REVISED DATE:01.07.2014
ERROR / FAULT CODE
CARRIER & MIDEA WRAC RANGE
REVISED DATE:01.07.2014
CARRIER WRAC: DISPLAY
Feature Feature Description Feature Feature Description
Display on Display on
PCB PCB
REVISED DATE:01.07.2014
CARRIER WRAC: ERROR
Feature Feature Description Feature Feature Description
Display on Display on
PCB PCB
REVISED DATE:01.07.2014
FAULT/ ERROR CODE
WRAC – 1.0, 1.5 & 2.0 TR DURAKOOL , ESTRELLA & G-NEX
MIDEA WRAC: DISPLAY PANEL
REVISED DATE:11.06.2014
MIDEA WRAC: CHANGE TEMP DISPLAY ⁰С ⁰F
Frosting protection on coil (Turn off the unit and restart to normal operation)
REVISED DATE:11.06.2014
ERROR / FAULT CODE
CARRIER, MIDEA & CAMIPRO HW SPLIT RANGE
REVISED DATE:01.07.2014
FAULT/ ERROR CODE
DURAKOOL HW – 1.0 & 1.5 TR
REVISED DATE:01.07.2014
FAULT/ ERROR CODE
DURAKOOL HW – 2.0 TR
X Not accept command Indoor Coil sensor Loose Connection/ Short Circuit/ Faulty
Flash
X Not accept command Room Sensor Connection circuit/ Short Circuit/ Faulty
Flash
Indoor Coil & Room sensor open circuit/ Short Circuit/
X Not accept command
Flash Faulty
O X Yes accept command Blower Motor Over Heated/ Open Circuit/ Faulty
DURAKOOL PLUS, STAR & NEO, DURAEDGE & PLUS HW- 1.0 & 1.5 TR
Operation LED Timer LED IDU accept Remote's Commond Fault Description
REVISED DATE:01.07.2014
FAULT/ ERROR CODE
DURAKOOL PLUS, STAR & NEO,
DURAEDGE & PLUS- HW – 2.0 TR
ERROR/ FAULT CODE- 2.0 TR, DURAKOOL PLUS, STAR & NEO, DURAEDGE & PLUS HW SPLIT UNIT
IDU accept Remote's
Operation LED Auto LED Timer LED Fault Description
Commond
X X Not accept command Indoor Coil sensor Open circuit/ Short Circuit/ Faulty
Flash
X X Not accept command Room sensor Open circuit/ Short Circuit/ Faulty
Flash
X X Not accept command Indoor Coil or Room sensor Open circuit/ Short Circuit/ Faulty
Flash
O X X Yes accept command Blower Motor Over Heated/ Open Circuit/ Faulty
REVISED DATE:01.07.2014
FAULT/ ERROR CODE
KURVE HW – 1.0, 1.5 & 2.0 TR
REVISED DATE:01.07.2014
FAULT/ ERROR CODE
NOVELLO SERIES, SUPERIA, MAGNA SERIES,
ELEKTRA, KOSMIC, FRESKO, FLAIR SERIES &
CAMIPRO - HW – 1.0, 1.5 & 2.0
ERROR/ FAULT CODE- NOVELLO SERIES, SUPERIA, MAGNA SERIES, ELEKTRA, KOSMIC & FRESKO
FLAIR RANGE & CAMIPRO - HW – 1.0, 1.5 & 2.0 TR
Display Operation LED Timer LED Fault Description
E1 X EEPROM Error
Flash 1 time
E4 X Dafault
Flash 4 time
IDU Room Temp. Sensor Loose Connection/ open circuit/
E5 X
Flash 5 time Short Circuit
IDU Evaporator Temp. Sensor Loose Connection/ open
E6 X
Flash 6 time circuit/ Short Circuit
E1 X EEPROM Error
Flash 1 time
E2 X Zero crossing detection Error
Flash 2 time
E3 X IDU motor speed out of Control
Flash 3 time
E4 X Over current protection of compressor occurred 4 times
Flash 4 time
E5 X IDU Room Temp. Sensor T-1, Loose Connection/ open circuit/ Short Circuit
Flash 5 time
E6 X IDU Evaporator Temp. T-2 Sensor, Loose Connection/ open circuit/ Short Circuit
Flash 6 time
(X) Off (O) Light ( ) Flash
REVISED DATE:01.07.2014
ERROR / FAULT CODE
CARRIER & MIDEA INVERTER RANGE
REVISED DATE:01.07.2014
IDU DISPLAY FUNCTION: ELEKTRA & SUPERIA INVERTER SERIES
Signal Receiver IDU DISPLAY FUNCTION
SYMBOL
DESCRIPTION
A B
Run Indication
Flash at 0.5Hz (1 Flash/ Sec) when the unit is standby. Illuminate when the
(A) run unit is turned on.
Timer Indicator
timer This indicator illuminates when TIMER is set ON/OFF.
