2010 Multi V Trouble Shooting Guide Book

2010
Trouble Shooting
Guide Book

www.lgeaircon.com
EE0CVVT-01A

2010
Trouble Shooting
Guide Book
Trouble Shooting Guide Contents

Basic Part
PAGE 5
Search with Error Code number

1. Basic Part 5
1.1 Unit conversion (Energy / Pressure) 6

Troubleshooting
Guide for each
1.2 NOMENCLATURE 7

PAGE 43
Error Code
1.3 LGMV Guideline 13
1.4 Temperature vs pressure of refrigerant 14
1.5 P-h Diagram 15
1.6 Cycle Circuit & Sensor 16
1.7 Outdoor Wiring Diagram 30

Component Check
PAGE 172

Electrical
2. Troubleshooting Guide for each Error Code (Refer page 4) 43

3. Electric Component Check 172


3.1 How to check main control box? 173
3.2 How to check inverter control box? 180

Solution Check
3.3 How to check Multi V Space control box? 187

PAGE 199
3.4 How to check indoor unit PCB? 190
3.5 How to check other electric components 191

4. Solution Check 199


Central control structure 200
A- Installation guide 201

Test functions
PAGE 277
B- Trouble shooting 217
C- Technical bulletin 258

5. Test functions (Plus II) 277


5.1 Sensor checking 281
5.2 Auto charging 283
5.3 Auto refrigerant checking 285
5.4 Pump down 287
5.5 Pump out 288
5.6 Vacuum mode 290
5.7 Static pressure compensation mode 290
No part of this publication may be reproduced, stored in or introduced into a retrieval 5.8 Pipe searching 291
system, or transmitted, in any form, or by any means (electronic, mechanical, photocopying, 5.9 Manual pipe searching 295

or otherwise), without prior permission of the LG Electronics Inc. Air-Conditioning Division


Appendix #1 : Resistance value table of temperature sensor 296
Search with Error Code number

R: Reserved
Error Error Error Error Error Error Error
Page Page Page Page Page Page Page
code code code code code code code
01 45 41 102 81 121 102 161 105 201 168 241 170
02 45 42 104 82 122 102 162 102 202 168 242 170
03 45 43 104 83 R 123 105 163 102 203 168 243 170
04 47 44 105 84 124 105 164 105 204 169 244 170
05 49 45 105 85 125 148 165 105 205 168 245 170
06 50 46 105 86 132 126 148 166 148 206 168 246 170
07 50 47 105 87 133 127 148 167 148 207 168 247
08 R 48 105 88 128 104 168 148 208 169 248 R
09 51 49 107 89 129 104 169 95 209 168 249
10 52 50 108 90 130 105 170 98 210 168 250 171
11 53 51 109 91 131 R 171 83 211 168 251 171
12 52 112 92 132 105 172 107 212 169 252 171
13 53 113 93 133 102 173 155 213 168 253 171
R
14 54 114 94 134 102 174 155 214 168 254
15 55 95 135 105 175 155 215 168 255
16 R 56 96 136 105 176 155 216 169 256
R
17 57 97 137 148 177 155 217 168 257
18 58 98 138 148 178 218 168 258

1. Basic Part
R
19 59 116 99 139 148 179 219 168 259
20 60 117 100 134 140 79 180 156 220 169 260
21 65 61 R 101 134 141 104 181 157 221 168 261
22 73 62 118 102 134 142 135 182 158 222 168 262
23 77 63 103 134 143 95 183 223 168 263
R
24 79 64 104 135 144 98 184 224 169 264
25 83 65 119 105 137 145 95 185 225 168 265
26 84 66 R 106 139 146 98 186 226 168 266
27 R 67 120 107 145 147 83 187 227 168 267 R
R
28 85 68 108 R 148 107 188 228 169 268
R
29 86 69 109 147 149 83 189 229 168 269
30 70 122 110 147 150 107 190 230 168 270
R
31 71 123 111 147 151 151 191 231 168 271
32 88 72 R 112 R 152 88 192 232 169 272
33 88 73 124 113 148 153 88 193 159 233 273
34 95 74 126 114 148 154 79 194 159 234 274
35 98 75 127 115 148 155 114 195 235 275
36 76 128 116 149 156 135 196 236 R 276
37 77 129 117 149 157 104 197 R 237 277
R
38 78 130 118 105 158 104 198 238 278
39 79 131 119 R 159 105 199 239 279
40 100 80 R 120 105 160 R 200 160 240 170 280

Basic Part_ 005


1.1 UNIT CONVERSION 1.2 NOMENCLATURE
1.2.1 Multi V Indoor Unit (R410A)

Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

Component Check
Electrical
Solution Check
1.2.2 Multi V Plus Outdoor Unit (R410A)

Test functions
006 _LG Air Conditioners System Basic Part_ 007
1.2.3 Multi V Plus II Outdoor Unit (R410A) 1.2.5 Multi V Space Outdoor Unit (R410A)

Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

Component Check
Electrical
1.2.4 Multi V Plus II Outdoor Unit (R410A)

Solution Check
1.2.6 Multi V Space II Outdoor Unit (R410A)

Test functions
008 _LG Air Conditioners System Basic Part_ 009
1.2.7 Multi V Sync Outdoor Unit (R410A) 1.2.9 Multi V Mini Outdoor Unit (R410A)

Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

Component Check
Electrical
1.2.8 Multi V Sync II Outdoor Unit (R410A)
1.2.10 Multi V Water II Outdoor Unit (R410A)

Solution Check
Test functions
B: Inverter and Heat Recovery

010 _LG Air Conditioners System Basic Part_ 011


1.2.11 Multi V Indoor Unit (R22) 1.3 LGMV Guideline

Abnormal Abnormal
No Item Unit R22,407C 410A Cause & Check Point
condition condition

Basic Part
Overcharging(30Hz),Fan Lock
above 2200 above 3200
1 High Pressure kPa 1100~1800 2000 ~ 3000 Overchaning(25Hz:Plus II)
below 900 below 1800 Ref. Leakage or Ref. Shortage
Low Pressure above 600 above 1300 Overcharging
2 kPa 300~500 600 ~ 1000
(Cooling) below 250 below 400 Ref. Leakage or Ref. Shortage
above 1000 above 1000 Ref. Leakage or Ref. Shortage
3 Indoor LEV Pulse 200~600 200~600
below 200 below 200 Overcharging
4 Outdoor LEV Pulse 1944 - 1344 - Full Open

Troubleshooting
Guide for each
Indoor pipe Overcharging

Error Code
5 ఁ above 0ఁ below -1ఁ above 0ఁ below -1ఁ
[Outlet-inlet] LEV fault
Indoor pipe Ref. Leakage,
6 ఁ 8ఁ~15ఁ above 17ఁ 6ఁ~15ఁ above 17ఁ
Inlet,Outlet Indoor Path. Clogging
Overcharging
High Pressure above 2300 above 3300
Trouble Shooting Guide Book

7 kPa 1600~2000 2500 ~ 3200 Fan Lock


(Heating)
below 1400 below 2300 Ref. Leakage or Ref. Shortage
above 800 above 1200 LEV fault
8 Low Pressure kPa 200~600 200 ~ 1200

Component Check
below 120 below 120 Ref. Leakage or Ref. Shortage

9 Indoor LEV Pulse 800~1900 - 200~1350 - Pipe Inlet/outlet Subcooling control

Electrical
300~1600 below 200 below 200 Overcharging
10 Outdoor LEV ఁ 200~800
(100~400) above 1800 above 1000 Ref. Leakage or Ref. Shortage
Discharge pipe - Overcharging
11 ఁ above 15ఁ below 15ఁ above 17ఁ below 17ఁ
Tb(condense) LEV fault
above 110ఁ above 110ఁ Ref. Leakage or Ref. Shortage
12 Comp. Discharge T. ఁ 60~100 60~100
below 50ఁ below 50ఁ LEV fault
Suction above 0.5ఁ below 0ఁ below 0ఁ Liquid compression, Overcharging

Solution Check
13 above 0.5ఁ
1.2.12 Multi V Plus Outdoor Unit (R22)

Superheat above 7ఁ above 7ఁ Ref. Leakage or Ref. Shortage
above 380V Below 320V Inv. PCB fault,
14 DC Link voltage(Plus II) V
Above 700V Voltage sensor fault

Test functions
- The pressure is relative value.
- The operation ratio of indoor unit is not less than 80% and the value of above table is measured at stable state with LGMV
- The value of above table is not absolute and can be changed according to operation status or installation environment
- The causes of above table are representative and another cause also can exist.

012 _LG Air Conditioners System Basic Part_ 013


1.4 Temperature vs. pressure of ref. 1.5 P-h Diagram
Saturation temperature vs. saturation pressure table for
each refrigerant R22
Absolute pressure = Guage pressure + 101.325 kPa

Basic Part
kPa = kgf/cm2 X 101.97

R-22 R-407C
Relative ‫ۀۑۄۏڼۇۀڭ‬
Temp. ‫ډۋۈۀگ‬ Relative pressure(kPaG) Temp.(୅)
Pressure ‫ۀۍېێێۀۍۋ‬
‫ڿۀۏڼۍېۏڼڮ‬ ‫ڿۀۏڼۍېۏڼڮ‬ ‫ڿۀۏڼۍېۏڼڮ‬
୅ kPaG ୅ ‫ێڼڢٻڿۀۏڼۍېۏڼڮ‬ kPaG
‫ڿۄېیۄڧ‬ ‫ڿۄېیۄڧ‬ ‫ێڼڢ‬
-30 62.56 -30 86.75 37.87 50 -35.26 -28.35

Troubleshooting
-25 100.11 -25 129.50 72.67 100 -28.52 -21.75

Guide for each


Error Code
-20 143.99 -20 179.43 113.92 150 -22.99 -16.34
-15 194.87 -15 237.28 162.41 200 -18.25 -11.71
-10 253.46 -10 303.86 218.96 250 -14.09 -7.64
-5 320.48 -5 378.98 284.43 350 -6.98 -0.69
Trouble Shooting Guide Book

0 396.66 0 466.50 359.72 400 -3.87 2.35


5 482.78 5 564.29 445.77 500 1.71 7.78
10 579.62 10 674.25 543.56 600 6.63 12.57

Component Check
15 687.99 15 797.30 654.12 750 13.09 18.85
20 808.69 20 934.41 778.51 850 16.94 22.59

Electrical
25 942.59 25 1086.55 917.87 1000 22.17 27.67
30 1090.55 30 1254.72 1073.36 1150 26.91 32.24
35 1253.46 35 1439.97 1246.28 1300 31.23 36.42
40 1432.25 40 1643.37 1437.87 1550 31.23 36.42
45 1627.89 45 1866.04 1649.67 1750 42.42 47.18
50 1841.36 50 2109.14 1883.24 2000 47.78 52.30
55 2073.75 55 2373.87 2140.33 2250 52.69 56.97

Solution Check
60 2326.16 60 2661.51 2422.98 2550 58.09 62.08
65 2599.83 65 2973.36 2733.60 2850 63.05 66.74
70 2896.07 70 3310.77 3075.22 3200 68.38 71.69
R410A

R-410A
Relative
Temp. Relative pressure(kPaG) Temp.(୅)
pressure
Saturated Saturated Saturated
୅ Saturated Gas kPaG
Liquid Liquid Gas

Test functions
-30 169.62 168.91 170 -30.09 -30.02
-25 229.70 228.81 230 -25.08 -25.01
-20 299.57 298.46 300 -20.06 -19.99
-15 380.23 378.87 380 -15.09 -15.01
-10 472.75 471.09 470 -10.21 -10.12
-5 578.21 576.21 580 -4.98 -4.89
0 697.76 695.38 700 0.04 0.13
5 832.60 829.77 830 4.86 4.96
10 983.94 980.63 980 9.84 9.94
15 1153.09 1149.25 1150 14.88 14.98
20 1341.39 1336.98 1350 20.18 20.29
25 1550.25 1545.26 1550 24.96 25.08
30 1781.19 1775.59 1800 30.36 30.47
35 2035.78 2029.59 2000 34.30 34.42
40 2315.76 2309.03 2300 39.71 39.82
45 2623.00 2615.82 2600 44.62 44.73
50 2959.61 2952.13 2950 49.84 49.95
55 3328.02 3320.49 3400 55.91 56.01
60 3731.18 3724.00 3700 59.61 59.70
65 4173.11 4166.98 4200 65.28 65.34
70 4746.09 4706.31 4700 70.17 70.17

014 _LG Air Conditioners System Basic Part_ 015


1.6 Cycle Circuit & Sensor 1.6.1.2 Main Outdoor Unit (Plus II 8HP)

1.6.1 Multi V Plus, Plus II


1.6.1.1 Main Outdoor Unit(5/6 HP)

Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

Component Check
Electrical
Solution Check
Test functions
016 _LG Air Conditioners System Basic Part_ 017
1.6.1.3 Main Outdoor Unit (Plus 8~14HP, Plus II 10~16HP) 1.6.1.4 Sub Outdoor Unit (Plus 8/10/12/14 HP)

Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

Component Check
Electrical
Solution Check
Test functions
018 _LG Air Conditioners System Basic Part_ 019
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
021 Basic Part_
1.6.2.2 Heating Mode
1.6.2 Multi V Sync, Sync II

020 _LG Air Conditioners System


1.6.2.1 Cooling Mode
Trouble Shooting Guide Book
1.6.2.3 Cooling Oriented Simultaneous Operation 1.6.2.4 Heating Oriented Simultaneous Operation

Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

Component Check
Electrical
Solution Check
Test functions
022 _LG Air Conditioners System Basic Part_ 023
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
025 Basic Part_
1.6.4 Multi V Space II (8, 10HP cooling only)
1.6.3 Multi V Space (10HP)

024 _LG Air Conditioners System


Trouble Shooting Guide Book
1.6.5 Multi V MINI (4HP/5HP/6HP) 1.6.6 Multi V MINI (4HP/5HP/6HP)

Cooling operation Heating operation

Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

Component Check
Electrical
Solution Check
Test functions
026 _LG Air Conditioners System Basic Part_ 027
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
029 Basic Part_
1.6.8 Multi V Water II H/P (20HP)
1.6.7 Multi V Water II H/P (10HP)

028 _LG Air Conditioners System


Trouble Shooting Guide Book
1.7. Outdoor Wiring Diagram 1.7.1.2 Multi V Plus II Sub 5,6HP(UY2)

1.7.1 Multi V Plus


1.7.1.1 Multi V Plus Main Unit

Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

Component Check
Electrical
Solution Check
Test functions
030 _LG Air Conditioners System Basic Part_ 031
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
033 Basic Part_
1.7.1.4 Multi V Plus II 10,12,14,16HP(UW1)
1.7.1.3 Multi V Plus II 8HP(UW1)

032 _LG Air Conditioners System


Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
035 Basic Part_
1.7.1.6 Multi V Plus Sub Unit
1.7.1.5 Multi V Plus II 10,12HP(UW1)

034 _LG Air Conditioners System


Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
037 Basic Part_
1.7.2.2 Multi V Space II

036 _LG Air Conditioners System


1.7.2.1 Multi V Space
Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
039 Basic Part_
1.7.3.2 Multi V Sync Sub Unit
1.7.3.1 Multi V Sync Main Unit

038 _LG Air Conditioners System


1.7.3 Multi V Sync
Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
041 Basic Part_
1.7.5 Multi V MINI

040 _LG Air Conditioners System


1.7.4 HR Unit
Trouble Shooting Guide Book
1.7.6 Multi V Water II
Trouble Shooting Guide Book

2. Troubleshooting
Guide for each
Error Code*

* Includede model :
Multi V Plus, Sync, Sync II, Plus II (Tropical), Water

042 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 043
Error code Error Contents Meaning Main Causes
[Cautions when measuring voltage and current of inverter power circuit] 01 Indoor unit air sensor error
Measuring values may differ depending on measuring tools and measuring circuits since voltage, 1. Indoor unit PCB wrong connection
Indoor unit sensor is
02 Indoor unit pipe inlet sensor error 2. Indoor unit PCB failure
current in the power supply or output side of the inverter has no since waveform. open/short
3. Sensor problem (main reason)
Especially, output voltage changes when output voltage of the inverter has a pattern of pulse wave. 06 Indoor unit pipe outlet sensor error
In addition, measuring values appear largely differently depending on measuring tools.
1) If using a movable tester when checking that output voltage of the inverter is constant (when Error diagnosis and countermeasure flow chart

Basic Part
comparing relative voltage between lines), always use an analog tester. Especially exercise particular
caution if the output frequency of the inverter is low, when using a movable tester, where change of
measured voltage values is large between other lines, when virtually same values appear actually or
Is sensor properly No
where there is danger to determine that failure of the inverter occurred. Connect properly to PCB
connected to PCB?
2) You can use rectification voltmeter ( ) if using commercial frequency tester when measuring
output values of the inverter (when measuring absolute values). Accurate measuring values cannot
Yes
be obtained with a general movable tester (For analog and digital mode).

Troubleshooting
Guide for each
Error Code
Is the resistance value No
Change the sensor
of sensor normal?*

Yes
Trouble Shooting Guide Book

Change the PCB

Component Check
Electrical
* In case the value is more than 100 ༮ (open) or less than 100 ȳ(short), Error occurs

Refer: Resistance value maybe change according to temperature of temp sensor,


It shows according to criteria of current temperature(·5% margin) ˧ Normal
Air temp sensor: 10୅ = 20.7༮ : 25୅= 10༮ : 50୅= 3.4༮
Pipe temp sensor: 10୅ = 10༮ : 25୅= 5༮ : 50୅= 1.8༮

Solution Check
CN-ROOM : Indoor air temp sensor

CN-PIPE2 : Pipe outlet temp sensor

CN-PIPE1 : Pipe inlet temp sensor

Test functions
Measure the resistance of outlet pipe temp sensor.

044 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 045
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes

1. Remote controller fault 1. Drain pump/float switch fault


Float switch is open due to rising of
The remote controller did not 2. Indoor unit PCB fault 2. Improper drain pipe location,
No transmission between cabled remote 04 Drain pump error condensate water level because of drain
03 receive the signal from indoor 3. Connector fault, Wrong clogging of drain pipe
controller & indoor unit pump fault or drain pipe clogging
unit during specific time connection 3. Indoor unit PCB fault
4. transmission cable problem

Error diagnosis and countermeasure flow chart Error diagnosis and countermeasure flow chart

Basic Part
Does the error happens No Is the drain pan filled
Replace cabled remote No Is Float switch short No
again if the remote half with condensate
controller On measuring its Replace float switch
controller is replaced?* water? (half level of
resistance?
float switch)*

Troubleshooting
Yes

Guide for each


Yes
Yes

Error Code
No Replace Indoor PCB or
Does the error occurred reconnect the connector
Check connection &
when the cable of remote
transmission cable **
controller is replaced?
Trouble Shooting Guide Book

In indoor unit PCB


Is drain pump working? No No
Does the terminal voltage
(Sound/drain noise/ Replace indoor unit PCB
for drain pump has
Yes contact etc.)
220V output?**

Component Check
Yes Yes
Replace indoor unit PCB ***

Electrical
Replace Drain Pump

* If there is no remote controller to replace : Use another unit’s remote controller doing well
** Check cable : Contact failure of connected portion or extension of cable are main cause No
Check any surrounded noise ( check the distance with main power cable) Drain pump blocked by Check the drain head height
˧ make safe distance from the devices generate electromagnetic wave foreign particles? and slope***
*** After replacing indoor unit PCB, do Auto Addressing & input unit’s address if connected to central controller.
(All the indoor units connected should be turned on before Auto Addressing

Solution Check
Yes
Checking float
switch
Remove it & clean the pump (Low position ૟ short ୒ 0 ohm )

Test functions
CN-REMO : Remote controller connection

୔The PCB can differ from model to model.


Check from the right source.
*If the float goes up higher than a half of float switch
then the circuit is open & the unit is stopped
automatically.

(High position ૟ Open )

float
Checking transmission cable connection status

Condensate water

046 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 047
Error code Error Contents Meaning Main Causes

1. Auto addressing is not done


2. transmission cable is not connected
No signal
Indoor & Outdoor 3. Short circuit of transmission cable
transmission
05 unit transmission 4. Indoor unit transmission circuit fault
between indoor
error 5. Outdoor unit transmission circuit fault
& outdoor units.
6. Not enough distance between power and transmission cable?
7. Is the fuse for main PCB power of outdoor unit burnt out?

Basic Part
float Error diagnosis and countermeasure flow chart

Replace the PCB of indoor unit


No displayed error
No Is total number of indoor
Does all indoor show
units connected displayed Re-connect after check the
this error code CH05?

Troubleshooting
after auto addressing? transmission cable of indoor

Guide for each


Error Code
unit displayed error**
A:Point to check rotating ***Indoor PCB drain pump connector Yes
END
(Check input of 220V)
Replace outdoor PCB after
(Marked as CN-DPUMP) No No checking
Is not the power
Trouble Shooting Guide Book

Is outdoor PCB LED


supplied at main terminal
flickering? Replace TRANS after checking
block of outdoor unit ?

Component Check
Float switch connector Yes Replace main PCB fuse after
Yes checking

Electrical
Check the insulation of inverter
No / constant compressor and then
Is main circuit breaker off? replace it
Float switch Housing (CN-FLOAT)
Yes Replace after capacity of
main circuit breaker?
Bad connection of power supply cable

Solution Check
If nothing goes wrong,
Turn on main circuit breaker
Main power supply problem
Check if the
transmission
cable is properly No
Re connect transmission cable
connected
to indoor / outdoor
terminal block?*
[***]Standard of drain pipe head height / slope Yes Outdoor PCB fault

Test functions
Replace after checking

Indoor PCB fault


Replace after checking

MAX 450

* If the DC voltage between transmission terminal A, B ** If the DC voltage between transmission terminal A, B
of outdoor unit is fluctuate within (-9V~+9V) then of indoor unit is fluctuate within (-9V~+9V) then
transmission from indoor unit is normal transmission from outdoor unit is normal

048 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 049
Error Code Error Contents Meaning Main Causes Error Code Error Contents Meaning Main Causes

Indoor unit outlet pipe Indoor unit outlet pipe temperature Problem in EEPROM inside 1.Error developed in transmission between the micro-
06 Refer to CH02 Indoor unit EEPROM
temperature sensor error sensor open or short 09 Indoor PCB ASS’Y ⇨ processor and the EEPROM on the surface of the PCB.
error
EEPROM 2.ERROR due to the EEPROM damage

1. Indoor units are in different mode


The Indoor units started later are
All Indoor units are not running in 2. PCB fault
07 operated in different mode from

Basic Part
same mode
earlier one.
3. Wrong setting of wired remote Error diagnosis and countermeasure flow chart
controller or remote controller fault*
- Replace the indoor unit PCB, and then make sure to do Auto addressing and input the address of central control

Error diagnosis and countermeasure flow chart

Troubleshooting
Guide for each
Is error code
Is operation mode of No

Error Code
No disappeared
outdoor & Indoor units Replace Indoor PCB****
after set operation
same?
mode same?***

Yes Yes
Trouble Shooting Guide Book

END

Component Check
Adjust outdoor main PCB ሲ Wired remote controller
dip switch setting **

Electrical
Solution Check
* Check mode select setting of wired remote controller.

