EN Operating instructions
further information
webcode: GW-4242
All rights including copyrights or industrial property rights are expressly reserved.
Keep the document for future reference.
© GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG
20.12.2021
Speed-APfunction
Speed Assembly and Programming, a particularly user-
friendly commissioning function for fast mounting, automated
NOTICE
setting and initialization of GEMÜ products. Dependent on Potentially dangerous situation!
type, activation uses an external impulse signal or existing ▶ Non-observance can cause damage to
precautions on the device (magnetic or housing switch). property.
Changeover to normal operating mode takes place automatic-
ally after successful completion.
The following symbols for the specific dangers can be used
Working medium
within a warning note:
The medium that flows through the GEMÜ product.
Control medium Symbol Meaning
The medium whose increasing or decreasing pressure causes Danger - corrosive materials
the GEMÜ product to be actuated and operated.
Control function
The possible actuation functions of the GEMÜ product. Danger - hot surfaces
sponsible for the production of the risk analysis and for com- 1
1
pliance with the resulting precautionary measures and re- 3
During operation:
9. Keep this document available at the place of use.
10. Observe the safety information.
11. Operate the product in accordance with this document.
12. Operate the product in accordance with the specifications.
13. Maintain the product correctly.
14. Do not carry out any maintenance work and repairs not de-
scribed in this document without consulting the manufac-
turer first.
In cases of uncertainty:
15. Consult the nearest GEMÜ sales office.
ately altern-
ately 1
LED conditions 1
3.3 Description
Size 1, 30 mm Size 2, 75 mm Size 2, 30 mm
5.2 Product with special function Y 5.3 Product with special function X
The product with special function Y is UL/CSA certified and The product with ordering option Special version X is intended
protected against explosion in accordance with ISA 12.12.01 for use in potentially explosive areas of zone 2 with gases,
(see "Technical data"). mists or vapours and zone 22 with combustible dusts in ac-
The product with special function Y can be connected to cordance with EU directive 2014/34/EU (ATEX) and IECEx.
switches, power supplies, PLC outputs and PLC inputs. The product has the following explosion protection marking:
The energy supply must be equipped with a switch or an over-
current protective device in the system. The switch or overcur- ATEX
rent protective device must be placed in a suitable and ac-
Gas: II 3G Ex ec nC IIC T4 Gc X
cessible position and also labelled as an isolating device for
the product with special function Y. Dust: II 3D Ex tc IIIC T 80 °C Dc X
The product user is responsible for providing connections that
comply with standards, a locking mechanism, cable compat- IECEx
ibility and warning signs. Gas: Ex ec nC IIC T4 Gc
Suitable locking clips must be used to secure the circular con- Dust: Ex tc IIIC T80°C Dc
nectors against becoming unintentionally loose or being Certificate: IECEx IBE 19.0011 X
loosened without the use of tools.
The product has been developed in compliance with the fol-
Installation, operation and maintenance must only be carried
lowing harmonised standards:
out by qualified trained personnel.
Do not repair the device yourself if it is faulty. Instead, replace • IEC 60079-0: 2011 (EN 60079-0:2012+A11:2013)
it with an equivalent new device. Repairs must only be carried • IEC 60079-15: 2010 (EN 60079-15:2010)
out by the manufacturer! • IEC 60079-31: 2013 (EN 60079-31:2014)
The device must only be used if its materials are resistant
• IEC 60079-7: 2017 (EN 60079-7+A1:2015)
against mechanical and/or chemical influences or corrosion
under the respective operating conditions to such a sufficient Use of the product is permissible in the following ambient
degree that the explosion protection is not impaired or nulli- temperature ranges: 0 °C to +40 °C
fied.
For use in potentially explosive areas, the following
conditions or operation limits must be observed:
Index X is applied to the explosion protection marking.
The following special conditions must be complied with:
1. Connection cables and connectors must be protected
from damage.
2. Layers of dust > 5 mm must be removed.
3. Warning label "Danger from electrostatic build-up".
4. Warning label "Do not disconnect when live".
The housing must be installed protected from mechanical in-
fluences.
RFID chips must not be read out in potentially explosive areas.
6 Order data
The order data provide an overview of standard configurations.
Please check the availability before ordering. Other configurations available on request.
Note: A valve specific mounting kit is required for assembly. For designing the mounting kit, the valve type, nominal size, control
function and actuator size must be stated.
