Ethernet Display Function
Ethernet Display Function
TMN 06/&E
Date : 22.May.2006
General Manager of
Software Research Laboratory
0 Your information
Sales agency
End user
3. Notice
4. Attached Document:
Export Control:
Controlled (Related item No. of Foreign Exchange Order Attachment List of
Japan: )
Non-controlledfor item No. 2 to 15 of Foreign Exchange Order Attachment List of Japan
NO. SRLB4-0615098
Date : 22.May.2006
Draw A-90128E
No.
Ed. Date Design Description page 1/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1 ETHERNET DISPLAY FUNCTION
Draw A-90128E
No.
Ed. Date Design Description page 2/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.1 Overview
By using this function, up to 8 stand-alone type CNCs can be connected to one PANEL i
(Since this, it is called a PC) over Ethernet, and a PC can be used as a display unit of CNCs.
HUB
PANEL i Ethernet
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
RYCARD
RYCARD
RYCARD
J A4 1
J A4 1
J A4 1
MO
MO
MO
E
E
J A4 1
J A4 1
J A4 1
M
M
ET HERNET
ET HERNET
ET HERNET
CP1 C2
P CP1 C2
P ... CP1 C2
P
Em bedded Ethernet
(B uilt-in Ethernet P ort)
P
1
P
1
1
CO
CO
CO
SL
O T1 SL
O T1 SL
O T1
SL
O T2 SL
O T2 SL
O T2
L ED1
L ED1
L ED1
L ED2
L ED2
L ED2
S WI T C H
S WI T C H
S WI T C H
PSW
PSW
PSW
Stand-alone type Series 30i/31i/32i
(The m axim um connection num ber is 8.)
• CNC screens which can be displayed and operated by Ethernet display function
For Maintenance (NCBOOT32E.exe)
- Display and Operation of BOOT screen
- Display and Operation of IPL screen
- Display of CNC power-on screen
- Display of CNC Alarm screen
Draw A-90128E
No.
Ed. Date Design Description page 3/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
• Setting of Ethernet address
- IP address of CNC is half fixation with 192.168.1.(10+N) [range : 192.168.1.10 –
192.168.1.17], and an end N is set by the rotary switch. Meanwhile, IP address of
the PC must be made 192.168.1.200 fixation.
TCP port number 8193 and 8198 are used in CNC side. UDP port number 8197 is
used in PC side. (It is not necessary to set these port numbers manually.)
- When the option parameter of Ethernet display function is not active, IP address
of CNC is fixed with 192.168.1.10.
NOTE
1. Please note the following points when you use Ethernet Display
function (including CNC Screen Display function via Embedded
Ethernet).
- The update cycle of the screen is slower than a standard LCD
unit. The update cycle of the screen doesn’t quicken more than
a standard LCD unit even if high-performance personal is used.
- The Ethernet Display function might be influenced sensitively
compared with a standard LCD unit when processing with a
load of high-speed and high-accuracy is done, and the update
cycle of the screen becomes slow.
2. Using Embedded Ethernet port of Stand-alone type CNC is
mandatory condition for Ethernet Display function.
3. When Ethernet display function is active, PCMCIA Ethernet card is
not available. When using FANUC LADDER-III and SERVO GUIDE,
use built-in port (The connector CD38A of the control unit for
Ethernet function).
4. Ethernet display function cannot be worked with Fast Ethernet
board.
5. In use of Ethernet display function, a PC over HSSB or a LCD unit
must be removed. If you want to use HSSB or a LCD unit, you must
install Graphic software.
6. Please select CPU and memory of a PC (including PANEL i) which
have enough performance or capacity to the number of connected
CNC or the load of application software using together. Pentium III
866MHz CPU or higher and 256MB memory or higher are
recommended when multiple CNCs are connected.