** Outdoor main PCB dip switch no.5 (Cooling) or no.6 (heating) is in On, different mode operation error
may be occurred because the operation mode is fixed by dip switch setting.

ሲ Dip switch Setting ሲ

1. Cooling mode only

Test functions
*** Dissolution method CH07 with remote controller
1) Error removal method : Turn off remote controller by pressing the On/Off button on the cabled remote controller.
The error code will be removed automatically after a few seconds.
With cableless remote controller: Turn off indoor unit, and turn on with the other operation
mode the error will disappeared
2) Immediately change the operation mode after the pressing the On/Off button .
The same operation mode as in the indoor unit started at first other than the defective unit mode (heating /cooling)

**** After replacing the indoor unit PCB, it should be done to do Auto addressing and input the address of central control

050 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 051
Error Code Error Contents Meaning Main Causes Error Code Error Contents Meaning Main Causes

1. Motor connector connection fault Indoor unit doesn’t get signal


Indoor unit BLDC fan motor Indoor BLDC fan motor feedback Indoor unit 1. Indoor 485 transmission PCB fault
10 2. Indoor PCB fault 11 from ODU for 3 minutes
failure signal is absent (for 50 sec.) transmission error 2. After PCB replacing, auto addressing was not done
3. Motor fault continuously

Error diagnosis and countermeasure flow chart

Basic Part
Error diagnosis and countermeasure flow chart

Is connector No After ODU main PCB No No


Connect properly After Auto addressing, Replace indoor unit 485
connection proper? reset, error code
error code disappears? transmission PCB
disappears?
Yes
Yes Yes

Troubleshooting
Guide for each
Error Code
Is fan motor No
Replace indoor unit fan motor
normal?*
END
Yes
Trouble Shooting Guide Book

Replace indoor unit PCB **

Component Check
Electrical
* It is normal when check hall sensor of indoor fan motor as shown below

Solution Check
hundreds kȳ hundreds kȳ

hundreds kȳ hundreds kȳ

Test functions
<Checking connection state of fan motor connector>

** Replace the indoor unit PCB, and then make sure to do Auto addressing and input the address of central control
(Notice: The connection of motor connector to PCB should be done under no power supplying to PCB)

052 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 053
- Compressor checking - Fan checking

Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

w“œšGppSGz •ŠGppGaG

Component Check
w“œšGaG

Electrical
*table #1

Solution Check
Test functions
*table #1
Multi B Plus II / Sync II / Multi V MINI Multi V MINI
Multi V Plus/Sync
Water II (1Ȱ) (3Ȱ)

U-V : 1.16ȳ · 7% U-V : 1.083ȳ· 10%


Inverter
1.2ȳ · 10% V-W : 1.19ȳ · 7% 0.188ȳ · 10% V-W : 1.123ȳ ·10%
Compressor
U-W : 1.21ȳ · 7% U-W : 1.096ȳ ·10%

U-V : 1.96ȳ · 10%


Const Speed
V-W : 1.91ȳ · 10% -
Compressor
U-W : 1.99ȳ · 10%

054 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 055
- EEV - EEV

Basic Part
Q

PCB connector

Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

Component Check
Electrical
<EEV wiring (Outdoor unit)>

Solution Check
Outdoor unit main LEV Outdoor unit sub cooling LEV Indoor unit LEV

Test functions
* : For this checking, you should make LED circuit by yourself

ྙ - ྛ : around 300˟ ྙ - ྛ : 104 · 6˟ ྙ - ྛ : around 300˟

ྚ - ྜ : around 300˟ ྚ - ྜ : 104 · 6˟ ྚ - ྜ : around 300˟

ྙ - ྜྷ or ྛ - ྜྷ : around 150˟ ྙ - ྞ or ྚ - ྞ or ྙ - ྜྷ or ྛ - ྜྷ : around 150˟

ྜ - ྞ : around 150˟ ྛ - ྞ or ྜ - ྞ : 52 · 3˟ ྜ - ྞ : around 150˟

056 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 057
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
059 Troubleshooting Guide for each Error Code_
- Inverter Compressor’s IPM

058 _LG Air Conditioners System


- Phase Bridge Diode
Trouble Shooting Guide Book
- Fan IPM - Fan IPM

Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

Component Check
Electrical
<1 fan UY chassis)>

Solution Check
Test functions
<2 fan system(UW, UW1 chassis)>

060 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 061
- Capacitors and resistor - Replacement procedure of the compressor(Plus II)

Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

Component Check
Electrical
Solution Check
Test functions
062 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 063
Error Code Error Contents Meaning Main Causes
- Replacement procedure of the compressor(Plus II) Plus :21
1. Over current detection at the inverter
Plus II:
compressor (U,V.W)
211,212,213,214
2. IPM overheating.
3. Insulation damage of the compressor
S IPM fault of inverter Defective inverter compressor,
N1 Right / compressor motor damage
Inverter element (IPM) defect
P 21 Comp. compressor 4. Low input voltage at the outdoor
A 5. Inverter compressor terminal disconnected

Basic Part
C or loose.
E N2 Left
6. Inverter PCB / IPM PCB defect
21 Comp.

Error diagnosis and countermeasure flow chart(Plus II)

Troubleshooting
Guide for each
Error Code

78ȳ · 89ȳ · 79ȳ · 
Trouble Shooting Guide Book

Component Check
Electrical
Solution Check
Test functions
064 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 065
Point Checking Part Check
(Function) points
INV - Deviation between phases should be less than 2A.
INV
Plus
Comp. 2. Power & 3. High pressure 4. DC-Link 6. transmission 5. Checking circuit
Running COMP start-relay switch & sensing & circuit to main for reverse phase
Current PCB drive circuit power-relay display circuit PCB of input power
drive circuit
(INV
(COMP COMP

Basic Part
start) part)

(plus)

U phase V phase W phase


7. On-board
Plus II

writing

Troubleshooting
Guide for each
connector

Error Code
1. MICOM
circuit
Trouble Shooting Guide Book

Coil resistance INV, const. speed comp. resistance :INV COMP ˧ 1.2˟·10%(Plus/Sync), 8. CT sensing
(No power) U-V: 1.16·7%ȳ, V-W: 1.19·7%ȳ, W-U: 1.21·7%ȳ(plus II/SyncII/Space II) MINI model : see page 00 circuit
Constant speed COMP : (U-V)1.96˟/(V-W)1.91˟/(U-W)1.99˟·10%)

Component Check
Electrical
9. PWM driving
signal output
circuit

Phenomena Check point How to check? Counter-measure

U-W phases resistance V-W phase resistance U-V phase resistance No power 2.Power -Input voltage should be 220V. - Check & replace fuse(3.15A),

Solution Check
at PCB (when power is supplied) T-N voltage (220V)
Insulation -Input resistance should be more than a few ༮ - If resistance value is
resistance Insulation resistance : INV COMP ˧ above 2༯, const. comp : above ༯ (when power is not supplied) 0~100˟ ,
(No power) replace PCB

No transmission 6.Transmiss -Yellow LED should blink. - Check yellow LED blinks or
ion circuit not
to main - When is OFF, check
PCB transmission

Test functions
with main PCB and replace

Malfunction of 9.PWM --Green LED should blink. - Replace PCB


Compressor inverter compressor signal -Check IC port coupler
connector cable of PWM drive
(when power is
not supplied)

Comp. connector Comp. conector Cooling fan connector Cooling fan operation
(Plus II)

1-2 Diode : 1.0V 2-3 Diode : 1.4V

Inverter compressor Red LED -When red LED blinks. -Check error code displayed at
PCB Error Error displays about inverter compressor PCB main PCB
IPM bolt connecting

066 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 067
Part Part
Check point Check
(Function) (Function) How to check? Counter-measure
points

Capacitor Electric capacity. -Electricity capacity of capacitor must be - Replace capacitor


IPM Check voltage & (To charge DC (when power is 2600~2800༲ and the resistance of capacitors when value is more or
resistance of voltage for not supplied) should be more than a few ༮ less than normal spec.
each phases inverter
(CH21 (When power compressor)
CH22) is not supplied)

Basic Part
(Plus)
(Plus)

P-U :DIODE(0.4V) P-V :DIODE(0.4V) P-W :DIODE(0.4V)


resistance(a few ༯) resistance(a few ༯) resistance(a few ༯)
* Check values at both

Troubleshooting
Guide for each
terminal of capacitor

Error Code
DC charging - Charged voltage of between terminals of capacitor - Check input voltage
voltage (= between IPM P-N terminal = DC link terminals) and
(When power is should be more than 450V replace capacitor
supplied) (At the moment of inverter compressor start)
Trouble Shooting Guide Book

Component Check
Magnet Magnet switch -When check resistance of 1st coil of magnet switch, -In case resistance is
N-U :DIODE(0.4V) N-V :DIODE(0.4V) N-W :DIODE(0.4V)
Switch 1st coil resistance should be 0.47 ༮ ˳ or 0 ˟,

Electrical
resistance(a few ༯) resistance(a few ༯) resistance(a few ༯)
(When power is not supplied) ૟ Replace Magnet
(Plus) switch
-When magnet switch is on, voltage should be 220V
Sub PCB (When power is not supplied) -When voltage is not
220V, magnet switch
is melt down
- Replace magnet

Solution Check
switch

Check the IPM terminal connecting condition

Test functions
Heat sink ** check point of 1st coil of magnet switch
cooling fan
Magnet switch - While pressing green button of magnet switch, -Replace magnet
(Plus) connection Voltage of each connectors should be 0V or switch
check Resistance should be 0~1˟
(In case power (Warning: power should not be supplied)
is not supplied)

Position of cooling fan Heat sink cooling fan


drive connector in main PCB

068 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 069
Part Check Part
(Function)
Check point
points (Function)
INV 1. Power &
5. Port from 6. Port from
COMP start-relay 2.220V
3. P port 4. N port Diode Reactor Check voltage
drive circuit connector IPM
PCB & resistance of
(INV each phases
(CH21, (When power
- - -
COMP

Basic Part
part)
CH22) is not supplied) + + +

(Plus II) P-U :28kȳ·10% P-V :28kȳ·10% P-W : 28kȳ·10%


(Plus II)
Reverse: P-U :Open P-V :Open P-W : Open

+ + +
U terminal

Troubleshooting
Guide for each
Error Code
7. On-board
V terminal writing connector
- - -
8. CT sensing circuit
Trouble Shooting Guide Book

9.Power relay
N-U :28kȳ·10% N-V :28kȳ·10% N-W : 28kȳ·10%
W terminal Reverse: N-U :Open N-V :Open N-W : Open

Component Check
10.Comm port

Electrical
& LED Check power
Heat sink supplay and
12. PWM LED 11. PWM driving signal output circuit
cooling fan operation
status

Phenomena Check point How to check? Counter-measure (Plus II)

No power 2.Power -Input voltage should be 220V. -T-N voltage (220V)


at PCB (when power is supplied)

Solution Check
-Input resistance should be more than a few ༮ - If resistance value is
(when power is not supplied) 0~100˟ ,
replace PCB

Position of cooling fan Heat sink cooling fan


drive connector in main PCB
(220V output)

Test functions
No transmission 10.Transmi -LEDs should blink. - Check LED blinks or not
(Fan, Main PCB) ssion circuit - When is OFF, check
to main, transmission
fan PCB with main, fan PCB

Inverter compressor 12. PWM -When red LED is on. -Check error code displayed at
PCB Error LED PWM is normal main PCB

070 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 071
Part Check Error code Error Contents Meaning Main Causes
How to check? Counter-measure
(Function) points
Plus:22 1. Compressor damage
Capacitor DC charging - Charged voltage of between terminals of capacitor - Check input voltage Plus II: 2. Current sensing sensor (CT) damage
and replace capacitor 221,222,223,224 3. Low input voltage
(To charge DC voltage (= between IPM P-N terminal = DC link terminals)
The current flowing at the CT 4. compressor terminal is disconnected or loose
voltage for (When power is should be more than 450V Over current of
N1 Right sensing circuit is more than the 5. Abnormality at the outdoor / indoor unit fan
inverter S inverter
supplied) (At the moment of inverter compressor start) 22 Comp. allowable maximum value of the 6. Cover or clogging
compressor) P compressor
A current (Outdoor unit covering during cooling mode

Basic Part
C / Filter clogged at the indoor during heating
N2 Left
(Plus II) mode )
E 22 Comp.
7. Defective inverter PCB/IPM PCB

Error diagnosis and countermeasure flow chart (Plus II)

Troubleshooting
* Check values at both

Guide for each


Error Code
terminal of capacitor

Magnet Magnet switch When magnet switch is on, output voltage should be When output voltage is
Switch 380V (Running) not 380V, Replace PCB
Trouble Shooting Guide Book

(Plus II)
O|T}GaGXUX]ȳ · ^LGVG}T~GaGXUX`ȳ · ^LGV|T~GaGXUYXȳ · ^LP

Component Check
Electrical
Solution Check
Test functions
072 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 073
Part Check Part Check
(Function) points How to check? Counter-measure (Function) points

INV PCB
T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within Standard·10% -Check supply power
and connection (Plus) * Measure the CT current with clamp meter -Multi V SPACE : U(+), U(-), V(+), V(-)
(Terminal - Voltage of 1ɐ(R-N,S-N,T-N) should be within
condition The current difference among
Block, Input 220V·10%. * Multi V PLUS
- Multi / Sync
V PLUS / Sync : R phase phases is less than 0.5A ·10%
power) - Voltage fluctuation should be within 10V
- While stand-by and in operation,

Basic Part
Voltage drop should be within 10V

Troubleshooting
Guide for each
Error Code
Checking points of 3ɐ(R-S) Checking points of 1ɐ(R-N)
Check ȳ - Resistance of R-S,S-T,R-T,R-N,S-N should be -Check short or not of
(In case power more than a few ༮ Control box (Noise filter,
PCB, cables)
Trouble Shooting Guide Book

is not supplied) U(+) U(-) V(+) V(-)


- Resistance of T-N should be within 40~50˟ - Replace transformer
(Main transformer of outdoor)

Component Check
FUSE Check - Voltage of fuse should be within 0~1V -In case of 220V,
disconnection of

Electrical
(Protect over- Fuse is disconnected.
loaded FUSE ૟ Replace FUSE
current) (when power is
supplied)
(plus)

3ɐ DIODE

Solution Check
Checking points of R ɐ fuse (Plus)
Check - Resistance of fuse should be within 0~1˟ -In case resistance is ˳,
disconnection of Fuse is disconnected.
FUSE ૟ Replace FUSE
(when power is
not supplied)

Nose filter Check voltage -Voltage of each connector (R-R,S-S,T-T) should - In case of 220V
(Noise emit & (When power is be within 0~40V It is disconnected
protect) supplied) ૟ Replace noise filter
(Plus) (Plus II)

Test functions
P-U :DIODE(0.4V) P-V :DIODE(0.4V) P-W :DIODE(0.4V)
resistance(a few ༯) resistance(a few ༯) resistance(a few ༯)

N-U :DIODE(0.4V) N-V :DIODE(0.4V) N-W :DIODE(0.4V)


resistance(a few ༯) resistance(a few ༯) resistance(a few ༯)
Checking points of Voltage

Check ȳ -Resistance of each connectors (R-R,S-S,T-T) -In case resistance is


(In case power should be within 0~10˟ ˳, noise filter is
Is not supplied) disconnected.
૟ Replace noise filter

074 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 075
Part Check Error Code Error Contents Meaning Main Causes
(Function) points
23(plus)
INV PCB 23(1~4,Plus II)
* Measure the CT current with clamp meter 1. Looseness of DC link terminal
(Plus II) DC voltage charging for 2. Damage in starting relay
S N1 Right Problem in DC charging voltage
*Current < 25A inverter compressor driving 3. Capacitor damage
P 23 Comp. after starting relay turned on
A defect 4. Defective sensing circuit of the
C N2 Left inverter PCB

Basic Part
E 23 Comp.

Error diagnosis and countermeasure flow chart(Plus II)

Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

Component Check
Electrical
3ɐ DIODE * After indoor unit turned on and the compressor is not operated,
(Plus II) just before magnetic switch is turned on
the voltage between the 2 terminal as below is more than 270V

Solution Check
Plus / Sync Plus II

Test functions
Part Check
How to check? Counter-measure
(Function) points

Capacitor Electric -Electricity capacity of capacitor must be -Replace capacitor


(To charge DC capacity. 2600~2800༲ and the resistance of capacitors when value is more or
voltage for (when power is should be more than a few ༮ less than normal spec.
inverter not supplied)
compressor)

* Check values at both


terminal of capacitor
-In case the measured value is different from the table, set multi tester to resistance mode
and measure. If the value is small (0 ȳ) or high (hundreds M ȳ), PCB needs to be
DC charging - Charged voltage of between terminals of capacitor - Check input voltage
replaced.
voltage (= between IPM P-N terminal = DC link terminals) and replace capacitor
- In case that bridge diode is damaged, check if inverter PCB assembly(IPM) is needed to be
replaced. (When power is should be more than 450V
supplied) (At the moment of inverter compressor start)

076 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 077
Part Check Error Code Error Contents Meaning Main Causes
How to check? Counter-measure
(Function) points
24(Plus Main) 1. High pressure switch defect
T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within 380·10% -Check supply power and 24(1~4,Plus II) 2. Fan defect of indoor unit or outdoor unit
(Terminal - Voltage of 1ɐ(R-N,S-N,T-N) should be within connection condition 3. Check valve of compressor clogged
S N1 Right 4. Pipe distortion due to the pipe damage
Block, Input 220·10%.
P 24 Comp. 5. Refrigerant overcharge
power) - Voltage fluctuation should be within 10V A Excessive rise of Compressor off due to 6. LEV defect at the indoor or outdoor unit .
- While stand-by and in operation, C N2 Left discharge pressure in the high pressure 7. Covering or clogging

Basic Part
Voltage drop should be within 10V. E 24 Comp. outdoor compressor switch in outdoor unit (Outdoor covering during the cooling mode /
Indoor unit filter clogging during the heating mode)
(plus) 8. SVC valve clogging
109 (Sub1) 9. Outdoor PCB defect
140 (Sub2) 10. HR unit valve coil defect(Multi V Sync)
154 (Sub3) 11. HR unit PCB defect(Multi V Sync)

Error diagnosis and countermeasure flow chart

Troubleshooting
Guide for each
Checking points of 3ɐ(R-S) Checking points of 1ɐ(R-N)

Error Code
Check ȳ - Resistance of R-S,S-T,R-T,R-N,S-N should be -Check short or not of
(In case power more than a few ༮ Control box (Noise filter, Is high pressure switch
No
PCB, cables) connector connected Connect securely
is not supplied)
to PCB?*
Trouble Shooting Guide Book

- Resistance of T-N should be within 40~50˟ - Replace transformer


(Main transformer of outdoor) Yes

Component Check
FUSE Check -Voltage of fuse should be within 0~1V -In case of 220V,
Is high pressure switch No No
(Protect over- disconnection of Fuse is disconnected. Is high pressure switch
connector short Replace high pressure switch

Electrical
loaded FUSE ૟ Replace FUSE terminal short?***
during off time?**
current) (when power is
(plus) supplied) Yes
Yes
Replace connecting cable

Checking points of R ɐ fuse No

Solution Check
Is SVC valve open? Open SVC valve
Check -Resistance of fuse should be within 0~1˟ -In case resistance is ˳,
disconnection of Fuse is disconnected. Yes
FUSE ૟ Replace FUSE
(when power is No
not supplied) Is this error appeared Re-check momentary
again after reset? problem or not
Nose filter Check voltage -Voltage (R-R,S-S,T-T) < 0~10V - In case of 220V
Yes
(Noise emit & (When power is ૟ If voltage is higer than 10~40V, check resistance It is disconnected
protect)

Test functions
Supplied) (Plus) (Plus II) ૟ Replace noise filter
Is high pressure No Replace PCB
more than 2500kPa CH24 : inverter compressor PCB
at manifold gauge? CH109~154 : sub unit PCB

Yes

Is high pressure of No
LGMV similar as Replace high pressure sensor
at manifold gauge?
Yes

Is it No Check pipe is blocked or


Multi V Sync ? not and take measure

Checking points of Voltage Yes

Check ȳ -Resistance of each connectors (R-R,S-S,T-T) -In case resistance is


(In case power should be within 0~10˟ ˳, noise filter is Next page
Is not supplied) disconnected.
૟ Replace noise filter

078 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 079
* Plus : Connector location of high pressure switch at PCB(Refer electrical component part for Multi V Space)

Is it Multi V Sync?
Inverter compressor PCB SUB outdoor unit PCB
Yes

Basic Part
Is HR unit valve No
Connect HR unit valve connector
connector normal ?

Yes

Is HR unit configuration No Check HR unit manual pipe address

Troubleshooting
Guide for each
on auto pipe detection? - Refer to HR unit manual pipe detection

Error Code
Yes

Is the pipe detection Checking short or not at connector of high Checking short or not at connector of high
No Set HR unit manual pipe detection
Trouble Shooting Guide Book

success during auto pressure switch pressure switch


- Refer to HR unit manual pipe detection
pipe detection?

Yes

Component Check
Electrical
Is HR unit valve LED turns on
No
when connected indoor unit Replace HR unit PCB
start to operate?