Order codes
1 Type Code 7 Pneumatic connection Code
Combi switchbox 4242 Air supply 6 mm angled connection, E4
exhaust air 6 mm angled connection
2 Fieldbus Code (for IP67 or piped air outlet)
Without, 24 V DC version 000 Air supply 1/4" angled connection, U8
AS-Interface, 31 slaves, 4I/4O A2 exhaust air 1/4" angled connection
AS-Interface, 62 slaves, 4I/3O A3
8 Option Code
AS-Interface, 62 slaves, 8I/8O A4
Without 00
DeviceNet DN
Manual override 01
IO-Link IOL
Inversed LED colours 40
3 Accessory Code Inversed LED colours, manual override 41
Accessory Z Inversed LED colours 80
deactivated high visibility position feedback
4 Housing material Code
Stainless steel base, PC cover 07 9 Flow rate Code
Order example
Ordering option Code Description
1 Type 4242 Combi switchbox
2 Fieldbus 000 Without, 24 V DC version
3 Accessory Z Accessory
4 Housing material 07 Stainless steel base, PC cover
5 Function 01 Combi switchbox, single acting
6 Electrical connection 01 M12 plug, 5-pin
7 Pneumatic connection 01 Connection thread M5 for size 1,
connection thread G1/8 for size 2
8 Option 01 Manual override
9 Flow rate 01 14 Nl/min, size 1
10 Travel sensor version 030 Potentiometer 30 mm length, size 1
11 Special version Without
7 Technical data
7.1 Medium
Working medium: Quality classes to DIN ISO 8573-1
Dust content: Class 3, max. particle size 5 μm, max. particle density 5 mg/m³
7.2 Temperature
Ambient temperature: Standard or with special version code Y 0–60 °C
Special version code X 0–50 °C
7.3 Pressure
Operating pressure: Size 1 Size 2
1 to 10 bar (at 40 °C) 2 to 7 bar
1 to 8 bar (at 60 °C)
Observe the maximum control pressure of the valve actuator.
Explosion protection: ATEX (2014/34/EU) and IECEx, order code Special version X
NEC 500 (ISA 12.12.01), order code for special version Y
EAC according to TR CU 012/211 - ATEX
Protection class: IP 65
IP 67 is achieved by piping away the exhausting air
IP NEMA 4X (UL 61010-1, UL 50E), only available as special version code Y
Line fuse: 630 mA medium time lag, for order code Fieldbus 000
Switching characteristic:
Stroke %
100%
Switching hysteresis
Switch point "Closed" 0%
t/ms
Switching output "Open" active
inactive
t/ms
td1 td1 td2
Switch points: The data in percent refer to the programmed stroke, before each end position
8 Dimensions
8.1 Size 1
Ø57 □42
98
95
20
13
WAF 20 for mounting kit M12x1,
WAF 20 for mounting kit M12x1,
X
X
x = 9 mm
x = 9 mm 13,6
WAF 24 for mounting kit M16x1,
WAF 24 for mounting kit M16x1,
x = 11 mm
x = 11 mm
dependent on valve used
47 16,6 dependent on valve used
Standard Compact
Dimensions in mm
8.2 Size 2
WAF 20 for mounting kit M12x1, WAF 20 for mounting kit M12x1,
x = 9 mm x = 9 mm
WAF 24 for mounting kit M16x1, WAF 24 for mounting kit M16x1,
x = 11 mm Potentiometer, 75 mm length x = 11 mm
dependent on valve used dependent on valve used Potentiometer, 30 mm length
Dimensions in mm
3. Tighten the operat- 4. Affix the O-ring 5 and the adapter 6. 10.2 Mounting the combi switchbox on linear actuators
ing
10.2.1 Preparations for mounting to the valve
bush 3 by turning it
clockwise. 1. Move the actuator A into zero position (actuator vented).
2. Remove optical position indicator 2 and / or protective cap
1 from the actuator top.
1 2
7 A
8
10.2.2 Assembling the adapter (linear actuator)
5. Attach the flange 6. Screw the flange plate on tight using With some mounting kits it is necessary to install an adapter
plate screws 8 (1–1.5 Nm). as well. This adapter is enclosed with the required mounting
7 kits. Valves with a normally open and double acting control
function (code 2+3) also include additional O-rings (1+2).
