You are on page 1of 18

17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022].

See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
IET Generation, Transmission & Distribution

Review Article

Impact of distributed generation on the ISSN 1751-8687


Received on 31st October 2019
Revised 7th August 2020
protection systems of distribution networks: Accepted on 24th August 2020
E-First on 13th November 2020
analysis and remedies – review paper doi: 10.1049/iet-gtd.2019.1652
www.ietdl.org

Matin Meskin1 , Alexander Domijan2, Ilya Grinberg3


1EatonCooper Power Systems, Franksville, WI 53126, USA
2The University of Texas Rio Grande Valley, Edinburg, TX 78539, USA
3The SUNY Buffalo State, Buffalo, NY 14260, USA

E-mail: matinmes@buffalo.edu

Abstract: Power networks, especially distribution networks, have been undergoing substantial changes since the application of
new technologies. Technology development in the early part of the 21st century has opened up new horizons for automated,
efficient and reliable power grids. New technologies, while enhancing the capability of the electrical networks and providing
opportunities and innovative solutions to the challenges of future networks, can also cause drawbacks that should be
investigated and taken into account. Distributed generation (DG) is one of the new technologies that improves the operation of
power grids. Despite tangible benefits that integration of DG units brings to electrical grids, their notable impacts on protection
systems of power networks raise many challenges and concerns on how a fault should be detected and isolated in active
distribution networks. Many attempts have been made to investigate the downside of the interconnection of DG units and
methods to mitigate their impacts have been proposed. This study reviews the impact of DG integration on protection systems
addressed in other research works and recapitulates suggested methods provided by scholars.

1 Introduction Electrical networks are subjected to short circuit faults that can
damage equipment and cause hazardous conditions to utility crews
Development and enhancement of new technologies in power and consumers. In these cases, the fault should be detected and
electronics make the application of small-scale power generators cleared as fast as possible. Usually, a three-phase fault poses the
more feasible than ever. The small-scale generator, also known as a highest magnitude of short circuit current in networks. Under
microsource or distributed energy resource (DER), has been around certain circumstances, however, other fault types would provide the
for some time, but its utilisation was limited to emergency backup highest level. For instance, the current magnitude of a phase-to-
systems or to feed power into isolated rural areas. These days, ground fault near a solidly grounded generator is drastically higher
however, small-scale generators are more common contributors to than a three-phase one. The fault current level depends on the
power generation. network topology, grounding arrangements, as well as the number
The dispersion of DER throughout the power grid leads to the of in-service generators. In addition to the pick-up settings of PDs,
concept of distributed generation (DG). Due to different coordination between some types of PDs depends on the fault
government regulations and varieties in utility policies, several current level. Thus, anything that can affect them, should be
definitions for DG have been presented. A survey done by considered in the fault calculation.
Congress International des Reseaux Electtriques de Distribution In power systems with numerous high capacity sources, the
(CIRED) showed the dissensus in the DG concept among experts addition of small DG units does not change the short circuit current
[1]. With this in mind, the International Energy Agency (IEA) and magnitude. On the other hand, the integration of many small- and
the Institute of Electrical and Electronic Engineers (IEEE) classify medium-sized DG units or high-capacity DG units should be taken
any source which is connected to the distribution level and which into account in the fault calculation as these conditions certainly
delivers power to the load as DG [2, 3]. impact the fault current level.
The rate of integration of DG units to the distribution level to The contribution of a DG unit to a fault current is related to the
meet the increasing power demand grows as a reasonable type of DG unit, which can be characterised as synchronous
replacement for costly network expansion. While this integration generators, induction generators and inverter-based units. However,
brings many advantages to consumers and power grids, it also the response of each type to a fault and its contribution to the fault
becomes a challenge from protection and control perspective. current varies.
Recent research study has highlighted the negative effects of DG Synchronous generators are mostly used in genset and
units on short circuit currents and overcurrent (OC) protection combined heat and power (CHP) DG units. To see the contribution
systems in distribution networks. Change in the direction of fault of the synchronous generator-based DG unit to the fault current
current flow, increase or decrease of fault current magnitude, the level, a simple case is studied.
blindness of protection, sympathy feeder trip, nuisance trip of the Most of the elements in electrical networks can be modelled as
circuit interrupting devices, and disruption of coordination between a series or parallel or series–parallel resistor and inductor (R–L)
protective devices (PDs) are some of the possible impacts of DG circuit, and hence the fault has a resistive–inductive nature [4].
unit integration. Fig. 1 depicts a circuit model for fault analysis in which the switch
This paper reviews possible challenges that protection system is used to model the short circuit. R + jXL is the summation of the
faces when a distribution network turns into an active electrical
synchronous generator internal impedance and the transmission
system, and the benefits and drawbacks of suggested solutions are
line impedance.
investigated.
Using the differential equation, the steady-state AC short circuit
current is given in (1).
2 Effect of DG units on fault current

IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960 5944
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Vs
iac t = 1 − e− t / T (1)
R

where T is the time constant defined in (2):

L XL
T= = (2)
R Rω

In reality, capacitors and inductors in networks store energy. This


energy will discharge during the fault and will increase the short
Fig. 1  Circuit model for fault current analysis [4]
circuit current. The additional short circuit current caused by the
stored energy is called the DC fault component and is shown in
following equation:

idc t = I0e−(t / T ) (3)

Total fault current, also known as asymmetrical fault current is


represented in (4).

Vs V s −(t / T )
if t = iac t + idc t = + I0 − e (4)
R R

According to Fig. 2, the DC component causes the fault current to Fig. 2  Asymmetrical fault current [4]
increase at the inception of the fault. This component will rapidly
decay. How fast the DC part decays, depends on the time constant
T given in (2).
Such a nature of the fault current is represented by the reactance
of a synchronous generator that varies from the inception of the
fault to the steady-state. Three different reactances are defined:
subtransient X′′d , transient X′d , and synchronous Xd reactance
[5]. Subtransient reactance is used for fault calculation during the
first cycle after fault inception. This condition lasts for ∼0.1 s. This
is followed by the transient condition, which continues for 0.5–2 s.
Finally, synchronous reactance is applied for the steady-state fault
calculation [5].
The contribution of induction machines to a fault current is Fig. 3  Three-phase fault at the terminal of an induction machine [4]
quite high at the beginning of the fault and decays quickly. The
fault current gets to zero in the steady-state condition because an substantially, which can deteriorate coordination between fuses.
induction machine is a self-excited machine and the flux in the This might even worsen with a higher DG penetration [7].
stator decays rapidly during fault without an external voltage In addition, the results of this study indicated that the short
source. The inertia of the induction machine affects the duration of circuit current of a phase-to-ground fault is somewhat higher than a
the fault. The heavier the induction machine is, the longer the fault three-phase fault current when a delta–wye transformer with
duration lasts [5]. Fig. 3 represents the fault current changes when grounded wye side delivers power to the grid from DG. The
a three-phase fault is developed at the terminal of an induction grounded wye side of the transformer causes the zero-sequence
machine. current to flow [7]. In general, X0 / X1 of the grid affects the
From the circuit analysis point of view, transient and magnitude of the zero-sequence current.
synchronous reactances reach infinity at the steady-state resulting In [8], six different inverters were examined and were
in the fault current decaying to zero [4, 5]. The behaviour of the ultimately classified into two categories based on their
induction motor and generator is identical. It also should be disconnection speed. One model is disconnected in less than one
mentioned that the contribution of wound-rotor and squirrel-cage cycle after the fault, and hence its contribution to the fault current
induction machines to the fault current are similar [5]. is almost zero. The second model is disconnected after several
Inverter-based DG units are rather new technologies and their cycles (up to 10 cycles) with a small contribution to the fault
contribution to the short circuit current has been studied in several current. The other difference is in the waveform of the fault
papers. The first attempt to address this issue was in 1985/1986 in current. In the first model, a sudden increase in magnitude occurs
Gardner, Massachusetts. A 13.8 kV feeder was chosen and 30 at the inception of the fault and then the fault current decreases to a
photovoltaic (PV) sources containing static power inverters with a negligible value while the magnitude of the waveform in the
capacity of 2 kW, were installed at the end of one phase [6]. The second model decreases slightly after the fault is developed.
study showed the small contribution of the inverters to the fault. According to the IEEE standard, if inverter terminal voltage is
The contribution was less than twice the rated inverter peak current <0.5 pu, PV unit will be disconnected in <6 cycles and therefore,
and continued <200 µs because the inverters turned off within one- PV unit contribution to the fault can be neglected. For inverter
half cycle after the fault inception. Therefore, the impact of terminal voltage higher than 0.5 pu during the fault, the PV unit
inverter-based DG units on the fault current was negligible and did contribution can impact the fault current since it may take up to
not affect the fault duration. The study also analysed 3 MW DG 120 cycles for the inverter to get disconnected [9].
units installed at various places along the feeder. The results In addition, it has been concluded that the contribution of the
indicated no influence on the fault current and no effect on PV inverter to the fault does not exceed 120% of the rated current
coordination between fuses [6]. of the inverter although the contribution is completely dependent
Another study confirmed that the contribution of an inverter- on the terminal voltage of the PV inverter [8].
based DG unit connected through a low impedance to the grid is so Another investigation has been conducted to determine the
small that it can be ignored [7]. On the other hand, a higher effects of the inverter control method on the fault conditions. Two
impedance between the inverter-based DG unit and the grid current control methods, one based on the synchronously rotating
increases the contribution of the DG unit to the fault current reference frame and the other using the stationary reference frame,
have been studied [10]. The results concluded that the outer control

IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960 5945
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Table 1 Contribution of Different DG types to Fault Current stationary reference frame contributes significantly to the positive
[14] sequence component [10].
Type of DG unit Contribution to Fault Current developed In general, based on the studies it can be stated that the
at the Terminal of Generator contribution of inverter-based DG units to the fault current would
Inverter-based 1–2 times the inverter rated current, duration not exceed 200% of their rated current [6–8, 10–13]. The
would be from a half cycle to several cycles contribution of different types of DG units to the fault current is
depending on the control method summarised in Table 1 [14].
According to the fact that the DG unit, regardless of its type,
will contribute to the fault current even if this contribution is
Synchronous 5–10 times the generator rated current for the negligible, the integration of DG units at the distribution level
Generator with subtransient and transient cycles, 2–4 times would cause the short circuit current in other parts of the network
Separate Exciter the generator rated current for steady-state to change.
Source condition A study of a simple radial network shows that integration of a
synchronous DG unit with the capacity of 1.5 MW will change the
Induction Generator 5–10 times the generator rated current for the short circuit current in different parts of the network. The point of
or Self-excited first few cycles, negligible after 5–10 cycles connection of the DG to the grid and location of the fault can affect
Generator the fault level in these parts. Fig. 4 depicts such simple network. As
can be seen, when there is no DG (Fig. 4a), the fault current
through RC1 and RC2 are the same for the fault on the feeder
marked by X. By adding the DG after RC1 (Fig. 4b), IUS decreases
while the fault current through the RC2 rises. Changing DG
connection to the location after RC2 (Fig. 4c) will result in the
reduction of fault current through RC1 and RC2. By placing the DG
after RC2 and fault location on the lateral feeder (Fig. 4d), the fault
current IUS drops and the fault current through RC2 flows in the
opposite direction. If IR exceeds the setting of recloser RC2, the
recloser will trip and terminate the power, which is not acceptable
from protection considerations [15].
Since many DG units can be installed at the distribution level,
the effect of DG units on the recloser–fuse sets has been
investigated in several studies. The connection of a DG unit after
recloser as shown in Fig. 5, can affect the fault current flowing
through the recloser. If a fault is developed on the tapped line and
the capacity of the DG is significant, then the fault current through
the fuse could be greater than the fault current through the recloser
[14, 16–19]. According to Fig. 6, this condition will worsen with
Fig. 4  DG impact on radial distribution network several DG units connected to downstream feeders.
(a) Typical radial distribution feeder without DG, (b) Typical radial distribution feeder In addition, the distance between the interconnected DG unit
with DG before recloser and fault at the end of feeder, (c) Typical radial distribution and the fault location would affect the fault current seen by recloser
feeder with DG after recloser and fault at the end of feeder, (d) Typical radial and fuse. The further the DG unit is from the recloser, the more the
distribution feeder with DG after recloser and fault before recloser [15] fault current seen by the recloser will decrease [17]. Also, a higher
change in fault level will occur when the DG unit with a
synchronous generator is used. On the other hand, inverter-based
DG units have the least effect on the short circuit current and its
duration [17].
Typically, several distribution feeders are connected in parallel
to sub-transmission substations. In this case, any DG unit on one
feeder would affect the fault current through the upstream circuit
breaker (CB)/recloser as well as fuses on parallel feeders. For
instance, as illustrated in Fig. 7, for a fault on feeder 2, if the size
of DG1 is significant enough, then the fault current seen by CB1/
Fuse1 will be greater than the short circuit current through the main
Fig. 5  Effect of DG unit on the current of recloser and fuse [16]
CB on the grid side. In other words, the introduction of the DG unit
to the feeder 1 will lead to the decrease of the fault current through
CB and increase of the fault current through CB1/Fuse1 [18–22].
The presence of DG2 at the same time on feeder 2 can even
exacerbate the condition causing the fault current through the CB
on the grid side to drop dramatically.
The fault current seen by CB2/Fuse2 in this case depends on
whether there is a DG on feeder 2 or not. In the case of a small size
DG2 on feeder 2, the short circuit current through CB2/Fuse2 is
substantial. On the other hand, a larger DG2 leads to a small fault
current flowing through CB2/Fuse2.
Fig. 6  Recloser–fuse set with several DG units connected after recloser The impact of several DG units connected to a feeder on the
[14] fault current seen by a CB/fuse located on the feeder have been
investigated in [22]. In this study, the DG units are in the form of
loops, current regulation scheme and synchronising scheme can PV sources. To calculate the contribution of each PV source to the
impact the fault current. However, the contribution of the inverter CB/fuse short circuit current, a generalised circuit, shown in Fig. 8,
to the short circuit current is insignificant. Moreover, during the has been proposed. Here, PD is the corresponding CB or fuse of
phase-to-ground fault, the synchronously rotating reference frame the feeder, I1 indicates the contribution of the PVs on adjacent
provides a considerable negative sequence component while the feeders and the grid side, I2 shows the contribution of all the PVs

