You are on page 1of 7

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/3928371

Technical requirements for the connection of dispersed generation to the grid

Conference Paper · February 2001


DOI: 10.1109/PESS.2001.970141 · Source: IEEE Xplore

CITATIONS READS
39 424

2 authors:

Stavros Papathanassiou Nikos D. Hatziargyriou


National Technical University of Athens National Technical University of Athens
183 PUBLICATIONS   5,800 CITATIONS    658 PUBLICATIONS   25,388 CITATIONS   

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

European Research Infrastructure supporting Smart Grid Systems Technology Development, Validation and Roll Out (ERIGrid) View project

DISTRES View project

All content following this page was uploaded by Nikos D. Hatziargyriou on 31 May 2014.

The user has requested enhancement of the downloaded file.


1

Technical Requirements for the Connection of


Dispersed Generation to the Grid
Stavros A. Papathanassiou, Member, IEEE, and Nicolas D. Hatziargyriou, Senior Member, IEEE

transparent, objective, widely accepted and easily applicable


Abstract-- The penetration of Dispersed Generation (DG) by utility engineers. This is now recognized by utilities and
sources in the grids is constantly increasing, as a result of both international organizations, working for the adoption of
technological advancements and institutional changes in the uniform technical procedures (e.g. [2-6]).
electric power industry. The connection of new installations is In Greece, several DG facilities (mainly renewables, such
often hindered by a variety of factors, including technical as wind and small hydro plants, often in autonomous island
considerations and requirements, usually resolved at the expense
grids) have been installed and operating during the last 15
of the investor. As the interest for installing new generation
facilities escalates, the adoption of transparent and easily years and significant experience has been accumulated
applicable technical evaluation procedures becomes more regarding their integration to the grid (typically at the MV
imperative. In this paper, the methodology and limits adopted in level). The recent deregulation of the Greek electricity sector
the connection guide of the Greek utility are outlined. Issues has created an enormous additional interest for investment in
addressed are the steady state and fast voltage variations, as well independent distributed generation. These factors called for a
as flicker and harmonic emissions. Simplified evaluation major update of the Greek connection guide, which has been
procedures are proposed, largely based on the relevant IEC recently completed by the Greek distribution utility (Public
publications, which are suitable for application by utility Power Corporation - PPC).
engineers in practical situations.
In this paper the technical requirements for the connection
of DG to the grid are presented, as included in the Greek
Index Terms—Dispersed Generation, Distribution Network,
Power Quality, Voltage Variations, Flicker, Harmonics.
guide, [6]. Issues addressed here are the slow and fast voltage
variations, flicker and harmonic emissions, whereas several
I. INTRODUCTION other important considerations (protection requirements,
network capacity, fault level contribution etc.) are left out, due