• Push in the spindle until it pushes against the spring and
then slowly release the pressure on the spring. 1
3
NOTICE
2
▶ For some valves (e.g. GEMÜ 650 and GEMÜ 687) it is ne-
cessary to fit a pressure disc between the threaded ad- 1. Move the actuator to the closed position.
apter and the actuator head. This is included in the re- 2. Place O-rings 1 and 2 into adapter 3.
quired mounting kits, sometimes with an additional O-ring 3. Screw adapter 3 into the actuator opening as far as it will
(only GEMÜ 650 with normally open and double-acting go and tighten.
control function – code 2+3).
▶ If the pressure disc does not have a groove for a seal, this
will already be inserted in the groove provided at the ad-
apter opening of the actuator head (e.g. GEMÜ 687 with
normally open control function – code 2).
6
11
9
10
Insert the O-ring 11 (if in- If included: Push the pressure
cluded) disc 9 over the adapter 6 and
into the corresponding groove insert the O-ring 10 in the in-
on the adapter 6. tended groove of the pressure
disc.
10.2.3 Assembling the stroke limiter (linear actuator) 10.2.4 Assembling and installing the combi switchbox (linear
actuator)
1. Screw distance piece 5 onto/
into actuator spindle 6.
DANGER
2. Move the actuator to the
Danger of explosion
closed position.
7.1 ▶ Risk of death or severe injury.
3. Insert the O-ring 7.1 in the
● Do not use the product as a step or
1
2 stroke limiter 1.
3
4
foothold.
7.2 4. Insert the O-ring 7.2 in the ● Prior to commissioning, ensure that
5 washer 4. the cover is fully closed and that the
5
5. Screw stroke limiter 1 with housing and the O-ring are not dam-
Option1 Option2
nut 2, seal 3 and washer 4 aged.
9 into the actuator opening.
8
6. Set stroke limiter 1 to the re-
6
quired stroke.
7. Make sure that the minimum
stroke is reached.
8. Secure stroke limiter 1 with
nut 2.
Key
1 Stroke limiter 7.1 1) O-ring
1)
7.2 M16 x 1 - WAF 24
2 Nut 8 Protective cap M12 x 1 - WAF 20 6
1)
3 Seal 9 Position indicator The thread size depends
1) Only available for valves with the NO and DA control functions. 1. Move the actuator into the OPEN position.
2) Only included in required mounting kits. The design depends on 2. Guide the product as far as it will go into the actuator
the valve. opening, the adapter 3 (see “Assembling the adapter (lin-
ear actuator)“, page 16) or the stroke limiter 1 (see “As-
sembling the stroke limiter (linear actuator)“, page 17)
and screw in clockwise against the initial spring tension.
3. Use the spanner flat of the travel sensor to tighten the
product.
4. Turn the housing clockwise to align the pneumatic or elec-
trical connections.
5. Connect the product electrically (see “Electrical connec-
tion“, page 20).
6. Connect the product pneumatically (see “Pneumatic con-
nection“, page 19).
7. Initialize the product (see “Commissioning“, page 22).
CAUTION
Incorrect installation of the product.
▶ Damage to the housing.
● Only tighten the product using the spanner flats provided
for this purpose.
9. The product with mounting kit and adapter is fully as- 2. Remove the screw 1 from the trigger cam 2.
sembled. 10.3.3 Assembling and installing the combi switchbox (quarter
turn actuator)
CAUTION
Incorrect installation of the product.
▶ Damage to the housing.
● Only tighten the product using the spanner flats provided
for this purpose.
10. The product with mounting kit and stroke limiter is fully 8
assembled.
7
CAUTION
Reduction of the flow at the vent connection 3
▶ Increased overpressure in the upper part of the housing E1
● Do not operate vent connection 3 with chokes, filters or
similar.
● Ensure that vent lines are always depressurised.
● Install vent lines free of tension and kinks.
Connec- Designation Connection
11.1 Size 1, standard, single acting tion size
1 Air supply connection M5
2 Working connection for process M5
E E valve
3 Venting connection with integrated M6 x 0.75 1)
check valve
Connec- Designation Connection E1 Housing ventilation with integrated M6 x 0.75 1)
tion size check valve
1 Air supply connection M5 1) only relevant for exhaust air duct and/or increase of protection
2 Working connection for process M5 class
valve
11.4 Size 2, standard, single acting
3 Venting connection with integrated M6 x 0.75 1)
check valve
E Housing ventilation with integrated M6 x 0.75 1)
check valve
1) only relevant for exhaust air duct and/or increase of protection
class
1) only relevant for exhaust air duct and/or increase of protection Connec- Designation Connection
class tion size
1 Air supply connection G 1/8
2 Working connection for process G 1/8
valve
3 Venting connection with silencer (in- G 1/8 1)
tegrated housing ventilation)
Connec- Designation Connection The M12 plugs may only be assembled, connected and com-
tion size missioned by trained personnel. The trained personnel must
have expertise in types of ignition protection, and regulations
4 Working connection for process G 1/8
and provisions for operating media in EX areas.