Yes

Solution Check
Is the resistance value of No
Replace HR unit valve coil **** Check resistance of HR unit valve coil : 1.85 k˟(·10%)
HR unit valve coil normal?****

Yes

- HR unit PCB-
Is the HR unit PCB valve No
measures ~220V in port? Replace HR unit PCB
[electric component part]

Test functions
Yes

Check HR unit coil


assembly location
Yes

Check for bent or blocked


from connected pipes
Check blocked HR Unit

080 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 081
* Plus II: Connector location of high pressure switch at PCB(Refer electrical component part for Mult V Space) Error Code Error Contents Meaning Main Causes

Plus:
25(Main)
Constant compressor pressure switch Inverter compressor pressire switch 147 (Sub1)
The power supply input voltage
149 (Sub2) Low / over voltage 1. Input voltage is abnormal(T-N)
tolerance is more or less than
171 (Sub3) of main PCB input 2. Outdoor unit main PCB defect
allowable standard
Plus I:,
251,252,253,

Basic Part
254

Error diagnosis and countermeasure flow chart

Is input voltage of main No Check input power from building

Troubleshooting
Guide for each
PCB (T-N) 190V~250V ?* is supplied correctly or not

Error Code
Yes

Replace main PCB


Trouble Shooting Guide Book

** Checking short or not at connector of high *** Checking short or not at connector of high

Component Check
pressure switch pressure switch

Electrical
Solution Check
* Check voltage at outdoor T/Block(220V)

Test functions
* Check voltage at outdoor T/Block(220V), Plus II

082 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 083
Error code Error Contents Meaning Main Causes

Plus II:
261,262,
263,264 1. U,Vㇵ connect orCOMP fault
S N1 Right At below min.Hz, 2. DC CT sensor fault
Compressor start failure
P 26 Comp. U,V current is lower than 1A 3. INV PCB fault
A 4. IPM component or connector fault

Basic Part
C N2 Left
E 26 Comp.

Error diagnosis and countermeasure flow chart

Troubleshooting
Error diagnosis and countermeasure flow chart

Guide for each


Error Code
Trouble Shooting Guide Book

Component Check
Electrical
Solution Check
Test functions
• Measure the CT current with clamp meter
: U(+), U(-), V(+), V(-)
- The current difference among phases is less
than 0.5A ·10%

U(+)U(-)V(+)V(-)

Multi V Space Multi V Plus II

084 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 085
Basic Part
Troubleshooting
Error diagnosis and countermeasure flow chart

Guide for each


Error Code
Trouble Shooting Guide Book

Component Check
Electrical
(U-V : 1.16ȳ · 7% / V-W : 1.19ȳ · 7% /U-W : 1.21ȳ · 7%)

Solution Check
Test functions
086 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 087
Error Code Error Contents Meaning Main Causes

32 (Plus Inv) 1. Temperature sensor defect of inverter Is it cooling mode of No


Plus II : Over-increase discharge Compressor is off compressor discharge pipe Multi V Sync ?
321,322, temperature of inverter because of over-increase 2. Refrigerant shortage / leak
323,324 compressor at main outdoor discharge temperature of 3. LEV defect Yes
Right unit inverter compressor 4. Liquid injection valve defect
SPACE 5. Check solenoid valve defect(Sync)
Comp.(N1)

Basic Part
Is the resistance value of No
33 (Plus Main) outdoor unit Check sol valve Replace HR unit valve coil
Plus II : normal?**
331,332,
333,334 Compressor is off 1. Temperature sensor defect of constant
Over-increase discharge Yes
because of over-increase (Space:Inv.) compressor discharge pipe?
temperature of constant
Left discharge temperature of 2. Refrigerant shortage/leak
SPACE (Space:Inv.) compressor at
Comp.(N2) constant (Space:Inv.) 3. LEV defect
main constant outdoor and
compressor at main and 4. Liquid injection valve defect Is the outdoor unit
plus sub constant outdoor unit No
sub outdoor unit 5. Check solenoid valve defect(Sync)

Troubleshooting
check sol valve measure ~220V? Replace outdoor unit PCB

Guide for each


100,101(Sub1)
[electric component part]

Error Code
102,103(Sub2)
152,153(Sub3)
Yes

Error diagnosis and countermeasure flow chart


Trouble Shooting Guide Book

Check for bent or blocked pipe


Is the additional ref. No

Component Check
amount correct? Adjust refrigerant amount
[Start up process]

Electrical
Yes * Error is generated if the resistance is more than 5Mȳ (open) and less than 2 ༮ (short)

Note: Standard values of resistance of sensors at different temperatures (·5% variation)


No 10୅ = 362༮ : 25୅= 200༮ : 50୅= 82༮ : 100୅= 18.5༮
Is there pipe crack
or trace of leakage?

Yes

Solution Check
Is the resistance of discharge No Replace discharge
temperature sensor normal?* temperature sensor

Weld / reconnect the Yes


cracked portion and
recharge refrigerant
Is LEV in outdoor unit normal
No
at heating operation? Replace outdoor unit LEV

Test functions
[refer electric component part] Check the resistance
of constant compressor
discharge temperature
Yes sensor

Does liquid injection No


Check liquid injection
corresponded
corresponded
operate normally?
Yes

Check another
No No components
Is it cooling mode of Is there pipe
and operation
Multi V Sync ? (strainer etc.) clogging?
conditions
Yes / Take measures
Yes

Check the resistance


inverter compressor
Next page Repair pipe clogging discharge temperature
Check the resistance
of constant compressor sensor
discharge temperature
* Resistance value of discharge temperature sensor
sensor
10୅ = 362༮, 25୅= 200༮, 50୅= 82༮, 100୅= 18.5༮

088 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 089
Check Check
Check points Check points
Loc. Loc.

Check outdoor Hot gas by pass


unit LEV Valve

Connector
resistance

Basic Part
1.85 k˟(·10%)

ྙ - ྛ : around 300˟ ྚ - ྜ : around 300˟ ྙ - ྜྷ : around 150˟

Troubleshooting
Guide for each
Error Code
Liquid by pass
valve
Trouble Shooting Guide Book

Connector
resistance

Component Check
ྛ - ྜྷ : around 300˟ ྚ - ྞ : around 300˟ ྜ - ྞ : around 150˟
1.85 k˟(·10%)

Electrical
Hot gas by pass
Valve

Connector
resistance
1.85 k˟(·10%)

Solution Check
Test functions
Liquid by pass
valve

Connector
resistance
1.85 k˟(·10%)

090 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 091
* Calculation of additional refrigerant amount * Calculation of additional refrigerant amount

R410A Multi V Plus, Plus II & Space R410A Multi V Sync


* R410A Correction Factor(CF)

Basic Part
Multi V
Plus,
Plus II

Troubleshooting
Guide for each
Error Code
Multi V
Trouble Shooting Guide Book

Space

Component Check
Electrical
Multi V
Sync II,

HQTCNN/WNVK8U[UVGO

Solution Check
Sync

Heat Pump / Sync

Test functions
HP 10 20 30 40 50 60
Multi V
Product Charge (kg) 7.3 8.8 16.1 17.6 24.9 26.4
Water II
CF (kg) 0 0 0 0 0 0

Cooling only / Heat Pump

HP 4 5 6
Multi V
MINI Product Charge (kg) 3.7 3.7 3.7

CF (kg) -0.5 0 0

092 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 093
Error Code Error Contents Meaning Main Causes
* Calculation of additional refrigerant amount
-Plus, Sync Error happens because of 3 1. High pressure sensor defect
R22 Multi V Plus 34
Over-increase of
times successive 2. Indoor or outdoor unit fan defect
(Main) compressor off due to over- 3. Deformation because of damage of refrigerant pipe
discharge pressure of
143 increase of high pressure 4. Over-charged refrigerant
compressor
(Sub1) by high pressure sensor 5. Indoor / outdoor unit LEV defect
145 7. When blocked

Basic Part
(Sub2) - Outdoor unit is blocked during cooling
169 Error happens because of 3 - Indoor unit filter is blocked during heating
Over-increase of water
(Sub3) times successive 8. SVC valve is clogged
temperature
Plus II: compressor off due to over- 9. PCB defect of outdoor unit
(Multi V Water)
341,342, increase of water 10. Indoor unit pipe temperature sensor defect
343,344 temperature 11. Insufficient water flow rate. (Multi V Water)

Error diagnosis and countermeasure flow chart

Troubleshooting
Guide for each
Error Code
No
Is service valve opened ? Open service valve

Yes
Trouble Shooting Guide Book

Are transmission No Check and repair transmission


cable / pipe connection

Component Check
cable / pipe connection
normal?

Electrical
Yes

Is the additional ref. No


amount correct? Adjust refrigerant amount
[Start up process]
* R22 Correction Factor(CF)
Yes

Solution Check
HP 5 6 8 10 12 14 16 18 20
Is fan normal?
Heat Product(kg) 4 4.5 10 10 10 10 20 20 20 (Indoor fan during heating
No Replace related parts
(Refer to Error 105~108)
Pump CF(kg) 0 0 -3 -2 -1 -1 -2 -2 -2 Outdoor fan during cooling)

6(380V) Yes
Product(kg) 4 4.5 10 10 10 20 20 20
Cool 10(220V) Is filter blocked
Only (Heating:indoor, No Clean indoor filter (heating)

Test functions
0(380V) Cooling:outdoor /outdoor heat exchanger (cooling)?
CF(kg) 0 0 -2 -1 -1 -2 -2 -2 heat exchanger)?
-3(220V)
Yes

HP 22 24 26 28 30 32 34 36 38 40 Is value of high pressure No


sensor same as Manifold Replace sensor of high pressure
30(50Hz) value(Is it high actually)?
Product(kg) 20 20 30 30 30 30 30 30 30
Heat 20(60Hz) Yes
Pump 0(50Hz)
CF(kg) -2 -2 0 0 0 1 1 2 2 Check indoor unit LEV
-1(60Hz) Is it Multi V Sync No Check indoor unit PCB
Or Multi V Water ? Check in/outdoor installation
30(50Hz) condition
Product(kg) 20 20 30 30 30 30 30 30 30 Yes
Cool 20(60Hz)
Only 0(50Hz)
CF(kg) -2 -2 0 0 0 1 1 2 2 Next page
-1(60Hz)

094 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 095
Is it Multi V Sync? Is it Multi V Water?

Yes

No is the resistance value No No

Basic Part
Is it heating mode ? of outdoor unit Replace HR unit valve coil Is water flowrate normal? Check water flow rate
check sol valve normal?*
Yes
Yes Yes

is the outdoor unit No


Check sol valve Replace outdoor unit PCB END
measure ~220V in port?

Troubleshooting
Yes

Guide for each


Error Code
Is HR unit valve No
Replace HR unit valve connector
connector normal ?
Trouble Shooting Guide Book

Yes

Component Check
No

Electrical
Is HR unit configuration Check HR unit manual pipe address
on auto pipe detection? - Refer to HR unit manual pipe detection

Yes

Is the pipe detection No Set HR unit manual pipe detection


success during auto
- Refer to HR unit manual pipe detection
pipe detection?

Solution Check
Yes

Is HR unit valve LED turns on


No
when connected indoor unit Replace HR unit PCB
start to operate?

Test functions
Yes

Is the resistance value of No


Replace HR unit valve coil
HR unit valve coil normal?*

Yes

Is the HR unit PCB valve No


measures ~220V in port? Replace HR unit PCB
[electric component part]

Yes

Check HR unit coil


assembly location
Yes

Check for bent or blocked


[1] Check sol valve coil resistance value : 1.85 k˟(·10%)
from connected pipes
Check blocked HR Unit HR unit valve coil resistance value : 1.85 k˟(·10%)

096 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 097
Error No. Error Contents Meaning Main Causes

1. Low pressure sensor defect Is it Multi V Sync?


2. Outdoor/indoor unit fan defect
-Plus, Sync 3. Refrigerant shortage/leakage Yes
35 (Main) 4. Deformation because of damage of refrigerant pipe
Error happens because
144 (Sub1) 5. Indoor / outdoor unit LEV defect
of 3 times successive No is the resistance value No
146 (Sub2) Excessive drop of 6. Covering / clogging
compressor off due to Is it heating mode? of outdoor unit Replace HR unit valve coil
170 (Sub3) discharge pressure of (outdoor unit covering during the cooling mode/
excessive drop of low check sol valve normal?**

Basic Part
compressor indoor unit filter clogging during heating mode)
pressure by the low
-Plus II: 7. SVC valve clogging
pressure sensor Yes Yes
351,352, 8. Outdoor unit PCB defect
353,354 9. Indoor unit pipe sensor defect
10. HR unit valve coil defect(Multi V Sync)
11. HR unit PCB defect(Multi V Sync) is the outdoor unit No
Check sol valve Replace outdoor unit PCB
measure ~220V in port?
Error diagnosis and countermeasure flow chart

Troubleshooting
Yes

Guide for each


Error Code
No
Is service valve
Open service valve
opened? No
Is HR unit valve
Replace HR unit valve connector
Yes connector normal ?
Trouble Shooting Guide Book

Yes
No
Are transmission cable/ check transmission/

Component Check
piping normal? piping correction.
Is HR unit configuration No Check HR unit manual pipe address

Electrical
Yes on auto pipe detection? - Refer to HR unit manual pipe detection

Is the additional ref. No Yes


amount correct? Adjust refrigerant amount
[Start up process] Is the pipe detection No
set HR unit manual pipe search address
Yes success during auto
- Refer to HR unit manual pipe detection
pipe detection?

Solution Check
No Yes
Is there pipe crack
or trace of leakage?

Yes
Is fan normal? No Check and replace related parts Is HR unit valve LED turns on No
(in heating outdoor fan,
Weld / reconnect the (error 105~108 reference) when connected indoor unit Replace HR unit PCB
in cooling indoor fan)
cracked portion and start to operate?
recharge refrigerant Yes

Test functions
Yes

No
Is strainer Ok?* Replace the strainer No
Is the resistance value of
Replace HR unit valve coil
HR unit valve coil normal?**
Yes
Yes

Are the values of manifold


Is the HR unit PCB valve No
and low pressure sensor same? No
Replace the pressure sensor measures ~220V in port? Replace HR unit PCB
( Is the low pressure value
[electric component part]
actually low?)
Yes
Yes

Check HR unit coil * In case of frost and high temperature difference between inlet and
No Check indoor unit LEV assembly location outlet of strainer, strainer blocking may happen
Is it Multi V Sync? Check indoor unit PCB (Caution: frost on the outlet area (afterward after half of body)
Check in/outdoor installation condition Yes
Yes

Check for bent or blocked ** Check sol valve coil resistance value : 1.85 k˟(·10%)
Next page from connected pipes
Check blocked HR Unit HR unit valve coil resistance value : 1.85 k˟(·10%)

098 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 099
Error code Error contents Meaning Main causes FUSE Check - Voltage of fuse should be within 0~1V -In case of 220V,
(Protect over- disconnection of Fuse is disconnected.
Plus:40 loaded FUSE
Plus II: ૟ Replace FUSE
current) (when power is
401,402,403,404 1. Fuse failure
supplied)
Low current at CT While inverter compressor 2. Defective noise filter
SP N1 Right or operation R phase current 3. R phase connection problem (plus)
A 40 Comp. CT sensor defect drops below 1A or CT short 4. CT sensor failure (inverter PCB
C failure)

Basic Part
N2 Left
E
40 Comp. Checking points of R ɐ fuse

Check -Resistance of fuse should be within 0~1˟ -In case resistance is ˳,


Error diagnosis and countermeasure flow chart disconnection of Fuse is disconnected.
FUSE ૟ Replace FUSE
(when power is

Troubleshooting
not supplied)

Guide for each


Error Code
Is the fuse normal? No
Replace the fuse
[refer electric component part]

Nose filter Check voltage -Voltage of each connector (R-R,S-S,T-T) should - In case of 220V
Yes
(Noise emit & (when power is be within 0~40V It is disconnected
Trouble Shooting Guide Book

protect) Supplied) ૟ Replace noise filter


(Plus) (Plus II)
Is noise filter normal? No

Component Check
Replace noise filter
[refer electric component part]

Electrical
Yes

After reset and restart the No


system, is CT value actually
less than 1A?* Replace Inverter PCB
-Plus/Sync : R phase

Solution Check
-Space : U, V phase

Yes

Check connection state of


R phase cable and reconnect

Test functions
Check ȳ -Resistance of each connectors (R-R,S-S,T-T) -In case resistance is
(When power should be within 0~10˟ ˳, noise filter is
* Measure the CT current with clamp meter -Multi V SPACE : U(+), U(-), V(+), V(-) Is not supplied) disconnected.
The current difference among ૟ Replace noise filter
- Multi V PLUS / Sync : R phase phases is less than 0.5A ·10%

U(+) U(-) V(+) V(-)

100 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 101
Error code Error contents Meaning Main causes

Plus:41 (Main inverter compressor)


Plus II:411,412,413,414

SPACE Right Comp.(N1)

Plus:
47 (Main constant compressor) 1. Connection of the compressor defect
Compressor

Basic Part
121 (Sub1 constant compressor 1) Sensor measurement discharge pipe temperature sensor
discharge pipe
122 (Sub1 constant compressor 2) valve is abnormal 2. Discharge pipe compressor sensor
temperature
133 (Sub2 constant compressor 1) (Open/Short) of the compressor (open/short) defect
sensor error
134 (Sub2 constant compressor 2) 3. Outdoor PCB defect
162 (Sub3 constant compressor 1)
163 (Sub3 constant compressor 2) Check the resistance inverter
compressor discharge
Plus II: temperature sensor
Check the resistance
471,472,473,474

Troubleshooting
Guide for each
of constant compressor
(Constant compress)

Error Code
discharge temperature
sensor
Error diagnosis and countermeasure flow chart
Trouble Shooting Guide Book

Sensor connection to PCB No


Insert sensor connector to PCB properly
is normal?

Component Check
Yes

Electrical
Is the resistance of No
Replace sensor
sensor normal?*

Yes

Solution Check
Is sensor resistance No
value same as temperature Replace corresponding outdoor PCB
value of LGMV?
Yes

Replace corresponding sensor

* Error is generated if the resistance is more than 5Mȳ (open) and less than 2 ༮ (short)

Test functions
Note: Standard values of resistance of sensors at different temperatures (·5% variation)
10୅ = 362༮ : 25୅= 200༮ : 50୅= 82༮ : 100୅= 18.5༮

Check the resistance Check the resistance


inverter compressor of constant
discharge compressor
temperature sensor discharge
temperature sensor

102 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 103
Error code Error contents Meaning Main causes Error code Error contents Meaning Main causes

Plus: Plus:
42 (Main) 44 (Main)
1. Bad connection of air temperature
117 (Sub1) 118 (Sub1)
Abnormal value of 1. Bad connection of low pressure connector connector
129 (Sub2) Sensor error of low 130 (Sub2) Sensor error of outdoor air Abnormal value of
sensor 2. Low pressure connector defect (Open/Short) 2. Air temperature connector
158 (Sub3) pressure 159 (Sub3) temperature sensor (Open/Short)
(Open/Short) 3. Outdoor PCB defect defect(Open/Short)
Plus II: Plus II:
3. Outdoor PCB defect
421,422,423,42 441,442,

Basic Part
4 443,444

Error code Error contents Meaning Main causes Plus:


45 (Main H/E A)
Plus: 48 (Main H/E B)
43 (Main) 123 (Sub1 H/E A)
116 (Sub1) 124 (Sub1 H/E B)
Abnormal value of 1. Bad connection of high pressure connector 1. Bad connection of air temperature
128 (Sub2) Sensor error of high 135 (Sub2 H/E A) Piping temperature sensor error
connector

Troubleshooting
sensor 2. High pressure connector defect(Open/Short)

Guide for each


157 (Sub3) pressure 136 (Sub2 H/E B) of heat exchanger in Abnormal value of sensor
(Open/Short) 3. Outdoor PCB defect 2. Air temperature connector

Error Code
Plus II: 164 (Sub3 H/E A) main & sub outdoor unit heat (Open/Short)
defect(Open/Short)
431,432,433,43 165 (Sub3 H/E B) exchanger (A,B)
3. Outdoor PCB defect
4 Plus II:
451,452,
453,453(H/E A)
Trouble Shooting Guide Book

Error diagnosis and countermeasure flow chart 481,482,


483,484(H/E B)

Is sensor connected No

Component Check
Connect sensor to PCB correctly Plus:
to PCB correctly?
46 (Main)

Electrical
1. Bad connection of air temperature
Yes 120 (Sub1)
connector
132 (Sub2) Compressor suction Abnormal value of
2. Air temperature connector
After replacement of No 161 (Sub3) temperature sensor error sensor (Open/Short)
Replace corresponding defect(Open/Short)
outdoor unit main PCB Plus II:
pressure sensor 3. Outdoor PCB defect
is the system normal? 461,462,
463,464
Yes

Solution Check
Plus:47
END
(constant compressor
of main outdoor unit)
Plus II: Discharge piping temperature
471,472,473,474 Abnormal value of sensor
sensor error of constant(Space: Refer to CH41
(Open/Short)
Inv.) compressor (Main unit)

Left
High pressure SPACE
Comp.(N2)
sensor

Test functions
Piping temperature sensor error
Plus:48 of heat exchanger in main & Abnormal value of sensor
Refer to CH45
(Heat exchanger B) sub outdoor unit heat (Open/Short)
exchanger (B)
Low pressure
sensor
Pressure sensor Error diagnosis and countermeasure flow chart
connection
Plus model on main PCB
Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly??