T he penetration of Dispersed Generation (DG) resources


(wind turbines, photovoltaics, fuel-cells, biomass, micro-
turbines, small hydroelectric plants etc., ranging from sub-kW
to space limitation reasons. The connection criteria and
relevant guidelines are based on the extensive set of IEC
standards regarding power quality (part of the IEC 61000
to multi-MW sizes) in distribution grids is increasing world- series of EMC publications), as well as on other relevant IEC
wide. The economic opportunities presented for private documents. The proposed evaluation methodologies are
investors in the deregulated electric industry environment and application oriented, in order to provide fast and reliable
the significant potential benefits for utilities (peak-shaving results, without requiring excessive data or sophisticated
capabilities, reduction of losses, better asset utilization etc.) software.
are contributing to this trend.
The incorporation of DG units in the grids alters their II. SLOW VOLTAGE VARIATIONS
traditional operating principle and poses new problems,
regarding power quality, supply reliability and safety, which In the case of overhead distribution networks, the steady
the utilities are still unfamiliar with and therefore unable to state voltage variations at the Point of Common Coupling
deal in a consistent and efficient manner. Although several (PCC) to the grid are usually the critical factor when
regulatory and business issues remain to be resolved, technical examining the connection of new DG sources. Traditionally,
questions are often the critical factors inhibiting the utilities have imposed limiting values to the acceptable steady
integration of new installations, [1]. To speed-up the state voltage deviations from the nominal value, both at the
evaluation and connection process, without compromising the MV and LV levels, which should not be exceeded in normal
operating and safety requirements of the grid, proper technical operation of the system. During the last decade, the statistical
evaluation procedures are required, which should be nature of the voltage variations has been recognized and
relevant norms have been issued, such as the European Norm
EN 50160, [7], which imposes statistical limits, in the sense
S. A. Papathanassiou is with the Distribution Department of the Public that a small probability of exceeding them is acceptable.
Power Corporation (PPC) of Greece, 22, Halkokondili st., 10432 Athens, Checking the conformity with these limits at the planning
GREECE (e-mail: st@power.ece.ntua.gr).
stage calls for elaborate procedures, such as probabilistic load
N. D. Hatziargyriou is with the Department of Electrical and Computer
Engineering, National Technical University of Athens (NTUA), Greece, 9, flow techniques (e.g. [8,9]), which are relatively difficult to
Iroon Polytechniou st., 15780 Zografou, Athens, GREECE (e-mail: apply and requirie data often unavailable in practice. For this
nh@mail.ntua.gr).
2

reason, utility directives for the connection of DG adopt network) and DG power factor varying from 0.95 inductive to
simpler and more straightforward procedures. The evaluation 0.95 capacitive.
procedure of [6] is outlined in the following. It uses 10-min The above procedure is generally unsuitable for cases of
average voltage values. high DG penetration, multiple DG installations on the same
At a first stage, the maximum steady-state voltage change feeder or when generators are connected to long feeders
ε(%) at the PCC is evaluated and compared to the limit, using serving significant consumer load. In such cases, the resulting
the following relation voltage variations are caused by the aggregate effect of all
S 100 generating facilities and the existing (or planned) network
ε (%) ≅ 100 n cos (ψ k + φ ) = cos (ψ k + φ ) ≤ 3 % (1) loads. Therefore, load flow calculations are required, taking
Sk R
into account the actual network configuration and loads. Four
where Sn is the DG rated apparent power, Sk the network short basic load-generation combinations should be examined:
circuit capacity at the PCC, ψk the phase angle of the network A. Minimum load-Minimum generation
impedance and φ the phase angle of the DG output current. B. Minimum load-Maximum generation
R=Sk/Sn is the short circuit ratio at the PCC. C. Maximum load-Minimum generation
The 3% limit imposed (the German Guide [5] and other D. Maximum load- Maximum generation
European national regulations impose an even more stringent In typical rural overhead grids, case B yields the maximum
2% limit) is strict for two reasons. First, the grid voltage levels and case C the minimum voltage levels. The maximum and
are determined by the aggregate effect of all connected minimum voltages, Umax and Umin, of each node must be
consumers and generators and hence no single connection appropriately bounded. In [6] the following requirements are
could be allocated the full variation limit. Second, in order to set for the steady state voltage of all nodes:
achieve a ±10% variation limit at the LV level, the MV grid
voltage should be more narrowly bounded. The median voltage of each node should not deviate more
than ±5% from the nominal voltage, so that it can be
10.0 compensated by the fixed tap settings of the MV/LV
7.5
R=10 distribution transformers (-5% to +5%, in steps of 2.5%):
U + U max
5.0 R=20 0.95 ⋅ U n ≤ U med = min ≤ 1.05 ⋅ U n (2)
R=40 2
2.5
The variation of the voltage around its median value should
ε (%)

