcheck whether the connected wire Rom
ost machine ‘A¢coractr oman mivofcompesor soma.
fate | Bright | Gythecomprensrisdamsgcithave
Srotesnont setnigeravon chien
Eatin
Wat papa clarpe dc whence
Water pump treslongtmetorsterng ofa
‘se (Ghthe bout machine flack of
tener pumpsdaagedschngs th water Pu
[Operavonor| Bag | __Worknosmally —___
|etachine|Norbright Tovar ic machieoiiinenp COMPTON
Note:in case that the equipment goes out of
order,please check it according to the above chart.
Contact us or professional refrigeration technician if
Brightfailing in shooting trouble. Non professional is allowed to
repair lest larger loss occur.
VII.Daily maintenance and service
(1)Check voltage,pump and flow rate, whether there are
foreign objects arojund the machine, whether there is water
in the water input pipe and whether the output loop water
pump of cooling tower is normal.
(2)Clean the transit screen for air cooling type machine
or clean the cooling water tower with clean water for water
cooling type machine according to heat elimination
condition if the refrigeration equipment has worked for
‘two or three months
(3)Clean and overhaul the whole machine yearly.
(4)It is recommended to operate under the cooperation
of professional refrigeration technician.