Yes

No
Is sensor value correct?* Replace sensor

Yes * If value is 100 ༮ ˦(open) or 100 ȳ ˨(short), error occurs

NB: Resistance value of temperature sensor change according to temperature


Replace corresponding It is normal if value shown as below (·5% error)
outdoor unit PCB Sensor of air temperature: 10୅ = 20.7༮ : 25୅= 10༮ : 50୅= 3.4༮
Plus II model Sensor of piping temperature: 10୅ = 10༮ : 25୅= 5༮ : 50୅= 1.8༮

104 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 105
Error Code Error Contents Meaning Main Causes

(plus)
49 (Main) The measured value of the 1. Abnormal input voltage
Outdoor voltage
148(Sub1) sensor is not 2. Outdoor line fuse damage
sensing error
150(Sub2) normal(Open/Short) 3. Outdoor main PCB defect
172(Sub3)

Basic Part
Error diagnosis and countermeasure flow chart

is the power input normal? No


(3 phase =380V·10%, Check power supply
single phase =220V·10%)

Measure resistance of outdoor air temperature Measure resistance of outdoor suction pipe
sensor Yes

Troubleshooting
temperature sensor

Guide for each


Error Code
Is the power input to No
the outdoor PCB Check the fuse and wiring
220V·10% ?
Yes
Trouble Shooting Guide Book

Change main PCB of outdoor

Component Check
* Check Line Fuse of MAIN PCB(Plus) * Check Line Fuse of MAIN PCB(Plus II)

Electrical
Measure resistance of outdoor HEX(A) Measure resistance of outdoor HEX(B)
temperature sensor temperature sensor

Solution Check
Part Check
How to check? Counter-measure
(Function) points

Test functions
T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within 380·10% -Check supply power and
(Terminal - Voltage of 1ɐ(R-N,S-N,T-N) should be within connection condition
Block, Input 220·10%.
power) - Voltage fluctuation should be within 10V
- While stand-by and in operation,
Voltage drop should be within 10V

Checking points of 3ɐ(R-S) Checking points of 1ɐ(R-N)

Check ȳ - Resistance of R-S,S-T,R-T,R-N,S-N should be -Check short or not of


Plus II model Control box (Noise filter,
(In case power more than a few ༮
is not supplied) PCB, cables)
- Resistance of T-N should be within 40~50˟ - Replace transformer
(Main transformer of outdoor)

106 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 107
Error Code Error Contents Meaning Main Causes Error Code Error Contents Meaning Main Causes

1. 130% more than outdoor unit rated capacity


(Plus II) ODU 3phase power 1. Input Voltage abnormal (R,S,T,N) Over-Capacity Sum of indoor unit capacity 2. Wrong connection of transmission cable/piping
Omitting one or more of
501,502, omission 2. Check power Line connection condition Plus:51
R,S,T input power (Sum of indoor unit capacity is exceed outdoor unit 3. Control error of sub outdoor unit DIP switch
503,504 error 3. Main PCB damage Plus II:511
more than outdoor capacity) capacity specification 4. Power supply defect of Sub unit PCB
5. Outdoor unit PCB defect

Error diagnosis and countermeasure flow chart

Basic Part
Error diagnosis and countermeasure flow chart
Check
No R~S/S~T/T~R phase voltage is 380V · 10%
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V · 10% Is capacity sum of
No Are quantity and capacity No Check transmission cables
Check connection condition and wiring if power is indoor units less than
of indoor units installed between indoor and outdoor
abnormal 130% of outdoor unit
same as the data of LGMV? units
capacity at LGMV?
Yes

Troubleshooting
Yes

Guide for each


Yes

Error Code
No Adjust the capacity of indoor
Is main PCB assembly normal? Replace Main PCB assembly
and outdoor unit

Yes
Is SUB DIP switch
Trouble Shooting Guide Book

No
5(SUB1), 6(SUB2) Adjust corresponding DIP switch
Recheck power and ON?*
installation condition

Component Check
Yes

Electrical
Is power of SUB PCB No Is main power really supplied? No Supply main
On? (Check LED blinking) (Terminal Block T-N) power again

Yes Yes

Check and replace PCB,


Line Fuse, Transformer

Solution Check
Is transmission
No
cables between outdoor units Re-connect
connected correctly?**

Yes

Is error code released


No

Test functions
in order(Sub2૟ Sub1૟Main) Replace Main or Sub PCB
after power reset?

Yes

End

108 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 109
* Dip switch setting of SUB unit(Plus) * Dip switch setting of SUB unit (Plus II)

SUB 1 SUB 2 SUB1 SUB2

Basic Part
Troubleshooting
Guide for each
Error Code
ON ON

1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Trouble Shooting Guide Book

Sub 1 : SW5 ON Sub 2 : SW6 ON

Component Check
Electrical
** In order to check transmission ** In order to check transmission
cables between outdoor units, cables between outdoor units,
check in order as below check in order as below
: PCB connectors ˧ : PCB connectors ˧
terminal block ˧ terminal block ˧
transmission cables transmission cables

Solution Check
1 1 1 1
2 2 2 2

3 3

Test functions
*** Press the red button for auto-addressing,

*** Press the red button for auto-addressing,

110 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 111
Error Code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes

Plus:52 Plus:53 1. Transmission cables are not connected


Plus II:521,522, Plus II: Transmission error In case Main PCB can’t receive 2. Transmission cables are short or open
523,524 531,532, (Indoor unit ˧ Main PCB) signal from indoor unit 3. No addressing after changing indoor unit PCB
Main controller can’t 1. Power cable or transmission cable is not connected 533,534 4. Outdoor Main PCB or indoor PCB defect
S N1 Right Transmission error between receive signal from 2. Defect of outdoor Main fuse/Noise Filter
P 52 Comp. (Inverter PCB ˧ Main PCB ) inverter controller 3. Defect of outdoor Main / inverter PCB
A
N2 Left

Basic Part
C
E 52 Comp. Error diagnosis and countermeasure flow chart

Error diagnosis and countermeasure flow chart


Are quantity of indoor No Is indoor unit No
units installed same as quantity correct after
Is transmission the data of LGMV? Auto Addressing?
LED (Yellow) of inverter No Is noise filter or fuse No
Replace noise filter or fuse
compressor normal?

Troubleshooting
Yes

Guide for each


PCB on? Yes

Error Code
Yes
Yes End

Replace inverter compressor PCB


Trouble Shooting Guide Book

No No
Is transmission cable Is power supplied
Re-connect transmission cable Supply power
connected correctly? to indoor units?

Component Check
Yes Yes

Electrical
No
Is MAIN PCB normal? Replace MAIN PCB
Replace indoor unit PCB or
Yes transmission PCB
after check defected indoor

Replace inverter compressor PCB

Solution Check
* The method of checking MAIN PCB and inverter compressor PCB (If normal, transmission LED blinks)
( Refer electrical component part for Multi V Space)

- Transmission connector & LED in inverter compressor PCB - Transmission connector & LED in MAIN PCB
In case of CH53, almost happened with CH05, the indoor units not operated actually are normal so check with same
method of CH05. and additionally check as shown as below and above flow chart

- Although the quantity of indoor units installed is same as LGMV data there may be a few indoor units with which
the number of transmission is not increased with LGMV

Test functions
- Although the quantity of indoor units installed is not same as LGMV data, and if transmission of the indoor unit
displayed at LGMV is done well then the indoor unit suspected to have some problem (and is not appear at LGMV)
may have following problems
ྙ wrong connection of transmission cable or power cable
ྚ fault of power / PCB / transmission cable
ྛ duplication of indoor unit number
- If transmission is not doing well wholly then the Auto Addressing is not done
(Plus) (Plus) - The case that CH53 appear at indoor unit also Auto Addressing is not done so indoor unit address may be duplicated

*After replacement of indoor unit PCB, Auto Addressing should be done, if central controller is installed then
the central control address also should be input.
in case that only transmission PCB is replaced above process is not needed

(Plus II) (Plus II)

112 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 113
Error code Error Contents Meaning Main Causes FUSE Check - Voltage of fuse should be within 0~1V -In case of 220V,
(Protect over- disconnection of Fuse is disconnected.
Plus: FUSE
loaded ૟ Replace FUSE
54 (Main)
current) (when power is
110 (Sub1) 1. Inverter PCB defect
Wrong connection of 3Ȱ Wrong connection of 3Ȱ power supplied)
141 (Sub2) 2. No power of R, S, T supplied
power supply cable (Reverse supply cable (Reverse direction /
155 (Sub3) 3. Wrong connection of R, S, T cables (plus)
direction / missing a phase) missing a phase)
Plus II: 4. Main fuse defect
541,542,

Basic Part
543,544
Checking points of R ɐ fuse

Error diagnosis and countermeasure flow chart Check -Resistance of fuse should be within 0~1˟ -In case resistance is ˳,
disconnection of Fuse is disconnected.
FUSE ૟ Replace FUSE
Is connection and phase (when power is
No
order of power cables to main / Connect correctly not supplied)

Troubleshooting
sub outdoor unit correct?*

Guide for each


Error Code
Yes

Is connection and phase No Nose filter Check voltage -Voltage of each connector (R-R,S-S,T-T) should - In case of 220V
Connect power cables in
order of power distribution (Noise emit & (when power is be within 0~40V It is disconnected
Trouble Shooting Guide Book

distribution panel correctly


panel correct?** protect) Supplied) ૟ Replace noise filter
Yes (Plus) (Plus II)

Component Check
Is CH 54 occurred again No

Electrical
after reset MAIN End
circuit breaker?

Yes

Is 3Ȱ Fuse normal? No
[refer electric Replace Fuse

Solution Check
component part]

Yes
Check the diode of inverter
fan PCB and in case of fault
replace inverter fan PCB
[refer electric component part]

Is noise filter
normal? No
Replace NOISE FILTER
[refer electric Check ȳ -Resistance of each connectors (R-R,S-S,T-T) -In case resistance is

Test functions
component part] (When power should be within 0~10˟ ˳, noise filter is
Yes Is not supplied) disconnected.
૟ Replace noise filter
Replace inverter compressor
PCB(CH54), SUB PCB(CH110,141,155)

* Check power cable connection state, **Check power cable connection state, phase order, power
phase (R-S-T) order, power supply state supply state in distribution panel
in control box of product

114 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 115
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes

Installing old Sub EEPROM Access error


Slave ODU mixed ODU and Plus II: Inverter PCB EEPROM and 1. EEPROM contact defect/wrong insertion
Plus II: 1Installing LGDC Slave Unit and Super sub
installation new slave ODU 601,602, error Check SUM error 2. Different EEPROM Version
591 Unit together
together 603,604 3. ODU inverter PCB assembly damage

Basic Part
Error diagnosis and countermeasure flow chart Error diagnosis and countermeasure flow chart

No 1.Check EEPROM insert direction/connection condition


Is EEPROM insertion
No 2.Check EEPROM Check SUM
normal?
Installed 3 UNIT or more? Recheck power and installation condition Replace if abnormality found

Yes

Troubleshooting
Guide for each
Yes

Error Code
Is inverter PCB assembly No
Replace inverter PCB assembly
Is LGDC Slave Unit No normal?
Recheck power and installation condition
installed?
Trouble Shooting Guide Book

Yes
Yes

Recheck power and installation condition

Component Check
No
Is Super Sub Unit

Electrical
Recheck power and installation condition
installed ?

Yes Inverter EEPROM

Slave,Sub Unit mixed installation

Solution Check
Test functions
116 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 117
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes

1. Defect of heat sink cooling fan


Heat sink temperature 1. Loose connection of temperature sensor connector
Plus: 2. Defect of inverter compressor PCB Plus: Abnormal value of sensor
Heat sink over heat Heat sink over heat sensor error of inverter 2. Temperature sensor defect (Open/Short)
62 3. Loose connection of connector of cooling fan 65 (Open/Short)
control PCB 2. Fan Main PCB defect
4. Defect of temperature sensor of heat sink

Error diagnosis and countermeasure flow chart

Basic Part
Error diagnosis and countermeasure flow chart

Is resistance value
Does cooling fan No No
of cooling fan coil correct? No
rotate while compressor Replace cooling fan Is sensor connected
[refer electric Connect PCB to sensor
operation? to PCB correctly?
component part]
Yes Yes Yes

Troubleshooting
Guide for each
Error Code
Replace main PCB Is value of sensor No
Replace sensor
resistance normal?*
No
Is value of sensor Yes
Replace sensor
Trouble Shooting Guide Book

resistance normal?*

Yes

Component Check
Replace inverter fan PCB

Electrical
* If value is 100 ༮ ˦(open) or 100 ȳ ˨(short), error occurs
Replace inverter fan PCB
NB: Resistance value of temperature sensor change according to temperature
It is normal if value shown as below (·5% error)
* Heat sink temperature sensor (·5% tolerance) : 10୅ = 20.0༮ : 25୅= 10.0༮ : 50୅= 3.5༮ : 85୅= 1.0༮ Heat sink sensor(·5% tolerance) : 10୅ = 20.0༮ : 25୅= 10.0༮ : 50୅= 3.5༮ : 85୅= 1.0༮

Solution Check
- Position of cooling fan drive connector in main PCB - Heat sink cooling fan
- Temperature sensor location of Heat sink - Measure the resistance of heat sink temperature sensor

Test functions
- Check DC 12V output during inverter - Heat sink temperature
compressor operation sensor connection

118 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 119
Error code Error Contents Meaning Main Causes
Error diagnosis and countermeasure flow chart(Plus II)
1. Fan motor defect / assembly
condition
abnormal
Fan RPM is 10RPM or less
2. Wrong connection of fan motor
Plus II: for 5 sec. when ODU fan
connector
671,672,673,673 starts or 40 RPM or less
(Hall sensor, U,V,W output)
after fan starting.

Basic Part
3. Reversing rotation after RPM target
Outdoor unit FAN apply
LOCK error 4. Fan PCB assembly defect

S N1 Right
After FAN drive signal
P 67 Fan 1. Motor connection defect
If the HALL SENSOR signal
A 2. FAN PCB defect
does not come on for 4 sec.
C N2 Left 3. Motor defect
E 67 Fan

Troubleshooting
Guide for each
Error Code
Error diagnosis and countermeasure flow chart(Plus)
Trouble Shooting Guide Book

Is the motor connection No


Reconnect motor connector
status normal?

Component Check
Yes

Electrical
No
Is the motor normal?* Replace FAN motor

Yes

Solution Check
Replace FAN PCB

* Check Hall sensor of BLDC FAN motor Ha(4),Hb(3) ૟-૟ Gnd(2) : 24MOhm
Ha(4),Hb(3) ૟-૟ Vcc(1) : 11KOhm

* Check resistance of LGDC FAN motor power wire 16.8ȳ·5% (75୅)

Test functions
resistance

16.8ȳ·5% (75୅)

120 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 121
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes

Constant Speed Constant Speed Constant Speed Compressor CT Inverter input current Micom input voltage isn't 1. Input voltage abnormal (T-N)
Plus II: Plus II:
Compressor CT Sensor Compressor CT Sensor Sensor CT within 2.5V ·0.3V at initial 2. ODU inverter PCB damage
701,702,703,704 711,712,713,714
Error Open/short defect sensor error state of power supply (CT sensing part)

Error diagnosis and countermeasure flow chart

Basic Part
Error diagnosis and countermeasure flow chart
Check
No R~S/S~T/T~R phase voltage is 380V ൥10%
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V ൥10%
Check connection condition and wiring if power is
Is constant speed compressor No abnormal
Check constant speed compressor
CT Sensor connection condition

Troubleshooting
Yes

Guide for each


CT Sensor wiring condition and locking
normal?

Error Code
No
Yes Is inverter PCB assembly normal? Replace inverter PCB assembly

Yes
Trouble Shooting Guide Book

Recheck power and installation condition

Recheck power and installation condition

Component Check
Electrical
Solution Check
Test functions
122 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 123
Error code Error Contents Meaning Main Causes

1.Overload operation (Pipe clogging/


Covering/EEV defect/Ref.
overcharge)
2.Compressor damage(Insulation
AC input instant over Inverter PCB input 3 phase
damage/Motor damage)
Plus II: current power
3.Input voltage abnormal(R,S,T,N)
731,732,733,734 error (Matter of current is over 50A(peak) for

Basic Part
4.Power line assemble condition
software) 2ms
abnormal
5.Inverter PCB assembly
damage(input current sensing part)

Error diagnosis and countermeasure flow chart

Troubleshooting
Guide for each
Error Code
1.Check Pipe clogging/distortion
2.Check Covering (Indoor/Outdoor Unit)
Is installation No
3.Check EEV connector assemble condition/normal operation
condition normal?
Trouble Shooting Guide Book

4.Check refrigerant pressure


Reassemble or manage if abnormality found
Yes

Component Check
Check
No R~S/S~T/T~R phase voltage is 380V ൥ 10%

Electrical
Is input voltage normal?
R~N/S~N/T~N phase voltage is 220V ൥ 10%
Check connection condition and wiring if power is abnormal
Yes

1.Check R,S,T,N connection condition


Is AC input Wire connection No
2.Check wire disconnection and wiring
condition normal?
Reassemble if abnormality found

Solution Check
Yes

1.Check inverter PCB assembly U,V,W connector connection


Is compressor condition
No
Wire connection 2.Check wire disconnection and wiring
condition normal? 3.Check compressor terminal connection condition(bad contact)
Reassemble if abnormality found
Yes

Test functions
Is inverter PCB assembly No Check inverter PCB assembly IPM normality
normal? Replace inverter PCB assembly

Yes

Recheck power and


installation condition

124 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 125
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes

During operation(compressor 1. CT sensor defect Offset of micom which senses


frequency 2. Capacity over of AVR Plus II: the 1.Input voltage is abnormal(not 15V)
Plus II: 3 Phase Power Fan CT sensor error
is over 50Hz), difference 3. Bridge R-N or S-N or T-N phase 751.752,753,754 fan motor phase current is not 2.Fan PCB assembly defect
741,742,743,744 Unbalance
between R & T phase is 5A for voltage unequally at indoor unit 2.5V
10 seconds. etc.

Error diagnosis and countermeasure flow chart

Basic Part
Error diagnosis and countermeasure flow chart
No Check 15V wire connection
Is input voltage normal?
Check abnormal wiring between Inverter PCB assembly & Reassemble or manage if abnormality found
Is inverter PCB assembly No
bridge diode (misconnection,disconnection)
power wiring normal? Yes
Rewiring if abnormal wiring found
Yes

Troubleshooting
Guide for each
Check No
Is Fan PCB assembly normal?

Error Code
Replace Fan PCB assembly
No R~S/S~T/T~R phase voltage is 380V ൥ 10%
Is input voltage normal?
R~N/S~N/T~N phase voltage is 220V ൥ 10%
Check connection condition and wiring if power is abnormal Yes
Yes
Trouble Shooting Guide Book

Recheck power and


installation condition
Does indoor unit power No Bridge R-N,S-N,T-N voltage equally

Component Check
bridge R,S,T phase equally?

Yes

Electrical
Is inverter PCB No
Replace inverter PCB assembly
assembly normal?

Yes

Solution Check
Recheck power and
installing condition

Test functions
126 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 127
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes

1.Overload operation
Plus II: Fan DC Link High Fan PCB DC link voltage 1.Input power abnormal Plus II: Fan Over Current Output current is over 5A for
2.Fan Motor defect
761,762,763,764 Voltage Error supplied over 780Vƒ 2.Fan PCB assembly defect 771,772,773,774 Error 40ms
3.Fan PCB assembly defect

Error diagnosis and countermeasure flow chart Error diagnosis and countermeasure flow chart

Basic Part
Check
R~S/S~T/T~R phase voltage is 380V ൥ 10%
No Is installation No No Check ODU fan motor assemble condition and locking
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V ൥ 10%
condition normal? Reassemble or replace if abnormality found
Check connection condition and wiring if power is
Yes abnormal Yes

Troubleshooting
Guide for each
1.Check resistance between each motor output terminal

Error Code
No Are the resistance No No
Is Fan PCB assembly normal? Replace Fan PCB assembly (16.8ൎ൥5% at 75൤C)
Between each phase and insulation
2. Check insulation resistance between ODU fan motor
resistance of motor output
terminal (U,V,W) and pipe (over 100Mൎ )
Yes terminal normal?
Replace fan motor if abnormality found
Trouble Shooting Guide Book

Yes
Recheck power and
installation condition
1.Check if color of motor output terminal(U,V,W) connector

Component Check
Is motor wire connection No matched with PCB’s
condition normal? 2.Check wire disconnection and wiring

Electrical
Reassemble or replace if abnormality found
Yes

No 1. Check fan PCB assembly IPM normal


Is Fan PCB assembly normal?
Replace Fan PCB assembly

Yes

Solution Check
Recheck power and
installation condition

Test functions
128 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 129
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes

1.Fan motor hall sensor defect 1.Fan motor defect/ assemble


2.ODU fan motor hall sensor condition abnormal
Plus II: Fan Motor Hall Sensor Fan Motor Hall Sensor disconnection Plus II: Fan Starting Failure 2.Fan motor connector
Fan Motor initial starting failure
781,782,783,784 Error short/open 3.ODU Fan Motor Hall Sensor wrong 791,792,793,794 Error misconnection(Hall sensor,
insertion U,V,W ouput)
4.Fan PCB assembly defect 3.Fan PCB defect

Basic Part
Error diagnosis and countermeasure flow chart Error diagnosis and countermeasure flow chart

Is fan motor assemble No Check ODU fan motor assemble condition and locking Is fan motor assemble No Check ODU fan motor assemble condition and locking
condition normal? Reassemble or replace if abnormality found condition normal? Reassemble or replace if abnormality found

Troubleshooting
Yes Yes

Guide for each


Error Code
1. Check resistance between each motor output terminal
No Are the resistance No No (16.8 ൎ ൥5% at 75൤C)
Is wiring between fan motor Recheck f an motor hall sensor connection Between each phase and insulation
2. Check insulation resistance between ODU fan motor terminal
and PCB normal? Reassemble if abnormality found resistance of motor output
(U,V,W) and pipe (over 100Mൎ)
Trouble Shooting Guide Book

terminal normal?
Replace fan motor if abnormality found
Yes Yes

Component Check
1. Check if color of motor output terminal(U,V,W) connector

Electrical
Check if connector color matched between fan motor
Is connector color between No Is fan motor connection No matched with PCB’s
hall sensor and PCB
Hall Sensor PCB matched? condition normal? 2. Check wire disconnection and wiring
Reassemble if abnormality found
Reassemble or replace if abnormality found
Yes Yes

No No Check fan PCB assembly IPM normal


Is fan PCB assembly normal? Replace Fan PCB assembly Is fan PCB assembly normal?
Replace Fan PCB assembly

Solution Check
Yes Yes

Recheck power and Recheck power and


installation condition installation condition

Test functions
130 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 131
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes
Plus II: Main PCB EEPROM 1. No EEPROM
EEPROM Access Error Error occurs when checking 1.EEPROM bad contact/wrong
861,862,863,864 Error 2. EEPROM wrong insertion
Plus II: Fan PCB EEPROM the EEPROM checksum as insertion
871,872,873,874 Error initializing after power is 2.EEPROM Version is different
supplied 3.ODU fan PCB assembly damage
Error diagnosis and countermeasure flow chart

Basic Part
Error diagnosis and countermeasure flow chart

Is EEPROM assemble No Reset after checking EEPROM assemble condition


condition normal? 1.Check EEPROM insertion direction/connection condition
Is EEPROM insertion normal? No 2.Check EEPROM checksum
Yes Replace EEPROM if abnormality found
Yes

Troubleshooting
Guide for each
No

Error Code
Is EEPROM 24C16? Replace EEPROM with 24C16 No
Is Fan PCB assembly normal? Replace fan PCB assembly

Yes
Trouble Shooting Guide Book

Yes
Recheck power and
installation condition
Recheck power and

Component Check
installation condition

Electrical
Solution Check
Test functions
132 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 133
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes
plus: Plus:
Over-increase of constant Compressor is off because of
100,101 (Sub1) 104 (Main)
compressor discharge Over-increase of constant compressor discharge Refer to CH33
102,103 (Sub2) 111 (Sub1)
temperature of Sub outdoor temperature of Sub outdoor unit
152,153 (Sub3) 142 (Sub2) Transmission 1. Loose connection of power cables
Master displays ODU number
156 (Sub3) Error /transmission cables (Open/Short)
which is not communicated.
Plus II: Between 2. Each outdoor unit PCB defect
Slave displays own error number
011˧041 Outdoors 3. Defect of PCB power

Basic Part
011˧042
* Discharge temperature sensor of constant compressor 011˧043
in the sub unit 011˧044

Error diagnosis and countermeasure flow chart(Plus)

Troubleshooting
Guide for each
Does transmission LED Is PCB input power of

Error Code
No No Check and replace
(Red) of corresponding transformer, PCB power fuse
corresponding parts/
Sub PCB blinks? [refer electric normal? [refer electric Input power
component part] component part]

Yes Yes
Trouble Shooting Guide Book

Replace related SUB PCB

Component Check
Electrical
Is transmission cables
No
of outdoors connected
Re-connect transmission cables
correctly? [refer electric
component part]
Yes

Solution Check
Replace MAIN PCB

Sub unit PCB

Test functions
LED 8 7 6 5 4

LED 3

LED 2

LED 1

40 sec later after power input,

LED1(blinking): Display normal micom condition


LED2, 3(On): Back-up for left/right compressor
LED4 : reserved
LED5(blinking) : Communicate with main
LED6(On) : Reverse connection at sub unit
LED7(On) : Right compressor is in operation
LED8(On) : Left compressor is in operation

134 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 135
Error diagnosis and countermeasure flow chart(Plus II) Error code Error Contents Meaning Main Causes

-Plus
1. Loose connection of transmission cables
Plus:Transmission error Plus:Transmission error between 2. Transmission cables are open/sort
Plus:105
between outdoor unit Main PCB outdoor Main PCB and fan Main 3. Outdoor Main PCB PCB defect
Plus II:
and fan Main PCB PCB (Fan ˧ outdoor main) 4. Fan Main PCB defect
11˧051
11˧52
Plus II:Transmission error Plus:Transmission error between -Plus II
11˧53

Basic Part
between outdoor unit Inv PCB outdoor Inv PCB and fan PCB 1. Wrong connection between Inverter and
11˧54
and fan PCB (Fan ˧ inv) Fan PCB
2. Fan PCB power not supplied
3. ODU Inv/Fan PCB defect

Error diagnosis and countermeasure flow chart(Plus)

Troubleshooting
Guide for each
Error Code
Is transmission LED No Is noise filter or fuse No
(yellow) of inverter fan normal ? [refer electric Replace noise filter or fuse
PCB on?* component part]

Yes
Trouble Shooting Guide Book

Yes

Replace inverter fan PCB

Component Check
Electrical
Are transmission cables No
of Main PCB / Fan PCB Re-connect transmission cables
connected normally?