REVISED DATE:01.07.2014
ERROR CODE: ELEKTRA & SUPERIA INVERTER SERIES
ERROR/ FAULT CODE ELEKTRA & SUPERIA INVERTER
Nos. of Flash
Display Timer LED Failure Description
Run LED
E0 1 X EEPROM error
E1 2 X Indoor and outdoor communication error
E2 3 X Zero crossing detection error
E3 4 X Fan speed has been out of control Indoor
E4 5 X Indoor room temperature sensor T1 open circuit or short circuit
E5 6 X Evaporator coil temperature sensor T2 open circuit or short circuit
EC 7 X Refrigerant leak detection error
F1 2 O Outdoor temperature sensor T4 open circuit or short circuit
F2 3 O Condenser coil temperature sensor T3 open or short circuit
F3 4 O Compressor discharge temperature sensor T5 open circuit or short circuit
F4 5 Outdoor EEPROM parameter error
P0 1 IPM malfunction or IGBT over-strong current
P1 2 Over voltage or too low voltage protection
P2 3 Temperature protection of compressor top
P4 5 Inverter compressor drive error
(X) Off (O) Light ( ) Flash
REVISED DATE:01.07.2014
ERROR CODE: ELEKTRA & SUPERIA INVERTER SERIES
E0/F4: EEPROM parameter error diagnosis and solution
Shut off the power supply If the EEPROM chip is welded on main PCB, YES Replace the indoor main PCB.
and turn it on 5 seconds replace the main PCB directly. Otherwise,
YES check whether the EEPROM chip plugged
later. Is it still displaying
the error code? in main PCB Well? NO Correct the connection
Change
Is the the IDU
Is the wiring wiring to main PCB
to the indoor the IDU and On Change
main PCB YES main PCB YES the YES ODU
connected connected power, if PCB
correctly? correctly? error
exist
REVISED DATE:01.07.2014
ERROR CODE: ELEKTRA & SUPERIA INVERTER SERIES
E3: Indoor fan speed has been out of control diagnosis and solution
Check
Shut off the Check the wires Check whether whether the
Shut off the power supply of fan motor. the fan motor
power supply, main PCB is
and turn it on 5 seconds YES YES Are all the YES is normal YES
rotate the fan by normal
later. Is it still displaying connections through index
hand. Does it through
the error code? good? 1?
rotate properly? index 2?
NO
NO
NO
NO
NO
The unit operates normally Find out the cause and Correct the Replace the NO Replace the
have it solved. For connections. Fan Motor
main PCB. The
example, check whether
If problem malfunction is
the fan is blocked or the YES
exist solved?
bearing is broken?
Measure the resistance value of each Power on and set the unit running in fan
winding by using the tester.? mode at high speed, After running for 15
seconds, measure the voltage of Pin-1 and
Pin-2. If value is less than 100V (208~240V
Power supply), the PCB must has problems
and need to be replaced
REVISED DATE:01.07.2014
ERROR CODE: ELEKTRA & SUPERIA INVERTER SERIES
E4/ E5/ F1/ F2/ F3: Open circuit or short circuit of temperature sensor diagnosis and solution
Check the connections between temperature Check the resistance value of the sensor NO Replace the sensor and check if
YES
sensor and main PCB. Are the connections good ? via table-1 and table- 2, is it normal? the problem happen again?
NO
YES
Correct the connections. Replace indoor or outdoor main PCB.
Temperature Sensors.
T1 : Room temp. sensor, T2 : IDU Coil temp. sensor, T3 : ODU coil temp. sensor, T4 : ODU Ambiant temp. sensor,
T5: Compressor discharge temp. sensor. Measure the resistance value of each winding by using the multi-meter.
Table 1: Some frequently-used R-T data for T1,T2,T3 and T4 and T4 sensor
Temperature (℃) 5 10 15 20 25 30 35 40 45 50 55 60
Resistance Value (KΩ) 26.9 20.7 16.1 12.6 10 8 6.4 5.2 4.2 3.5 2.8 2.4
Table 2: Some frequently-used R-T data for T5 sensor
Resistance Value (KΩ) 141.6 87.9 88 70 56.1 45.2 36.6 29.8 24.4 20.1 16.6 13.8
REVISED DATE:01.07.2014
ERROR CODE: ELEKTRA & SUPERIA INVERTER SERIES
COMPRESSOR CHECKING
Resistance at (20⁰С)
Position DA108X1C-23EZ DA130M1C-31FZ DA130S1C-20FZ DA150S1C-20FZ DA250S2C-30MT
Blue - Red
Blue - Black 1.1Ω 0.95Ω 0.95Ω 0.95Ω 0.55Ω
Red - Blue
REVISED DATE:01.07.2014
IDU DISPLAY FUNCTION: KURVE INVERTER SERIES
Frequency Indicator
3
This indicator appears only when the compressor is in operation and indicates the current operating frequency
Temperature Indicator
(A) Usually it displays the temperature settings. When change the setting temperature, this indicator begins to flash, and
4
stops 20 seconds later. (B) It displays the room temperature when the air conditioner is in FAN only operation. (C)
Displays the malfunction code or protection code.
Operation Indicator
5
This indicator flashes after power is on and illuminates when the unit is in operation
Timer Indicator
6
This indicator illuminates when TIMER program is set ON/OFF
Clean Air Indication lamp (on some models)
7
Lights up when CLEAN AIR feature is activated
REVISED DATE:01.07.2014
ERROR CODE: KURVE INVERTER SERIES
REVISED DATE:01.07.2014