5946 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
between the PD and the fault point and I3 represents the double-phase-to-ground faults will cause the highest fault currents
contribution of all the PVs after the fault location. in the feeder next to the faulty feeder.
The fault current seen by the PD can be approximately shown in
(5) [22]. 3 Effect of DG units on protection systems
Zs Any changes in the fault current level at any point within the power
IPD = IS + I system would affect the operation of PDs. This section reviews the
Zs + Z1 + Z2 + Z3 + Rf 1
possible negative effects that the integration of DG units would
Z3 + Rf have on PDs. These impacts can be classified as follows:
− I (5)
Zs + Z1 + Z2 + Z3 + Rf 2
Rf • Reverse power flow.
− I • False tripping.
Zs + Z1 + Z2 + Z3 + Rf 3
• Blinding of protection.
Both rising and falling terms contribute to the fault current. • Unwanted islanding.
Depending on the size of PV sources at each part of the feeder, the • Unsynchronised reclosing.
fault current would increase or decrease. In addition, the duration • Loss of main power.
of the contribution of each PV source to the fault current is related
to their distance from the fault. The further the PV source is, the 3.1 Reversed power flow
longer its contribution to the fault will be. The reason is that the
terminal voltage of a remote PV source drops lower compared to In the conventional distribution network, the power flows from the
the one close to the fault. Since the short circuit current of the PV transmission to the downstream loads on the distribution side,
source does not exceed twice its rated current, the contribution of which causes the unilateral flow of power. The integration of DG
the PV sources will be smaller than the contribution from the grid. units to the distribution level of the power network would cause the
However, any level of contribution to the fault changes the fault power flow direction to change depending on the size of the DG
current seen by CBs and fuses which leads to other protective unit [19, 24, 26]. Fig. 7 (ignoring the fault and DG2) illustrates an
problems [22]. example of reverse power flow. Without DG1, the power only
In the aforementioned cases, only radial distribution networks flows from the grid to the loads on feeders 1 and 2 while the
have been taken into account. Other studies on looped distribution presence of DG1 would change the direction of power flow in part
systems show that the fault current in the loops will only rise when of feeder 1. The size of the DG should be large enough to provide
DG units are connected to any busbar within the loop [23, 24]. the required power for loads on feeder 2. If the reverse current
In [25], the effect of different size of asynchronous DG units on flowing through CB1/Fuse1 goes beyond the current setting of
the fault current in a looped distribution network has been CB1 or rated current of Fuse1, CB1/Fuse1 would operate, which is
examined. It has been indicated that the sizes of connected DGs unacceptable.
and the location of the fault have a significant impact on the fault
current. For a fault on one feeder, the short circuit current in the 3.2 False tripping
adjacent feeder is higher when more DGs on the adjacent feeder False tripping, also known as a nuisance or unwanted tripping, is a
come into service. The higher fault current on the neighbouring condition in which an inappropriate PD operates or backup PD
feeder happens when the fault is developed farther from the functions sooner than the primary one. False tripping can cause a
beginning of the other feeder except for the phase-to-ground fault healthy feeder to become disconnected or an unnecessary outage of
cases. The study also represents that the phase-to-ground and a distribution feeder to occur (this type of false tripping is also
known as sympathetic tripping). For instance, in Figs. 4d, 5 and 6,
the fuse on the lateral feeder should only clear permanent faults.
All temporary faults, which occur most of the time, should be
cleared by the upstream recloser on the substation side. Locating
the DG units at any point after the recloser will increase the fault
current through the fuse and therefore, the fuse would blow up for
a temporary fault and give rise to an unnecessary feeder
disconnection [14–18, 27, 28].
Another example of unwanted tripping is illustrated in Fig. 7, in
which a fault on feeder 2 may cause the CB or the fuse located on
the adjacent healthy feeder to operate incorrectly. In this case,
before DG integration, the fault on feeder 2 is only fed by the grid
while after DG integration, the fault current can also flow through
feeder 1. If the capacity of connected DGs is significant, the fault
current through CB1/Fuse1 can exceed the setting of the CB or the
rated current of the fuse and prompt incorrect operation of CB1/
Fuse1 [18, 19, 22].
It has been shown in several papers that the interconnection of
DG units to downstream feeders in distribution networks would
cause false tripping of PDs on the healthy feeders [15, 16, 19, 21–
26, 29]. In looped distribution networks or networks with multiple
Fig. 7  Parallel distribution feeders with their interconnected DG units
distribution feeders connected to a substation, the situation can get

Fig. 8  Contribution of different PV sources to the fault current [22]

IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960 5947
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Fig. 9  MV network with DG unit
(a) Single-line diagram, (b) Thevenin equivalent circuit [30]

Fig. 10  Impact of DG unit on the fault currents of branches in a sample network [31]

complicated and even deteriorate because different PDs can be delivers power to the grid. The ratio between these two currents is
falsely affected, and numerous healthy feeders may be taken out of described in (6).
service due to DG units on these healthy feeders [16, 21–25, 29,
30]. I1 Zg Zs + ZL
= (6)
I k Z s Z g + Z L + Z LZ g
3.3 Blinding of protection
where ZS is the aggregate of the impedances on the grid side, Zg
Blinding of protection happens when a PD, which must operate and
clear the fault, is rendered inoperative. For instance, when the fault shows the impedance of the DG and ZL represents the impedance
current seen by an overcurrent protective device (OCPD) falls of the feeder to the fault point. Based on (6), the DG unit might
behind its setting due to changes in network configuration, the PD reduce the contribution of the grid to the fault current with respect
cannot detect the fault and, consequently, it does not trip. to the impedances of the grid and the DG unit in addition to the
In Fig. 5, one of the most usual blindings of protection cases is fault location. In other words, the connection of the DG will result
represented. Most of the faults in transmission and distribution in a reduction of the fault current seen by the relay at the beginning
networks are temporary faults and, therefore, the faulty feeders do of the feeder. If the grid impedance is very high and the impedance
not need to be taken out and checked by the crews for the fault. of the feeder to the fault point is negligible (e.g. fault occurs at the
Reclosers, in this case, operate two or three times and close the very beginning of the feeder), the fault current seen by the feeder
feeder breaker. If the fault is a self-cleared one, the reclosing action relay before and after the connection of the DG will be somewhat
will be successful. On the other hand, when a permanent fault is equal. However, if the size of the DG is high and the impedance to
developed on the lateral feeder, the recloser will be blocked after the fault point is significant, the fault current seen by the relay in
two or three recloses and other PDs (e.g. the fuse on the lateral the presence of the DG unit will decrease significantly [30, 31]. It
feeder for the fault on it as shown in Fig. 5) will function and should be mentioned that for the sake of simplicity, the voltage
remove the fault. The interconnection of a DG unit after the magnitude and angle of the DG unit in Fig. 9 is assumed to be
recloser, when a temporary fault on the tapped line occurs, will equal to the grid voltage magnitude and angle during the fault. In
cause the fault current through the recloser to drop and as a result, reality, these voltages are different, and they have an impact on the
the recloser would not clear the fault before the fuse melts [14–19, fault current measured by the feeder relay; however, this effect can
22, 30]. This problem is depicted in Figs. 4b, 6 and 7. The size of be neglected comparing to the effect of impedances.
the DG unit, location of the fault, network impedance and fault To define how the impedances of the grid, feeders and DG unit
resistance can affect the fault current through an OCPD. can cause the blinding of protection, the fault current on a lateral
The effect of the size of DG units can be described by (5). feeder and the contribution of the grid to the short circuit current
According to this formula and Fig. 8, if the sizes of DG units with and without the DG unit are calculated for a sample network
I2 and I3 are significant, their contribution to the fault will grow, represented in Fig. 10 [31].
resulting in a decrease of the fault current seen by PD. In other For a three-phase fault on the lateral branch, the fault current
words, the high penetration DG units I2 and I3 will reduce the through the recloser and the fuse will be identical when no DG unit
contribution of the upstream DG units as well as the contribution of is connected to the network.
the grid to the fault. On the other hand, if their contributions are
negligible (i.e. their sizes are small), then the PD senses almost the V
IR without_DG = IF without_DG = (7)
same fault current as if no DG was connected [22]. ZS + ZL
In [30], the impact of the DG impedance and the location of the
fault on the blinding of protection have been discussed. Fig. 9 With the DG unit in play, the short circuit current seen by each
shows a medium voltage (MV) network with a DG unit and its recloser and fuse are given in (8) and (9), respectively. As evident
Thevenin equivalent circuit. An OCPD is installed at the beginning from these equations, the current through the recloser decreases in
of the feeder before the DG unit. The fault can be developed at any the presence of the DG unit, while the fault current seen by the fuse
location along the feeder. increases [31].
Presume Ik is the fault current seen by the feeder relay when
there is no DG unit. The relay then measures I1 when the DG unit V V
IR with_DG = = (8)
ZS + ZL(ZS + Zg)/Zg ZS + ZL (ZS /Zg) + 1