Yes

No
Is green LED of

Solution Check
Replace Main PCB
Main PCB blinks?**

Yes

Replace inverter fan PCB

Test functions
* Location of inverter transmission connector of **Location of PCB transmission connector of
Main PCB and LED Inverter FAN and LED

136 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 137
Error code Error Contents Meaning Main Causes

Plus:106
Plus II:
11˧061 1. Overload operation (Pipe
12˧062 clogging/Covering/EEV
13˧063 IPM protection circuit defect/Ref. overcharge
14˧064 Over current of Main outdoor activation 2. ODU fan motor assemble condition abnormal

Basic Part
fan motor (inverter fan IPM fault) (over current / (Coil disconnection/Short/Insulation damage)
S N1 Right overheating) 3. Fan PCB heatsink assemble condition
P 106 Fan abnormal
A 4. Fan PCB assembly defect
C N2 Left
E 106 Fan

Error diagnosis and countermeasure flow chart(Plus)

Troubleshooting
Guide for each
Error Code
No
Is it Multi V Space ? Multi V Plus & Sync
Yes
Trouble Shooting Guide Book

Yes

Is inverter fan IPM PCB No

Component Check
㤸㠄㉔Ḱ 㐔䝬㉔ 㢨ᷝ normal? [refer electric Replace inverter fan IPM PCB
component part]

Electrical
Yes

Is inverter fan PCB No


Normal? [refer electric Replace inverter fan PCB
component part]

Yes

Solution Check
Is inverter fan motor No
Normal? [refer electric Replace inverter fan motor
component part]

Yes

Adjust connection after

Test functions
check PWM signal cables
[refer electric component part]

* check fan motor


- [Multi V Plus & Sync]Check Inv the resistance
on fan motor connectors - [Multi V Space] Check hall sensor of BLDC fan motor

- Resistance between cables : 18 ·3ȳ Ha(4),Hb(3) ૟-૟ Gnd(2) : 24 Mȳ


- Resistance between cables(LGDC fan) : 19 ·7% (75୅) Ha(4),Hb(3) ૟-૟ Vcc(1) : 11 kȳ

Vcc
Gnd
1 Hb
2 Ha
3 4

138 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 139
Part Check
How to check? Counter-measure Part Check
(Function) points How to check? Counter-measure
(Function) points
Inverter fan
No power
IPM PCB
on PCB
10. Comm. circuit

1. PWM signal connector

Basic Part
2. Input circuit of 3ɐ &
1. MICOM LED DC rectifying circuit
4. IPM
9. On-boarding 3. In/Output connector
connector of reactor
2. DC supply terminal

Troubleshooting
Guide for each
(DC310V)
8. Heat sink

Error Code
temperature 4. DC-Link output voltage
sensor connector

7. PWM
Trouble Shooting Guide Book

drive circuit
5. DC-Link electrolytic
capacitor

Component Check
6. SMPS power

Electrical
circuit
3. Outdoor unit fan connectors

1.PWM signal -Check 9pin connectors -Replace cables & check


2.3ij power -Input voltage of 3ɐ 4 wires should be -Check supply voltage,
2.Fan DC power - DC voltage should be charged of 310V soldering condition of Input circuit 3ɐ 380V, 1ɐ 220V noise
PCB

Solution Check
3.Outdoor - While Fan operating, in case voltage of filter, fuse
- Check half wave rectifying circuit diode
fan connector - connectors(U-V,V-W,U-W) is 100~300V - Replace connectors & (R-Reactor1: 0.6V, S-Reactor1: 0.6V: -Replace inverter fan
- ˧ Normal inverter T-Reactor1: 0.6V) PCB
4. IPM -- Check Diode(P-N : 0.95V, PCB if not charging
- P-U,P-V,P-W: 0.55V
- N-U,N-V,N-W: 0.55V - Replace inverter IPM
PCB

Test functions
R, S, T, N Reactor 1

10. -Yellow LED should blink. -Check yellow LED blinks


Transmission or not
DIODE㽕㥉(P-U : 0.5V) circuit with -When is OFF / ON
main PCB continuously,
check transmission
with main PCB

Red LED -When red LED blinks, error code happens -Check error code at
about inverter fan PCB main PCB

140 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 141
Error diagnosis and countermeasure flow chart (Plus II)
Multi V Space BLDC FAN PCB

No
Is fan motor assemble Check ODU fan motor assemble condition and locking
4.SW_SEL 6.CN_COMM condition normal? Reassemble or replace if abnormality found
LED01M : PWM Enable 5.SW_DIR [MAIN PCB૟>FAN PCB] :5,6,8HP
[louver
LED02M : display error [FAN direction] [FAN૟>COMP PCB] : 10HP
selection]
Yes

Basic Part
7.CN_POWER2 No 1.Check fan motor U,V,W connector connection condition
3.Power supply [louver power supply] Is fan motor wire connection Reassemble wire if abnormality found
condition normal? 2.Check fan motor wire disconnection
Replace ODU fan motor if abnormality found
LED01K
Yes
(FAN૟>INV
communication)

Troubleshooting
8.SW01M,02M,03M

Guide for each


1.Check fan PCB connector condition

Error Code
[PCB JIG check] Is fan PCB assemble No Reassemble if abnormality found
9.CN_WIRTE condition normal? 2.Check assemble condition between fan PCB and Heatsink
[on boarding Reassemble heatsink if abnormality found
light]
10.CN_M1S,M2S Yes
Trouble Shooting Guide Book

[louver signal input]

2.CN_DC LINK 11.CN_SENSOR


[DC power supply [FAN signal input] No

Component Check
sensor) Is fan PCB assembly normal? Replace fan PCB assembly

Electrical
12.CN_MOTOR1,2
1.CN_POWER
[louver signal output] Yes
[PCB power
supply)

13.CN_FAN
[FAN signal output)
Recheck power and
installation condition]

Solution Check
Situation Monitoring Location How to check? Counter-measure

Power does not turn 1.CN POWER -AC voltage measure 220V -Input voltage (220V)
on -Replace related parts (FAN PCB)
3. Power supply - ZNR01D( barrister ),FUSE burn out
(CH105) checkup

FAN motion disabled 2.CN_DC LIINK -DC 470V~520V displays - Check and replace
-DC 380V and above are normal CAPACITOR

Test functions
- Replace PCB
13.CN_FAN - U,V,W electric flow measurement - Check up and replace
(CH106) stabilize connection and motor
11.CN_SENSOR -Check connectors
(CH67)
(FAN PCB) (FAN PCB)
communication does 6. CN-COMM -Flick LED01K -Check PCB power
not work (CH105) - check connector and PCB (power supply(220V)
supply ,communication) -Check and replace connector
and PCB

Louver does not 4.SW_SEL Check if connector is connected -connect connectors (if there
work -DC24V display check are no louver)
7.CN_POWER2
-Connection status check -Check and Replace trance and
10.CN_M1S,M2S power supply
Connection status check
12.CN_MOTOR1,2 -Check and replace louver
motor and connection part

Check and replace louver


motor and connection part

142 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 143
Multi V Plus II LGDC FAN PCB Error code Error Contents Meaning Main Causes

Plus:107
Plus II:
11˧071
12˧072
13˧073 DC voltage charging Low voltage of Main 1. Bad connection of voltage lead cable of main PCB DC link
14˧074 failure of inverter fan outdoor fan motor 2. Fan main PCB capacitor defect
N motor drive (below 380V) 3. Fan main PCB defect

Basic Part
CN Micom S N1 Right
Write P 107 Fan
A
W C N2 Left
E 107 Fan
V 2. CN FAN Right

Troubleshooting
Guide for each
Error diagnosis and countermeasure flow chart(Plus)

Error Code
1. CN DC Link

CN Heat Sink
Trouble Shooting Guide Book

6. CN Inverter
Communication Is DC LINK cable No
Adjust DC LINK cables
Normal?*

Component Check
DC 15V Power Input 3. CN FAN Left Yes
terminal

Electrical
4. CN Hall Sensor Replace inverter fan PCB
(Right) P

5. CN Hall Sensor
(Left)

Solution Check
Error diagnosis and countermeasure flow chart(Plus II)

Situation Monitoring Location How to check? Counter-measure


No 1. Check DC_Link Wire connection
FAN motion disabled 1.CN_DC LIINK -DC 470V~520V displays - Check DC Voltage at FAN PCB Is wiring between fan motor
2. DC_Link
-DC 380V and above are normal terminal (more than 380V— and PCB normal?
Replace wire if abnormality found
Normal)
2/3. CN_FAN - U,V,W electric flow measurement - Replace PCB Yes
(CH106) stabilize - Check up and replace

Test functions
-Check connectors connection and motor
4/5. CN_HALL
SENSOR(CH67) No
Measure DC_Link voltage
Is DC_Link voltage normal?
Check inverter PCB if voltage is below 380V
Communication does 6. CN-COM (CH105) -Flick LED01K - Check DC power input
not work - Check 15V DC power input terminal Yes
- Check Connector - Check and replace connector
and PCB
No
Fan IPM P-N & U,V,W Is Fan PCB assembly normal? Replace fan PCB assembly

Yes

Replace inverter fan PCB

144 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 145
Error code Error Contents Meaning Main Causes

Plus:
Excessive rise of high pressure in Compressor Off due to the high pressure switch
109 Refer to CH24
- Inverter fan main PCB - Inverter fan IPM PCB outdoor unit in outdoor unit
(Sub1)

Plus: Outdoor 3 phase power supply problem

Basic Part
Wrong connection of 3 phase power cable
110 (Reverse phase / No power in 1 or 2 Refer to CH54
(Reverse phase / Phase omission)
(Sub1) phase)

104 ˧ transmission error between the outdoor


Plus: units (Main outdoor unit is not receiving signal
Transmission error between outdoor
111 from Sub units) Refer to CH104
units
(Sub1) 147, 149, 171 ˧ Sub outdoor units are not

Troubleshooting
Guide for each
receiving signal from Main outdoor unit

Error Code
Trouble Shooting Guide Book

(Plus)

Component Check
Electrical
Solution Check
Test functions
Check DC Voltage 470~520

(Plus II)

146 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 147
Error code Error Contents Meaning Main Causes
Error code Error Contents Meaning Main Causes
Plus:
113 (Main) 116 Sensor measured value of resistance is
High pressure sensor Refer CH43
125 (Sub1) (Plus Sub1) abnormal (Open / Short)
Outdoor unit
137 (Sub2)
liquid pipe Abnormal sensor 1. Defective temperature sensor connection
166 (Sub3)
(condenser) resistance value 2. Temperature sensor defect(Open / Short)
Plus II: 117 Sensor measured value of resistance is
temperature (Open/Short) 3. Outdoor unit main PCB defect Low pressure sensor Refer to CH42
11˧131 (Plus Sub1) abnormal (Open/Short)
sensor error
12˧132

Basic Part
13˧133
14˧134
118 Outdoor unit air temperature Sensor measured value of resistance is
Refer to CH44
(Plus Sub1) sensor error abnormal (Open / Short)
Error code Error Contents Meaning Main Causes

Plus:
114 (Main sub-cool inlet) 120 Compressor suction pipe Sensor measured of resistance value is
Refer to CH46
115 (Main sub-cool outlet) (Plus Sub1) temperature sensor error abnormal (Open/Short)

Troubleshooting
126 (Sub1 sub-cool inlet)

Guide for each


127 (Sub1 sub-cool outlet)

Error Code
138 (Sub2 sub-cool inlet) 121 (Plus Sub1
139 (Sub2 sub-cool outlet) constant compressor 1) Compressor discharge pipe Sensor measured value of resistance is
Refer to CH41
167 Sub3 sub-cool inlet) 122 (Plus Sub1 temperature sensor error abnormal (Open/Short)
Outdoor unit sub- 1. Defective temperature sensor connecter constant compressor 2)
168 (Sub3 sub-cool outlet) Abnormal sensor
cooling inlet / outlet connection
Trouble Shooting Guide Book

resistance value
temperature sensor 2. Temperature sensor defect(Open / Short)
Plus II: (Open/Short)
error 3. Outdoor unit main PCB defect
11˧141(sub-cool inlet) 123 (Plus Sub1 HEX A) Sub outdoor unit heat exchanger Sensor measured value of resistance is
12˧142 Refer to CH45
124 (Plus Sub1 HEX B) (A,B) pipe sensor error. abnormal (Open/Short)

Component Check
13˧143
14˧144,

Electrical
11˧151(sub-cool outlet) 125 Outdoor liquid pipe (condenser) Sensor measured value of resistance is
11˧152 Refer to CH113
(Plus Sub1) sensor error abnormal (Open/Short)
11˧153
11˧154
126 (Plus Sub1
Error diagnosis and countermeasure flow chart Sub-cool inlet) Outdoor unit sub-cool inlet / outlet Sensor measured value of resistance is
Refer to CH114
127(Plus Sub1 sensor error abnormal (Open/Short)
• Sub-cool circuit in the
Sub-cool outlet)
outdoor unit

Solution Check
Is temperature sensor No 128 Sensor measured value is abnormal
connector connections Check and correct connection High pressure sensor error Refer to CH43
(Plus Sub2) (Open/Short)
are normal?
Yes
129 Sensor measured value is abnormal
Low pressure sensor error Refer to CH42
(Plus Sub2) (Open/Short)
Is the value of temperature No
Replace sensor (Plus)
sensor resistance normal?*
130 Outdoor unit air temperature Sensor measured value is abnormal

Test functions
Refer to CH44
Yes (Plus Sub2) sensor error (Open/Short)

132 Compressor suction temperature Sensor measured value is abnormal


Replace outdoor unit PCB Refer to CH46
(Plus Sub2) sensor error (Open/Short)

* Sensor resistance 100 ༮ over (open) or 100 ȳ below (short) will generate error (Plus II) (Plus II)
133 (Plus Sub2 Const
compressor1) Compressor discharge pipe Sensor measured value is abnormal
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value Refer to CH41
according to outdoor unit temperature by referring below table (·5% tolerance) 134 (Plus Sub2 Const temperature sensor error (Open/Short)
compressor2)
Air temperature sensor: 10୅ = 20.7༮ : 25୅= 10༮ : 50୅= 3.4༮
Pipe temperature sensor: 10୅ = 10༮ : 25୅= 5༮ : 50୅= 1.8༮

- Liquid pipe temp sensor - Sub-cool inlet temp sensor - Sub-cool outlet temp sensor Sub Outdoor unit heat exchanger
135 (Plus Sub2 HEX A) Sensor measured value is abnormal
(A,B) pipe temperature sensor Refer to CH45
136 (Plus Sub2 HEX B) (Open/Short)
error

137 (Plus Sub2


Sub-cool Liquid Pipe)
Outdoor unit Sub-cool Liquid Pipe,
138 (Plus Sub2 Sensor measured value is abnormal
Inlet / outlet temperature sensor Refer to CH113/114
Sub-cool inlet) (Open/Short)
error
139 (Plus Sub2
Sub-cool outlet)

148 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 149
Error Code Error Contents Meaning Main Causes Error Code Error Contents Meaning Main Causes

140 Excessive rise in outdoor high Compressor Off due to the high pressure Plus:
Refer to CH24
(Plus Sub2) pressure switch in outdoor unit 151
Function error of 4way 1. Wrong operation of 4way valve because of sludge etc. inflow
Plus II: Function error of
(reversing valve) in 2. No pressure difference because of compressor fault
11˧511 outdoor 4way
Main or Sub outdoor 3. Wrong installation of In/outdoor common pipe
11˧512 (reversing valve)
Outdoor 3 phase power supply units 4. 4way valve defect
141 Wrong wiring at outdoor unit 11˧513
problem (Reverse phase / phase Refer to CH54
(Plus Sub2) (phase reversal / phase omission ) 11˧514
omission)

Basic Part
Error diagnosis and countermeasure flow chart
Transmission error between outdoor units
104 (Main outdoor unit is not receiving sub
142 Transmission error between outdoor
outdoor unit s signals) Refer to CH104
(Plus Sub2) units Is 4-Way valve connecter
147, 149, 171 (Sub outdoor units are not No
receiving main unit signals) connection are properly Reconnect it
connected?

Troubleshooting
Guide for each
Error Code
Yes
143 (Plus Sub1)
Excessive rise in high pressure Compressor Off due to high pressure sensor Refer to CH34
145 (Plus Sub2)
Is 4 Way valve coil No
Change 4 Way valve coil
resistance normal?*
Trouble Shooting Guide Book

144 (Plus Sub1) Yes


Excessive drop in low pressure Compressor Off due to low pressure sensor Refer to CH35
146 (Plus Sub2)

Component Check
Is 4 way valve coil connected No
Re-insert 4 way valve coil
to 4 way valve normally?**

Electrical
1. Input Voltage in the installation region =
147 (Plus Sub1) Yes
Low voltage/ High voltage 3phase 380V·10% Refer to CH25
149 (Plus Sub2)
2. Single Phase = 220 ·10%
In case of more than
2 units, does main outdoor No
Refer to CH 51 & make measure
unit recognize
㜼 as more
148 (Plus Sub1) than 2 units? ***
Outdoor voltage sensing error Measured value is abnormal (Open/Short) Refer to CH49
150 (Plus Sub2)

Solution Check
Yes

After reset, can we


check supply voltage at PCB No
Replace outdoor unit PCB
when starting heating
mode operation****

Yes

No Check and replace compressor,


Is compressor working

Test functions
Magnet switch, corresponding PCB
normally?
[refer electric component part]
Yes

After opposite
mode operation to present No If the same error is occurred in
mode, is the same error near future replace 4way valve
occurred again?
Yes

Replace 4 way valve*****

150 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 151
(Plus) (Plus ȤȤ)

* Measure the resistance of 4way valve


* Location of 4way valve connector on
Main / Sub PCB (marked as 4way)

Basic Part
Troubleshooting
Guide for each
Error Code
Main PCB
Trouble Shooting Guide Book

** Confirm the 4way valve coil is inserted to the end

Component Check
Electrical
Solution Check
*** When power is supplied in order as follow (Sub2૟Sub1૟Main)
3rd number indicates outdoor quantity at Main PCB 7-segment LED
- Outdoor unit 1set : Model code-capacity(or 10)-..
- Outdoor unit 2set : Model code(Main)-Model code(sub)-capacity(or 20)-..
- Outdoor unit 3set : Model code(Main)-Model code(sub1)- Model code(sub2)- capacity(or 30)- ..

