Download as PDF, TXT or read online on Scribd

GO Industrial

2/11-15 Baylink Ave


Deception Bay 4508
sales@goind.com.au

NOTES :

1. Hazardous Area Classification


has been assessed using
- AS/NZS 60079.10.1
2. Gas Group IIA
DIP POINT
3. Temp Class T3
ZONE 1 4.
R0.5 M 5. Interior of tank and interstitial
spaces are Zone 0.

INSIDE PUMP BAY


VENT OUTLET
ZONE 1
ZONE 1
R1.5 M

FROM TANK SHELL


LEGEND :
ZONE 2
R1.5 M GAS / VAPOUR

ZONE 0

ZONE 1
FROM PUMP BAY
ZONE 2
R2 M ZONE 2

FROM PUMP BAY

0 25/07/2022 Initial Issue SM


NO. DATE REVISION BY

DWG TITLE
----
0.6 M
ENGINEER CHECK BY
SM SM
JOB NO DRAWN BY
SM
SCALE DATE
NTS 25/07/2022
DWG NO.
EXAMPLE
SHEET NO. SHEET SIZE

2 of 6 A3