7. When using PANEL i, USB QWERTY MDI, FA full keyboard or the
general full keyboard is necessary. And please refer to “Connection
manual of PANEL i for Ethernet display function (Technical
Report A-85131E)”
8. The DHCP client function becomes unavailable automatically when
using Ethernet display function.
Draw A-90128E
No.
Ed. Date Design Description page 4/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
9. When using Ethernet display function in Windows XP Service Pack
2 at the first time, the warning screen of the security like the
following figure might be displayed. In this case, choose " unblock ".
Draw A-90128E
No.
Ed. Date Design Description page 5/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.2 Example of Network configuration
HUB
CNCScrnE
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
RY C A RD
RY C A RD
RY C A RD
RY C A RD
RY C A RD
J A41
J A41
J A41
J A41
J A41
MO
MO
MO
MO
MO
E
E
J A4 1
J A4 1
J A4 1
J A4 1
J A4 1
M
M
LADDER-III SERVO GUIDE
ET H E RN E T
ET H E RN E T
ET H E RN E T
ET H E RN E T
ET H E RN E T
CP1 C2
P CP1 C2
P CP1 C2
P CP1 C2
P CP1 C2
P
P
1
1
CO
CO
CO
CO
CO
SL
O T1 SL
O T1 SL
O T1 SL
O T1 SL
O T1
SL
O T2 SL
O T2 SL
O T2 SL
O T2 SL
O T2
L ED1
L ED1
L ED1
L ED1
L ED1
L ED2
L ED2
L ED2
L ED2
L ED2
S WI T C H
S WI T C H
S WI T C H
S WI T C H
S WI T C H
PSW
PSW
PSW
PSW
PSW
PANEL i C NC 1 C NC 2 C NC 3 C NC 4 C NC 5
(192.168.1.200) (192.168.1.10)(192.168.1.11) (192.168.1.12) (192.168.1.13) (192.168.1.14)
The following software is necessary to use Ethernet Display function on the above
configuration.
<CNC>
1. Control Software for Ethernet Display function (656N edition 01 or later)
2. BOOT Software (60W1 edition 13 or later)
3. Control Software for Embedded Ethernet function (656E edition 10 or later)
4. Software for Communication management function (656F edition 10 or later)
5. Ethernet Display function (Option)
6. CNC Screen Display function (Option)
<Personal Computer>
1. Disk for CNC Screen Display function (edition 02.7 or later)
Draw A-90128E
No.
Ed. Date Design Description page 6/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
Example2 Machine which does not need a display unit in normal operation
CNCScrnE
J A4 1
J A4 1
J A4 1
RY C A RD
J A41
MO
E
J A4 1
M
LADDER-III SERVO GUIDE
E T HERNE T
CP1 C2
P
P
1
CO
SO
L T 1
SO
L T 2
LED1
L ED2
S WI T C H
P SW
N otebook P C C NC
(192.168.1.200) (192.168.1.10)
The following software is necessary to use Ethernet Display function on the above
configuration.
<CNC>
1. Control Software for Ethernet Display function (656N edition 01 or later)
2. BOOT Software (60W1 edition 13 or later)
3. Control Software for Embedded Ethernet function (656E edition 10 or later)
4. Software for Communication management function (656F edition 10 or later)
5. Ethernet Display function (Option)
6. CNC Screen Display function (Option)
NOTE
If one CNC is connected to a PC by “peer to peer”, Ethernet display
function is not mandatory. In this case, CNC’s node number is fixed
with “0” (IP address: 192.168.1.10).
<Personal Computer>
1. Disk for CNC Screen Display function (edition 02.7 or later)
Draw A-90128E
No.
Ed. Date Design Description page 7/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
Example3 Connection of CNCs into network of a factory
PC1 connects to CNC1, CNC2 and CNC3 via HUB1, and PC2 connects to CNC4, CNC5 and
CNC6 via HUB2, as a display unit respectively.
Furthermore, if you want to communicate with PC3 located on the factory network, Fast
Ethernet board is necessary per each CNC. And PC3 should be connected to the option board
via another HUB3.