0.0
not exceed ±3% of the nominal voltage, so that the voltage
-2.5-180 -135 -90 -45 0 45 90 135 180
level at the LV network remains within the ±10% limit,
-5.0
after the median deviation has been corrected:
-7.5
2 ⋅ ∆U = U max − U min ≤ 0.06 ⋅ U n (3)
-10.0
ψ k +φ (deg)
It should be noted that each of the four load flow scenarios
has a certain probability of occurrence, which is difficult to
9 evaluate in real-world situations. Hence, common sense and
8 application of some engineering judgement are necessary, in
7 order to exclude improbable situations. Proper account must
PF=0.95 cap.
6 also be taken of the voltage regulating means of the network
5 (ULTCs of HV/MV transformers, line voltage regulators,
ε (%)

4
PF=1.0
switchable capacitors etc.), which normally operate on time
3 scales of 30 s-1 min and therefore affect the steady-state (10-
2 min average) voltage.
PF=0.95 ind.
1
0 III. RAPID VOLTAGE CHANGES - FLICKER
0 10 20 30 40 50
Short circuit ratio R
According to the EN 50160 definition, rapid changes of the
voltage are fast variations of its rms value between two
Fig. 1. Voltage change ε(%) as a function of angle ψk+φ, for three values of consecutive levels, which are sustained for a certain
the short circuit ratio R (top diagram) and ε(%) as a function of R, for
three power factor values of the DG (bottom diagram). (unspecified) duration. For consistency with the slow voltage
changes definition, it is assumed that the rapid changes are
Eq. (1) is accurate enough for most practical purposes (its much faster than the 10-min averaging interval.
error being less than 0.5% for R ≥15). Depending on the grid Rapid voltage changes are induced either by switching
angle ψk and the power factor angle φ of the installation, operations within the premises of the DG installation (usually
short-circuit ratios down to 15 or even lower may be start/stop operations of equipment), or by the variability of the
acceptable, as illustrated in the top diagram of Fig. 1. The output power during normal operation. The magnitude of the
effect of the DG power factor on the voltage variations is also change and the resulting flicker emissions should be limited,
important, as it is evident in the bottom diagram of Fig. 1, to avoid disturbing other nearby installations. Measures of the
drawn for ψk.≈55o (corresponding to ACSR-95 MV overhead
3

flicker emissions are the short term, Pst, and long term, Plt, are set, which are the overall disturbance limits allowed at the
flicker severity indices ([10-12]). planning stage (generally lower than the compatibility levels).
Regarding switching operations, the limits imposed depend Indicative values for the planning levels in MV systems,
on the voltage level (LV or MV) where the customer is according to IEC 61000-3-7, are:
connected, the size of the equipment and the frequency of the Pst ≤ 0.9 and Plt ≤ 0.7
operations. Taking into account the requirements of the The allocation of the above limits to individual producers is
relevant IEC documents, [12-16], the following limits are set made according to the principles presented in the next section
in [6] for the relative (%) voltage change: for harmonics (equations similar to (10) and (12) are applied)
TABLE I and takes account of the following:
RAPID VOLTAGE CHANGE MAGNITUDE LIMITS • Voltage flicker at the MV network is the combined result
Frequency of switching operations, r of emissions from loads connected at this voltage level and
(h-1: per hour, d-1: per day) flicker transferred from the HV grid.
r > 1 h-1 2 d-1 < r < 1 h-1 r < 2 d-1
• The flicker emissions from individual installations are
LV

Steady-state change, dc ≤3%


Maximum change, dmax ≤4% ≤ 5.5 % ≤7% superimposed to determine the overall voltage flicker level
r>10 h-1 1 h-1<r≤10 h-1 r≤1 h-1 in the network.
Steady-state change, dc -
MV

