03
Replaces: 11.02
H/A/D 6639
From series 25
Type VT 5041-2X/.
Contents Page – Integral part of the SYDFE1 pressure and flow control system
(series 1X and 2X) for controlling A10VSO... axial piston units
Features 1
with DFE1 control
Ordering code 2
– Implementation of the electronic functions of the DFE1 control;
Functional description 2 pressure and swivel angle control; optional power limiter
Block circuit diagram / pin assignment 3 – Circuitry of the pressure controller can be matched to existing
Technical data 4 hydraulic fluid volumes (actuator plus lines)
Indicator / adjustment elements 5 – Differential amplifier inputs
Unit dimensions 6 – Controller for valve spool position
Supplementary information 6 – Minimum value generator for pressure and swivel angle
controller
– Self-clocking output stage
– Pressure-related leakage compensation (can be switched off)
– Polarity reversal protection for power supply
Card holder: – Switchable actual pressure value input (current, voltage, range)
– Type VT 3002-2X/32, see RE 29 928 – LED lamps on the front panel:
Single card holder without power supply unit • Error / no enable “H1“
• Internal supply voltage “H2“
Power supply unit:
– Indicator instrument for actual swivel angle value on the front
– Type VT-NE32-1X, see RE 29 929 panel (optional)
Compact power supply unit 115/230 VAC –> 24 VDC
– Power limiter with internal or external command value
• Output 1 (60 VA) for supplying amplifier card type VT 5041 feedforward (optional)
• Output 2 (25 VA) for supplying pressure transducers;
e.g. types HM 12 or HM 13, see RE 29 933
© 2003
by Bosch Rexroth AG, Industrial Hydraulics, D-97813 Lohr am Main
All rights reserved. No part of this document may be reproduced or stored, processed, duplicated or circulated using
electronic systems, in any form or by means, without the prior written authorisation of Bosch Rexroth AG. In the event
of contravention of the above provisions, the contravening party is obliged to pay compensation.
VT 5041 – 2X/ /*
Series 25 to 29
(25 to 29: unchanged technical data
and pin assignment) = 2X
Additional functions:
– Without power limiter, without indicator instrument =1
– With power limiter, with indicator instrument =3
Preferred types
Material no. Type
R900749982 VT5041-2X/1
R900749983 VT5041-2X/3
Functional description
VT 5041-2X analogue amplifiers are designed as plug-in cards in The amplifier card is fitted with an error signal output, to which a
Euro-format. As a standard, they are provided with one command voltage of 0 V is applied in the case of an error. At the same time, LED
value input each for pressure and swivel angle [1] (power limiter, “H1” lights up and the output stage is deactivated.
optional). The actual pressure value is sensed by a pressure trans- The following events trigger an error message:
ducer. A position transducer on the pump acquires the actual swivel
– Actual pressure value greater than permissible system pressure
angle value. The acquired actual values are processed in an amplifier
(socket 2 pact > 10 V)
[10 and 12] and compared with the injected command values. Mini-
mum value generator [4] ensures that only the controller assigned to – Enable signal missing at connection 26c
the relevant working point is automatically activated. The output sig- – Excessive temperature of the output stage
nal of minimum value generator [4] becomes the command value for – Cable break or range of swivel angle feedback exceeded
the closed control loop of the valve.
– Cable break or range of valve spool position feedback exceeded
The optional power limiter is automatically activated by the feed-
– Cable break “proportional solenoid“
forward of a suitable command value. The power command value
can be provided internally or externally. If required, it acts directly on – Cable break “pressure transducer“ (only in conjunction with set-
swivel angle controller [3] via a minimum value generator [13]. ting 4 to 20 mA)
The actual valve value (position of the valve spool) is acquired by an In the case of an error, the output stage is deactivated and the valve
inductive position transducer. Oscillator/demodulator circuit [10] proc- spool pushed by a spring to its mechanical end position. The error
esses the signal. Valve spool position controller [5] determines and can only be acknowledged by a reset of the enable signal.
processes the system deviation. The output signal of valve controller The pressure-related pump leakage can be compensated for via the
[5] forms the command value for self-clocking current output stage swivel angle control loop using potentiometer [15].
[6], which controls the proportional solenoid of the valve.