Operation
monitoring Office
PC 3
(192.168.2.100)
CIMPLICITY i CELL
C NC 1 C NC 2 C NC 3 C NC 4 C NC 5 C NC 6
PC 1 PC 2
(192.168.1.200) (192.168.1.200)
Embedded Ethernet
NOTE
The basic network construction of Ethernet display function should
consist of only CNCs and a PC for display. If the network equipment
such as other PC that is not the communication partner of CNC exists
on the same network, the communication-processing load of CNC
rises, and the refresh of display data might become slow.
So avoid connecting with the network at the whole factory. But, it will
be possible to connect other PCs that are configured as IP address
group of the above for the purpose of maintenance temporarily.
Draw A-90128E
No.
Ed. Date Design Description page 8/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.3 Setting and confirmation of display number
To use Ethernet display function, set “display number” to [5: Sets CNC to a display unit of
Ethernet connection] with the rotary switch.
Draw A-90128E
No.
Ed. Date Design Description page 9/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.3.2 Confirmation of display number
The registered display number can be confirmed with the following two methods.
NOTE
After confirming the display number, always return the rotary switch to
the original position.
Draw A-90128E
No.
Ed. Date Design Description page 10/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.4 Setting and confirmation of node number
In the Ethernet display function, the node number, which is an end N of the IP address
192.168.1.(10+N), should be set.
NOTE
You should select the number "0" to "7" (though "0" to "F" is displayed
on 7-segment LED).
NOTE
The node number must differ from those of the other CNCs.
Draw A-90128E
No.
Ed. Date Design Description page 11/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.4.2 Confirmation of node number
The registered node number can be confirmed with the following two methods.
NOTE
After confirming the display number, always return the rotary switch to
the original position.
Draw A-90128E
No.
Ed. Date Design Description page 12/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.5 Choice of start-up sequence
By adjusting the rotary switch, the start-up sequence of CNC can be chosen as follows.
NOTE
When the position of the rotary switch is ‘0’ or ‘F’, CNC continues to
wait forever until establishing the communication with a PC, keeping
the boot state.
COP21A:LCD connector
MTSW:Rotary switch
PSW:Push switch
Draw A-90128E
No.
Ed. Date Design Description page 13/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.6 NCBOOT32E.exe
NCBOOT32E.exe is the software, which displays a screen for the maintenance, watching over
the communication between the PC and CNC.
NOTE
NCBOOT32E.exe is bundled to the Disk for CNC Screen
Display function (edition 02.7 or later).
When the rotary switch is adjusted to position 'F' and CNC is powered-on, this software will
display BOOT screen and then IPL screen.
Furthermore, you can register the application software, which runs after closing IPL screen.
Usually, CNC Screen display function (CNCScrnE.exe) is entered.
Draw A-90128E
No.
Ed. Date Design Description page 14/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
When the icon on the system tray is left-clicked, the following pop-up menu is displayed.
The disconnected CNCs are indicated with a light-color.
When choosing a node number from the pop-up menu, the selected CNC screen (BOOT
screen, IPL screen, the system alarm screen or the registered application software) appears in
the foremost of PC screen.
NOTE
To operate NCBOOT32E.exe, the use of a mouse or a touch panel is
recommended.
Draw A-90128E
No.
Ed. Date Design Description page 15/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.6.1 BOOT Screen
When the rotary switch is adjusted to position 'F' and CNC is powered-on, NCBOOT32E.exe
will establish the communication with CNC and will display BOOT screen.
If PC is connecting to several CNCs, each BOOT screen is displayed.
Draw A-90128E
No.
Ed. Date Design Description page 16/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.6.2 Location for storing S-RAM/F-ROM data files
When clicking the button [Settings…], the following screen is displayed, and you can specify
a place of the storage of the system data file and the S-RAM data file.
Choose either of the memory card of CNC unit or folder of the PC.