5948 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
V The blinding of protection for a radial feeder with different OC
IF with_DG =
ZL + (ZSZg)/(ZS + Zg) relays has been investigated and it has been shown that
V (9) interconnection of the considerable size of DG units between two
=
ZL + ZS /((ZS /Zg) + 1) OC relays, will lead to the reduction of the fault current measured
by the backup relay for a fault in front of the primary relay. The
The amount of increase and reduction in both the currents depends fault current is so low that the backup relay cannot detect the fault
on the network and the DG unit impedances. A small size DG unit at all. In the case of primary relay failure, the backup relay cannot
connected to a strong network will decrease the recloser fault detect and clear the fault [32]. Fig. 12 depicts this case. OC relay R1
current to a lesser extent while a larger size DG unit integrated to a is the backup relay for relay R2 for the fault in front of R2 in this
weak network will reduce it significantly and lead to blinding of sample radial distribution network. The connected DG contributes
protection [31]. to the fault in such a way that the backup relay R1 might not sense
Consider Fig. 11 to find the influence of the fault resistance on the fault depending on the size of the DG unit.
the fault current through the OCPDs in the presence of DG units. In a looped distribution network or radial distribution networks
The fault current through each of PD1 and PD2 are given in (10) with several radial feeders connected to a substation, the
and (11), respectively. connection of any DG unit to any point of the loop or any point on
the parallel feeders will lead to blinding of protection [23–25, 29].
VS Z2 + Rf Connecting passive DG units, such as wind turbines and PV units,
IPD1 = − I (10) in which there is no control over the input (and therefore to the
ZS + Z1 + Z2 + Rf ZS + Z1 + Z2 + Rf 1
output) of the unit makes the problem even more complicated. It is
VS ZS + Z1 shown that the reduction in the wind turbine generation will cause
IPD2 = + I (11) the relay on the nearby feeder not to sense the fault current
ZS + Z1 + Z2 + Rf ZS + Z1 + Z2 + Rf 1
occurring on this feeder [24].
In all the aforementioned works, the blinding of protection in
For a low resistance fault close to the beginning of the second
OCPDs (e.g. OC relay, CB, recloser and fuse) have been discussed.
feeder (Z2 is small), ZS + Z1 ≫ Z2 + Rf and the fault currents
The impact of DG units on the distance relay can appear either in
IPD1 and IPD2 can be approximated the following: the form of under-/over-reach [29, 33–34] or in the form of
blinding of protection [34]. In addition, the impact of a
VS synchronous DG unit on the distance relay is more pronounced
IPD1 ≅ (12)
ZS + Z1 than from an inverter-based DG unit [34].
Distance relay calculates the impedance based on the
VS measurement of the voltage and current at the installation point,
IPD2 ≅ + I1 (13)
ZS + Z1 and therefore any change in the voltage and/or the current can
change the measured impedance. For instance, as shown in Fig. 13,
Regarding the above equations, in a low resistance fault near the a fault at point F2 is in the second zone of relay R1 before
DG unit, the fault current seen by IPD1 remains approximately interconnection of the DG unit.
unchanged while IPD2 rises. When a high resistance fault far from After DG integration, the fault current IF1 decreases and relay R1
the DG unit ZS + Z1 ≪ Z2 + Rf occurs, IPD1 drops and IPD2 is may see the fault in its third zone meaning the DG unit gives rise to
almost constant according to (14) and (15). the under-reach of the distance relay or R1 cannot detect the fault at
all. The same problem can occur for the fault at point F1. This fault
VS is in the first zone of relay R1 before the DG connection. However,
IPD1 ≅ − I1 (14) the presence of the DG unit will cause the fault current through this
Z2 + Rf
relay, IF′ 1, to reduce, resulting in the under-reach phenomenon in
VS distance relay R1.
IPD2 ≅ (15)
Z2 + Rf
3.4 Nuisance islanding
Therefore, the low resistance fault will bring about false tripping Nuisance islanding, also known as unwanted islanding or
while the high resistance fault gives rise to the blinding of unwanted/nuisance tripping of production units, refers to the
protection.

Fig. 11  Effect of fault resistance on the fault current seen by each PD [22]

Fig. 12  Blinding of protection in radial distribution network

IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960 5949
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Fig. 13  Effect of DG units on distance relays

condition in which a part of distribution system unintentionally, fault current magnitude could be below the device settings [17, 30,
and with no preplan, becomes isolated from the rest of the power 32].
system.
In conventional distribution networks, when the distribution 4 Impact of DG units on the coordination between
network gets disconnected from the rest of the system for any
reason, the network is completely de-energised, and therefore no
PDs
problem arises in terms of personnel safety and protection systems. Distribution networks can be classified by voltage level into two
However, active distribution networks, with several DG units, categories: low voltage (LV) distribution systems (voltage range
would still be energised even though it is isolated from the main <600 V) and MV distribution systems with a voltage range
generation source. Aside from the hazards for maintenance crews, between 600 V and 69 kV. A combination of distance and
the protection system of distribution networks is not designed to directional OC relays is typically used in MV distribution networks
deal with the islanding conditions. During the islanding, the short with voltages of 33 kV and above to protect them against faults. In
circuit level in the isolated part decreases due to a reduction in MV distribution networks with voltage <33 kV, definite time and
generation. If a fault occurs in the isolated part, the protection inverse time OC relays, reclosers and high voltage fuses are
system might not detect it during islanding mode and the fault generally the backbone of protection systems. In LV distribution
would not be cleared. Consequently, in addition to the destructive networks, fuses are typically applied for protection purposes. A
damage to equipment, people will be exposed to fatal electrical sample distribution network including a protection system is
hazards. represented in Fig. 14. As mentioned above, the integration of DG
units would pose the problem of false tripping and/or the blinding
3.5 Unsynchronised reclosing of protection to the protection system, resulting in disrupted
coordination between PDs.
Most of the faults throughout power systems are temporary and In conventional radial distribution networks, the OC relays are
self-clearing. Therefore, the application of reclosers for momentary non-directional. In addition, reclosers are coordinated with fuses in
disconnects is prevalent nowadays, especially with respect to a way that reclosers operate and clear temporary faults first. In case
distribution grids to improve the power quality of the networks [17, of a permanent fault, fuses will blow up and isolate the faulted
35]. When a fault happens, the PDs detect and initiate a trip to area. Now the protection system of active distribution grids is
CBs, and thus the feeding of the short circuit will be interrupted. investigated in the following.
After the reclose interval period (dead time), the recloser closes For a fault on bus 5 as shown in Fig. 14, the contribution of
back the CB. The reclose interval time is usually between 0.2 and DG3 to the fault will cause the fuse F22 to be subjected to the
0.5 s depending on the network conditions. This procedure is reverse fault current. If this reverse fault current is significant
typically implemented two to four times. For temporary faults, the enough, F22 will blow and all the consumers on this otherwise
reclosing function will restore power to consumers, while for healthy feeder will experience an outage. If the contribution of
permanent faults, the recloser will be blocked after two to four DG1 is substantial enough, the fault current from the grid flowing
reclosing attempts and consumers at the distribution level will be through the recloser RC2 falls while the fault current seen by F2
exposed to sustained interruption until maintenance crews detect increases and may go above its rated current. As a result of DG1
and eliminate the root cause of the fault. and DG3 connections to the grid, F2 would blow and RC2 might
The introduction of DG units to distribution networks means not operate, leading to miscoordination between RC2 and F2.
continuous feed to the fault even though the CB at the head of the The same can happen when a fault is developed on branch 1 in
feeder is tripped by its corresponding PD. The DG will keep the presence of DG2. In this case, the contribution of DG2 to the
injecting the current to the fault, and hence the fault is not cleared fault can be significant enough to reduce the portion of the current
and the arc at the fault location is not fully dissipated. from the grid, leading to miscoordination between F1 and RC1.
Consequently, the recloser procedure will fail. This condition is The deterioration of coordination between reclosers and fuses due
called unsynchronised/out-of-phase reclosing [17, 35]. to the presence of DG units has been investigated and discussed in
The damaging of rotating DGs, deterioration of the equipment many studies [15–19, 37–40].
insulation, reduction of apparatus service life and increase in The impact of DG units on coordination between fuses is the
maintenance costs are some impacts of out-of-phase reclosing. subject of many examinations [16, 19, 26, 28, 38, 41]. Each fuse
Additionally, power quality issues, such as prolonged power has two curves: minimum melting (MM) and total clearing (TC).
outages, is another undesirable effect of reclosing failure [35]. Two fuses are coordinated if, for any fault along the feeder on
Inverter-based DG units would be less vulnerable to which the main fuse is located, the TC characteristic of the backup
unsynchronised reclosing because they are equipped with current fuse is below the MM characteristic of the main fuse by a secure
surge protection [35]. margin. Connection of DG units would cause miscoordination
The incompatibility of DG integration and auto reclosing has between fuses, depending on the location of the DG units. For
been reported in many research works [22, 31, 32, 36]. instance, DG2 connected to bus 2, will increase fault current for
any fault located along branch 1. If the coordination between F1
3.6 Loss of main power and F11 still exists for higher short circuit current, then it is not
likely affected [16, 38]. For DG4 integrated to branch 2,
If the main grid is disconnected for any reason, a part of the system miscoordination between F1 and F12 is obvious: for a fault on
will be in islanding mode. DG units in the islanded part can cause branch 2, fuse F12 must blow sooner than fuse F1 while, for a fault
safety problems. Moreover, the DG units contributing to the fault on feeder 1 (between recloser RC1 and bus 2), fuse F1 must
current may not trigger the OCPDs in the islanded part because the operate faster than fuse F12. Therefore, coordination criteria

5950 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Fig. 14  Sample distribution network

cannot be fulfilled since both fuses sense the same fault current R3 for downstream faults and now it should operate faster than R3
[16, 42]. for upstream faults, which is infeasible [15, 16, 22, 29, 30, 33, 42,
Miscoordination between reclosers and fuses is another topic of 49, 51].
interest that has been discussed in [16, 19, 43–48]. Reclosers are
used to avoid permanent interruption and save fuses when 5 Improvement of protection systems in
temporary faults occur. In case of permanent faults, reclosers
advance to their slow curves and let fuses to blow up and clear the
distribution networks with DG units
fault. Studies have demonstrated that the coordination between Many attempts have been made to mitigate the impact of DG units
recloser and fuse no longer exists when a DG unit with on the power systems to which they are connected. Some solutions
considerable penetration is located between them. In Fig. 14, for consider protection system reformation while a few of the others
instance, the fault current seen by recloser RC2 is reduced for a take the capacity and the characteristics of DG units into account.
temporary fault on bus 5 and DG1 in service. In this case, the fuse The suggested methods can be classified as follows.
F2 may blow faster than recloser RC2 leading to miscoordination
between RC2 and F2. 5.1 Disconnection of DG units
Another problem appears in the coordination of OC relays. In
Fig. 14, OC relays R2 and R3 are coordinated in a way that R3 Disconnecting all DG units during the fault is the easiest solution
initiates first for the faults on branch 5 and R2 operates only when for this problem [17, 19, 21, 46]. Since most of the faults in
R2 does not clear the fault. If DG1 is only connected to the grid, distribution networks are temporary faults, disconnecting all DG
for a fault on branch 5, the fault current through R3 increases while units is not reasonable and prevents the network from taking
the fault current seen by R2 drops, and hence the coordination is advantage of the connection of DG units. Another disadvantage of
still maintained. With the only DG5 integrated to the network, the this method is the voltage sag issue when high penetration DG
fault current through both relays will increase for the fault on units are disconnected. In addition, utilities do not have access to
branch 5. In this case, coordination between OC relays R2 and R3 DG units installed by customers and therefore, cannot shut them
would be lost. So, depending on the type, capacity and location of off. This method needs a fault detection system at the DG location.
connected DG units in addition to the fault location, coordination The fault detection system should detect the fault at the very
between OC relays might no longer exist [13, 16, 21, 23–25, 32, beginning of the fault and should be able to distinguish between the
33, 49–53]. Consequently, for the DG units connected between the fault and other disturbances like switching heavy loads. In some
primary and backup OC relays, coordination will still be valid, cases, reclosers may clear the fault very fast before the fault
while the integration of DG before the backup OC relay would lead detection system of the DG unit can detect the fault and shut off
to miscoordination. These concerns cannot be applied to inverter- DG.
based DG units since their contribution to the fault current is The suggested method in [56] is based on the disconnection of
limited to twice the inverter rated current [54, 55]. the DG units from the faulted area and reconnection to the rest of
Finally, the reverse fault current can flow through PDs due to the network through other paths if any. This method needs to
the connection of DG units to the network. Besides its impact on monitor and control all CBs remotely. Therefore, a costly
fuse–fuse coordination and fuse maloperation discussed above, the communication channel as well as the installation of CBs all over
reverse fault current gives rise to the coordination conflict between the grid is required.
OC relays. In Fig. 14, OC relay R2 is a backup for R3, and its
operating time is longer. For a fault on bus 1, while DG6 is
connected to branch 5, relay R2 should be initiated faster than R3
and clear the fault. However, OC relay R2 is the backup relay of

IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960 5951
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
5.2 Recalculation and/or resizing of protective devices It is suggested to connect SFCL in series with DG unit to limit
its current during the fault condition [63, 64, 68, 69] while other
DG units will change the fault levels in the grid, resulting in a potential locations for placement of SFCL have also been
deterioration of coordination between OCPDs. To avoid selectivity investigated [65, 69, 70]. The installation of SFCL at a specific part
disruption, the configuration of the distribution system, which of the network can reduce the contribution of that part to the fault
encompasses DG units, should be investigated and new settings for current. Following the DG unit connection, its adverse effect on
reclosers, OC and distance relays should be chosen based on the OCPDs located on this part of the grid can be mitigated. This
fault analyses and coordination studies [18, 23, 27, 33, 38, 39, 43– method, however, results in a rise of operating times of OCPDs
45, 55, 57–61]. In addition, fuses should be resized based on new when DG units are out of service and, therefore, the time setting of
conditions. PDs should be reduced. Furthermore, other non-fault transients can
Since fuses and reclosers are the most common PDs in cause SFCL to trigger. For instance, the starting current of wind
distribution networks with voltage levels up to 20 kV, several turbine generators can trigger the SFCL incorrectly and give rise to
papers have addressed fuse–recloser miscoordination in the a deep voltage drop along downstream distribution feeders [65].
presence of DG units in these networks [39, 43–45, 58]. Installing Another disadvantage of SFCLs emerges in relation to
DG unit between the fuse and recloser (for instance DG2 on bus 2 renewable-based DG units due to the uncertainty of the output
as shown in Fig. 14) would bring about the blinding of protection generation. Due to the variation in generated power, the
in the recloser and false tripping in the fuse. Their solution to avoid contribution of renewable-based DG units to the fault fluctuates,
this problem and regain coordination is based on the calculation of making it complicated to find a specific setting for SFCL.
the fault current for the fuse and recloser for the worst-case Coordinating reclosers and SFCLs is another issue that has
scenario. The recloser curves are then scaled down based on the drawn the attention of researchers [78]. It has been shown, when
fuse–recloser ratio (FRR), which is the ratio of the fault current the SFCL current setting is greater or equal to the recloser current
seen by the fuse to the fault current seen by the recloser. For this setting, the recloser will fail to operate. The setting of the SFCL
solution to be effective, the recloser should be of the must be less than the recloser setting for the recloser to operate
microprocessor type with a variety of curves [43]. In this solution, properly [78].
the fuse remains unchanged and only the recloser curves are shifted The application of FCL to restore coordination between OCPDs
to meet new conditions. has been examined in [66, 67]. The FCL is connected in series to
Studies have shown that the recalculation of OC relay settings the DG unit to reduce the fault current to the values when no DG is
based on the maximum generation of integrated PV sources solves integrated into the network. The results show that coordination is
the misoperation of OC relays [55, 60, 61]. However, this solution restored successfully with no need to any extra cost or change in
degrades the sensitivity of the entire protection system, especially PDs [66, 67]. Since the network configuration is subjected to a
when PV sources do not contribute to power generation [55]. variety of changes, coordination might no longer exist with FCL in
The problem with this method is that the DG units are not service. FCL could negatively impact the coordination between
always in service. The output of the renewable-based DG units, PDs by reducing the fault current when it is not needed.
such as PV units or wind turbines, is variable and fluctuates as Finding the optimal size and/or location of FCL has been
weather conditions vary. Therefore, the calculation of optimal investigated in some research works [71–77]. This method has the
settings for fuses, reclosers and relays is not feasible. Moreover, aforementioned issues of using FCL. Additionally, since the
higher time settings obtained in this method, result in an increase network configuration changes intermittently, the optimal size
of the fault-clearing time, when DG units are not in service. This and/or location of FCL that works for a given network
longer clearing time would put the equipment and stability of the configuration, may not work for other network configurations.
network at risk.
5.5 Limiting DG size
5.3 Directional protection
The size and location of DG units can aggravate miscoordination in
Since the fault current can flow in any direction in the network distribution systems [16, 39]. Thus, the largest possible size of a
with DG units, coordination between OC relays and reclosers no DG unit for which the coordination between PDs is still maintained
longer exists. To solve miscoordination, equipping OC relays with should be identified [39, 40, 45, 49, 51, 63, 64, 79, 80].
directional element has been proposed in some research studies No need to change the existing protection system or to install
[33, 38, 51, 59, 62]. Directional OC relays at both ends of feeders new devices are the upsides of this method. However, simply
with DG units can maintain coordination and improve the considering protective issues alone and eliminating other issues,
selectivity of the protection system. such as power quality and reliability of the system, is this method's
However, adding directional OC relays to both ends of feeders disadvantage. It also requires restricting the capacity that private
in an active distribution network makes the coordination more entities can install, which is not practically feasible.
complicated since DG units are not always in service [51] and Finding optimal DG size that satisfies loss reduction, voltage
contribution of inverter-based DG units to the fault current is profile improvement and protection coordination retention has been
negligible [55, 62]. Moreover, such a solution is only applicable to examined in [81]. The study has demonstrated that the optimal DG
OC relays and reclosers as fuses cannot be equipped with the size is dependent on the DG location and by changing the place of
directional element. DG across the network, different DG sizes, as well as different
values in loss reduction and voltage magnitude, can be achieved.
5.4 Application of fault current limiter
DG units can increase short circuit current level in distribution 5.6 Inverter control methods for inverter-based DG units
networks leading to the loss of coordination between OCPDs. If the The protective problems described in the previous sections are less
fault current remains unchanged in the presence of DG, likely to occur in the presence of inverter-based DG units due to
coordination can be maintained. Considering this fact, some their smaller contribution to the fault current. However, an inverter-
researchers have proposed the application of fault current limiter based DG unit increases the possibility of recloser failure, or it can
(FCL) or superconducting fault current limiter (SFCL) [63–77]. worsen islanding problems. To eliminate the effect of inverter-
SFCL is a device, which uses superconductors to limit the based DG units on PDs completely, several solutions have been
magnitude of current during a fault. Underrated current conditions, proposed in [17, 82–87].
the resistance of the device is low and allows the current to pass Disconnecting inverter-based DG units from the grid when a
through it. During the fault, the resistance of the device increases fault or islanding occurs is one of the solutions [17]. Disadvantages
rapidly and reduces the fault current. The current at which SFCL of this method have been discussed in Section 5.1.
resistor increases is called SFCL operating current and should be Reducing the inverter current during the fault has been
designed specifically based on network conditions. proposed as another solution to maintain coordination. To do so,
different control strategies have been introduced [82–87]. A fast
5952 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
and reliable fault detection method is required to trigger the the real-time scenario, the settings of PDs are calculated and
inverter current control procedure. changed online based on the current condition and configuration of
One of the control strategies is to use the point of common the system.
coupling (PCC) voltage to detect the fault and reduce the inverter Using the pre-calculated scenario, a study has been done to
current when the PCC voltage falls behind a predefined value (88% change the setting of OC relays during islanding and grid
of the nominal voltage at PCC) [82, 85]. The suggested method in connection [89, 90]. The method utilises voltage values to detect
[86] has used voltages in α–β stationary reference to reduce the the islanding and OC relay settings are readjusted accordingly.
output real power and therefore to decrease the inverter current. To During the islanding, frequency is monitored to detect re-
generate the α–β stationary voltage, the voltage after the inverter energising of the grid. When the grid is back in service, the OC
filter has been used. The drawback of these strategies is that some relay will switch to its previous settings. The settings of OC relays
non-fault disturbances, such as heavy load switching may cause the in the grid connection mode could be different based on the
voltage at PCC or inverter filter to drop. In cases of short circuit connection/disconnection of several DG units [89].
with very low fault current such as high impedance fault, the Online methods suggest online monitoring of the network and if
current reduction is not necessary [83]. To address the former any change in the network configuration or DG generation occurs,
downside, the current of the PD ahead of the DG unit is taken into load flow and the short circuit should be run based on the new
account in addition to PCC voltage. If the PCC voltage is lower condition [68, 92–94]. The pickup current and/or time setting of
than a predefined value and the current of the intended PD is relays and reclosers then should be updated according to new load
greater than a preset value, the current reduction control will be flow and short circuit results.
activated to decrease the output current [83]. In some situations, The combination of offline and online methods has been
there is a significant distance between the locations of the PD and investigated to overcome miscoordination between OC devices in
the DG unit. This requires a communication channel between them, the distribution networks [48, 91, 95]. In this method, several
which adds to the cost or it might not be possible at all. If there is network configurations and different DG generations are
more than one PD ahead of the DG unit, the application of this considered to obtain different settings of OC relays and reclosers.
method is very complicated if not impossible. DG1 in Fig. 14 with Those values are set on the relays and reclosers. Then network
two PDs (R1 and F1) in front of it is an example of this kind of conditions are monitored online and when a change occurs, a signal
network configuration. will be sent to PDs to change their settings and adjust them with
Application of phase lock loop (PLL) along with the voltage the new conditions.
drop at the inverter output (the voltage after inverter filter) to detect In [91] a comprehensive adaptive protection system has been
the fault and reduce the inverter current is another proposed designed by combining offline and online methods. In the offline
method [87]. The inverter output currents are used as the input of segment, short circuit currents, as well as load flow for different
PLL. If the error signal of PLL exceeds a predefined threshold, scenarios (DG connections or changes in the network
then the inverter current is reduced by changing the reference real configuration), are calculated. The results are then stored in the
power to zero while the reference reactive power is kept above zero adaptive protection system. During network operation, if the sum
[87]. The predefined threshold of PLL should be set correctly of the phase currents is equal to the total load current, the system is
otherwise other disturbances like inrush current of transformer or in the normal condition. Otherwise, if the sum is zero, then a fault
capacitor switching can trigger the inverter current control is developed at a DG unit terminal. After clearing the fault, the
procedure. system should be updated, and load flow and short circuit analyses
Application of a flywheel doubly-fed induction machine (FW- should be run again. If the sum is significantly greater than the total
DFIM) energy storage system in parallel with conventional load current, then the greatest phase current is compared with the
inverter-based DG unit is suggested in [84]. The DW-DFIM system short circuit currents stored in the adaptive protection system to
improves the power quality of renewable DG units in normal detect the faulted area. A trip will be initiated then to open the
conditions as well as provides an exponentially decaying current corresponding CBs and to isolate the faulted area. After that,
during the fault in order to trigger PDs. This combination emulates reclosers will reclose back the CBs to restore the network in case
the synchronous generator response during faults [84]. Such a of a temporary fault. For a permanent fault, the CBs remain open
control strategy is only appropriate when OC relays are used. In the and the network information will be updated. The load flow and
case of a fuse–recloser arrangement, this control method can short circuit will be run, and new results will be stored in the
expedite the operation of the fuse, which is not satisfactory. For adaptive protection system.
example, in Fig. 14, an inverter-based DG1 with this control The offline adaptive protection system needs a very complex
method enhances coordination between R2 and R3, but it calculation to consider all the conditions and the system can fail if
deteriorates coordination between RC2 and F2. Besides, this unforeseen circumstances occur. The online methods should be
method is costly as it needs a three winding transformer and FW- fast, and a large amount of data is required to make the decision. If
DFIM energy storage system. the fault and the change in network configuration or DG generation
occur at the same time, the online method will fail. Additionally, a
5.7 Adaptive protection fast communication system should be installed in the distribution
networks along with a full monitoring and control system, which
Adaptive protection can be defined as an online modification of are costly.
protective settings to address changes in the network by means of
external control signals. Using this concept, some researchers 5.8 Multiagent-based method
considered potential advantages of adaptive protection to enhance
protection of distribution networks with high penetration of DG The multiagent-based adaptive protection scheme to enhance the
units [43, 44, 48, 58, 68, 88–95]. OC protection in active distribution networks has been introduced
To tackle the recloser–fuse miscoordination, online in [24, 96–100]. A multiagent scheme is a structure, in which all
modification of the recloser curves based on FRR is recommended. objects (also known as agents) involved in a problem deal with
If the FRR < 1, the fault current seen by the recloser is less than the each other and share the data to resolve the problem [96]. Relays,
fault current through the fuse and, hence, the recloser curves CBs, current transformers, voltage transformers (PT/VT) or
should be scaled down to maintain the recloser–fuse coordination capacitor voltage transformers, PD coordination, configurator and
[43, 44, 58, 88]. DG units form the agents. Agents are independent functioning
Adaptive protection for OC relays can be used in two ways: without any human control. They can communicate with each other
pre-calculated (offline) setting and real-time (online) setting [58]. and react to any changes in the system. The relay agents report
In the pre-calculated scenario, settings of different cases are their fault currents to the coordination agent, and it shares the data
calculated and stored in the OC relay and an external signal will with the configurator. The configurator defines the fault location
activate the appropriate setting. This external signal is generated and provides a list of relays to trip or block and sends back the list
based on changes in current, voltage and/or equipment statuses. In to the coordination agent, from where the relay agents get either

IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960 5953
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
trip or block signal [24, 96, 97]. Some schemes suggest data together to differentiate between normal and fault conditions [62].
exchange between relay agents, which enables each relay to make Additionally, this protection scheme must be equipped with a
decision autonomously based on the neighbours' data [98–100]. directional relay to properly detect the fault direction [62]. This
In [98], each relay agent sends out the wavelet coefficients of protection scheme can effectively detect the fault in the presence of
the current it senses to the nearby relay agents, while in other a DG unit as well as maintains the coordination between OC relays
research works, phasor values are used to detect the faulted section. [109–111]. Voltage dependency is the downside of this method, in
This method requires fast communication system for which the installation of PT/VT is costly and, in some cases, not
transferring data between agents and when the communication feasible due to the lack of room.
channel is down, or the data is distorted, the performance of the
method is in doubt. 5.12 Network matrix algorithm