Test functions
**** Check the output voltage of terminal socket ***** Checking method for outdoor unit of 3unit system
during heating operation : 220V (·10%) ྙ Close all the SVC valves of high / low pressure common pipe
ྚ Operate system
ྛ Check the difference of high and low pressure
with LGMV for each unit (Main, Sub1, Sub2)
ྜ If there is a unit in which the difference is not increased
then the 4way valve of that unit is defective

152 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 153
Error Code Error Contents Meaning Main Causes
Error Code Error Contents Meaning Main Causes
Plus:
152,153 Excessive rise of the constant Constant speed compressor Off due to the 173
Refer to CH33
(Plus Sub3) compressor discharge temperature excessive rise in discharge temp (MAIN constant)
174, 175 1. Constant compressor defect
Over-increase of
(sub1 constant 1,2) 2. Discharge temperature sensor defect
temperature
154 Excessive rise in outdoor high Compressor Off due to the high pressure 176, 177 Abnormal staring of 3. Outdoor temperature sensor defect
Refer to CH24 after constant
(Plus Sub3) pressure switch in outdoor unit (sub2 constant 1,2) constant compressor 4. Outdoor main PCB defect
compressor
Plus II: 5. Magnet switch defect

Basic Part
starts
11˧731 6. Wrong connection of constant compressor cables
Outdoor 3 phase power supply 11˧732
155 Wrong wiring at the outdoor 3 phase 11˧733
wiring wrong Refer to CH54
(Plus Sub3) (Reverse phase / Phase omission) 11˧734
(Reverse phase / Phase omission)

transmission error between outdoor units


104 (Main outdoor unit is not receiving sub Error diagnosis and countermeasure flow chart
156 transmission error between
outdoor unit s signals) Refer to CH104

Troubleshooting
(Plus Sub3) outdoor units

Guide for each


147, 149, 171 (Sub outdoor units are not

Error Code
receiving main unit signals) Is resistance value
(insulation & phase to phase)
of corresponding constant No
157 Abnormal resistance value of sensor Replace constant compressor
High pressure sensor error Refer to CH43 compressor normal ?
(Plus Sub3) measurement ( Open / Short ) [refer electric
Trouble Shooting Guide Book

component part]
158 Abnormal resistance value of sensor
Low pressure sensor error Refer to CH42 Yes
(Plus Sub3) measurement ( Open / Short )

Component Check
159 Outdoor unit air temperature Abnormal resistance value of sensor No

Electrical
Refer to CH44 Is cables’ connection
(Plus Sub3) sensor error measurement ( Open / Short ) Adjust connection of cables
of compressor normal? *

Compressor suction Abnormal resistance value of sensor Yes


161(Plus Sub3) Refer to CH46
temperature error measurement ( Open / Short )

162 (Plus Sub3 constant Is discharge temperature


No
compressor1) Compressor discharge pipe Abnormal resistance value of sensor sensor of compressor Replace discharge
Refer to CH41

Solution Check
163 (Plus Sub3 constant temperature sensor error measurement ( Open / Short ) normal? [refer electric temperature sensor
ompressor2) component part]

Yes
164 (Plus Sub3 HEX A) Pipe sensor error of the main and Abnormal resistance value of sensor
Refer to CH45
165 (Plus Sub3 HEX B) sub units heat exchanger (A,B) measurement ( Open / Short )
Is magnet switch No
normal? [refer
㜼 electric Replace magnet switch
Abnormal resistance value of sensor component part]
Sensor error at the outdoor
166(Plus Sub3) measurement Refer CH113
liquid refrigerant pipe
Yes

Test functions
( Open / Short )

167 (Plus Sub3 sub- No


cooling inlet) Outdoor unit sub-cooling sensor Abnormal resistance value of sensor Is outdoor air temperature Replace outdoor air
Refer to CH114 sensor normal? temperature sensor
168 (Plus Sub3 sub- error at inlet / outlet measurement ( Open / Short )
cooling outlet)
Yes
* cables connection between constant compressor
Compressor Off due to the high pressure and magnetic switch
169(Plus Sub3) Excessive rise in high pressure Refer to CH34
sensor Replace outdoor unit PCB

Compressor Off due to the low pressure


170(Plus Sub3) Excessive low pressure drop Refer to CH35
sensor

1.Input voltage in the installation region


Excessive Low voltage / High
171(Plus Sub3) = 3phase 380V·10% Refer to CH25
voltage
2. Single phase = 220V ·10%

Abnormal resistance value of sensor


172(Plus Sub3) Outdoor voltage sensing error Refer to CH49
measurement ( Open / Short )
(Puls) (Puls II)

154 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 155
Error Code Error Contents Meaning Main Causes Error Code Error Contents Meaning Main Causes

Multi V Water II Error happen because of 3 times Multi V Water II


180 successive compressor off due 181 1. Bad connection of temperatureconnector
Anti-Freezing Error of 1. Insufficient water flow rate Water temperature Abnormal value of sensor
Master (11૟801) to over-decrease of temperature Master (11૟811) 2. Temperaure sensor defect
Plate Heat Exchanger 2. Temperature sensor defect Sensor Error (Open / Short)
Slave1 (12૟802) by water pipe sensor and Heat Slave1 (12૟812) 3. Outdoor PCB defect
Slave2 (13૟803) exchanger sensor Slave2 (13૟813)

Basic Part
Error diagnosis and countermeasure flow chart Error diagnosis and countermeasure flow chart

No No
Is temperature sensor
Is water flow rate normal? Check Water flow rate and Power reset Connect temperature sensor on PCB
Connection Condition normal?

Troubleshooting
Guide for each
Error Code
Yes Yes

No
Trouble Shooting Guide Book

Is temperature sensor No
Connect temperature sensor on PCB Is the resistance value of
Connection Condition normal? * Replace temperature sensor
temperature sensor normal?

Yes

Component Check
Yes

Electrical
Replace outdoor unit PCB
No
Is the resistance value of
Replace temperature sensor
temperature sensor normal?

* If value is 100 ༮ ˦(open) or 100 ȳ ˨(short), error occurs


Yes
NB: Resistance value of temperature sensor change according to temperature
It is normal if value shown as below (·5% error)

Solution Check
Replace outdoor unit PCB
Sensor of air temperature: 10୅ = 20.7༮ : 25୅= 10༮ : 50୅= 3.4༮
Sensor of piping temperature: 10୅ = 10༮ : 25୅= 5༮ : 50୅= 1.8༮

* If value is 100 ༮ ˦(open) or 100 ȳ ˨(short), error occurs

NB: Resistance value of temperature sensor change according to temperature


It is normal if value shown as below (·5% error)
Sensor of air temperature: 10୅ = 20.7༮ : 25୅= 10༮ : 50୅= 3.4༮
Sensor of piping temperature: 10୅ = 10༮ : 25୅= 5༮ : 50୅= 1.8༮

Test functions
156 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 157
Error Code Error Contents Meaning Main Causes
Error Code Error Contents Meaning Main Causes
Plus II:
Multi V Water II 11˧931 Heat sink
Transmission error Fan PCB heatsink 1. Heatsink temperature sensor defect
182 1. Power cable or transmission cable is not 11˧932 temperature is
between Main PCB can’t receive temperature high 2. Fan PCB assembly defect
Master (11૟821) connected 11˧933 over 95¶C
(Main PCB Æ Sub signal from Sub PCB 11˧934
Slave1 (12૟822) 2. Defect of Sub / Main PCB
PCB)
Slave2 (13૟823)
Plus II: 1. Heatsink temperature sensor
Heatsink

Basic Part
11˧941 Fan PCB heatsink defect(Open/Short)
Temperature
Error diagnosis and countermeasure flow chart 11˧942 temperature sensor
Sensor
2. Wrong connection of temperature sensor
11˧943 error connector
Abnormal
11˧944 3. Fan PCB assembly defect

No
Error diagnosis and countermeasure flow chart
Is Sub Mciom LED blink? Push reset button

Troubleshooting
Guide for each
Error Code
Yes
Is temperature sensor No Check connection of heat sink
inserted to fan PCB? temperature connector
Trouble Shooting Guide Book

No
Is Error disappear ? Instant Error
Yes

Component Check
Yes

No

Electrical
Is temperature sensor Check connection condition of
Replace outdoor unit Main PCB attached to heat sink? heat sink and temperature sensor

Yes

Check heat sink temperature


sensor wire disconnection
No
Is termperature ‫ ݬ‬Measure temperature sensor

Solution Check
sensor normal? resistance(10kȳ ·5% at 25¶C)
‫ ݬ‬Replace the sensor if
abnormality found
Yes

No
Is fan PCB assembly
㜼 normal? Replace fan PCB assembly

Yes

Test functions
Recheck power and installation
condition

158 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 159
Error Code
Error
Contents
Meaning Main Causes ඖ Auto addressing
1. HR unit’s power cable or transmission cable connection defect
After the Auto operation,
2. After Auto-Addressing, wrong address setting of the indoor
Pipe detection
if the number of the indoor
unit (Defective indoor power / transmission error and PCB Turn on “HR unit ૟ Indoor unit ૟
200 units detected is different
error
from the number
defect) Outdoor unit” in the order named ඖ Outdoor unit main PCB
3. Wrong setting of the HR unit’s rotary switch or dip switch
communicating indoor unit
4. HR unit PCB defect
<7 Segment>

Basic Part
H1 01…H1 04
failed to search pipe 1. HR unit’s power cable or transmission cable connection defect
H2 01…H2 04 Wait for 3 minute
connected to HR unit valve 2. After Auto-Addressing, wrong address setting of the indoor
H3 01…H3 04 Pipe
of marked number unit
H4 01…H4 04 detection
(Ex : H1 02 ૟no.2 valve (Defective indoor power / transmission error and PCB defect)
. error
pipe of no.1 HR unit failed 3. Wrong setting of the HR unit’s rotary switch or dip switch
.
to search) 4. HR unit PCB defect
.

Troubleshooting
Press SW02M of the ODU main PCB

Guide for each


Error Code
for 5 seconds
Error diagnosis and countermeasure flow chart
Trouble Shooting Guide Book

’88’ is displayed on the ODU main PCB and


H.R. unit green No the HRU PCB
LED (communication LED) blinks Check H.R. unit input power (220V·10%)

Component Check
periodically ?
Yes

Electrical
Yes

After 2~7 minute, the number of IDU


Check installation status of communication line connected is displayed at 7-seg of the
Check H.R. unit Rotary switch and and connected pipe
Dip Switch setting outdoor unit ˩HR unit ˩outdoor unit
ODU main PCB
<SW03M>
Yes Yes (Dip switch)

Solution Check
Check if all indoor unit is CH05 with
The number of HRU connected is displayed
Operate auto pipe detection after the H.R. unit on (Refer to CH05)
at 7-seg of the ODU main PCB
pipe is sufficiently refrigerated
after resetting outdoor unit
and HR unit 30 minutes before <SW02M> <SW01M>
Yes

Test functions
Is the Auto-pipe detection No Equal number of “IDU No
success? Adjust H.R. unit manual pipe detection and displayed one”?
(is the Error disappeared?) in terms of “wiring”
Yes Check power and communication wiring
Yes between ODU, HRU, IDU

Finish

Retry auto addressing after solving problem


Completion of the IDU auto addressing

[NB] If Indoor units/transmission cables of HR unit and cables of power 220V has been changed each other,
transmission parts and indoor will be burnt

160 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 161
ඖ Auto pipe detection ඖ Manual pipe detection

Confirm the IDU auto addressing setting In case of auto pipe detection failure

Basic Part
Turn off “No.1 of SW02M of the HRU” Turn on “No.1 of SW02M of HR unit”

Check the proper setting of


No. 2 & 3 of SW02M of the HRU Reset the power of HRU PCB
(Model of HRU & number of IDU)

Troubleshooting
Guide for each
Reset the power of HRU PCB Enter central control address into each IDU

Error Code
using its wired remote controller
Confirm the No. 5 DIP S/W of SW01B
of the ODU PCB
Trouble Shooting Guide Book

- Outdoor temp is over 15୅ : ON


Manually set the address of each valve
- Outdoor temp is below 15 ୅ : OFF
corresponding with the central control

Component Check
address of IDU connected to the valve

Electrical
In case of changing 5 DIP S/W of SW01B
of the ODU, reset power of the ODU main
PCB. Turn on No.5 of SW01B
of ODU PCB”
Wait for 3 minute

Solution Check
Press SW01V of the ODU main PCB Reset the power of ODU PCB
for 5 second

The number of HRU connected is displayed


at 7-seg of the ODU main PCB, and Wait for about 5 minutes
then ’88’ is displayed

Test functions
Outdoor unit is operating
for 5~30 minutes. The number of IDU installed is displayed

After ODU stopped, the number of IDU Display error on the ODU PCB / HRU PCB
detected is displayed at 7-seg of the ODU - ODU PCB : HR unit No. ૟ Valve No. No
Equal number of
main PCB for 1 minute (Example: H1 01) “IDU and Displayed one”?
- HRU PCB : ‘200’

Yes
Equal number of IDU No
and displayed one? Turn off No.5 of SW01B Check the central control address of IDU
in terms of “piping” Check the piping among ODU, IDU, HRU
of ODU PCB and HRU
Yes

Completion of the manual pipe detection Retry manual pipe detection


Completion of the auto pipe detection Retry auto pipe detection

162 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 163
ඖ HR Unit PCB

Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

Component Check
Green LED blinking :

Electrical
Communication OK

ඖ Switch setup of HR Unit

Solution Check
Test functions
164 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 165
ඖ Manual addressing of valves on HR unit PCB
(with SW01M, SW03M, SW04M)

Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

Component Check
Electrical
T v—Œ™ˆ›–•aGu–•Œ
T kš—“ˆ aGu–•Œ
SW01M SW03M SW04M

Solution Check
No.1 of SW01M
T v—Œ™ˆ›–• aGu–UXG–Gz~WXtG–•G›–Gˆ‹‹™ŒššGˆ“œŒGJX
T kš—“ˆ GaGlŸš›•ŽGˆ“œŒGšˆŒ‹G•GllwyvtGšG
‹š—“ˆ Œ‹ •G^TzlnU
SW01M SW03M SW04M

T v—Œˆ›–• azŒ›G›ŒG‹Ž›G–GXWG›–G›ŒG•œ”‰Œ™G•G

Test functions
n™–œ—GoŽG‹ˆ›ˆG–G›ŒGž™Œ‹G™Œ”–›ŒGŠ–•›™–“G
Š–••ŒŠ›Œ‹G›–G›ŒGŠ–™™Œš—–•‹•ŽG•‹––™Gœ•›G›–G›ŒG
SW03M
ˆ“ŒGJXG‰ G—™ŒššGz~WZtGzV~
SW01M SW04M
T kš—“ˆ GaGkŽ›G•Š™Œˆš•ŽGž›G›ŒG›”ŒšG–G—™ŒššG
SW03M z~WZtGzV~GšG‹š—“ˆ Œ‹G•G“Œ›G^Tzln SW03M

Tv—Œ™ˆ›–•GaGzŒ›G›ŒG‹Ž›G–GXG›–G›ŒG•œ”‰Œ™G•G
n™–œ—Gs–žG‹ˆ›ˆG–G›ŒGž™Œ‹G™Œ”–›ŒGŠ–•›™–“G
Š–••ŒŠ›Œ‹G›–G›ŒGŠ–™™Œš—–•‹•ŽG•‹––™Gœ•›G›–G›ŒG
ˆ“ŒGJXG‰ G—™ŒššGz~W[t SW04M
SW01M SW03M Tkš—“ˆ GaGkŽ›G•Š™Œˆš•ŽGž›G›ŒG›”ŒšG–G—™ŒššG
SW04M z~W[tGzV~GšG‹š—“ˆ Œ‹G•G™Ž›G^Tzln SW04M

No.1 of SW01M
Tv—Œ™ˆ›–•GaGu–UGXG–Gz~WXtG–G›–GšˆŒG›ŒG
ˆ‹‹™ŒššG–Gˆ“ŒGJX
Tkš—“ˆ GaG“XX” ‹š—“ˆ Œ‹G•G^TzlnG‹šˆ——Œˆ™š
SW01M SW03M SW04M

166 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 167
Error Code Error Contents Meaning Main Causes Error Code Error Contents Meaning Main Causes

201(HR unit1) 205(HR unit2) HR unit liquid 1. Defective connection in HR unit power supply and
1. Defective temperature sensor connection 204(HR unit1) 208(HR unit2) transmission transmission
209(HR unit3) 213(HR unit4) pipe Abnormal value of sensor transmission connection
2. Temperature sensor defect(Open/Short) 212(HR unit3) 216(HR unit4) error between error between
217(HR unit5) 221(HR unit6) temperature measurement ( Open / Short ) 2. Wrong setting of the HR unit Rotary switch and
3. Defective HR unit PCB 220(HR unit5) 224(HR unit6) the HR unit and the HR unit and
225(HR unit7) 229(HR unit8) sensor error Dip switch
228(HR unit7) 232(HR unit8) outdoor unit outdoor unit
3. Defective HR unit PCB

HR unit
202(HR unit1) 206(HR unit2)
Error diagnosis and countermeasure flow chart

Basic Part
Sub-cooling 1. Defective temperature sensor connection
210(HR unit3) 214(HR unit4) Abnormal value of sensor
inlet pipe 2. Temperature sensor defect(Open/Short)
218(HR unit5) 222(HR unit6) measurement ( Open / Short )
temperature 3. Defective HR unit PCB
226(HR unit7) 230(HR unit8)
sensor error
H.R. unit green No
HR unit LED (communication LED) blinks Check H.R. unit input power (220V·10%)
203(HR unit1) 207(HR unit2) periodically ?
Sub-cooling Abnormal value of sensor 1. Defective temperature sensor connection
211(HR unit3) 215(HR unit4) Yes
discharge pipe measurement 2. Temperature sensor defect(Open/Short)
219(HR unit5) 223(HR unit6)

Troubleshooting
temperature ( Open / Short ) 3. Defective HR unit PCB Yes

Guide for each


227(HR unit7) 231(HR unit8)
sensor error

Error Code
Check installation status of communication line
Check H.R. unit Rotary switch and and connected pipe
Dip Switch setting outdoor unit ˩HR unit ˩outdoor unit
Error diagnosis and countermeasure flow chart
Trouble Shooting Guide Book

Yes Yes

Component Check
Is the sensor connected to no
Reconnect sensor to PCB

Electrical
HR unit PCB properly? Replace HR unit PCB

yes

Is the sensor resistance no


Replace sensor
level normal?*
[NB] If Indoor units/transmission cables of HR unit and cables of power 220V has been changed each other,

Solution Check
yes transmission parts and indoor will be burnt

Replace HR unit PCB

* Sensor resistance 100 ༮ over (open) or 100 ȳ below (short) will generate error

Test functions
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (·5% tolerance)
Air temperature sensor: 10୅ = 20.7༮ : 25୅= 10༮ : 50୅= 3.4༮
Pipe temperature sensor: 10୅ = 10༮ : 25୅= 5༮ : 50୅= 1.8༮

168 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 169
Error Code Error Contents Meaning Main Causes Error Code Error Contents Meaning Main Causes

1. Defective transmission connection 1. NOISE occurs


Central controller transmission failure
2. Defective CNU 2. CNU defect
240 connector error between central controller
3. Incorrect IP address of central controller or CNU Central controller Received check sum is different from 3. Temporary error of Timing mismatch
(CNU Connection failure) and CNU 250
4. Defective transmission network Check sum Error calculated check sum data 4. A/C product defect
5. PI485 communication cable open or
connection defect
Error diagnosis and countermeasure method

Basic Part
1. NOISE occurs
1) Check transmission cables are connected correctly or not 2. CNU defect
2) If central controller is connected to total network, check IP of CNU, central controller Central controller 3. Temporary error of Timing mismatch
3) Replace CNU 251 Length of received data : 0
Receive Zero Error 4. A/C product defect
5. PI485 communication cable open or
connection defect
Error Code Error Contents Meaning Main Causes

Troubleshooting
Guide for each
1. Defective CNU 1. NOISE occurs
Central controller data Central controller to CNU data

Error Code
241 2. Center controller initialization 2. CNU defect
transmission error (Sending error) transmission failure
failure Central controller Setting address and actual address 3. Temporary error of Timing mismatch
252
Wrong Address Error are different each other 4. A/C product defect
5. PI485 communication cable open or
Central controller receive Error CNU to Central controller on time 1. Defective CNU connection defect
242
Trouble Shooting Guide Book

(Data receiving error ) data receiving error 2. Central controller initialization error

When data length from 1. Mismatching 1. NOISE occurs

Component Check
Central controller receive buffer 2. CNU defect
243 CNU is longer than data length 2. Defective CNU
overflow (In excess data receive) Central controller 3. Temporary error of Timing mismatch
defined at protocol 3. transmission noise error 253 No response from air conditioner

Electrical
Disconnection Error 4. A/C product defect
5. PI485 communication cable open or
1. Defective CNU connection defect
Central controller receive time out transmission failure
244 2. Initialization failure of central
(Receiving time : 3sec ˦) between central controller and CNU
controller

Error diagnosis and countermeasure method


Data sending failure from central 1. CNU defect
245 Central controller Send Timeout controller to CNU within designated 2. Initialization failure of central

Solution Check
time controller 1) Check system setting address of central controller and actual address is matched or not
2) Re-start service program(engine) of central controller
3) Replace CNU
Data receiving failure of central 1. CNU defect
246 Central controller Receive Timeout controller from CNU within 2. Initialization failure of central
designated time controller

Test functions
170 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 171
3.1 How to check main control box?
(a) Plus

Basic Part
2 6
4
3
5

Troubleshooting
Guide for each
Error Code
1

Component Check
Electrical
No. Part Check
How to check? Counter-measure
(Function) points

3. Electric
1 T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within 380·10% -Check supply power
(Terminal - Voltage of 1ɐ(R-N,S-N,T-N) should be within 220·10%. and connection
Block, - Voltage fluctuation should be within 10V condition
Input - While stand-by and in operation,

Component Check
power)

Solution Check
Voltage drop should be within 10V

Checking points of 3ɐ(R-S) Checking points of 1ɐ(R-N)

Test functions
Check ȳ - Resistance of R-S,S-T,R-T,R-N,S-N should be -Check short or not of
(In case more than a few ༮ Control box (Noise
power filter, PCB, cables)
is not - Resistance of T-N should be within 40~50˟ - Replace transformer
supplied) (Main transformer of outdoor)

2 FUSE Check - Voltage of fuse should be within 0~1V -In case of 220V,
(Protect disconnection Fuse is disconnected.
over- of FUSE ૟ Replace FUSE
loaded (when power
current) is supplied)

Checking points of R ɐ fuse

Check -Resistance of fuse should be within 0~1˟ -In case resistance is


disconnection ˳, Fuse is
of FUSE disconnected.
(when power ૟ Replace FUSE
is not
supplied)

172 _LG Air Conditioners System Electrical Component Check_ Electrical Component Check_ 173
(a) Plus (a) Plus

No. Part Check No. Part Check


How to check? Counter-measure How to check? Counter-measure
(Function) points (Function) points

3 Nose filter Check voltage -Voltage of each connector (R-R,S-S,T-T) should - In case of 220V 5 EOCR Time, Current -Rotary switch setting should be correct
(Noise emit & (When power be within 0~40V It is disconnected (Cut off over- Rotary (Current:30~40A, Time:5sec)

Basic Part
protect) is ૟ Replace noise filter loaded switch Setting
Supplied) current to
protect TIME
constant
compressor)
Current(A)

Troubleshooting
Connection -R cable and T cable should be connected each other

Guide for each


Error Code
condition

6 Outdoor MAIN PCB 2. AC 220V 19. DC12V


10. LEV drive circuit
Power connector Cooling fan
Plus Plus II
3. AC power
Trouble Shooting Guide Book

out circuit to
drive valves
Check ȳ -Resistance of each connectors (R-R,S-S,T-T) -In case resistance is 8. JIG transmission
(In case power should be within 0~10˟ ˳, noise filter is connector

Component Check
Is not supplied) disconnected. 18. 7- segment display
૟ Replace noise filter 13. Central control signal &

Electrical
on-board writing circuit
4 Magnet Magnet switch -When check resistance of 1st coil of magnet switch, -In case resistance is 1. MICOM circuit
9. Pressure, temperature sensor
switch 1st coil resistance should be 0.47 ༮ ˳ or 0 ˟, circuit
(When power is not supplied) ૟ Replace Magnet 15. FAN transmission circuit
When magnet switch is on, voltage should be 220V switch
17. Outdoor option setting switch
(When power is not supplied)
-When voltage is not 14. compressor transmission circuit