It is possible to change at any time.
Draw A-90128E
No.
Ed. Date Design Description page 17/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.6.3 Operation of System data
When clicking the [System Data] tab, the following screen is displayed and you can handle
the system data of F-ROM.
When clicking the [Load…] button, the file choice screen opens.
When choosing a file and clicking the [Load] button, the selected file is written in F-ROM.
When clicking the [Save] button, the selected system data of F-ROM is stored to a file.
When clicking the [Check] button, the selected system data is checked and its result is
reported.
When clicking the [Delete] button, the selected system data is deleted from F-ROM.
Note
System data accessible by [Save] and [Delete] operation is user file
only, like ladder program.
Draw A-90128E
No.
Ed. Date Design Description page 18/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.6.4 Operation of S-RAM
When clicking the [SRAM] tab, the following screen is displayed and you can handle S-RAM
data.
S-RAM data which was backed up to CNC’s F-ROM automatically is shown in the screen.
Select the data you want to restore and click the [Restore] button, and the data will be
restored.
Incidentally, the automatic back-up file names are pre-defined and cannot be renamed.
Draw A-90128E
No.
Ed. Date Design Description page 19/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.6.5 Operation of File
When clicking the [File] tab, the following screen is displayed, and you can handle the files
on the memory card of the CNC unit or the hard disk of the PC.
Note
When the formatting of memory card is executed, the contents are
cleared.
Draw A-90128E
No.
Ed. Date Design Description page 20/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.6.6 IPL Screen
When the [Close] button of the BOOT screen is pushed, the BOOT screen disappears and IPL
screen will appear as follows.
If PC is connecting to several CNCs, each IPL screen is displayed.
Additional information)
In CNC control unit with LCD, the operations equal with SYSTEM SERVICE MENU can be
executed by powering up CNC pushing the following MDI key’s pattern.
However, in Ethernet display function, these operations are not supported.
Please always use SYSTEM SERVICE MENU of the above IPL screen.
(Reference)
SYSTEM SERVICE MENU MDI operation at
corresponding to operation of the right power-up in CNC unit
with LCD
0. END None
1. IPL MONITOR <-> + <.>
2. BACK-UP CNC DATA ALL CLEAR <DELETE> + <RESET>
3. LOCKED PROGRAM ALL CLEAR <M> + <0>
Draw A-90128E
No.
Ed. Date Design Description page 21/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.6.7 CNC Alarm Screen
CNC alarm screen appears when the system alarm occurs on CNC unit.
If PC is connecting to several CNCs, each system alarm screen is displayed.
(The above is an instance. the contents change depending on the system alarm which
occurred in CNC.)
CAUTION
When system alarm is caused by very serious problem like memory
error, main processor unit error and Embedded Ethernet related
problem, system alarm screen might not be displayed.
As for the details of CNC alarm screen operation, refer to “11.25 SYSTEM ALARMS” and
“11.26. SYSTEM ALARMS RELATED TO THE PMC AND I/O LINK” of Maintenance
manual B-63945EN/02.
Draw A-90128E
No.
Ed. Date Design Description page 22/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.6.8 Status Screen
By either of the following operations, the following status screen is displayed.
・ Double-clicks the icon on the system tray.
・ Right-clicks the icon on the system tray, and clicks [Open] on the popped up menu.
Furthermore, when checking [Pop up this windows on communication error] beforehand, the
status screen is displayed automatically just when the communication error occurs.
In the status screen, communication status, CNC status, IP address and MAC address of CNC
can be confirmed.
Draw A-90128E
No.
Ed. Date Design Description page 23/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.6.9 Option Setting Screen
By either of the following operations, the option setting screen is displayed.
・ Clicks [Settings…] on the status screen.
・ Right-clicks the icon on the system tray, and clicks [Settings…] on the popped up menu.
In the option setting screen, you can register the application software for the purpose of CNC
operation you want to execute after completing IPL process of CNC.