[ ] = Cross-reference to block circuit diagram on page 3
16c u =
Reference potential – 9 2
1 + 4 3 6 ≈
8a 1
10
= 4a 4
≈ 6a 3
26c
Enable (> 21 V) R6 R7 Valve position transducer
26a
+UB
32a 8 7 Shield 1)
30a + 15 V = 14a (2)
+ UB ≈
+ = – 15 V 10
Swivel angle
= 10a 1
H2 8 transducer on
28a 7 ≈
0 V (⊥) the pump
20a R8 R9 12a 2( )
– 15 V
22a 26a
⊥ Shield 1)
24a Explanation re indicator and Note:
+ 15 V
RE 30 241/11.02
adjustment elements (H, R), – Connection of the swivel angle transducer is valid for clockwise rotating
1 Differential amplifier 6 Output stage 11 Input amplifier see page 5 pump
2 Pressure controller 7 Output stage enable 12 Divider
241/02.03
Operating range:
– Upper limit value uB(t)max 35 V
– Lower limit value uB(t)min 21 V
Power consumption PS 35 VA
Current consumption Inom 0.6 A (Imax = 1.25 A)
Fuse IF 1.6 A T
Inputs:
– Command values (pressure, swivel angle) Ui 0 to 10 V; Re= 100 kΩ
– Actual value (pressure) Ui 0 to 5 V or 0 to 10 V; Re= 100 kΩ
Ii 0 to 20 mA or 4 to 20 mA; Re= 500 Ω
– Power selection (p • a)comm (only with VT 5041-2X/3...) Ui 0 to 10 V; Re> 100 kΩ
– Enable Ue > 21 V (use relay with contact for currents < 10 mA)
Outputs:
– Output stage
• Solenoid current / resistance Imax 2.5 A; R(20) = 2 Ω
– Drivers for inductive transducers:
• Oscillator frequency f ca. 5 kHz
• Voltage amplitude (USS) Ua 10 V
– Signal voltages
• Actual value (pressure, swivel angle) U 0 to 10 V
• Swivel angle control active U Ub –1 V
• Power limiter active (only with VT 5041-2X/3...) U Ub –1 V
– Auxiliary voltages U ± 15 V ± 3 %; 10 mA
– Error signal
• L-active Uo ≥ UB – 5 V; 10 mA (short-circuit-proof); error at Uo < 1 V
• H-active Uo < 1 V; error at ≥ UB – 5 V; 10 mA
– Measuring sockets
• Pressure command value (pcomm) “1“ U + 10 V =^ 100 %
• Actual pressure value (pact) “2“ U + 10 V =^ 100 %
• Swivel angle command value (acomml) “3“ U – 10 V =^ 100 %
• Actual swivel angle value (aact) “4“ U + 10 V ^= 100 %
• Spool position command value (scomm) “5“ U ± 10 V =^ ± 100 %
^
• Actual spool position value (sact) “6“ U ± 10 V = ± 100 %
Type of transducer:
– for pump IW 9 (throttle circuit; ± 4 mm; 3-wire connection)
– for valve DM2 (transformer circuit; ± 0.6 mm; 4-wire connection)
Type of connection 32-pin male connector, DIN 41 612, form D
Card dimensions Euro-card 100 x 160 mm, DIN 41 494
Front panel dimensions:
– Height 3 HE (128.4 mm)
– Width circuit board conductor side 1 TE
– Width component side
• VT 5041-2X/1... 5 TE
• VT 5041-2X/3... 9 TE
Permissible operating temperature range J 0 to 50 °C
Storage temperature range J – 20 to + 70 °C
Weight
• VT 5041-2X/1... m 0.19 kg
• VT 5041-2X/3... m 0.21 kg
Note:
For details on Environment simulation tests in the fields of
EMC (electromagnetic compatibility), climate and mechanical stress,
see RE 30 024-U (declaration on environmental compatibility).
R8
J9 R6
R7 R9
R4
J10
H1 J11 J1 J2 R31)
H2
off
R2
on
J6
J3 J4 J5 R1
on F1
J7 J8 1,6 A T
off
LED lamps:
H1 Error / no enable (red) For further information and notes, see commissioning instructions
H2 Internal voltage supply (green) for the SYDFE1-2X closed-loop control system (RE 30 024-B
or latest version of RE 30 022-01-B)!
1) Only with VT 5041-2X/3
R4 R4
H1 H1
H2 H2 +
50 100
R2 R2
3HE (128,4)
100
89
100 50
–
1 2 1 2
3 4 3 4
5 6 5 6
7 8 7 8
VT VT
15
5041 5041
Supplementary information
Note: Electrical signals processed by control electronics (e.g. actual value) must not be used for activating safety-relevant
machine functions!
(See also uropean standard “Safety requirements for fluid power systems and components – hydraulics“, EN 982).
Bosch Rexroth AG Bosch Rexroth Limited The data specified above only serves to describe
Industrial Hydraulics the product. No statements concerning a certain
D-97813 Lohr am Main Cromwell Road, St Neots, condition or suitability for a certain application
Zum Eisengießer 1 • D-97816 Lohr am Main Cambs, PE19 2ES can be derived from our information.
Telefon 0 93 52 / 18-0 Tel: 0 14 80/22 32 56 The details stated do not release you from the
Telefax 0 93 52 / 18-23 58 • Telex 6 89 418-0 Fax: 0 14 80/21 90 52 responsibility for carrying out your own
eMail documentation@boschrexroth.de eMail: info@boschrexroth.co.uk assessment and verification. It must be
Internet www.boschrexroth.de remembered that our products are subject to a
natural process of wear and ageing.