Solution Check
220V, magnet switch
is melt down 16. Auto-Addressing
- Replace magnet 11. I/D˩O/D transmission
switch circuit
4. Power Trans In
connector
12. O/D˩O/D transmission
circuit

Test functions
6. AC 220V power 5. AC voltage sensing circuit 7. Power Trans Out connector
connector for (T-N input voltage check)
** check point of 1st coil of magnet switch central control
Magnet switch -While pressing green button of magnet switch, - Replace magnet Defect Check point How to check? Counter-measure
connection Voltage of each connectors should be 0V or switch
No power 2.Power terminal -Input voltage should be 220V. -Check fuse(3.15A), T-N voltage
check Resistance should be 0~1˟
at PCB (when power is supplied) ૟-If resistance is 0~100˟ , replace
(In case power (Warning: power should not be supplied)
2.Power terminal -Input resistance should be more than PCB
is not supplied)
a few ༮(when power is not supplied)
7.Transformer -Output voltage should be 14V,9V -Check transformer and connection
No trans- 11.I/D˩O/D -DC voltage of connectors should be -Replace PCB, transformer and
mission 12.O/D˩O/D various (-7V~+7V) check connection points
14.Inverter -Yellow LED should blink. -Check Main / Inverter compressor PCB
compressor and
15.Inverter fan -Green LED should blink connection points
-Check Main / Inverter fan PCB
In case 3. AC 220V -Voltage of PCB should be 220V at LGMV -Replace PCB and check connection points
PCB AC output to drive -Replace PCB and check connection points
power valves and -Output voltage should be showed as
output is below
others
0
Sensor(5V), Cooling fan(12V),LEV(12V)

174 _LG Air Conditioners System Electrical Component Check_ 175


(a) Plus (b) Plus ȤȤ
No. Part Check
How to check? Counter-measure
(Function) points

7 Outdoor Coil resistance 1st side : 42˟ -Replace transformer


transformer (when power 2nd side :2.4˟, 0.25˟ and check
2 4

Basic Part
(Supplies is not supplied) connection points
2.4 ˟ 0.25 ˟
power to PCB
and
transmission)

Black : Input (220V)


Blue : Output (8.5V)
Red : Output (13V)

Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

42 ˟

In/Output 1st side : 220V (AC) -Replace transformer

Component Check
voltage 2nd side : 14V, 9V(AC) and check 1 4
3

Electrical
(when power is connection points
supplied)

No. Part Check


How to check? Counter-measure
(Function) points

Solution Check
1 T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within 380·10% -Check supply power
(Terminal - Voltage of 1ɐ(R-N,S-N,T-N) should be within 220·10%. and connection
Block, - Voltage fluctuation should be within 10V condition
Input - While stand-by and in operation,
power)
Voltage drop should be within 10V

Test functions
Checking points of 3ɐ(R-S) Checking points of 1ɐ(R-N)

Check ȳ - Resistance of R-S,S-T,R-T,R-N,S-N,T-N should be -Check short or not of


(In case more than a few ༮ Control box (Noise
power filter, PCB, cables)
is not - Replace transformer
supplied)

176 _LG Air Conditioners System Electrical Component Check_ 177


(b) Plus ȤȤ (b) Plus ȤȤ
No. Part Check
How to check? Counter-measure No. Part Check
(Function) points How to check? Counter-measure
(Function) points
2 Nose filter Check voltage -Voltage of each connector (R-R,S-S,T-T) should - In case of 220V
6 Outdoor MAIN PCB
(Noise emit & (When power be within 0~40V It is disconnected

Basic Part
Inverter
protect) is ૟ Replace noise filter PCB Comm.
Supplied) LED
Reset button

Inv. PCB Communication On-boarding Terminal


Terminal
Inv. Comp. High
Pr. Switch Main LEV LGMV Terminal
Sub-cooling Auto Address
LEV

Const. Comp.
Central controller

Troubleshooting
High Pr. Switch

Guide for each


Error Code
Sub-cooling
sensor
Trouble Shooting Guide Book

Check ȳ -Resistance of each connectors (R-R,S-S,T-T) -In case resistance is Const. Comp. Liquid Valve
Inv discharge,
Inv. Comp. Liquid Valve
HEX1, HEX 2
(In case power should be within 0~10˟ ˳, noise filter is

Component Check
AC Fan Power Supply
Sensors
Is not supplied) disconnected. Const. Comp.
Magnetic Switch

Electrical
૟ Replace noise filter Hot Gas Sol. Valve
Outdoor air,
Constant Comp Heater Suction temp.,
3 Magnet Magnet switch -When check resistance of 1st coil of magnet switch, -In case resistance is Constant comp.
Inv. Comp Heater
switch 1st coil resistance should be 0.47 ༮ ˳ or 0 ˟, 4-Way Valve
discharge
sensor
(Constant (When power is not supplied) ૟ Replace Magnet
speed When magnet switch is on, voltage should be 220V switch 220V Power
compressor) (When power is not supplied)
Input

-When voltage is not

Solution Check
220V, magnet switch Jig Power High Pressure
Terminal, 220V Constant Comp. Sensor
is melt down Current Sensor Low Pressure
Sensor
- Replace magnet
Communication
switch terminal

Defect Check point How to check? Counter-measure

Test functions
No power 2.Power terminal -Input voltage should be 220V. -Check fuse(3.15A), T-N voltage
** check point of 1st coil of magnet switch
at PCB (when power is supplied) ૟-If resistance is 0~100˟ , replace
2.Power terminal -Input resistance should be more than PCB
4 CT Current Current to -Check wiring a few ༮(when power is not supplied)
Sensor Constant
Compressor
No trans- I/D˩O/D -DC voltage of connectors should be -Replace PCB and
mission O/D˩O/D various (-7V~+7V) check connection points
14.Inverter -Yellow LED should blink. -Check Main / Inverter compressor PCB
compressor and
connection points

In case 3. AC 220V - Check Noise filter output -Replace Noise filter


PCB AC output to drive -Voltage of PCB should be 220V at -Replace PCB and check connection
power valves and LGMV points
output is Others -Output voltage should be
0
Sensor(5V), Cooling
fan(220V),LEV(12V)

178 _LG Air Conditioners System Electrical Component Check_ 179


3.2 How to check inverter control box? (a) Plus
(a) Plus Loc. Part Check
How to check? Counter-measure
(Function) points

3 Capacitor Electric capacity. - Electricity capacity of capacitor must be - Replace capacitor


(To charge (when power is 2600~2800༲ and the resistance of capacitors when value is more or

Basic Part
DC voltage not supplied) should be more than a few ༮ less than normal spec.
for inverter
compressor)
3 * Check values at both
terminal of capacitor

4 2

Troubleshooting
Guide for each
Error Code
DC charging - Charged voltage of between terminals of - Check input voltage and
voltage capacitor replace capacitor
(When power is (= between IPM P-N terminal = DC link
1 supplied) terminals)
Trouble Shooting Guide Book

should be more than 450V


7 5 (At the moment of inverter compressor start)
8 6 4 INV compressor 2. Power & 3. High pressure 4. DC-Link 6. transmission 5. Checking circuit

Component Check
PCB start-relay switch & sensing & circuit to main for reverse phase
drive circuit power-relay display circuit PCB of input power

Electrical
drive circuit

No. Part Check 7. On-board


How to check? Counter-measure
(Function) points writing connector

Solution Check
1 T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within 380·10% - Check supply voltage
(Terminal (When power - Voltage of 1ɐ(R-N,S-N,T-N) should be within & connection points
block, Power is supplied) 220·10%. Check noise filter, 1. MICOM
input) - Voltage fluctuation should be within 10V fuse circuit
- While standby and in operation,
Voltage drop should be within 10V
9. PWM driving
signal output
circuit 8. CT sensing circuit

Test functions
Phenomena Check point How to check? Counter-measure
Checking points of 3ɐ(R-S) Checking points of 1ɐ(R-N)
No power 2.Power -Input voltage should be 220V. - Check & replace fuse(3.15A),
2 REACTOR Resistance of - Resistance of reactor should be within 1~3˟ - In case resistance is at PCB (when power is supplied) T-N voltage (220V)
(DC voltage connectors & (When power is not supplied) ˳, coil is -Input resistance should be more than a few ༮ - If resistance value is 0~100˟ ,
connection (when power is not supplied) replace PCB
stabilization) - Voltage between terminals of reactor should be disconnected.
condition No 6.Transmission -Yellow LED should blink. - Check yellow LED blinks or not
within 0~1V (When power is supplied) ૟ Replace reactor
transmission circuit to main - When is OFF, check transmission
PCB with main PCB and replace
Malfunction of 9.PWM signal -Green LED should blink. - Replace PCB
inverter cable -Check IC port coupler
compressor of PWM drive
(when power is
not supplied) 1-2 Diode : 1.0V 2-3 Diode : 1.4V

Inverter Red LED -When red LED blinks. -Check error code displayed at
compressor Error displays about inverter compressor PCB main PCB
***Reactor for INV compressor Reactor for INV Fan PCB Error

180 _LG Air Conditioners System Electrical Component Check_ 181


(a) Plus (a) Plus

Loc. Part Check No. Part Check


How to check? Counter-measure How to check? Counter-measure
(Function) points (Function) points

5 Inverter 1. MICOM circuit 10. Comm. circuit 7 Inverter 1. PWM signal connector
fan PCB fan

Basic Part
IPM PCB
4. IPM
9. On-boarding 2. Input circuit of 3ɐ &
lighting connector DC rectifying circuit

8. Heat sink
3. In/Output connector
temperature
of reactor
sensor connector
2. DC supply terminal

Troubleshooting
Guide for each
7. PWM (DC310V)

Error Code
drive circuit 4. DC-Link output voltage

6. SMPS power
Trouble Shooting Guide Book

circuit 5. DC-Link electrolytic


capacitor
3. Outdoor unit fan connectors

Component Check
Phenomena Check point How to check? Counter-measure

Electrical
Phenomena Check point How to check? Counter-measure
No power 2.3ɐ power - Input voltage of 3ɐ 4 wires should be -Check supply voltage, noise
on PCB Input circuit 3ɐ 380V, 1ɐ 220V Reactor 1 filter, fuse Inverter fan 1.PWM signal - Check 9pin connectors - Replace cables & check
R, S, T, N
- Check half wave rectifying circuit diode -Replace inverter fan PCB is not rotating 2.Fan DC power - DC voltage should be charged of 310V soldering condition of PCB
(R-Reactor1: 0.6V, S-Reactor1: 0.6V: 3.Outdoor - While Fan operating, in case voltage of - Replace connectors & inverter
T-Reactor1: 0.6V) fan connector connectors(U-V,V-W,U-W) is 100~300V PCB if not charging
˧ Normal
4. IPM - Check Diode(P-N : 0.95V, - Replace inverter IPM PCB

Solution Check
P-U,P-V,P-W: 0.55V
N-U,N-V,N-W: 0.55V

R(+) - Reactor1(-) : 0.6V

No 10. Transmission -Yellow LED should blink. -Check yellow LED blinks or not
transmission circuit with main -When is OFF / ON continuously, Check DIODE(P-U : 0.5V)
PCB

Test functions
check transmission with main PCB

Inverter fan Red LED -When red LED blinks, error code happens -Check error code at main PCB
PCB error about inverter fan PCB 8 IPM Check voltage
& resistance
of
6 3ɐ Check voltage & each phases
DIODE resistance of (When power
each phases is not
(when power is supplied)
not supplied)
P-U :DIODE(0.4V) P-V :DIODE(0.4V) P-W :DIODE(0.4V)
resistance(a few ༯) resistance(a few ༯) resistance(a few ༯)
P-U :DIODE(0.4V) P-V :DIODE(0.4V) P-W :DIODE(0.4V)
resistance(a few ༯) resistance(a few ༯) resistance(a few ༯)

N-U :DIODE(0.4V) N-V :DIODE(0.4V) N-W :DIODE(0.4V)


N-U :DIODE(0.4V) N-V :DIODE(0.4V) N-W :DIODE(0.4V) resistance(a few ༯) resistance(a few ༯) resistance(a few ༯)
resistance(a few ༯) resistance(a few ༯) resistance(a few ༯)

182 _LG Air Conditioners System Electrical Component Check_ 183


(b) Plus ȤȤ (b) Plus ȤȤ

Loc. Part Check


How to check? Counter-measure
(Function) points
2 4 Inverter 2 220V Power input
fan PCB

Basic Part
4
3

1 700 DC
Link

Troubleshooting
Guide for each
Error Code
DC 15V
Output N- Phase
terminal Terminal

PFC
R- Phase
On-boarding
Trouble Shooting Guide Book

(To Diode)
terminal
R- Phase
Terminal
(From Noise
filter)

Component Check
T- Phase

Electrical
Terminal
(From Noise
filter)

Inverter Error LED T- Phase Terminal (To Diode)


Inv. On-boarding terminal
11 Fan PCB Communication
U,V,W Output terminal 11 Main PCB Communication
Phenomena Check point How to check? Counter-measure Main, Fan PCB Communication LED

Solution Check
REACTOR Resistance of - Resistance of reactor should be within - In case resistance is
(DC voltage connectors & 1~3˟ ˳, coil is disconnected. Phenomena Check point How to check? Counter-measure
stabilization) connection (When power is not supplied) ૟ Replace reactor
condition - Voltage between terminals of reactor should No power 2.Power -Input voltage should be 220V. -T-N voltage (220V)
be within 0~1V (When power is supplied) at PCB (when power is supplied)
-Input resistance should be more than a few -If resistance value is 0~10,
༮ (when power is not supplied) replace PCB

Test functions
No transmission 10.Transmissio -LEDs should blink. - Check LED blinks or not
(Main PCB) n circuit to - When is OFF, check
3ɐ DIODE Check voltage & main, fan PCB
-In case the measured value is different from the (Fan PCB) transmission with main, fan
resistance of PCB
table, set multi tester to resistance mode
each phases
and measure. If the value is small (0 ȳ) or high
(when power is
(hundreds M ȳ), PCB needs to be
not supplied) replaced. Inverter 12. PWM LED -When red LED blinks. -Check error code displayed
- In case that bridge diode is damaged, check if compressor PCB PWM is normal at main PCB
inverter PCB assembly (IPM) is needed to be Error
replaced.

184 _LG Air Conditioners System Electrical Component Check_ 185


(b) Plus ȤȤ 3.3 How to check Multi V Space control box?
Loc. Part Check
How to check? Counter-measure * MUTLI V SPACE 10HP C/BOX
(Function) points

4 Inverter
fan PCB 10 11

Basic Part
10 11 12 6 12
9

5 8 7
7 8 5

Troubleshooting
Guide for each
Error Code
4
3 6 3
Trouble Shooting Guide Book

Component Check
1 1
2

Electrical
Phenomena Check point How to check? Counter-measure

DC link DC link Checking DC Link in inv. PCB


voltage check connection
and IPM between Inverter
N2(COMP B,FAN B) N1(MAIN control + COMP A,FAN A)

Solution Check
check* and Fan PCB
NO Name Function NO Name Function
* IPM check: [CN CD_LINK] 1 T/BLOCK 3 phase 4 line power input 1 T/BLOCK 3 phase 4 line power input
After
disconnecting Excessive electric blockade
all connector 2 FUSE 2 FUSE Excessive electric blockade(30A)
(30A)

3 Noise filter Block and discharge noise 3 Noise filter Block and discharge noise

LOGIC control of the whole

Test functions
- - - 4 MAIN PCB
product
No 10. Transmission -Yellow LED should blink. -Check yellow LED blinks or not
5 FAN PCB BLDC FAN control 5 FAN PCB BLDC FAN control
transmission circuit with -When is OFF / ON continuously,
Inverter PCB check transmission with main
6 COMP PCB BLDC COMP control 6 COMP PCB BLDC COMP control
PCB

Switching degauss ,(COMP Switching degauss ,(COMP


7 IPM 7 IPM
output) output)

3 phase power commutation 3 point phase commutation


8 DIODE 8 DIODE
degauss (+) degauss (+)

9 TRANSE Supply MAIN PCB power

DC voltage stabilization and DC voltage stabilization and


10 REACTOR 10 REACTOR
power factor beveling power factor beveling

DC voltage recharge DC voltage recharge


11 CAPACITOR 11 CAPACITOR
Inverter fan Red LED -When red LED blinks, error code happens -Check error code at main PCB (COMP,FAN) (COMP,FAN)
PCB error about inverter fan PCB
12 Magnet S/W BLDC COMP switch 12 Magnet S/W BLDC COMP switch

186 _LG Air Conditioners System Electrical Component Check_ 187


Multi V SPACE COMP PCB Multi V SPACE BLDC FAN PCB
4.SW_SEL 6.CN_COMM
[louver 5.SW_DIR [MAIN PCB૟>FAN PCB] :5,6,8HP
2.CN09 3.CN05 4.CN01 selection] [FAN direction] [FAN૟>COMP PCB] : 10HP
LED01M : PWM Enable
[COMP૟>FAN[3point sensor] [power supply START RELAY] LED02M : display error
Communication]

Basic Part
1.CN06 7.CN_POWER2
[MAIN૟>COMP 3.Power supply [louver power supply]
Communication]
LED01K
(FAN૟>INV
12. LED01,02K communication)
8.SW01M,02M,03M

Troubleshooting
Guide for each
5.CN04 [PCB JIG check]

Error Code
11. Function key [high pressure switch 9.CN_WIRTE
& Power-Relay] [on boarding light]
10.CN_M1S,M2S
2.CN_DC LINK [louver signal input]
Trouble Shooting Guide Book

6.Power supply [DC power


11.CN_SENSOR
supply sensor)
[FAN signal input]
1.CN_POWER

Component Check
[PCB power 12.CN_MOTOR1,2
supply) [louver signal output]

Electrical
13.CN_FAN
[FAN signal output)
9.CN02 8.CN IIPM 7.CN GATE1,2
[DC LINK sensor] Situation Monitoring Location How to check? Counter-measure
10.CN14
Power does 1.CN POWER -AC voltage measure 220V -Input voltage (220V)
[COMP output sensor]

Solution Check
not turn on
3. Power supply (CH105) - ZNR01D( barrister ),FUSE burn out -Replace related parts
checkup
Monitoring
Situation How to check? Counter-measure FAN motion 2.CN_DC LIINK -DC 470V~520V displays - Check and replace CAPACITOR
Location
disabled -DC 380V and above are normal - Replace PCB
PCB power does not 4.CN01 -input voltage must be 220V (power on) -LINE FUSE(3.15A)
turn on 13.CN_FAN(CH106) - U,V,W electric flow measurement Check up and replace connection
(CH52) manage after checking input
11.CN_SENSOR(CH67) stabilize and motor
-input resistance is over ༮.(power off) voltage 220V
-Check connectors
-replace PCB if the resistance is

Test functions
0~100˟ communicat 6. CN-COMM -Flick LED01K -Check PCB power supply(220V)
ion does (CH105) - check connector and PCB (power -Check and replace connector and
not work supply ,communication) PCB
Communication does 1.CN06 -yellow LED(LED01,02K)must flick. -check communication and FAN
not work 2.CN09 PCB and MAIN PCB if the yellow
Louver does 4.SW_SEL -Check if connector is connected - connect connectors (if there are no
(CH52) LED is flick or OFF (check
not work louver)
connection and replace PCB)
7.CN_POWER2 -DC24V display check -Check and Replace trance and
COMP malfunction 10.CN14 -constant COMP output U(-),V(-),W -replace after checking PCB and power supply
COMP if the difference is over 2A
10.CN_M1S,M2S -Connection status check -Check and replace louver motor
9.CN02 -DC voltage within 470V~520V and connection part
-replace after checking CAPACITOR
and PCB 12.CN_MOTOR1,2 - Connection status check - Check and replace louver motor
8.CNIPM -check connection status and connection part
7.CN_GATE
(CH21 Replace and check motor and
connection
CH22 *BLDC motor monitoring method
CH23) 1 2
3 4 Ha(4),Hb(3) ૟-૟ Gnd(2) : 24MOhm
Ha(4),Hb(3) ૟-૟ Vcc(1) : 11KOhm

Deficiency error 3.CN05 -3 point power line (noise filter latter part) - Readjust and Replace after Vcc Gnd
(CH54) over 380V checking FUSE, input power , Hb Ha
connection line

188 _LG Air Conditioners System Electrical Component Check_ 189


3.4 How to check indoor unit PCB? 3.5 How to check other electric components?
3.CN_FLOAT
[Drain pump (a) Plus
13.CN_POWER 1.CN_MOTOR 2.CN_CC3 sensor]
[power supply_220V] [indoor motor] [DRY CONTACT
Name Check
boarding] Check points
4.CN_OPTION Loc.
[additional function] Display Outdoor unit

Basic Part
Value of main PCB
5. Sensing part main display Value Main PCB
5 sec later after power input,
[pipe] PCB in (At the
outdoor moment that 4X Main model name
6.CN_REMO unit power is 50 Sub1(when connected)
[remote control supplied) 50 Sub2(when connected)
power &
communication] XX Total operation capacity in Hp

Troubleshooting
Guide for each
(Ex: 20 Hp ૟ 20)

Error Code
7.CN_HVB
12.CN_DRAIN [plasma] 25 Normal state
[Drain pump 11.CAPACITOR 9.CN_VANE1,2 8.CN_DISP Others : PCB checking mode
Output part_220v] [internal$ external]] [louver operation] [reception part PCB 22 In case of R22 refrigerant
10.CN_LEV connection port] R410A: 41
Trouble Shooting Guide Book

[indoor LEV operation]

* Outdoor unit communication PCB front side Outdoor unit communication PCB backside

Component Check
* When there is
communication error(U01Y)

Electrical
1 8
2 7
14.CN_A5 3 6
[indoor PCB 4 5
connection] DIODE MODE measurement
8-1,2,3,4 : 1.2V
5-1,2,3,4 : 0.7V
Communication

Solution Check
Connection (A,B)
Monitoring
Situation How to check? Counter-measure Outdoor
Location
PCB, remote control 13.CN_POWER -input voltage must be 220V.(power on) -manage and check input voltage 220V sub unit
power does not come - Barrister (ZNR01N),FUSE,,PCB check -replace and check relate parts PCB display
on Value Sub PCB
(When power
Communication does 14.CN_A5 -check connection -readjust and check connection is supplied)
not work
LED 8 7 6 5 4
communication -Check connection PCB latter U01Y -Replace and check IC(DIODE) display

Test functions
PCB -- green LED flick (flick initially) -Replace after checking communication condition) LED 3
PCB and indoor unit PCB power supply
LED 2
Outdoor unit motor 1.CN_MOTOR -Error CH10(FAN LOCK) when it does not -replace and check motor and
does not work operate after remote control operation connection LED 1
11.CAPACITOR -DC 310V is recharged Replace CAPACITOR

40 sec later after power input,


Outdoor unit sensor 5. sensor -is LG MV sensor value normal? -replace and check connection and
error (CH01,02,06) sensor part
LED1(blinking): Display normal micom condition
LED2, 3(On): Back-up for left/right compressor
Outdoor unit front 8.CN_DISP -check indoor unit front panel LED -reception PCB and connection part
panel reception defect operation reception PCB and connection part LED4 : reserved
and remote control - Wireless remote control and forced LED5(blinking) : Communicate with main
does not work operation switch operation LED6(On) : Reverse connection at sub unit
Indoor unit leakage 12.CN_DRAIN -DRAIN display AC 220V -replace PCB LED7(On) : Right compressor is in operation
3.CN_FLOAT -CH04 display or DRAIN operation - Replace DRAIN pump and check LED8(On) : Left compressor is in operation
connection status
CH03 and remote 6.CN_REMO -When remote control operate and when -remote control, indoor unit PCB check
control does not work indoor unit operation -eliminate noise and check
--intermittent CH03 occurrence automatic communication line connection status
ON/OFF check remote control SETTING

190 _LG Air Conditioners System Electrical Component Check_ 191


(a) Plus (b) Plus ȤȤ

Name Check point Name Check


Check points
Outdoor unit ඞ Dip switch Setting ඞ Loc.
PCB DIP
Display Outdoor unit
switch Value of main PCB
8 7 6 5 4 3 2 1

Basic Part
main display Value
PCB in (At the
outdoor moment that
unit power is
ON supplied)
1. Main unit

Troubleshooting
DIP RE Function Method / description

Guide for each


s/w SET

Error Code
1 X Cooling operation control No. 1 ON૟ push RED button 3 times for 3 sec.
૟ display 01, 0F by turns (#1 indoor unit OFF)
૟ Push BLACK button for 3 sec.
Trouble Shooting Guide Book

૟ display 01,0P by turns


૟ A few sec. later display 01, 0N by turns (#1 indoor unit ON)
૟ Push RED button for 1 sec.