The following rule is commonly applied for the summation


Maximum change, dmax ≤2% ≤3% ≤4%
of flicker (used for Plt as well):
A simplified evaluation of the voltage change at the PCC Pst = 3
∑P
i
3
st , i (7)
during the starting (cut-in) of the DG equipment can be made During normal operation, voltage changes resulting from
using the following relation: fluctuations of the DG output power may create flicker
S 100 problems, which is a well-known concern for WTs, [19,20].
d max (%) = 100 ⋅ k ⋅ n = ⋅k (4)
Sk R According to the IEC 61400-21 CDV, the expected flicker
For an accurate evaluation of dmax(%), k should be the indices of WTs can be assessed using the flicker coefficient,
voltage change factor kU(ψk), which is defined for WTs in IEC c(ψk,va), dependent on the average annual wind speed, va, of
61400-21 CDV, [17], and is given as a function of the grid the WT installation site and the grid short circuit impedance
angle ψk. For simplified calculations, k can be set equal to the angle, ψk:
S
ratio of the equipment starting current to its rated current, Pst = Plt = c(ψ k , va ) (8)
ranging from less than 1 to higher than 8, depending on the Sk
type of equipment and the starting method used. Summation For the total flicker emission of a wind farm comprising N
rules for simultaneous switchings of equipment need not be WTs, the following relation is applied:
applied, due to the very low probability of coincident events. 1 N
∑ ( c (ψ k , va ) ⋅ Si )
2
Flicker emissions resulting from switching operations can PstΣ = Plt Σ = (9)
be calculated as ([17]): S k i =1
1 Limits for flicker emissions during normal operation and
18  N 3.2  3.2
Pst =  ∑ N10,i ( k f ,i (ψ k ) ⋅ S n,i )  (5) their allocation to individual users of the system are the same
Sk  i =1  as for switching operations.
1
8  N 3.2  3.2
Plt =  ∑ N120,i ( k f ,i (ψ k ) ⋅ S n,i )  (6) IV. HARMONICS
S k  i =1 
The use of advanced power converters at the front end of
where N is the number of generators in the customer facilities
many DG types (photovoltaics, fuel-cells, variable speed WTs
operating in parallel, Sn,i the rated capacity and kf,i(ψk) the
and even small gas and hydro turbines) is constantly
flicker step factor of unit i (defined in [17]). N10,i and N120,i are
increasing, posing harmonic control requirements for their
the maximum number of switching operations that can take
connection to the grid. During the last decade several national
place in a 10-min and a 120-min interval for unit i. If the
and international standards and recommendations have been
flicker factor is unavailable, the flicker has to be evaluated
developed (e.g. [21-24]), permitting the elaboration of
either by the shape characteristics and the frequency of the
appropriate evaluation procedures. In this section, the
disturbance (IEC 61000-3-3, [13], provides useful guidance),
requirements of the Greek guide are outlined. The adopted
or by simulation using a software implementation of the
approach is based on the IEC set of standards, comprising
flickermeter algorithm of IEC 61000-4-15, [12].
three basic steps: First, the definition of acceptable voltage
At the LV level, limits for the calculated flicker indices, Pst
distortion limits (planning levels), second, the allocation of
and Plt, are:
global harmonic voltage limits to individual producers (or
Pst ≤ 1 and Plt ≤ 0.65 consumers) and third, the determination of the corresponding
At the MV level, the determination of exact limits is left to current distortion limits for a specific connection.
the utilities. In broad terms, depending on the compatibility For LV systems specific compatibility levels are given in
levels (i.e. the existing disturbance level in the grid, [18]) and IEC 61000-2-2, [25], and IEC 61000-3-6, [24], which also
the internal quality objectives of the utility, the planning levels serve as planning levels, and are included in Table 2. At
4

TABLE 2
PLANNING LEVELS FOR LV, MV AND HV NETWORKS (IEC 61000-3-6, [24])
Odd harmonics ≠3k Odd harmonics = 3k Even harmonics
Order Harmonic voltage (%) Order Harmonic voltage (%) Order Harmonic voltage (%)
h LV MV HV h LV MV HV h LV MV HV
5 6 5 2 3 5 4 2 2 2 1.6 1.5
7 5 4 2 9 1.5 1.2 1 4 1 1 1
11 3.5 3 1.5 15 0.3 0.3 0.3 6 0.5 0.5 0.5
13 3 2.5 1.5 21 0.2 0.2 0.2 8 0.5 0.4 0.4
17 2 1.6 1 >21 0.2 0.2 0.2 10 0.5 0.4 0.4
19 1.5 1.2 1 12 0.2 0.2 0.2
23 1.5 1.2 0.7 >12 0.2 0.2 0.2
25 1.5 1.2 0.7
>25 0.2+ 0.2+ 0.2+
1.3⋅  25   25   25 
  0.5⋅   0.5⋅  
 h   h   h 
THD: 8 % at LV, 6.5 % at MV, 3% at HV