valve
2. Securely lay the connection cables or ensure sufficient
1) only relevant for exhaust air duct and/or increase of protection tension relief.
class
3. Refer to the technical data and cable gland documentation
11.6 Information for use in damp conditions for details of the wire cross sections.
The following information is intended to help when installing 4. Protect the product and the cables from damage.
and operating the product in damp conditions. 5. Only clean the product with an anti-static or damp cloth.
1. Cables and pipework must be laid so that condensate or 6. Only operate the product when it is fully assembled.
rain water that remains on the pipework/cables cannot
enter the screw fittings of the product's M12 plugs. 12.2 Potential equalization – special function X and Y
2. Check that all cable glands of the M12 plugs and the fit-
Connecting the potential equalization device
tings are mechanically secured.
12 Electrical connection
NOTICE
Risk: Electrostatic discharge
▶ Destruction of electronic components
● When mounting the potentiometer, take the necessary
ESD safety precautions.
1. Use a screw M4x6 to attach the potential equalization
device to the electrical position indicator.
DANGER
ð Potential equalization for metal housings in potentially
Danger of explosion
explosive areas: Minimum 4 mm².
▶ Risk of severe injury or death.
● Do not connect or disconnect the
2. Secure the connection against working itself loose.
device until the power has been
12.3 24 V, ordering option Fieldbus, code 000
switched off or the area has been clas-
sified as non-hazardous. 12.3.1 Pin assignment
● The standard version of the product
(without special function X or Y) must 2
3 1
not be used in potentially explosive 8
4 7
zones.
5 6
● Danger from sparking. Never discon-
nect the connection cables when live.
Pin Signal name
NOTICE 1 U, 24 V DC, supply voltage
Risk of cable break 2 24 V DC, Open end position output
▶ Overtightening can result in damage to the internal 3 U, GND
cables.
4 24 V DC, Closed end position output
● Turn electrical connections once by max. 360°.
5 24 V DC, programming input
2 6 24 V DC, control input
3 5 1 7 24 V DC, error output
4 8 n.c.
Pin 5 and pin 6 are highly active. If not used, connect to GND
or leave open.
12.1 Electrical connection The following errors are indicated via pin 7 (error output):
1. Connect the product in accordance with the pin assign- Sensor error, pneumatic error, programming error, internal er-
ment. ror
For electrical connection, we recommend the M12 connectors 12.3.2 Inputs (pin 5, 6)
for EX areas from IFM, series EVCxxA. Input impedance
Low level
Pin Signal name
≤ 5 V DC
1 AS-Interface +
12.3.3 Outputs (pin 2, 4, 7) 2 -
Internal wiring 3 AS-Interface -
4 n.c.
5 -
2 n.c.
3 U, GND
4 C/Q IO-Link
5 -
NOTICE
Incorrect initialization
● Always carry out initialization without operating medium
pressure on the process valve. Carry out initialization of
the process valve in neutral position (NO/NC).
NOTICE
Maximum cable length ● For delivery of the product assembled on a valve at the
factory, the complete construction is already ready for op-
Baud rate Trunk cable Drop cable
eration at a control pressure of 5.5 to 6 bar without oper-
[kBaud] Thick Thin cable Max. cable Max. drop ating pressure. A reinitialization is recommended if the
cable length per cable ac- plant is operated with a different control pressure or if the
drop cable cumulated mechanical end positions have been changed (e.g. seal
length replacement on the valve or actuator replacement). The
125 500 m 100 m 6m 156 m initialization is retained even in the event of voltage
250 250 m 100 m 6m 78 m cutoff.
500 100 m 100 m 6m 39 m
NOTICE
12.6.2 Pin assignment
● For delivery of the product without factory setting (e.g. for
2
delivery without valve) initialization must be carried out
once for correct operation. This initialization must be re-
3 5 1 peated every time that the process valve is changed (e.g.
seal replacement or actuator replacement).
4
1. Connect the connection cable tension-free and without
Pin Signal name any bends or knots.