5.9 Application of distance protection Network matrix and fault direction matrix can be used to determine
the faulted section [112]. The network matrix demonstrating the
Distance protection is applied to the transmission and sub- network structure has rows equal to the number of feeders and
transmission levels and due to its high price, it is not used at the columns equal to the number of nodes and shows how feeders are
distribution level. Nowadays, the integration of DG units to the connected to nodes. This matrix should be developed before the
distribution level has raised several protection issues for the fault inception. The fault direction matrix is another required
OCPDs, especially OC relays. Consequently, the application of matrix, which is created after the fault initiation based on the data
distance protection at the distribution level has caught the attention received from FTUs. The disadvantage of this method is
of some researchers [58, 101–103]. Distance protection is requirement for large memory capacity to store the network matrix
fundamentally directional and can cope with the bilateral fault and updating this matrix after each change in the network topology.
current flow caused by the connection of DG units. Likewise, Distortion of data from FTU affecting the fault direction matrix
coordinating distance relays is much easier than OC relays because also causes incorrect fault detection.
the change of the fault current has a little impact on distance To reduce the size of the network matrix, it is suggested to use
protection. However, the over-reach and under-reach of distance the network fault-related matrix, with only feeders and nodes that
relay, the effect of the resistive fault on its reach and coordination get involved in the fault [113]. In this approach, both fault-related
with recloser are challenging issues that should be addressed. and fault direction matrix rely on the data coming from FTUs and
Adaptive distance protection has been suggested in [103] to are negatively affected by possible data distortion.
mitigate the impact of DG unit on the distance relay, which appears
in the form of under-reach or over-reach of its zones. 5.13 Artificial neural network (ANN) and optimisation method

5.10 Application of differential protection ANNs application to protection has drawn the attention of
researchers [114, 115]. Although it can accurately detect the faulted
Partial line differential protection [58, 104], phase differential segment, it has many disadvantages. First, it requires training for
protection [105, 106], amplitude difference [107] and differential different fault types and fault locations. Secondly, if the network
current ratio [108] are other solutions investigated in research configuration changes, the method is more likely to detect the
studies. faulted section incorrectly. Finally, the results indicate that ANN
In partial differential protection, the subtraction and summation suffers from inaccuracy when a high impedance fault is developed,
of the currents at both ends of the line or feeder are compared in which case the impedance fault cannot be predicted before the
against each other. If the subtraction is greater than the summation, fault [115].
there is a fault on the feeder. Otherwise, the fault is out of the The iterative optimisation methods have been investigated in
protection zone or the network is under normal condition [58]. In [116–120]. They use the fault data collected by FTUs to structure
[104] the application of positive sequence current in the differential an objective function. The objective function shows whether a
scheme for feeders without lateral branches has been suggested. switch senses the fault current or not. An optimal method is then
For feeders with lateral branches, the voltage should be considered applied to solve the objective function and to detect the faulted
in addition to differential current to detect the internal fault section. Although the optimisation method tolerates data distortion,
accurately. If the voltage is below the threshold while the it must be run iteratively to get the result and the solution may not
differential current is above the setting value, there is an internal converge in the real distribution networks with hundreds of
fault [104]. switches. Even if the method converges in the real distribution
In the phase differential, the differences between current phases network, the possible long convergence time makes this method
at both ends are compared. If the phase difference is in the range of slow and ineffective since the fault must be detected and isolated
−90°, 90° , there is a fault on the feeder. If the phase difference is quickly. Additionally, this method needs FTU to be installed at all
equal to −180°, the fault is out of the intended feeder or there is no switches as well as a communication network to transfer data.
fault in the network [105, 106]. This kind of protection can provide The method proposed in [121] applies the shortest path
precise protection in the network with DG units and changes in the optimisation to locate the fault. This method is only practical for
fault current caused by DG units turning on and off cannot affect it. smaller networks with a few dozen nodes. For larger distribution
It does not need to be coordinated with other PDs in the network networks, this method needs a longer time to detect the faulted
since it is unit-type protection and its protection zone is limited to section or may not converge at all.
both ends of the feeder. However, this protection system requires a
fast, reliable communication channel to exchange current 5.14 Other methods
information.
The proposed methods in [107, 108], which work based on Replacing the fuse with a sectionaliser to have better control and to
finding the largest fault current, are very restrictive since they maintain coordination [19] and finding the best location for the DG
cannot detect the fault properly if more than one fault occurs connection to maintain coordination between PDs [44] have been
simultaneously in the network. If the DG contribution to the fault proposed in some research papers. However, these methods are
current is smaller than what is supplied by the grid, these methods very expensive, and the latter may not be feasible for all networks
cannot find the faulted section. Additionally, these methods need and customers.
the feeder terminal unit (FTU) to be installed with all the switches Using the magnitude of fault current contributed by all power
in the distribution network. sources, including the DG unit, to determine the faulted line is
another suggested solution [122]. This method needs a matching
table that can be obtained by running the short circuit program
5.11 Voltage-dependent OC protection
offline to calculate and store the maximum and minimum fault
This protection is based on the fact that the voltage drops during currents of each bus for different fault types. When a fault occurs,
the fault while the current rises. The current and voltage are used the contributed fault currents’ magnitudes are collected and

5954 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
compared to the matching table. If the current is between the coefficients of other currents from neighbour relays are used to
minimum and maximum magnitudes, that feeder could be a faulted detect the faulted section.
line. The method requires very large memory capacity to store Several improved impedance-based methods have been
short circuit currents, is dependent on the network topology, calls suggested, in which voltages and currents of several nodes are used
for the matching table to be updated after each change, and to increase the accuracy [128–133]. These methods assume that
depends on prefault conditions. Moreover, for the feeders with no impedance of distribution feeders is available. The results indicate
DG connected at their end (also known as passive branches), the that the proposed methods are more accurate than traditional
fault current magnitude of that line is required as well to methods for active distribution networks. Distribution feeders are
distinguish the faulted feeder. exposed to damages and therefore must be replaced or repaired in
Four-way circuit switches with OC relays are another possible case of any damage. Any changes in the feeder or its conductors
solution for active distribution networks with renewable-based DG result in the feeder impedance change, which can impact the
units [123]. In this scheme, two load break switches (LBS) and two outcome of these methods. The impedance matrix in these methods
CBs are used to connect renewable-based DG units to the must be updated after each maintenance in order to accurately
distribution network. The renewable-based DG unit is connected to estimate the fault location.
either LBS or CB while the other LBS and CB are connected to the These approaches are very complicated since they are iterative
feeder. The OC relay of this four-way circuit switches should be methods and require all the network data to calculate the fault
coordinated with the other OC relays on the feeder. location. In some cases, the prefault [130] and/or the postfault
[128] currents and voltages are required, which increase the
6 Fault location complexity and calculation time and may result in degrading the
accuracy in case of lacking the valid updated data.
6.1 Impact of DG units To avoid using voltages and currents of several nodes, a method
Finding the location of temporary and permanent faults in the described in [134] suggests the application of feeder positive
distribution networks is very important to improve power sequence impedance and the prefault load current as well as the
reliability and quality. It helps the maintenance crew to inspect the fault current of one node, where the fault locator is installed. These
faulted segment for possible damage after a transient fault or to data are used to estimate preliminary fault location and then the
repair the faulted section and restore the service in the shortest time distance to the fault and load current are modified iteratively to
possible after a permanent fault. Traditional fault location methods find the final fault location [134]. This model simplifies the
known as a distance-based method, are mostly based on the distribution network as the inherent unbalance in distribution
impedance calculation using the measured currents and voltages at systems and mutual coupling between phases are eliminated. A
the main substation. These methods are subjected to substantial revised approach to consider both network unbalanced nature and
errors in the distribution networks with DG units. Studies indicate mutual coupling is presented in [135]. Both techniques rely on the
that the position of loads, the location of the fault, the fault impedance database. If the impedance database is not up-to-date,
resistance, the point at which DG unit is connected to the significant error in estimating the fault location will occur.
distribution network and the type and capacity of the DG unit have Methods to estimate fault location in active distribution
the significant impacts on the error of fault location identification networks with the application of ANN are presented in [136–138].
[124–127]. An offline simulation for different types and locations of the faults
For the fault located upstream of DG unit, the calculated fault should be run to create a database for ANN training. Since their
location is fairly close to the real fault location. The fault location training is restricted, estimates of the real conditions would not be
is estimated farther than it actually is when the fault occurs at the accurate enough especially when the network configuration
downstream of the DG unit due to the decrease of contribution of changes. As it is not possible to train an ANN before changes
the main substation to the fault current [124, 126]. happen, it is more likely to have a considerable fault distance error
Comparing synchronous-based and induction-based DG units, for any possible untrained topology. Additionally, data distortion
the internal voltage of induction machines collapses few cycles can negatively impact ANN functionality, which has not been
after the inception of the fault while the internal voltage of the discussed.
synchronous machines maintains almost unchanged during the
fault. Consequently, the contribution of induction machines to the 7 Summary
fault current decays after few cycles while synchronous generators Tables 2 and 3 summarise the methods to improve protection
keep contributing to the fault current for fault duration. Therefore, systems and enhance the estimation of fault location in active
synchronous machines significantly degrade the accuracy of the distribution networks, respectively.
fault location [124]. Generally, if the DG unit capacity is
significant or the network behind the DG unit is weak (i.e. the short
circuit capacity of the network is smaller than the DG unit), the 8 Conclusion
impedance-based fault location algorithms undergo considerable DG integration has become more prevalent since it adds flexibility
error for the faults located downstream of the DG unit [126]. to the network. Such integration, however, brings about challenges
Studies have confirmed that distance-based methods are and complexity to the protection and control system of the
exposed to errors in the presence of high penetration of DG units network. Network operation and planning benefit from DG
[125, 127]. The fault location is overestimated in the presence of connection, while protection and control systems suffer from this
DG units. integration. This paper has reviewed possible issues when DG units
Another problem of the distance-based methods is the effect of are introduced to distribution networks and has critically portrayed
the load. Loads in distribution systems are distributed along the all the efforts that the researchers have undertaken to address these
feeders resulting in significant errors when the distributed loads issues.
between the main substation and the DG unit are large [125–127]. This critical review indicates that many suggested workarounds
The impact of the load can be relieved to a large extent by utilising cannot be generalised for all distribution networks. Without
load compensation methods [125, 127]. modernising distribution systems and introducing more smart
detection means, an effective approach to determine and isolate
6.2 Solutions faults would be out of the reach.
Using a travelling wave to estimate the fault is proposed in [98].
The method extracts the wavelet coefficients first and then
calculates the time difference between transients. The wavelet-
based method finds the accurate fault distance, but it needs to find
the faulted section first and then uses the appropriate current to
estimate the fault location. To do so, the extracted wavelet

IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960 5955
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Table 2 Suggested methods to improve protection systems in active distribution networks
Method Advantage Disadvantage
disconnecting all DGs during fault – easy to apply – not reasonable for temporary faults
– no need to install new – cannot be applied to DGs installed by private sector
devices or change current
protective system

disconnecting DGs from faulted area – needs to monitor and control all CBs remotely
and connecting to other unfaulted – needs a communication channel
parts – difficult, if not impossible, to be implemented

recalculation/resizing of protective easy to apply – finding optimal settings for fuses, reclosers and relays is not feasible
devices since DG units are not always in service or their outputs (in case of PV
units or wind turbines) fluctuate
– using higher time settings in this method, results in increase of the
fault-clearing time, when DG units are not in service

directional protection maintains coordination – needs PT to be installed


– needs directional OC relays on both ends of feeders
– coordination is more complicated due to increase in number of OC
devices
– only applicable to reclosers and OC relays and not fuses

fault current limiter maintains coordination – reduces the contribution of other part of network to the fault current.
OC protective devices in those parts are affected
– prolongs the operating time of OC protective devices when no DG is in
service
– other non-fault transients such as the starting current of wind turbine
generators can trigger SFCL incorrectly
– when SFCL current setting is greater or equal to the recloser current
setting, the recloser will fail to operate
– network configuration changes, may result in miscoordination with FCL
in service

limiting DG size maintains coordination – restricts customers


– other factors such as power quality and reliability of the system are not
considered to calculate DG size

disconnection of inverter-based DG maintain coordination – eliminating the advantages of DG units during islanding
units – not reasonable for temporary faults
– cannot be applied to inverter-based DGs installed by private sector

reducing the inverter current during maintain coordination in high – non-fault disturbances, such as load increase may cause the voltage
the fault fault current drop at PCC
– current reduction is not necessary in case of very low fault current
(e.g. high impedance fault)

application of FW-DFIM energy – improves the power quality of – only appropriate for OC relays
storage renewable DG units in normal
conditions
– emulates the synchronous – worsens coordination between fuse–recloser
generator response during – it is costly
faults

pre-calculated (offline) – maintains coordination – needs accurate network data


– high flexibility – needs very complex calculation to consider all conditions
– very likely to fail if unforeseen circumstances occur
– inapplicable to fuses

real-time (online) – maintains coordination – needs accurate network data


– high flexibility – after any change in network, new load flow and short circuit currents
should be recalculated
– needs a fast communication system
– inapplicable to fuses