higher voltage levels (MV and HV), however, it is the EUhi


responsibility of the utility to determine the compatibility U hi = Z h ⋅ I hi ≤ EUhi ⇒ I hi ≤ EIhi = (13)
Zh
levels in its network and then define appropriate planning
where Uhi and Ihi are the h-order harmonic voltage and current
levels. For reference purposes, Table 2 summarizes indicative
due to connection i and EUhi, EIhi the respective limits
planning levels suggested in IEC 61000-3-6, which can be
allocated to this connection.
applied in the absence of more specific data.
For LV systems IEC 725, [26], establishes a reference
The coordination of harmonic emission control at the
system impedance, permitting thus the direct determination of
different voltage levels (LV, MV and HV) of the system,
harmonic current limits, as defined in IEC 61000-3-2 and
requires to take account of distortion transmitted from one
61000-3-4 ([22,23]). For MV systems, however, no
voltage level to the other. Hence, the distortion limit GhMV,
standardized reference impedance is available and the
available to all installations connected to the MV system, can
evaluation of the system harmonic impedance Zh is the most
be found as
difficult part of the whole procedure. A simplified approach
GhMV = a LahMV − (ThHM ⋅ LhHV )
a
(10) can be established, with reference to the simplified network
where LhΜV and LhΗV are the MV and HV planning levels for situation of Fig. 2, where all network capacitance is
the harmonic order h (from Table 2) and ThHM the harmonic aggregated at the MV busbars and any possible resonance in
transfer coefficient from HV to MV level (ranging from below the HV system is ignored.
1.0 to more than 3). a is the exponent of the harmonic MV MV Line PCC
HV TF
summation rule: HV Network ZL

Uh = a ∑U
i
a
hi or I h = a
∑I i
a
hi (11)
ZS

ΖΤ
Other feeders

DG
IEC 61000-3-6, [24], suggests: a=1 for h<5, a=1.4 for Aggregate
5≤h≤10 and a=2 for h>10, since harmonics of higher order Capacitance
tend to have random phase angles. Sk
From GhMV, the voltage distortion limit EUhi for an
individual installation can then be determined, in proportion to
Fig. 2. MV network equivalent for simplified harmonic emission evaluation.
its rated power, Sn,i:
S For systems without significant capacitance and no PFC
EUhi = GhMV a n ,i = GhMV a si (12)
St correction capacitors or filters in the DG installations:
where St is the total «feeding capacity» of the network (e.g. Zh ≈ h ⋅ X k (14)
equal to the rated MVA of the feeding transformer). The ratio where Xk is the fundamental frequency inductive component
si can also be interpreted as the ratio of the connected of the short circuit impedance at the PCC.
equipment rated power to the total capacity of the distorting The aggregate capacitance in Fig. 2 accounts for the single
equipment in the network. parallel resonance with the upstream system (but not for other
It is common practice in harmonic studies to regard the possible higher order resonances). If all resistances and
connected equipment as harmonic current sources (although system loads in Fig. 2 are ignored, the resonant frequency fr
this may not be correct in certain cases), whereas the limits and the respective harmonic order hr (not necessarily integer)
discussed previously refer to the harmonic distortion of the are given by
system voltage. In order to relate these quantities, the system S f S kS
harmonic impedance Zh at the PCC is needed. Then: f r = f1 kS ⇒ hr = r = (15)
Qc f1 Qc
5