1 Shield 2. Switch on supply voltage.
2 V+ 3. POWER LED on.
3 V- 4. Use suitable connectors.
4 CAN_H 5. Connect the control medium lines tension-free and
without any bends or knots.
5 CAN_L
6. Connect the product pneumatically to the process valve.
7. Connect the pneumatic tubes and activate the pneumatic
control air supply of max. 7 or 9 bar.
8. Carry out initialisation on-site or via communication inter-
face.
1 13.1.4.1 A2 version
Automatic programming mode:
NOTICE
1. Set DO3 = 1. (automatic programming)
▶ If the magnet is held against the housing cover for too 2. Briefly (>100 ms) set DO2 = 1. (The product is in program-
long, the programming mode is left and the previous ming mode)
state is restored.
3. Set DO3 = 0.
1. Connect supply voltage.
4. The product moves automatically in end positions OPEN
2. Briefly (>100 ms) hold a magnet (e.g. 1242000ZMA) to the and CLOSED.
position marked PROG 1 on the housing cover.
5. The product automatically goes into normal operation.
ð The OPEN and CLOSED LEDs flash alternately. 6. Programming mode is automatically terminated if the
3. Remove magnet. valve does not move for 5 seconds.
ð OPEN and CLOSED LEDs flash slower alternately. ð The end positions are set.
ð High visibility LED flashes alternately green / orange. ð The OPEN, CLOSED and high visibility LEDs light up de-
ð The process valve moves automatically 2 times each pending on the product (see “LED displays“, page 6).
to position OPEN and CLOSED. Manual programming mode:
4. Programming mode is automatically terminated if the 7. Set DO3 = 0. (manual programming)
valve does not move for 5 seconds. 8. Set DO2 = 1. (The product is in programming mode)
ð The end positions are set. 9. Open valve until end position is reached.
ð The OPEN, CLOSED and high visibility LEDs light up de- 10. Close valve until end position is reached.
pending on the product (see “LED displays“, page 6). 11. Set DO2 = 0. (The product is in normal operation)
ð The end positions are set. 13.1.5 Initialization of end positions via programming input
ð The OPEN, CLOSED and high visibility LEDs light up de- (pin 5) 24 V version
pending on the product (see “LED displays“, page 6). 1. Connect supply voltage.
ð The OPEN, CLOSED and high visibility LEDs light up de- ð The end positions are set.
pending on the product (see “LED displays“, page 6).
Manual programming mode:
5. Set DO1 = 0. (manual programming)
6. Set DO2 = 1. (The product is in programming mode)
7. Open valve until end position is reached.
8. Close valve until end position is reached.
9. Set DO2 = 0. (electrical position indicator in normal opera-
tion)
ð The end positions are set.
ð The OPEN, CLOSED and high visibility LEDs light up de-
pending on the product (see “LED displays“, page 6).
13.1.4.3 A4 version
Automatic programming mode:
1. Briefly (>100 ms) set DO2 = 1. (The product is in program-
ming mode)
2. Open valve until end position is reached.
3. Close valve until end position is reached.
4. Programming mode is automatically terminated if the
valve does not move for 5 seconds.
ð The end positions are set.
ð The OPEN, CLOSED and high visibility LEDs light up de-
pending on the product (see “LED displays“, page 6).
Manual programming mode:
5. Set DO1 = 1. (manual programming)
6. Set DO2 = 1. (The product is in programming mode)
7. Open valve until end position is reached.
8. Close valve until end position is reached.
9. Set DO2 = 0. (The product is in normal operation)
ð The end positions are set.
ð The OPEN, CLOSED and high visibility LEDs light up de-
pending on the product (see “LED displays“, page 6).
Vendor-ID: 401
Device-ID: 424201
Device → Master
Master → Device
NOTICE
▶ All IO-Link parameters that contain sub-indexes can also be addressed in bundles via sub-index 0.
