GO Industrial
2/11-15 Baylink Ave
Deception Bay 4508
sales@goind.com.au
NOTES :
1. Hazardous Area Classification
has been assessed using
- AS/NZS 60079.10.1
2. Gas Group IIA
DIP POINT
3. Temp Class T3
ZONE 1 4.
R0.5 M 5. Interior of tank and interstitial
spaces are Zone 0.
INSIDE PUMP BAY
VENT OUTLET
ZONE 1
ZONE 1
R1.5 M
FROM TANK SHELL
LEGEND :
ZONE 2
R1.5 M GAS / VAPOUR
ZONE 0
ZONE 1
FROM PUMP BAY
ZONE 2
R2 M ZONE 2
FROM PUMP BAY
0 25/07/2022 Initial Issue SM
NO. DATE REVISION BY
DWG TITLE
----
0.6 M
ENGINEER CHECK BY
SM SM
JOB NO DRAWN BY
SM
SCALE DATE
NTS 25/07/2022
DWG NO.
EXAMPLE
SHEET NO. SHEET SIZE
2 of 6 A3