where SkS is the short circuit capacity at the MV busbars of the of future DG penetration, such as tariffication policies,
HV/MV substation and Qc is the total capacitive reactive metering practices, pricing of power quality characteristics
power of the MV network. A rough and conservative etc.
estimation of Zh (usually providing results on the safe side) is
then given by the “envelope impedance curve” of IEC 61000- VI. REFERENCES
3-6, shown in Fig. 3. The resonant amplification factor, kr, of [1] R.B. Alderfer, M.M. Eldridge, T.J. Starrs, “Making Connections: Case
the system impedance at the PCC typically varies between 2 Studies of Interconnection Barriers and their Impact on Distributed
and 5 in public distribution networks ([24]), depending mainly Power Projects”. NREL Report SR-200-28053, July 2000.
on the damping effect of the system loads. [2] IEEE Std. P1547: Distributed Resources Interconnection with Electrical
Power Systems. (Under preparation by IEEE/SCC21).
Zh [3] IEEE Std. 929 (2000): Recommended Practice for Utility Interface of
Photovoltaic Systems.
[4] “Recommendation for the Connection and Parallel Operation of
Z hr Generating Facilities at the MV Network”, VDEW, 2nd Edition, 1998
kr =
Zhr hr ⋅ X kV (in German).
[5] “Recommendation for the Parallel Operation of Generating Facilities at
the LV Network of Electric Utilities”, VDEW, 3rd Edition 1991 –
Revised 1996 (in German).
[6] “Technical requirements for the interconnection of independent
hr⋅XkV
generation to the grid”. Public Power Corporation (PPC) of Greece,
2001.
Order h [7] European Norm EN 50160, “Voltage characteristics of electricity
supplied by public distribution systems”. CENELEC, 1999.
0 hr 1.5hr [8] N.Hatziargyriou, T.Karakatsanis, M.Papadopoulos, “Probabilistic load
flow in distribution systems containing dispersed wind power
Fig. 3. System harmonic impedance approximation, using the «envelope
generation”, IEEE Trans. Power Systems, Vol. 8, No. 1, February 1993.
impedance curve» (IEC 61000-3-6, [24]).
[9] N.G. Boulaxis, S.A. Papathanassiou, M.P. Papadopoulos, “Wind
turbine effect on the voltage profile of distribution networks”. To
For installations with filters or significant PFC capacitance, appear in Renewable Energy.
in more complex networks or when there are resonances in the [10] IEC 868-0 (1991), Part 0: Evaluation of flicker severity.
HV network, the approach presented above may not be [11] IEC 868 (1986): Flickermeter. Functional design and specifications.
Amendment No. 1 (1990).
suitable. Manual computation of Zh is possible in certain cases [12] IEC 61000-4-15 (1997), Part 4: Testing and measurement techniques –
(IEC 61000-3-6 provides relevant examples) but the Section 15: Flickermeter-Functional and design specifications.
application of harmonic load flow software is recommended, [13] IEC 61000-3-3 (1994), Part 3: Limits – Section 3: Limitation of voltage
since the harmonic distortion of the voltage may be maximum fluctuations and flicker in low-voltage supply systems for equipment
with rated current ≤ 16Α.
at points other than the equipment PCC. [14] IEC 61000-3-5 (1994), Part 3: Limits – Section 5: Limitation of voltage
fluctuations and flicker in low-voltage power supply systems for
equipment with rated current greater than 16 Α.
V. CONCLUSIONS [15] IEC 61000-3-11 (2000), Part 3: Limits – Section 11: Limitation of
voltage changes, voltage fluctuations and flicker in low voltage supply
In this paper a presentation of the technical requirements systems for equipment with rated current < 75 Α and subject to
for the connection of new distributed generation resources to conditional connection.
[16] IEC 61000-3-7 (1996), Part 3: Limits – Section 7: Assessment of
the distribution networks has been made, including assessment emission limits for fluctuating loads in MV and HV power systems –
methodologies suitable for practical applications. The criteria Basic EMC publication.
and procedures presented are part of the Greek utility guide, [17] IEC 61400-21 (CDV 2000): Measurement and assessment of power
[6], and are largely based on the set of relevant IEC quality characteristics of grid connected wind turbines.
[18] IEC 61000-1-1 (1992), Part 1: General – Section 1: Application and
publications. The requirements and evaluation procedures interpretation of fundamental definitions and terms.
introduced ensure that the connection of DG resources will [19] M.P. Papadopoulos, S.A. Papathanassiou, S.T. Tentzerakis, N.G.
not adversely affect the power quality and safety of operation Boulaxis, “Investigation of the Flicker Emission by Grid Connected
of the grid. Here the emphasis is placed on power (voltage) Wind Turbines”. Proc. of 8th IEEE Int. Conf. on Harmonics and Quality
of Power, Athens, 1998.
quality issues, including steady state and rapid voltage [20] S.A. Papathanassiou, S.J. Kiartzis, M.P. Papadopoulos, A.G. Kladas,
variations, flicker and harmonic emissions. “Wind turbine flicker calculation using neural networks”. To appear in
It is expected that technological advancements in the Wind Engineering.
following years will call for another (probably more radical) [21] ANSI/IEEE Std. 519 (1992): Recommended Practice and Requirements
for Harmonic Control in Electric Power Systems.
update of the evaluation methodologies. For instance, active [22] IEC 61000-3-2 (2000), Part 3: Limits – Section 2: Limits for harmonic
front end converters, with load balancing, flicker cancellation current emissions (equipment input current ≤ 16Α per phase).
and active filtering capabilities, will soon find their way in [23] IEC 61000-3-4 (1998), Part 3: Limits – Section 4: Limitation of
emission of harmonic currents in low -voltage power supply systems
commercial DG equipment. The grid operating principle will
for equipment with rated current greater than 16Α.
also evolve, permitting the exploitation of distributed [24] IEC 61000-3-6 (1996), Part 3: Limits – Section 6: Assessment of
generation resources for providing back-up power to parts of emission limits for distorting loads in MV and HV power systems.
the grid during power failures, increasing thus the service [25] IEC 61000-2-2 (1990), Part 2: Environment – Section 2: Compatibility
levels for low-frequency conducted disturbances and signalling in
reliability. Apart from the core technical issues, several other public supply systems.
market and regulatory factors will affect critically the degree
6