Index Su- Access Parameters Length Data type Default settings Setting options
[Hex] bindex rights
0x10 0 ro Vendor Name 6 byte StringT GEMUE -
0x12 0 ro Product Name 13 byte StringT 4242 IO-Link -
0x13 0 ro Product ID 8 byte StringT 4242 IO-LINK -
0x15 0 ro Serial number 9 byte StringT 0–4294967296 -
0x16 0 ro Hardware Revision 8 byte StringT Rev. xx -
0x17 0 ro Firmware Revision 10 byte StringT V x.x.x.x -
0x50 1 rw Inversion of LED colours 1 bit Boolean 0 0 = standard
1 = inversed
2 rw Inversion of feedback sig- 1 bit Boolean 0 0 = standard
nals 1 = inversed
3 rw Function of high visibility 3 bit UIntegerT 3 0 = off
1 = open/closed (33%)
2 = open/closed (66%)
3 = open/closed (100%)
4 rw Programming mode 1 bit Boolean 0 0 = automatic
1 = manual
5 rw On site programming 1 bit Boolean 0 0 = enabled
1 = disabled
6 rw Inversion of outputs 1 bit Boolean 0 0 = standard
1 = inversed
0x51 1 rw Switch Point OPEN re- 8 bit UIntegerT 25% 3%–97%
quest
2 rw Switch Point CLOSED re- 8 bit UIntegerT 12% 3%–97%
quest
3 ro Switch Point OPEN real 8 bit UIntegerT 25% Display of values 3%–97%
4 ro Switch Point CLOSED real 8 bit UIntegerT 12% Display of values 3%–97%
0x52 1 rw Alarm Stroke reduction 4 bit UIntegerT 1 0 = disabled
OPEN 1 = 25% of Switch Point
2 = 50% of Switch Point
3 = 75% of Switch Point
2 rw Alarm Stroke reduction 4 bit UIntegerT 1 0 = disabled
CLOSED 1 = 25% of Switch Point
2 = 50% of Switch Point
3 = 75% of Switch Point
3 rw Alarm opening time 8 bit UIntegerT 0 0 = disabled
1–255 s
4 rw Alarm closing time 8 bit UIntegerT 0 0 = disabled
1–255 s
5 rw Valve type 8 bit UIntegerT 0 0 = unknown
1 = normally closed
2 = normally open
0x53 1 ro Programmed position 16 bit UIntegerT 0 Display of numerical values
OPEN 0–4092
Index Su- Access Parameters Length Data type Default settings Setting options
[Hex] bindex rights
2 ro Programmed position 16 bit UIntegerT 0
CLOSED
3 ro Programmed position 16 bit UIntegerT 0
STROKE
0x54 1 ro Last position OPEN 16 bit UIntegerT 0
2 ro Last position CLOSED 16 bit UIntegerT 0
3 ro Last position STROKE 16 bit UIntegerT 0
0x56 1 rw Valve cycles user 24 bit UIntegerT 0 Resettable to 0,
display of numerical values
0–16777215
2 ro Valve cycles total 24 bit UIntegerT 0 Display of numerical values
0–16777215
0x57 1 ro Counter Powerfail 16 bit UIntegerT 0 Display of numerical values
2 ro Counter Power on 16 bit UIntegerT 0 0–65535
Setting Function
Step 1 High visibility position indicator off
Step 2 High visibility position indicator on (100%)
Step 3 High visibility position indicator on (33%)
Step 4 High visibility position indicator on (66%)
Error messages and location function are not affected by the setting and always remain active (100%).
Programming mode
Selection of programming mode (see “Initialization of the end positions via IO-Link“, page 23).
Local programming
On-site programming can be disabled to prevent unauthorized activation.
These tolerances enable operational changes e.g. compensation of diaphragm swelling during sterilization to ensure reliable
end position feedback.
In the event of overlapping of the set value for CLOSED feedback or if the minimum possible switch point is overstepped, the
maximum possible value is used. The value used can be read out from the parameter "Threshold open real".
Total stroke
Stroke reduction
OFF
Stroke reduction
25 %
25 %
25 %
Stroke reduction
50 %
50 %
50 %
Stroke reduction
75 %
75 %
75 %
Feedback Feedback
(threshold) (threshold)
Setting Function
Off Warning deactivated
25% Warning becomes active 25% before loss of end position feed-
back
50% Warning becomes active 50% before loss of end position feed-
back
75% Warning becomes active 75% before loss of end position feed-
back
The delay time before the warning occurs corresponds to the time of parameter Alarm opening time.
NOTICE
▶ If the parameter Alarm opening time is deactivated (setting 0), the alarm Stroke reduction is deactivated.
NOTICE
▶ If the parameter Alarm closing time is deactivated (setting 0), the alarm Stroke reduction is deactivated.
If the time between activation of the combi switchbox and reaching of the valve end position exceeds the set delay time, a pneu-
matic fault is output. After automatic programming is performed, the value is automatically set to 2x the measured operating
time.
NOTICE
▶ The pneumatic fault is only active after automatic end position programming has been carried out.
▶ After manual end position programming, the pneumatic fault is deactivated.