5956 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License

Method Advantage Disadvantage
multiagent-based method – maintains coordination – needs a fast communication system to share data between
agents and the control center
– high flexibility - data distortion impacts the method performance
– high accuracy

regular distance protection – inherently directional – subjected to over-/under-reach in the presence of DGs
– can be coordinated easier than OC – fault resistance impacts its reach
relays – coordination of distance relays and reclosers is challenging
– it is costly

adaptive distance protection – inherently directional – coordination of distance relays and reclosers is challenging
– can be coordinated easier than OC – it is costly
relays
– less subjected to over-/under-reach
– less impact of resistive fault

partial line differential protection – high accuracy – needs communication channel to transfer data between two
– detects the fault very fast ends
– does not need to be coordinated
with other protective devices

phase differential protection the same advantages as partial line the same disadvantages as partial line differential protection
differential protection method method

amplitude difference – cannot detect the fault properly if more than one fault occurs
simultaneously
– cannot find the faulted section if DG contribution to the fault
current is smaller than grid contribution
– needs the feeder terminal unit (FTU) to be installed with all
switches in network

differential current ratio the same disadvantages as amplitude difference method

voltage dependent overcurrent maintains coordination – needs directional element


protection – needs PT to be installed

network matrix algorithm high accuracy – needs pre-fault calculation


– needs precise network data
– needs bulk memory capacity to store network matrix
– data distortion impacts the method performance

ANN high accuracy for trained cases – training for different fault types and fault locations is required
– the method is more likely to misoperate if the network
configuration changes
– the method operates inaccurately when a high impedance fault
occurs

replacing fuses with sectionalisers – enhances controllability it is costly


– maintains coordination

finding the best location for the DG – easy to apply is not feasible for all networks and customers
connection – no need to install new devices or
change current protective system

using the contribution of all sources to – needs bulk memory capacity to store short circuit currents
the fault – depends on the network topology
– matching table to be updated after each change in network
– depends on pre-fault conditions
– needs fault current of feeders with no DG connected at their
end

four-way circuit switches with OC – maintains coordination – it is costly


relays

IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960 5957
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Table 3 Proposed methods to enhance estimation of fault location
Method Advantage Disadvantage
travelling wave high accuracy – needs to find the faulted section first and then uses the appropriate current to
estimate the fault location

improved impedance- more accurate than traditional – needs accurate impedance of distribution feeders
based methods methods – very complicated since they are iterative methods
– some proposed methods require pre-fault and/or post-fault currents and
voltages
– some methods eliminate inherent unbalance in distribution systems and
mutual coupling between phases

ANN high accuracy for trained cases – training for different fault types and fault locations is required
– the method is more likely to miscalculate the fault distance if the network
configuration changes

9 References [22] Baran, M.E., Hooshyar, H., Shen, Z., et al.: ‘Accommodating high PV
penetration on distribution feeders’, IEEE Trans. Smart Grid, 2012, 3, (2), pp.
[1] CIRED.: ‘Dispersed generation; preliminary report of CIRED’. Int. Conf. on 1039–1046
Electricity Distribution, Working Group WG04, Brussels, Belgium, June 1999 [23] Maki, K., Repo, S., Jarventausta, P.: ‘Effect of wind power based distributed
[2] International Energy Agency (IEA).: ‘Distributed generation in liberalized generation on protection of distribution network’. Eighth IEE Int. Conf. on
electricity market’ (IEA Publications, 2002) Developments in Power System Protection, 2004, vol. 1, pp. 327–330
[3] IEEE.: ‘IEEE standard for interconnecting distributed resources with electric [24] George, S.P., Ashok, S.: ‘Multiagent based adaptive relaying for distribution
power systems’, IEEE Std 1547–2003, July 28 2003, pp. 1–28 network with distributed generation’. Int. Conf. on Energy, Power and
[4] Keller, J., Kroposki, B.D.: ‘Understanding Fault Characteristics of Inverter- Environment: Towards Sustainable Growth (ICEPE), Shillong, 2015, pp. 1–6
Based Distributed Energy Resources’, National Renewable Energy [25] Driesen, J., Vermeyen, P., Belmans, R.: ‘Protection issues in microgrids with
Laboratory, January 2010 multiple distributed generation units’. Power Conversion Conf. (PCC ‘07),
[5] IEEE Std 141-1993.: ‘IEEE recommended practice for electric power Nagoya, 2007, pp. 646–653
distribution for industrial plants’, April 1994, pp. 109–184 [26] de Britto, T.M., Morais, D.R., Marin, M.A., et al.: ‘Distributed generation
[6] Gulachenski, E.M., Kern, E.C.Jr., Feero, W.E, et al.: ‘Photovoltaic Generation impacts on the coordination of protection systems in distribution networks’.
Effects on Distribution Feeders (No. EPRI-EL-6754-Vol. 2)’, Electric Power IEEE/PES Transmission and Distribution Conf. and Exposition: Latin
Research Inst., Palo Alto, CA (United States); New England Power Service America, 2004, pp. 623–628
Co., Westborough, MA (United States), Ascension Technology, Lincoln [27] Jennett, K.I., Booth, C.D., Coffele, F., et al.: ‘Investigation of the sympathetic
Center, MA (United States); Electric Research and Management, Inc., State tripping problem in power systems with large penetrations of distributed
College, PA (United States); Worcester Polytechnic Inst., MA (United States), generation’, IET Gener. Transm. Distrib., 2015, 9, (4), pp. 379–385
September 1991 [28] Walling, R.A., Saint, R., Dugan, R.C., et al.: ‘Summary of distributed
[7] Kroposki, B., Vaughn, A.: ‘DG Power Quality, Protection, and Reliability resources impact on power delivery systems’, IEEE Trans. Power Deliv.,
Case Studies Report’, National Renewable Energy Laboratory, August 2003 2008, 23, (3), pp. 1636–1644
Available at http://www.nrel.gov/docs/fy03osti/34635.pdf [29] Hussain, B., Sharkh, S.M., Hussain, S.: ‘Impact studies of distributed
[8] Katiraei, F., et al.: ‘Investigation of solar PV inverters current contributions generation on power quality and protection setup of an existing distribution
during faults on distribution and transmission systems interruption capacity’. network’. Int. Symp. on Power Electronics, Electrical Drives, Automation and
Proc. 39th Annual Western Protective Relay Conf., Spokane, WA, 2012 Motion (SPEEDAM 2010), Pisa, France, 2010, pp. 1243–1246
[9] IEEE 929: ‘IEEE recommended practice for utility interface of photovoltaic [30] Kauhaniemi, K., Kumpulainen, L.: ‘Impact of distributed generation on the
(PV) systems’, 2000 protection of distribution networks’. Eighth IEE Int. Conf. on Developments
[10] Behnke, M., Ellis, A.: ‘Contribution of photovoltaic power generation in Power System Protection, 5–8 April 2004, Vol. 1, pp. 315–318
systems to AC short circuits – a survey of current modeling practices and [31] Dai, F.T.: ‘Impacts of distributed generation on protection and autoreclosing
challenges’. IEEE 39th Photovoltaic Specialists Conf. (PVSC), Tampa, FL, of distribution networks’. 10th IET Int. Conf. on Developments in Power
2013, pp. 3128–3133 System Protection (DPSP 2010), Manchester, UK, 2010, pp. 1–5
[11] Turcotte, D., Katiraei, F.: ‘Fault contribution of grid-connected inverters’. [32] Ogden, R., Yang, J.: ‘Impacts of distributed generation on low-voltage
IEEE Electrical Power & Energy Conf. (EPEC), Montreal, QC, 2009, pp. 1–5 distribution network protection’. 50th Int. Universities Power Engineering
[12] Ball, G.J., Blackburn, D.C., Gish, W., et al.: ‘Static power converters of 500  Conf. (UPEC), 1–4 September 2015, pp. 1–6
kW or less serving as the relay interface package for non-conventional [33] Cheung, H., Hamlyn, A., Wang, L., et al.: ‘Investigations of impacts of
generators’, IEEE Trans. Power Deliv., 1994, 9, (3), pp. 1325–1331 distributed generations on feeder protections’. IEEE Power & Energy Society
[13] Firouz, Y., Farhadkhani, S., Lobry, J., et al.: ‘Numerical comparison of the General Meeting, Calgary, Canada, 2009, pp. 1–7
effects of different types of distributed generation units on overcurrent [34] Nimpitiwan, N., Heydt, G.T., Ayyanar, R., et al.: ‘Fault current contribution
protection systems in MV distribution grids’, Renew. Energy, 2014, 69, pp. from synchronous machine and inverter based distributed generators’, IEEE
271–283 Trans. Power Deliv., 2007, 22, (1), pp. 634–641
[14] Barker, P.P., De Mello, R.W.: ‘Determining the impact of distributed [35] Dugan, R.C., McDermott, T.E.: ‘Operating conflicts for distributed generation
generation on power systems: part I. Radial distribution systems’. IEEE on distribution systems’. Rural Electric Power Conf., Little Rock, AR, 2001,
Power Engineering Society Summer Meeting, Seattle, WA, 2000, vol. 3, pp. pp. A3/1–A3/6
1645–1656 [36] Katiraei, F., Iravani, M.R., Lehn, P.W.: ‘Micro-grid autonomous operation
[15] Doyle, M.T.: ‘Reviewing the impacts of distributed generation on distribution during and subsequent to islanding process’, IEEE Trans. Power Deliv., 2005,
system protection’. IEEE Power Engineering Society Summer Meeting, 20, (1), pp. 248–257
Chicago, IL, 2002, vol. 1, pp. 103–105 [37] Silva, J.A., Funmilayo, H.B., Bulter-Purry, K.L.: ‘Impact of distributed
[16] Girgis, A., Brahma, S.: ‘Effect of distributed generation on protective device generation on the IEEE 34 node radial test feeder with overcurrent
coordination in distribution system’. Large Engineering Systems Conf. on protection’. 39th North American Power Symp. (NAPS ‘07), Las Cruces,
Power Engineering (LESCOPE ‘01), Halifax, NS, 2001, pp. 115–119 NM, 2007, pp. 49–57
[17] Morren, J., Haan, S.W.H.D.: ‘Impact of distributed generation units with [38] Zamani, A., Sidhu, T., Yazdani, A.: ‘A strategy for protection coordination in
power electronic converters on distribution network protection’. IET 9th Int. radial distribution networks with distributed generators’. IEEE PES General
Conf. on Developments in Power System Protection (DPSP 2008), Glasgow, Meeting, Minneapolis, MN, 2010, pp. 1–8
2008, pp. 664–669 [39] Habibabadi, R.A.: ‘New method on the relays protective coordination due to
[18] Hadjsaid, N., Canard, J.F., Dumas, F.: ‘Dispersed generation impact on presence of distributed generation’. IEEE Power Engineering and Automation
distribution networks’, IEEE Comput. Appl. Power, 1999, 12, (2), pp. 22–28 Conf. (PEAM), Wuhan, China, 2012, pp. 1–4
[19] IEEE Power System Relay Committee.: ‘Impact of distributed resources on [40] Chaitusaney, S., Yokoyama, A.: ‘Impact of protection coordination on sizes of
distribution relay protection’. IEEE, August 2004 several distributed generation sources’. Int. Power Engineering Conf.,
[20] Driesen, J., Belmans, R.: ‘Distributed generation: challenges and possible Singapore, 2005, Vol. 2, pp. 669–674
solutions’. IEEE Power Engineering Society General Meeting, Montreal, [41] Dugan, R.C., Rizy, D.T.: ‘Electric distribution protection problems associated
Canada, 2006, pp. 1–8 with the interconnection of small, dispersed generation devices’, IEEE Trans.
[21] Vijitha, K., Selvan, M.P., Raja, P.: ‘Short circuit analysis and adaptive zonal Power Appar. Syst., 1984, PAS-103, (6), pp. 1121–1127
protection of distribution system with distributed generators’. Int. Conf. on [42] Koumba, P.M., Chériti, A., Doumbia, M.L.: ‘Impacts of distributed generation
Energy, Power and Environment: Towards Sustainable Growth (ICEPE), on the coordination of protective devices in distribution network’. IEEE 28th
Shillong, 2015, pp. 1–6 Canadian Conf. on Electrical and Computer Engineering (CCECE), Halifax,
NS, 2015, pp. 460–465