If multiple CNCs are connecting and you want to control the registered application software
by using the changer screen explained later, the check box must be checked additionally.
Choose the node number from the [Node] list box. And the application software name
registered for the selected node number will be displayed at the center of the screen.
When clicking the [New…] button, a new application software name can be registered. If a
blank character is included in the path, put the path between double quotations.
When clicking the [Remove] button, the chosen application software name can be deleted.
When clicking the [Edit] button, the chosen application software name can be edited.
If an argument is added, "%s" means IP address. If you want to express %' itself, describe
"%%".
Example) To execute CNC screen display function after CNC start-up, application software
name is described as follows.
“C:¥Program Files¥CNCScreenE¥CNCScrnE.exe” /H=%s:8193
Draw A-90128E
No.
Ed. Date Design Description page 24/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
More than one application software can be registered for each node(CNC). In this case, all
of the registered application software starts at the same time.
If your application software cannot start up normally, for example, the following dialog box
appears; "Node [xxx]: Couldn't execute the Application Program. [yyy]".
([xxx] is the node number, [yyy] is a command line character string)
Draw A-90128E
No.
Ed. Date Design Description page 25/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.6.10 Changer Screen
By the following operations, the changer screen is displayed.
・ Clicks [Screen Changer] on the status screen.
・ Right-clicks the icon on the system tray, and clicks [ScreenChanger] on the popped up
menu.
・ Pushes the Hot Key (Ctrl-Alt-N)
The changer screen is always displayed in the front than other screens.
The node number corresponding to a hollow-shaped button on the changer screen meets
following conditions.
・ The application software that was started up from NCBOOT32E.exe.
・ The application software that is displayed most ahead.
When clicking a node number except for the selected node number, the application software
of the newly selected node number will be displayed in the most front.
Or when pushing Shift+Fx key, the corresponding application software will be selected.
Shift+F1 : Node0, Shift+F2 : Node1, Shift+F3 : Node2, Shift+F4 : Node3,
Shift+F5 : Node4, Shift+F6 : Node5, Shift+F7 : Node6, Shift+F8 : Node7
When the application software is quitted, a dialog box "Node [xxx]:The registered
Application Program has terminated. Restart? [yyy]" is displayed. If clicking the button [Yes],
the application will restart again. ([xxx] is the node number, [yyy] are a command line
character string)
Note
If you click [NO], the registered application software does not start
again automatically any longer. And it does not synchronize with the
changer screen.
Draw A-90128E
No.
Ed. Date Design Description page 26/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
When the registered application software cannot be found, a dialog box, "Node [xxx]: No
Application Program exists for this node.” is displayed. ([xxx] is a node number)
Draw A-90128E
No.
Ed. Date Design Description page 27/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
1.7 Start-up of CNC Screen Display
To run CNC Screen Display function (CNCScrnE.exe) after CNC initialization, the
application software name of CNC screen display function should be registered to the option
setting screen of NCBOOT32E.exe. In this case, the argument (/H=%s: 8193), which
specifies the IP address and the port number of CNC, must be added to the application name.
If argument is not added, the following setting screen is displayed, and IP address and the port
number must be entered here.
When connecting with CNC, CNC screen like the following figure is displayed.
The IP address and the port number of CNC are displayed in the title bar.
Note
When using CNC Screen Display function, its option is needed.
Draw A-90128E
No.
Ed. Date Design Description page 28/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai
Related parameter
#7 #6 #5 #4 #3 #2 #1 #0
13114 P15
[Data type] Bit
P15 Display unit type of CNC Screen Display function is ;
1: 15-inch display unit type
0: 10.4-inch display unit type
Note
This parameter is available only for CNC Screen Display function of
Stand-alone typeFS30i/31i/32i-A
Draw A-90128E
No.
Ed. Date Design Description page 29/29
Date 18.05.06 Design. S.Inoue Apprv. N.Mutai