NOTICE
▶ The pneumatic fault is only active after automatic end position programming has been carried out.
▶ After manual end position programming, the pneumatic fault is deactivated.
Programmed stroke
Determined stroke of linear actuator during last correctly executed end position programming (in AD values). The change in
valve stroke can be calculated in conjunction with the parameter "Last stroke".
Last stroke
Determined stroke of linear actuator during last completed switching cycle (in AD values). The change in valve stroke can be
calculated in conjunction with the parameter Programmed stroke.
Counter Powerfail
Power failure counter.
Counter Power on
Power on counter.
Counter Programming
Executed end position programming processes counter.
Reset to default
Reset to default settings.
Actual AD-value
Current value of AD converter.
14.4 Events
Event Mode Type Code
Internal error Appear/Disappear Error 0x8CA2
Sensor error in position OPEN Appear/Disappear Error 0x8CA4
Sensor error in position CLOSED Appear/Disappear Error 0x8CA5
Programming error with no stroke Appear/Disappear Error 0x8CA6
Programming error with to less stroke Appear/Disappear Error 0x8CA7
Programming error after sensor error Appear/Disappear Error 0x8CA8
Not calibrated Appear/Disappear Error 0x8CA9
Pneumatic error in position OPEN Appear/Disappear Warning 0x8CB0
Pneumatic error in position CLOSED Appear/Disappear Warning 0x8CB1
Pneumatic error between position Appear/Disappear Warning 0x8CB2
Stroke reduction OPEN Appear/Disappear Warning 0x8CB5
Stroke reduction CLOSED Appear/Disappear Warning 0x8CB6
Parameter value out of Range Single Shot Notification 0x8DE0
Parameter value changed Single Shot Notification 0x8DE1
15.1 Inputs
Bit Default Function Version Logic
A2 A3 A4
DI0 0 Indication of OPEN position X X X 0 = process valve not in OPEN position
1 = process valve in OPEN position
DI1 0 Indication of CLOSED position X X X 0 = process valve not in CLOSED position
1 = process valve in CLOSED position
DI2 0 Indication of operating mode X X X 0 = normal operation
1 = programming mode
DI3 0 Error 2 X X X see error analysis
DI4 0 Error 3 - - X
DI5 0 Error 4 - - X
DI6, not used - - X
DI7
PF 0 Error 1 X X X see error analysis
15.2 Outputs
Bit Default Function Version Logic
A2 A3 A4
DO0 0 Activation of pneumatic outlet 2 X - - 0 = pneumatic outlet 2 vented
1 = pneumatic outlet 2 pressurized
0 Activation of pneumatic outlet 2 / 4 X X X 0 = pneumatic outlet 2 vented, pneumatic
outlet 4 1) pressurized
1 = pneumatic outlet 2 pressurized, pneu-
matic outlet 4 1) vented
DO1 0 Activation of pneumatic outlet 4 1) X - - 0 = pneumatic outlet 4 1)vented
(pilot valve 2) 1 = pneumatic outlet 4 1)pressurized
not used X - -
0 Programming mode - X - 0 = manual programming
1 = automatic programming
0 - - X 0 = automatic programming
1 = manual programming
DO2 0 Setting slave in programming mode X X X 0 = normal operation
1 = programming mode
DO3 0 Programming mode X - - 0 = manual programming
1 = automatic programming
0 Function of high visibility position indic- - - X 0 = activated
ator 1 = deactivated
DO4 0 Inversion of feedback signals - - X 0 = standard
1 = inversed
DO5 0 Inversion of LED colours - - X 0 = standard
1 = inversed
DO6 0 Location function - - X 0 = deactivated
1 = activated
DO7 0 On-site programming - - X 0 = enabled
1 = disabled
Parameter Switch point OPEN [%] Switch point CLOSED [%] A3 A4*
P2 P1 P0
0 0 0 12 25 X -
0 0 1 25 25 X X
0 1 0 6 12 X -
0 1 1 6 6 X -
1 0 0 12 12 X -
1 0 1 12 6 X -
1 1 0 25 6 X -
1 1 1 25 12 X X
Identity
Class Inst. Attr. Function Value
1h 1h 1h Vendor ID 869
2h Product Type 48
3h Product Code 4242
4h Rev. 2.2 1)
5h Status Device status according to DeviceNet specifications
6h Series No. Continuous serial number
7h Name 4242 DN combi switchbox
V+
V-
CAN_H
120 Ω 120 Ω
1/4 W 1/4 W
CAN_L
Shield
Protective Protective
earth earth
Drop cable Trunk cable
16.3 Inputs