5958 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
[43] Brahma, S.M., Girgis, A.A.: ‘Microprocessor-based reclosing to coordinate [70] Zeineldin, H.H., El-Saadany, E.F.: ‘Fault current limiters to mitigate recloser-
fuse and recloser in a system with high penetration of distributed generation’. fuse miscoordination with distributed generation’. 10th IET Int. Conf. on
IEEE Power Engineering Society Winter Meeting, New York, NY, vol. 1, Developments in Power System Protection (DPSP 2010), Manchester, UK,
2002, pp. 453–458 2010, pp. 1–4
[44] Naiem, A.F., Hegazy, Y., Abdelaziz, A.Y., et al.: ‘A classification technique [71] Hongesombut, K., Mitani, Y., Tsuji, K.: ‘Optimal location assignment and
for recloser-fuse coordination in distribution systems with distributed design of superconducting fault current limiters applied to loop power
generation’, IEEE Trans. Power Deliv., 2012, 27, (1), pp. 176–185 systems’, IEEE Trans. Appl. Supercond., 2003, 13, (2), pp. 1828–1831
[45] Chaitusaney, S., Yokoyama, A.: ‘Prevention of reliability degradation from [72] Teng, J.H., Lu, C.N.: ‘Optimum fault current limiter placement with search
recloser–fuse miscoordination due to distributed generation’, IEEE Trans. space reduction technique’, IET Gener. Transm. Distrib., 2010, 4, (4), pp.
Power Deliv., 2008, 23, (4), pp. 2545–2554 485–494
[46] Tailor, J.K., Osman, A.H.: ‘Restoration of fuse-recloser coordination in [73] Jo, H., Joo, S., Lee, K.: ‘Optimal placement of superconducting fault current
distribution system with high DG penetration’. IEEE Power and Energy limiters (SFCLs) for protection of an electric power system with distributed
Society General Meeting – Conversion and Delivery of Electrical Energy in generations (DGs)’, IEEE Trans. Appl. Supercond., 2013, 23, (3), pp.
the 21st Century, Pittsburgh, PA, 2008, pp. 1–8 5600304–5600304
[47] Pan, Y., Ren, W., Ray, S., et al.: ‘Impact of inverter interfaced distributed [74] Zhao, Y., Krause, O., Saha, T.K.: ‘A new approach for optimal allocation of
generation on overcurrent protection in distribution systems’. IEEE Power multiple SFCLs in a power system with distributed generation’. IEEE PES
Engineering and Automation Conf., Wuhan, China, 2011, pp. 371–376 Asia-Pacific Power and Energy Engineering Conf. (APPEEC), Brisbane
[48] Hussain, B., Sharkh, S.M., Hussain, S., et al.: ‘An adaptive relaying scheme Australia, 2015, pp. 1–5
for fuse saving in distribution networks with distributed generation’, IEEE [75] Elmitwally, A, Gouda, E, Eladawy, S.: ‘Optimal allocation of fault current
Trans. Power Deliv., 2013, 28, (2), pp. 669–677 limiters for sustaining overcurrent relays coordination in a power system with
[49] Lu, Y., Hua, L., Wu, J., et al.: ‘A study on effect of dispersed generator distributed generation’, Alexandria Eng. J., 2015, 54, (4), pp. 1077–1089
capacity on power system protection’. IEEE Power Engineering Society [76] Elmitwally, A., Gouda, E., Eladawy, S.: ‘Restoring recloser-fuse coordination
General Meeting, Tampa, FL, 2007, pp. 1–6 by optimal fault current limiters planning in DG-integrated distribution
[50] Jennett, K., Coffele, F., Booth, C.: ‘Comprehensive and quantitative analysis systems’, Int. J. Electr. Power Energy Syst., 2016, 77, pp. 9–18
of protection problems associated with increasing penetration of inverter- [77] Ibrahim, D.K., Zahab, E.E.D.A.E., Mostafa, S.A.E.A.: ‘New coordination
interfaced DG’. 11th Int. Conf. on Developments in Power Systems approach to minimize the number of re-adjusted relays when adding DGs in
Protection (DPSP), Birmingham, UK, 2012, pp. 1–6 interconnected power systems with a minimum value of fault current limiter’,
[51] Mashayekhi, M., Meskin, M., Farahbakhsh, A.: ‘Impact of size and location Int. J. Electr. Power Energy Syst., 2017, 85, pp. 32–41
of distributed generation on overcurrent relays in active distribution [78] Rhee, S.B., Lee, J.K., Lee, B.W.: ‘Impacts of superconducting fault current
networks’. North American Power Symp. (NAPS), Morgantown, WV, 2017, limiters on the recloser operation in distribution electric power systems’,
pp. 1–6 IEEE Trans. Appl. Supercond., 2011, 21, (3), pp. 2197–2200
[52] Conti, S.: ‘Analysis of distribution network protection issues in presence of [79] Chaitusaney, S., Yokoyama, A.: ‘An appropriate distributed generation sizing
dispersed generation’, Electr. Power Syst. Res., 2009, 79, (1), pp. 49–56 considering recloser-fuse coordination’. IEEE/PES Transmission &
[53] Mashau, T., Kibaara, S., Chowdhury, S., et al.: ‘Impact of distributed Distribution Conf. & Exposition: Asia and Pacific, Dalian, China, 2005, pp.
generation on protection coordination in a radial distribution feeder’. 46th Int. 1–6
Universities’ Power Engineering Conf. (UPEC), Soest, Germany, 2011, pp. 1– [80] Sadeh, J., Bashir, M., Kamyab, E.: ‘Effect of distributed generation capacity
5 on the coordination of protection system of distribution network’. IEEE/PES
[54] Ravindra, H., Faruque, M.O., McLaren, P., et al.: ‘Impact of PV on Transmission and Distribution Conf. and Exposition: Latin America (T&D-
distribution protection system’. 2012 North American Power Symp. (NAPS), LA), Sao Paulo, Brazil, 2010, pp. 110–115
Champaign, IL, 2012, pp. 1–6 [81] Abdel-Ghany, H.A., Azmy, A.M., Elkalashy, N.I., et al.: ‘Optimizing DG
[55] Meskin, M., Iyer, P., Domijan, A.: ‘Impact of PV sources on the overcurrent penetration in distribution networks concerning protection schemes and
relays in medium voltage distribution networks’. Ninth Annual IEEE Green technical impact’, Electr. Power Syst. Res., 2015, 128, pp. 113–122
Technologies Conf. (GreenTech), Denver, Co., 29–31 March 2017, pp. 271– [82] Yazdanpanahi, H., Li, Y.W., Xu, W.: ‘A new control strategy to mitigate the
275 impact of inverter-based DGs on protection system’, IEEE Trans. Smart Grid,
[56] Viawan, F.A., Karlsson, D., Sannino, A., et al.: ‘Protection scheme for 2012, 3, (3), pp. 1427–1436
meshed distribution systems with high penetration of distributed generation’. [83] Su, C., Liu, Z., Chen, Z., et al.: ‘An adaptive control strategy of converter
Power Systems Advanced Metering, Protection, Control, Communication, based DG to maintain protection coordination in distribution system’. IEEE
and Distributed Resources, Clemson, SC, 2006, pp. 99–104 PES Innovative Smart Grid Technologies, Istanbul, Turkey, 2014, pp. 1–6
[57] Sherbilla, N.F., Kawady, T.A., Elkalashy, N.I., et al.: ‘Modified setting of [84] Abdel-Khalik, A.S., Elserougi, A.A., Massoud, A.M., et al.: ‘Fault current
overcurrent protection for distribution feeders with distributed generation’. contribution of medium voltage inverter and doubly-fed induction-machine-
IET Conf. on Renewable Power Generation (RPG 2011), Edinburgh, based flywheel energy storage system’, IEEE Trans. Sust. Energy, 2013, 4,
Scotland, 2011, pp. 1–6 (1), pp. 58–67
[58] Pan, Y., Voloh, I., Ren, W.: ‘Protection issues and solutions for protecting [85] Fani, B., Hajimohammadi, F., Moazzami, M., et al.: ‘An adaptive current
feeder with distributed generation’. 66th Annual Conf. for Protective Relay limiting strategy to prevent fuse-recloser miscoordination in PV-dominated
Engineers, College Station, TX, 2013, pp. 92–111 distribution feeders’, Electr. Power Syst. Res., 2018, 157, pp. 177–186
[59] Kamel, A., Alaam, M.A., Azmy, A.M., et al.: ‘Protection coordination for [86] Salem, M.M., Elkalashy, N.I., Atia, Y., et al.: ‘Modified inverter control of
distribution systems in presence of distributed generators’, Electr. Power distributed generation for enhanced relaying coordination in distribution
Compon. Syst., 2013, 41, (15), pp. 1555–1566 networks’, IEEE Trans. Power Deliv., 2017, 32, (1), pp. 78–87
[60] Tekpeti, B.S., Kang, X., Huang, X.: ‘Fault analysis of solar photovoltaic [87] Ebrahimi, E., Sanjari, M.J., Gharehpetian, G.B.: ‘Control of three-phase
penetrated distribution systems including overcurrent relays in presence of inverter-based DG system during fault condition without changing protection
fluctuations’, Int. J. Electr. Power Energy Syst., 2018, 100, pp. 517–530 coordination’, Int. J. Electr. Power Energy Syst., 2014, 63, pp. 814–823
[61] Fani, B., Bisheh, H., Karami-Horestani, A.: ‘An offline penetration-free [88] Shah, P.H., Bhalja, B.R.: ‘New adaptive digital relaying scheme to tackle
protection scheme for PV-dominated distribution systems’, Electr. Power Syst. recloser-fuse miscoordination during distributed generation interconnections’,
Res., 2018, 157, pp. 1–9 IET Gener. Transm. Distrib., 2014, 8, (4), pp. 682–688
[62] Meskin, M., Iyer, P., Domijan, A., et al.: ‘Enhancement of overcurrent [89] Mahat, P., Chen, Z., Bak-Jensen, B., et al.: ‘A simple adaptive overcurrent
protection in active medium voltage distribution networks’. IEEE 6th Int. protection of distribution systems with distributed generation’, IEEE Trans.
Conf. on Renewable Energy Research and Applications (ICRERA), San Smart Grid, 2011, 2, (3), pp. 428–437
Diego, CA, 2017, pp. 937–942 [90] Maki, K., Repo, S., Jarventausta, P.: ‘Methods for assessing the protection
[63] Hemmati, S., Sadeh, J.: ‘Applying superconductive fault current limiter to impacts of distributed generation in network planning activities’. 9th Int.
minimize the impacts of distributed generation on the distribution protection Conf. on Developments in Power System Protection (DPSP 2008), Glasgow,
systems’. 11th Int. Conf. on Environment and Electrical Engineering Scotland, 2008, pp. 484–489
(EEEIC), Venice, Italy, 2012, pp. 808–813 [91] Brahma, S.M., Girgis, A.A.: ‘Development of adaptive protection scheme for
[64] Lee, H.J., Son, G., Park, J.W.: ‘A study on wind-turbine generator system distribution systems with high penetration of distributed generation’, IEEE
sizing considering overcurrent relay coordination with SFCL’, IEEE Trans. Trans. Power Deliv., 2004, 19, (1), pp. 56–63
Appl. Supercond., 2011, 21, (3), pp. 2140–2143 [92] Baran, M., El-Markabi, I.: ‘Adaptive over current protection for distribution
[65] Kincaid, J., Abdulhadi, I., Emhemed, A.S., et al.: ‘Evaluating the impact of feeders with distributed generators’. IEEE PES Power Systems Conf. and
superconducting fault current limiters on distribution network protection Exposition, New York, NY, 2004, Vol 2, pp. 715–719
schemes’. Proc. 46th Int. Universities’ Power Engineering Conf. (UPEC), [93] Gaber, S., Hassan, K., Megahed, A.: ‘A novel adaptive wide area protection
Soest, Germany, 2011, pp. 1–5 scheme for smart grids with distributed generation’. Nineteenth Int. Middle
[66] El-Khattam, W., Sidhu, T.S.: ‘Restoration of directional overcurrent relay East Power Systems Conf. (MEPCON), Cairo, 2017, pp. 802–810
coordination in distributed generation systems utilizing fault current limiter’, [94] Shih, M.Y., Conde, A., Leonowicz, Z., et al.: ‘An adaptive overcurrent
IEEE Trans. Power Deliv., 2008, 23, (2), pp. 576–585 coordination scheme to improve relay sensitivity and overcome drawbacks
[67] Tang, G., Iravani, M.R.: ‘Application of a fault current limiter to minimize due to distributed generation in smart grids’, IEEE Trans. Ind. Appl., 2017,
distributed generation impact on coordinated relay protection’. Int. Conf. on 53, (6), pp. 5217–5228
Power Systems Transients (IPST'05), Montreal, Canada, June 19–23 2005, [95] Schaefer, N., Degner, T., Shustov, A., et al.: ‘Adaptive protection system for
pp. 1–6 distribution networks with distributed energy resources’. 10th IET Int. Conf.
[68] El-Khattam, W., Sidhu, T.S.: ‘Resolving the impact of distributed renewable on Developments in Power System Protection (DPSP 2010), Manchester, UK,
generation on directional overcurrent relay coordination: a case study’, IET 2010, pp. 1–5
Renew. Power Gener., 2009, 3, (4), pp. 415–425 [96] Maiola, P.C., Rolim, J.G.: ‘A multi-agent system for protection coordination
[69] Zhang, Y., Dougal, R.A.: ‘Novel dual-FCL connection for adding distributed of radial systems in the presence of distributed generation’. 11th IET Int.
generation to a power distribution utility’, IEEE Trans. Appl. Supercond., Conf. on Developments in Power Systems Protection (DPSP 2012),
2011, 21, (3), pp. 2179–2183 Birmingham, UK, 2012, pp. 1–6

IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960 5959
© The Institution of Engineering and Technology 2020
17518695, 2020, 24, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2019.1652 by CAPES, Wiley Online Library on [17/11/2022]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
[97] Wan, H., Li, K.K., Wong, K.P.: ‘An adaptive multiagent approach to [119] Gong, M., Xu, Z., Xie, Y., et al.: ‘Fault-section location of distribution
protection relay coordination with distributed generators in industrial power network containing distributed generation based on the multiple-population
distribution system’, IEEE Trans. Ind. Appl., 2010, 46, (5), pp. 2118–2124 genetic algorithm of chaotic optimization’. 2017 Chinese Automation
[98] Perera, N., Rajapakse, A.D., Gole, A.M.: ‘Wavelet-based relay agent for Congress (CAC), Jinan, China, 2017, pp. 4984–4988
isolating faulty sections in distribution grids with distributed generators’. The [120] Wu, F., Zhao, J., Zhu, B., et al.: ‘A MOPSO based faulty section location
8th IEE Int. Conf. on AC and DC Power Transmission, London, UK, 2006, method for distribution networks with PVs’. 2017 IEEE PES Asia-Pacific
pp. 162–166 Power and Energy Engineering Conf. (APPEEC), Bangalore, India, 2017, pp.
[99] Ghorbani, J., Choudhry, M.A., Feliachi, A.: ‘Fault location and isolation using 1–5
multi agent systems in power distribution systems with distributed generation [121] Contreras, A.F., Ramos, G.A.: ‘Fault location algorithm based on shortest
sources’. 2013 IEEE PES Innovative Smart Grid Technologies Conf. (ISGT), path optimization problem for distribution networks with DG’. 2014 IEEE
Washington, DC, 2013, pp. 1–6 PES T&D Conf. and Exposition, Chicago, IL, 2014, pp. 1–5
[100] Hoang, T.T., Tuan Tran, Q., Besanger, Y.: ‘A multiagent and IEC 61850-based [122] Ma, J., Lu, Y., Du, J., et al.: ‘A new fault location scheme based on distributed
fault location and isolation system for distribution network with high PV short-circuit current in distribution system with DGs’. 2008 IEEE Int. Conf.
integration – a CHIL implementation’. 2019 IEEE Int. Conf. on Environment on Sustainable Energy Technologies, Singapore, 2008, pp. 1189–1194
and Electrical Engineering and 2019 IEEE Industrial and Commercial Power [123] Chen, L.H.: ‘Overcurrent protection for distribution feeders with renewable
Systems Europe (EEEIC/I&CPS Europe), Genova, Italy, 2019, pp. 1–6 generation’, Int. J. Electr. Power Energy Syst., 2017, 84, pp. 202–213
[101] Sinclair, A., Finney, D., Martin, D., et al.: ‘Distance protection in distribution [124] EL-Fouly, T.H.M., Abbey, C.: ‘On the compatibility of fault location
systems: how it assists with integrating distributed resources’, IEEE Trans. approaches and distributed generation’. 2009 CIGRE/IEEE PES Joint Symp.
Ind. Appl., 2014, 50, (3), pp. 2186–2196 Integration of Wide-Scale Renewable Resources into the Power Delivery
[102] Chilvers, I., Jenkins, N., Crossley, P.: ‘Distance relaying of 11 kV circuits to System, Calgary, Canada, 2009, pp. 1–5
increase the installed capacity of distributed generation’, IEE Proc. – Gener., [125] Marvik, J.I., Petterteig, A., Hoidalen, H.K.: ‘Analysis of fault detection and
Transm. Distrib., 2005, 152, (1), pp. 40–46 location in medium voltage radial networks with distributed generation’. 2007
[103] Ma, J., Li, J., Wang, Z.: ‘An adaptive distance protection scheme for IEEE Lausanne Power Tech, Lausanne, Switzerland, 2007, pp. 1191–1196
distribution system with distributed generation’. 5th Int. Conf. on Critical [126] Das, S., Santoso, S., Maitra, A.: ‘Effects of distributed generators on
Infrastructure (CRIS), Beijing, China, 2010, pp. 1–4 impedance-based fault location algorithms’. 2014 IEEE PES General Meeting
[104] Gao, H., Li, J., Xu, B., ‘Principle and implementation of current differential Conf. & Exposition, National Harbor, MD, 2014, pp. 1–5
protection in distribution networks with high penetration of DGs’, IEEE [127] José, B.D.S., Cavalcante, P.A.H., Trindade, F.C.L., et al.: ‘Analysis of
Trans. Power Deliv., 2017, 32, (1), pp. 565–574 distance based fault location methods for smart grids with distributed
[105] Zhang, F., Mu, L.: ‘Wide-area protection scheme for active distribution generation’. IEEE PES ISGT Europe 2013, Lyngby, Denmark, 2013, pp. 1–5
networks based on phase comparison’. 5th Int. Conf. on Electric Utility [128] Brahma, S.M.: ‘Fault location in power distribution system with penetration
Deregulation and Restructuring and Power Technologies (DRPT), Changsha, of distributed generation’, IEEE Trans. Power Deliv., 2011, 26, (3), pp. 1545–
China, 2015, pp. 927–932 1553
[106] Alvin, T.G.M., Abidin, I.Z., Hashim, H., et al.: ‘Phase comparison protection [129] Orozco-Henao, C., Mora-Flórez, J., Pérez-Londoño, S.: ‘A robust method for
for distribution networks with high PV penetration’. IEEE Innovative Smart single phase fault location considering distributed generation and current
Grid Technologies – Asia (ISGT ASIA), Kuala Lumpur, Malaysia, 2014, pp. compensation’. Sixth IEEE/PES Transmission and Distribution: Latin
216–221 America Conf. and Exposition (T&D-LA), Montevideo, Uruguay, 2012, pp.
[107] Guo-fang, Z., Yu-ping, L.: ‘A fault location algorithm for urban distribution 1–7
network with DG’. Third Int. Conf. on Electric Utility Deregulation and [130] Alwash, S.F., Ramachandaramurthy, V.K., Mithulananthan, N.: ‘Fault-
Restructuring and Power Technologies, Nanjing, China, 2008, pp. 2615–2619 location scheme for power distribution system with distributed generation’,
[108] Guo-fang, Z., Yu-ping, L.: ‘Development of fault location algorithm for IEEE Trans. Power Deliv., 2015, 30, (3), pp. 1187–1195
distribution networks with DG’. 2008 IEEE Int. Conf. on Sustainable Energy [131] Menchafou, Y., Markhi, H.E., Zahri, M., et al.: ‘Impact of distributed
Technologies, Singapore, 2008, pp. 164–168 generation integration in electric power distribution systems on fault location
[109] Saleh, K.A., Zeineldin, H.H., Al-Hinai, A., et al.: ‘Optimal coordination of methods’. 3rd Int. Renewable and Sustainable Energy Conf. (IRSEC),
directional overcurrent relays using a new time–current–voltage Marrakech, Morocco, 2015, pp. 1–5
characteristic’, IEEE Trans. Power Deliv., 2015, 30, (2), pp. 537–544 [132] de Nunes, J.U.N., Bretas, A.S.: ‘Extended impedance-based fault location
[110] Agrawal, A., Singh, M., Tejeswini, M.V.: ‘Voltage current based time inverse formulation for active distribution systems’. 2016 IEEE Power and Energy
relay coordination for PV feed distribution systems’. National Power Systems Society General Meeting (PESGM), Boston, MA, 2016, pp. 1–5
Conf. (NPSC), Bhubaneswar, India, 2016, pp. 1–6 [133] Naidu, O., Gore, R., George, N., et al.: ‘A new approach for fault location on
[111] Jamali, S., Borhani-Bahabadi, H.: ‘Recloser time–current–voltage modern distribution systems with integrated DER’. Biennial Int. Conf. on
characteristic for fuse saving in distribution networks with DG’, IET Gener. Power and Energy Systems: Towards Sustainable Energy (PESTSE),
Transm. Distrib., 2017, 11, (1), pp. 272–279 Bangalore, India, 2016, pp. 1–6
[112] Chao, Y., Zeng, X., Xia, Y.: ‘Improved algorithm for fault location in [134] Bretas, A.S., Salim, R.H.: ‘Fault location in unbalanced DG systems using the
distribution network with distributed generations’. 2008 Int. Conf. on positive sequence apparent impedance’. 2006 IEEE/PES Transmission &
Intelligent Computation Technology and Automation (ICICTA), Hunan, Distribution Conf. and Exposition: Latin America, Caracas, Venezuela, 2006,
China, 2008, pp. 893–896 pp. 1–6
[113] Wu, N.: ‘A new fault location algorithm for distribution network with DG’. [135] Hagh, M.T., Hosseini, M.M., Asgarifar, S.: ‘A novel phase to phase fault
CICED 2010 Proc., Nanjing, China, 2010, pp. 1–7 location algorithm for distribution network with distributed generation’.
[114] Calderaro, V., Piccolo, A., Galdi, V., et al.: ‘Identifying fault location in CIRED 2012 Workshop: Integration of Renewables into the Distribution Grid,
distribution systems with high distributed generation penetration’. AFRICON Lisbon, Portugal, 2012, pp. 1–4
2009, Nairobi, 2009, pp. 1–6 [136] Javadian, S.A.M., Haghifam, M.R., Rezaei, N.: ‘A fault location and
[115] Mesbah Maruf, H.M., Müller, F., Hassan, M.S., et al.: ‘Locating faults in protection scheme for distribution systems in presence of DG using MLP
distribution systems in the presence of distributed generation using machine neural networks’. 2009 IEEE Power & Energy Society General Meeting,
learning techniques’. 9th IEEE Int. Symp. on Power Electronics for Calgary, Canada, 2009, pp. 1–8
Distributed Generation Systems (PEDG), Charlotte, NC, 2018, pp. 1–6 [137] Zayandehroodi, H., Mohamed, A., Shareef, H., et al.: ‘Performance
[116] Yue, Y., Zhao, H., Zhao, Y., et al.: ‘A study of distribution network fault comparison of MLP and RBF neural networks for fault location in
location including distributed generator based on improved genetic distribution networks with DGs’. IEEE Int. Conf. on Power and Energy,
algorithm’. 3rd Int. Conf. on System Science, Engineering Design and Kuala Lumpur, Malaysia, 2010, pp. 341–345
Manufacturing Informatization, Chengdu, China, 2012, pp. 103–106 [138] Agrawal, R., Thukaram, D.: ‘Identification of fault location in power
[117] Tao, W., Yang, G., Zhang, J.: ‘Fault section locating for distribution network distribution system with distributed generation using support vector
with DG based on improved ant colony algorithm’. IEEE 8th Int. Power machines’. IEEE PES Innovative Smart Grid Technologies Conf. (ISGT),
Electronics and Motion Control Conf. (IPEMC-ECCE Asia), Hefei, China, Washington, DC, 2013, pp. 1–6
2016, pp. 1985–1989
[118] Kong, T., Jia, M., Sun, G.: ‘Application of bacterial foraging algorithm for
fault location in distribution networks with DG’. 2016 China Int. Conf. on
Electricity Distribution (CICED), Xi'an, China, 2016, pp. 1–4

5960 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 24, pp. 5944-5960
© The Institution of Engineering and Technology 2020

You might also like