[26] IEC 725 (1981): Considerations on reference impedances for use in Nikos D. Hatziargyriou was born in Athens,
determining the disturbance characteristics of household appliances and Greece, in 1954. He received the Diploma in
similar electrical equipment. Electrical and Mechanical Engineering from
NTUA, Athens, Greece, in 1976 and M.Sc and
Ph.D. degrees from UMIST, Manchester, UK, in
VII. BIOGRAPHIES
1979 and 1982, respectively. He is currently
Stavros Papathanassiou (S’1993, M’1998) was born Professor at the Power Division of the Electrical
in Thesprotiko, Greece, in 1968. He received the and Computer Engineering Department of NTUA.
Diploma in Electrical Engineering from the National His research interests include Dispersed
Technical University of Athens (NTUA), Greece, in Generation and Renewable Energy sources,
1991 and the Ph.D. degree in 1997 from the same Dynamic Security and Artificial Intelligence techniques. He is member of
University. Currently, he is with the Distribution CIGRE SC38, member of the Technical Chamber of Greece, senior IEEE
Department of the Public Power Corporation of member and currently Chairman of the IEEE Greek Power Chapter.
Greece, engaged in power quality and dispersed
generation issues. His research mainly deals with
wind turbine modeling and control, electric machines
and drives and the integration of dispersed generation to the grid. He is a
member of the IEEE and a registered professional engineer and member of the
Technical Chamber of Greece.

View publication stats

You might also like