Bit Default Designation Function Logic
0 0 State Valve 1 Status query pneumatic outlet 2 0 = pneumatic outlet 2 vented
(pilot valve 1) 1 = pneumatic outlet 2 pressurized
1 0 State Valve 2 Status query pneumatic outlet 4 0 = pneumatic outlet 4 vented
(pilot valve 2) 1 = pneumatic outlet 4 pressurized
2 0 Programmingmode Feedback for operating mode 0 = normal operation
1 = programming mode
3 0 Position Closed Feedback CLOSED position 0 = process valve not in CLOSED position
1 = process valve in CLOSED position
4 0 Position Open Feedback OPEN position 0 = process valve not in OPEN position
1 = process valve in OPEN position
5 0 Calibrationmode Feedback calibration mode 0 = normal operation
1 = calibration mode
6 0 Global warnings General warning 0 = warning not active
1 = warning active
7 0 Global errors General error 0 = error not active
1 = error active
As seen from the DeviceNet master, Class 64h, Inst. 1h, Attr. 1h
16.4 Outputs
Bit Default Designation Function Logic
0 0 active valve 1 Activation of pneumatic outlet 2 0 = pneumatic outlet 2 vented
(pilot valve 1) 1 = pneumatic outlet 2 pressurized
1)
1 0 active valve 2 Activation of pneumatic outlet 4 0 = pneumatic outlet 4 1)vented
(pilot valve 2) 1 = pneumatic outlet 4 1)pressurized
2 not used
3 0 Location function Location function 0 = location function not active
1 = location function active
4 not used
5 0 Manual program- Manual programming mode 0 = manual programming mode not act-
ming ive
1 = manual programming mode active
6 0 Automatic program- Automatic programming mode: 0 = automatic programming mode not
ming active
1 = automatic programming mode active
7 not used
As seen from the DeviceNet master, Class 64h, Inst. 1h, Attr. 1h
1) Activation of outlet 4, only for double acting function (code 02)
Class Inst. Access rights Attr. Parameters Length Data type Default Setting options
setting
Fh 15h Get 1h Valve position 2 byte UINT 0
Fh 16h Get 1h Sensor error 1 byte USINT 0 0 = Sensor OK
1 = Sensor error position
closed
2 = Sensor error position
open
Fh 17h Get 1h Programming error 1 byte USINT 1 0 = Programming OK
1 = not calibrated
2 = no stroke
3 = stroke < min. stroke
4 = Sensor error position
closed
5 = Sensor error position
open
6 = Sensor error position
closed + open
Fh 18h Get 1h Pneumatic error 1 byte USINT 0 0 = Pneumatic OK
1 = Pneumatic error posi-
tion
closed
2 = Pneumatic error posi-
tion open
3 = Pneumatic error middle
position
Fh 19h Get 1h Internal error 1 byte USINT 0 0 = Device OK
1 = un-valid crc-check
2 = un-valid serial number
3 = Memory error
Fh 1Ah Get 1h Stroke reduction 1 byte USINT 0 0 = Stroke OK
warning 1 = Stroke reduction posi-
tion
closed
2 = Stroke reduction posi-
tion open
3 = Stroke reduction posi-
tion
closed + open
Fh 1Bh Get/Set 1h Valve cycles user 4 byte UDINT 0 Resettable to 0,
display of numerical values
0–429496729
Fh 1Ch Get 1h Valve cycles total 4 byte UDINT 0 Display of numerical val-
ues
0–429496729
20 Disassembly
1. Disassemble in reverse order to assembly.
2. Deactivate the control medium.
3. Disconnect the control medium line(s).
4. Disassemble the product. Observe warning notes and
safety information.
21 Disposal
1. Pay attention to adhered residual material and gas diffu-
sion from penetrated media.
2. Dispose of all parts in accordance with the disposal regu-
lations/environmental protection laws.
22 Returns
Legal regulations for the protection of the environment and
personnel require that the completed and signed return deliv-
ery note is included with the dispatch documents. Returned
goods can be processed only when this note is completed. If
no return delivery note is included with the product, GEMÜ
cannot process credits or repair work but will dispose of the
goods at the operator's expense.
1. Clean the product.
2. Request a return delivery note from GEMÜ.
3. Complete the return delivery note.
4. Send the product with a completed return delivery note to
GEMÜ.