RE 30 241/02.02
Replaces: 30 240
H/A/D 6639
Series 2X
Type VT 5041-2X/.
Contents Page – Integral part of the SY.DFE1 pressure and flow control system
(series 1X and 2X) for controlling A10VSO... axial piston units
Features 1
with DFE1 control
Ordering code 2
– Implementation of the electronic functions of the DFE1 control;
Functional description 2 closed-loop pressure and swivel angle control; optional power
Block circuit diagram / pin assignment 3 limitation
Technical data 4 – Pressure controller can be matched to existing hydraulic fluid
Indicator/ adjustment elements 5 volume (actuators plus lines)
Unit dimensions 6 – Differential amplifier inputs
Supplementary information 6 – Controller for valve spool position
– Minimum value generator for pressure and swivel angle
controller
– Self-clocking output stage
– Pressure-related leakage compensation (can be switched off)
Card holder: – Polarity reversal protection for voltage supply
– Type VT 3002-2X/32, see RE 29 928
Single card holder without power supply unit – Switchable actual pressure input (current, voltage, range)
Power supply unit: – LED lamps on front panel:
– Type VT-NE32-1X, see RE 29 929 • Error / no enable “H1“
Compact power supply unit 115/230 VAC → 24 VDC • Internal supply voltage “H2“
• Output 1 (60 VA) for supplying amplifier card type VT 5041 – Indicator instrument for actual swivel angle value on front
• Output 2 (25 VA) for supplying pressure transducers; panel (optional)
e.g. type HM 12 or HM 13, see RE 29 933 – Power limiter with internal or external command value
selection (optional)
Ordering code
VT 5041 – 2X/ /*
Series 20 to 29
(20 to 29: unchanged technical data and
pin assignment) = 2X
Additional functions:
– Without power limiter, without indicator instrument =1
– With power limiter, with indicator instrument =3
Preferred types
Material no. Type
00749982 VT5041-2X/1
00749983 VT5041-2X/3
Functional description
VT 5041-2X analogue amplifiers are designed as plug-in cards in The amplifier card is fitted with an error signal output, to which a
Euro-format. As a standard, they are provided with one command voltage of 0 V is applied in the case of an error. At the same time, LED
value input each for pressure and swivel angle [1] (power limitation "H1" lights up and the output stage is de-energised.
optional). The actual pressure value is sensed by a pressure trans- The following events result in an error message:
ducer. A position transducer on the pump acquires the actual swivel
– The actual pressure value is greater than the permissible system
angle value. The acquired actual values are processed in an amplifier
pressure (pact > 10 V)
[10 and 12] and compared with the specified command values. Mini-
mum value generator [4] ensures that only the controller assigned to – Enable signal missing at connection 26c
the relevant working point is automatically activated. The output sig- – Excessive output stage temperature
nal of minimum value generator [4] becomes the command value for – Cable break or swivel angle feedback out of range
the closed control loop of the valve.
– Cable break or spool position feedback out of range
The optional power limiter is automatically activated when a suit- – Cable break “proportional solenoid“
able command value is fed forward. The power command value can
– Cable break “pressure transducer“ (only with setting 4 to 20 mA)
be provided internally or externally. When required, it acts via a mini-
mum value generator [14] directly on the swivel angle controller [3]. In the case of an error, the output stage is de-energised and the
valve spool pushed by a spring to its mechanical end position. The
The actual valve position (position of the valve spool) is sensed by an
error can only be acknowledged by a reset of the enable signal.
inductive position transducer. Oscillator/demodulator circuit [10] pro-
cesses the signal. Valve spool position controller [5] establishes and With the help of an offset potentiometer [15] it is possible to com-
processes the system deviation. The output signal of valve controller pensate for pressure-related pump leakage via the closed swivel angle
[5] forms the command value for self-clocking current output stage control loop.
[6], which controls the proportional solenoid of the valve.
[ ] = Reference to the block circuit diagram on page 3
1 2 5
+UB
R1 R2
J10 ϑ 2a
12 +2 9 Error message (^
= High)
0 to 5/10 V or 8c 2c
pact = Error message (^
= Low)
0/4 to 20 mA i(u)
J6...J8 u ≥1
Reference potential H1
10c 15
11 R4 24c pact: 0 to + 10 V Measuring
– 3 J9 12c αact: – 10 V to + 10 V outputs
– 10 to + 10 V 14c
αcomm = u
13 P
3/6
adjustment elements (H, R), – The connection of the swivel angle transducer is valid for a clockwise
1 Differential amplifier 6 Output stage 11 Input amplifier see page 5 rotating pump
2 Pressure controller 7 Output stage enable 12 Divider
8 Power supply unit 13 Minimum value generator
1) For notes on shielding, see ("( )" anti-clockwise rotating pump)
3 Swivel angle controller
Hydraulics
Industrial
4 Minimum value generator 9 Cable break detector 14 Indicator instrument engineering notes for the – Differences between αcomm (socket 3) and αact (socket 4) result from the
5 Valve spool position controller 10 Oscillator/demodulator 15 Leakage compensation complete system, RE 30024-01-B setting of R4 (leakage compensation)
Industrial
Hydraulics
Technical data (for applications outside these parameters, please consult us!)
Note:
For details on Environment simulation tests in the fields of
EMC (electromagnetic compatibility), climate and mechanical stress,
see RE 30 024-U (declaration on environmental compatibility).
R8
J9 R6
R7 R9
R4
J10
H1 J11 J1 J2 R31)
H2
off
R2
on
J6
J3 J4 J5 R1
on F1
J7 J8 1,6 A T
off
LED lamps:
H1 Error / no enable (red) For further information and notes, see commissioning instructions
H2 Internal supply voltage (green) for SYDFE1-2X closed-loop control systems (RE 30 024-02-B)!
1) with VT 5041-2X/3 only
R4 R4
H1 H1
H2 H2 +
50 100
R2 R2
3HE (128,4)
100
89
100 50
–
1 2 1 2
3 4 3 4
5 6 5 6
7 8 7 8
VT VT
15
5041 5041
Supplementary information
Note: Electrical signals processed by control electronics (e.g. actual value“) must not be
used for switching safety-relevant machine functions!
(See European standard “Safety requirements for fluid power systems and components
– hydraulics“, EN 982)