Component Check
૟ display 02, 0F by turns (#2 indoor unit OFF)
૟ (go on…)

Electrical
1 O SAVE MODE No.1 ON ૟ RESET
/ Target high pressure down, target low pressure up

2 O CAPACITY UP No.2 ON ૟ RESET Initial setup


/ Target high pressure up, target low pressure down
There are 4 initial setup steps before running.
1,2 X Heating operation No.1, No.2 ON All DIP switch setting must be completed before initial setup.
control / Same process as cooling operation 1) Step 1 : factory setting value display

Solution Check
3 O Inverter compressor BACKUP No.3 ON ૟ RESET
Factory setting value is displayed in 7 segment on PCB for 24sec.
operation / while inverter compressor failure, operate more than indoor unit All dip switches must be set properly before step 1.
capacity (SINGLE:70K,SERIES:110K)

4 O Constant No.4 ON ૟ RESET


compressor 1 BACKUP operation / while constant compressor failure, operate more than indoor unit
capacity (SINGLE:70K,SERIES:110K)

3,4 O MAIN UNIT BACKUP No.3, No.4 ON ૟ RESET / when MAIN unit failure

Test functions
5 O Cooling operation LOCK No.5 ON ૟ RESET / locking cooling operation mode

6 O Heating operation LOCK No.6 ON ૟ RESET / locking heating operation mode

7 X Forced oil return operation No.7 ON ૟ Push BLACK button for 2 sec. ૟ display 01(Oil return)

2. Sub unit
DIP RE Function Method / description
s/w SET

3 O Constant compressor 1 BACKUP No.3 ON ૟ RESET


operation / while constant compressor1(left) failure,
operate more than indoor unit capacity (SINGLE:70K,SERIES:110K)
Example) 30HP, R410A
4 O Constant compressor 2 BACKUP No.4 ON ૟ RESET
operation
63 ‫ ݬ‬63 ‫ ݬ‬63 ‫ ݬ‬30 ‫ ݬ‬2 ‫ ݬ‬25
/ while constant compressor2(right) failure,
‫ ݬ‬41
operate more than indoor unit capacity (SINGLE:70K,SERIES:110K)

5 O SUB1(2UNIT) No.3 ON ૟ RESET / SUB1 recognition (2UNIT)

6 O SUB2(3UNIT) No. 4 ON ૟ RESET / SUB2 (3UNIT)

5,6 O SUB3(4UNIT) No.3, No.4 ON ૟ RESET / SUB3 recognition (4UNIT)

192 _LG Air Conditioners System Electrical Component Check_ 193


(b) Plus ȤȤ (b) Plus ȤȤ

Name Check point

Outdoor unit
PCB DIP ඞ Dip switch Setting ඞ
switch

Basic Part
1 2 3 4 5 6 7 8 9 10 11 12 13 14
ON
8 7 6 8 7 6

OFF

1. Main unit

Troubleshooting
Guide for each
Error Code
No. RESET Function Dip Switch

1 Standard Setting All Off

2 0 Short Pipe length No.1 ON


Trouble Shooting Guide Book

Target high pressure down, target low pressure up

3 0 Long pipe length No.2 ON

Component Check
Target high pressure Up, target low pressure down

Electrical
4 0 Longest Pipe length No.1, No.2 , ON

5 X Refrigerant Auto Charging No.1, No.2, No.7 ON

6 X Refrigerant checking No.1, No.2, No.7, No.14 ON

Solution Check
7 0 Forced Cooling operation No.5 ON

8 0 Forced Heating operation No.6 ON

9 0 Dry Contact No.5, No.6 ON

10 0 Snow No.8 ON

11 X Forced defrosting No.9 ON

12 0 Snow + Forced defrosting No.8 , No.9 ON

Test functions
13 0 Outdoor unit fan low static No.12 ON
pressure compensation

14 0 Outdoor unit fan low static No.13 ON


pressure compensation

15 0 Night low noise No.12, No.14 ON

16 X Pump down No.10 ON

17 X Forced Oil return No.7 ON

18 X Vacuum mode No.11, No.14 ON

194 _LG Air Conditioners System Electrical Component Check_ 195


(b) Plus ȤȤ (b) Plus ȤȤ

Name Check point Name Check location and method

Outdoor unit ඞ Dip switch Setting ඞ Inverter compressor drive current (When compressor is starting)
PCB DIP
- Driving current fluctuation of Inv. compressor should be less than 2A(Plus)
switch

Basic Part
1 2 3 4 5 6 7 8 9 10 11 12 13 14
ON
8 7 6 8 7 6

OFF

2. Settings of slave outdoor unit

Troubleshooting
Guide for each
Error Code
No. RESET Function Dip Switch Check current of U phase Check current of V phase Check current of W phase

1 0 Slave 1 No.5, No.7, ON


- Driving current fluctuation of Inv. compressor should be less than 2A(Plus II)
Trouble Shooting Guide Book

2 0 Slave 2 No.6, No.7, ON

3 0 Slave 3 No.5, No.6, No.7, ON

Component Check
Electrical
3. Settings of corresponding outdoor unit

No. RESET Function Dip Switch


Coil resistance of compressor (When power is not supplied)

Compressor
1 0 Inverter comp. back-up No.3 ON Check resistance of INV,constant compressor

Solution Check
INV, const. speed comp. resistance :INV COMP ˧ 1.2˟·10%(Plus),
2 0 Unit back-up No.4 ON
U-V: 1.16·7%ȳ, V-W: 1.19·7%ȳ, W-U: 1.21·7%ȳ(plus II)
3 X Pump out No.10, No.14, ON :Constant speed COMP : (U-V)1.96˟/(V-W)1.91˟/(U-W)1.99˟·10%)

Test functions
Resistance between U-W Resistance between V-W Resistance between U-V

Insulation resistance of compressor (when power is not supplied)

Check insulation resistance of constant compressor


(inverter compressor : a few 2༯˦,constant compressor : a few ༯˦)

196 _LG Air Conditioners System Electrical Component Check_ 197


(C) Plus, Plus ȤȤ

Name Check location and method

Check outdoor unit LEV

ྙ - ྛ : around 300˟ ྚ - ྜ : around 300˟ ྙ - ྜྷ : around 150˟


Trouble Shooting Guide Book

ྛ - ྜྷ : around 300˟ ྚ - ྞ : around 300˟ ྜ - ྞ : around 150˟

Measurement of outdoor unit LEV coil resistance

4. Solution Check
LEV

Outdoor unit main LEV Outdoor unit sub cooling LEV Indoor unit LEV

ྙ - ྛ : around 300˟ ྙ - ྛ : 104 · 6˟ ྙ - ྛ : around 300˟

ྚ - ྜ : around 300˟ ྚ - ྜ : 104 · 6˟ ྚ - ྜ : around 300˟

ྙ - ྜྷ or ྛ - ྜྷ : around 150˟ ྙ - ྞ or ྚ - ྞ or ྙ - ྜྷ or ྛ - ྜྷ : around 150˟

ྚ - ྜ or ྜ - ྞ : around 150˟ ྛ - ྞ or ྜ - ྞ : 52 · 3˟ ྚ - ྜ or ྜ - ྞ : around 150˟

198 _LG Air Conditioners System Solution Check_ 199


Central control Structure
A. Installation guide

Basic Part
3rd part 1. Multi-
Multi-V + Simple Central Controller
LonTalk/ BACnet
2. CAC(Single,Multi) + Simple Central Controller
BMS
Ethernet

Troubleshooting
(TCP/IP)

Guide for each


Gateway 504 505 4
3. Multi-
Multi-V + CAC + Simple Central Controller

Error Code
CNU AC Smart
Server SCC
LonWorks BACnet ACP D.C
4. Eco-
Eco-V + Simple Central Controller
Trouble Shooting Guide Book

EIA-485

Component Check
506 6
5. Multi-
Multi-V + ACP + Simple Central Controller

Electrical
Telemetering apparatus
PI485 Interface PDI
SGL Dry Gu|#frqwdfw
contact

UART 6. Multi-
Multi-V + CAC + ACP + Simple Central Controller
LGAP
LG’s A/C

Solution Check
Outdoor unit
7. Multi-
Multi-V + Eco-
Eco-V + CAC + ACP + Simple Central Controller
Indoor unit

Multi V
Remote
Multi MPS Single CAC Ventilator
8. Multi-
Multi-V + Eco-
Eco-V + AC Manager + ACP
controller

Test functions
200 _LG Air Conditioners System Solution Check_ 201
㶢 Multi-V+ Simple central controller. 1ea [ 1 Line wiring ] 㶢 Multi-V+ Simple central controller. 2ea [ 1 Line wiring ]

Rotary DIP PI485 Indoor unit Rotary DIP PI485 Indoor unit

Basic Part
switch switch Controller DIP switch Outdoor – Indoor unit connection address switch switch Controller DIP switch Outdoor – Indoor unit connection address
setting setting setting (*) setting setting setting setting (*) setting

[00] … [03] [00] … [03]


ODU ODU

Troubleshooting
Guide for each
Master Series 2

Error Code
[0] 1,2 ON Series 2 [04] … [07] [0] 1,2 ON [04] … [07]
& &
IDU IDU
Series 2 [09] … [0B] Series 2 [10] … [13]
Trouble Shooting Guide Book

No need [1] 2 ON Slave No need


[0C] … [0F] [14] … [1F]

Component Check
PI485 PI485

Electrical
Solution Check
(*): incase of using external PI485. See page 257 㶢 Multi-V+ Simple central controller. 3ea [ 1 Line wiring ]
ඟ Process
ྙ Indoor address Setting Rotary DIP PI485 Indoor unit
୔ must be not duplicated switch switch Controller DIP switch Outdoor – Indoor unit connection address
setting setting setting (*) setting
ྚ Install PI485, Wiring RS485 line(Bus Method)

Test functions
ྛ PI485 Dipswitch Setting
Power on [00] … [03]
୔ Check PI485 Red LED blinking. It must equal to number of connected I/U ODU
[0] 1,2 ON Master [04] … [07]
ÆIf different, Check outdoor Auto_addressing Series 2
ྜ Setting Rotary switch on Simple central controller. &
IDU
୔ same to the 1st digit of connected indoor unit address [10] … [13]
Series 2
ྜྷ Setting Dip switch on Simple central controller Slave
[1] 2 ON
Turn the power ON: No need [14] … [1F]
PI485
After 3 Minutes (Searching Time)
Simple central controller must recognize all indoors [20] … [23]
(you can check by pushing total On + Total Off + 13)
[2] 2 ON Slave
୔ If not recognize all indoors, repeat upper process [24] … [2F]

(*): incase of using external PI485. See page 257


202 _LG Air Conditioners System Solution Check_ 203
㶢 Multi-V+ Simple central controller. 3ea [ 2 Line wiring ] 㶢 CAC (Multi/ Single) + Simple central controller. 1ea

Rotary DIP PI485 Indoor unit Rotary DIP PI485 Indoor unit

Basic Part
switch switch Controller DIP switch Outdoor – Indoor unit connection address switch switch Controller DIP switch Outdoor – Indoor unit connection address
setting setting setting (*) setting setting setting setting setting

[00]
[00] … [03] [01]
[02]

Troubleshooting
ODU

Guide for each


Master

Error Code
[0] 1,2 ON Series 2 [04] … [07] [0] 1,2 ON
& PMNFP14A0, [03]
IDU
[10] … [13] [04]
Trouble Shooting Guide Book

Series 2
[05]
[1] 2 ON Slave [1,4,5 ON]
No need [14] … [1F]

Component Check
or
PI485 [06]

Electrical
[20] … [23] [2,4,5 ON]
(*)
[2] 1,2 ON Master Max. 16 indoor unit
[24] … [2F]

Solution Check
(*): incase of using external PI485. See page 257
(*) The DIP switch setting must follow to below table:

Test functions
204 _LG Air Conditioners System Solution Check_ 205
㶢 Multi V + CAC (Multi/ Single) + Simple central controller. 2ea 㶢 Ventilator + Simple central controller. 1ea

Rotary DIP PI485 Indoor unit Rotary DIP PI485 Indoor unit

Basic Part
switch switch Controller DIP switch Outdoor – Indoor unit connection address switch switch Controller DIP switch Outdoor – Indoor unit connection address
setting setting setting setting setting setting setting (*) setting

Multi V ODU [00] … [03]


[00]
Series 2

Troubleshooting
Guide for each
& PHNFP14A0

Error Code
Master [0] 1,3 ON
[0] 1,2 ON
Multi V IDU
[04]
Series 2
[04] … [07]
Trouble Shooting Guide Book

[3,4 ON]
No need
PI485
[09]
[1] 2 ON Slave

Component Check
[10]

Electrical
PMNFP14A0, [11] [0C]
[12]

[1,4,5 ON]
[13]
or
[14]

Solution Check
[15]
[2,4,5 ON]
ඟ Process
(*)
[16] ྙ Dipswitch setting on Eco-V Main PCB, Power On
ྚ Eco-V address Setting.
ྛ Install PI485, Wiring RS485 line (Bus Method)

Test functions
ྜ PI485 Dipswitch Setting
(*): incase of using external PI485. See page 257 Power on
(**) The DIP switch setting must follow to below table: ୔ Check PI485 Yellow LED blinking.
ྜྷ Setting Rotary switch on Simple C.C.
ྞ Setting Dip switch on Simple C.C. and Power on.
ྟ wait for 3 Minute (Searching Time)
(you can check by pushing total On + Total off + 13)

206 _LG Air Conditioners System Solution Check_ 207


㶢 Ventilator + Simple central controller. 2ea [1 line wiring] 㶢 Ventilator + Simple central controller. 2ea [2 line wiring]

Rotary DIP PI485 Indoor unit Rotary DIP PI485 Indoor unit

Basic Part
switch switch Controller DIP switch Outdoor – Indoor unit connection address switch switch Controller DIP switch Outdoor – Indoor unit connection address
setting setting setting (*) setting setting setting setting (*) setting

[00] [00]
PHNFP14A0

Troubleshooting
Guide for each
PHNFP14A0

Error Code
[0] 1,3 ON Master [0] 1,3 ON Master
[0F] [0F]
[3,4 ON]
Trouble Shooting Guide Book

[3,4 ON]
[10] [10]
[1] 3 ON Slave [1] 1,3 ON Master

Component Check
Electrical
[1F] [1F]

Solution Check
ඟ Process
ྙ Dipswitch setting on Eco-V Main PCB, Power On
ྚ Eco-V address Setting.
ྛ Install PI485, Wiring RS485 line (Bus Method)

Test functions
ྜ PI485 Dipswitch Setting
Power on
୔ Check PI485 Yellow LED blinking.
ྜྷ Setting Rotary switch on Simple C.C.
ྞ Setting Dip switch on Simple C.C. and Power on.
ྟ wait for 3 Minute (Searching Time)
(you can check by pushing total On + Total off + 13)

208 _LG Air Conditioners System Solution Check_ 209


㶢 Air conditioner + Ventilator 㶢 Multi-V+ ACP + Simple central controller. [ 1 Line wiring ]
+ Simple central controller [1 line wiring]
Rotary DIP PI485 Indoor unit Rotary DIP PI485 Indoor unit

Basic Part
switch switch Controller DIP switch Outdoor – Indoor unit connection address switch switch Controller DIP switch Outdoor – Indoor unit connection address
setting setting setting (*) setting setting setting setting (*) setting

[00] … [03] [00] … [03]


PMNFP14A0, ODU

Troubleshooting
Guide for each
PMNFP14A1 Series 2

Error Code
[0] 1,3 ON [04] … [07] [04] … [07]
&
IDU
[1,4,5 ON] Series 2 [10] … [13]
Trouble Shooting Guide Book

PHNFP14A0 [08]
[0] 2 ON Slave No need
[14] … [1F]

Component Check
PI485

Electrical
[0C]
[3,4 ON]

[1] 2 ON Slave

Solution Check
㶢 Air conditioner + Ventilator 㶢 Multi-V+ ACP + Simple central controller. [ 2 Line wiring ]
+ Simple central controller [2 line wiring]
Rotary DIP PI485 Indoor unit
Rotary DIP PI485 Indoor unit switch switch Controller DIP switch Outdoor – Indoor unit connection address
switch switch Controller DIP switch Outdoor – Indoor unit connection address setting setting setting (*) setting
setting setting setting (*) setting

Test functions
[00] … [03]
[00] … [03]
ODU
[0] 2 ON Slave Series 2 [04] … [07]
[0] 1,2 ON &
[04] … [07]
IDU
Series 2 [10] … [13]

No need
PI485 [14] … [1F]
PHNFP14A0 [00]
[0] 1,3 ON [1] 2 ON Slave

[0F]
[3,4 ON]

(*): incase of using external PI485. See page 257


210 _LG Air Conditioners System Solution Check_ 211
㶢 Multi-V + CAC + ACP + Simple central controller. [ 1 Line wiring ] 㶢 Multi-V + CAC + Vent + ACP + Simple central controller.
[ 1 Line wiring ]
PI485 Rotary DIP PI485 Indoor unit
Rotary DIP Indoor unit

Basic Part
switch switch Controller Outdoor – Indoor unit connection address switch switch Controller DIP switch Outdoor – Indoor unit connection address
DIP switch
setting setting setting setting setting setting (*) setting
setting (*)

ODU
Series 2 [00] … [03] PMNFP14A0, [00] … [03]
&

Troubleshooting
Guide for each
IDU

Error Code
[04] … [07] [04] … [07]
Series 2 [1,4,5 ON]
No need
PI485
or [08]
[09]
Trouble Shooting Guide Book

PMNFP14A0,
[2,4,5 ON] [0F]
[0] 2 ON Slave [0] 2 ON Slave
[10]

Component Check
(*)
[11] [10]
[1,4,5 ON]

Electrical
PHNFP14A0
[12]
or

[1] 2 ON Slave [13] [1] 3 ON Slave


[2,4,5 ON] [3,4 ON]
(*)

Solution Check
㶢 Multi-V+ CAC + ACP + Simple central controller. [ 2 Line wiring ] 㶢 Multi-V+ ACP + Simple central controller. [ 2 Line wiring ]

Rotary DIP PI485 Indoor unit Rotary DIP PI485 Indoor unit
switch switch Controller DIP switch Outdoor – Indoor unit connection address switch switch Controller DIP switch Outdoor – Indoor unit connection address
setting setting setting (*) setting setting setting setting (*) setting

Test functions
[00] PMNFP14A0,
[00]

[01] … [0F] [1,4,5 ON] [01] … [0F]


PMNFP14A0, or
[0] 2 ON Slave 2 ON Slave
[0]
[2,4,5 ON]
[1,4,5 ON]
[10] … [1E] (*)
or
[10] … [1E]
[2,4,5 ON] [1D] … [1F]
PHNFP14A0
(*) [1D] … [1F]
[1] 2 ON Slave
[1] 3 ON Slave

[3,4 ON]

(*): incase of using external PI485. See page 257


(*): incase of using external PI485. See page 257

212 _LG Air Conditioners System Solution Check_ 213


㶢 AC Manager system
Connect to LG Central controller (setting PDI in “SLAVE” mode)

Scene 1 Outdoor units are installed nearby each other

Basic Part
w–™›GX [_\G“•Œ

w–™›G[ ZÞ Z_W}

Troubleshooting
Guide for each
Error Code

wp[_\


Trouble Shooting Guide Book

Component Check
Electrical
~ˆ››G”Œ›Œ™ wkp
ju†v|{mhu
㶢 Power Distribution Indicator

Solution Check
Test functions
214 _LG Air Conditioners System Solution Check_ 215
Not connect to Central controller

zŠŒ•ŒGY j–••ŒŠ›Œ‹G•‹––™Gœ•›G—Œ™UGvœ›‹––™Gœ•›G“ŒššG›ˆ•GX]
B. Trouble shooting

Basic Part
OšŒ››•ŽGwkpGˆšG|•›P

Case A1: Several indoor unit error (242)


Case A2: all I/U of the same O/U error (242)
Case A3: all I/U of the same 485 line error (242)

Troubleshooting
Guide for each
ZÞ Z_W} … Case A4: indoor unit can’t be controlled by S.C.C but ACP

Error Code
Case B1: impossible to access ACP Web
Case B2: ACP access is not stable
Trouble Shooting Guide Book

p•T–œ›G‹––™GŠ–””U Case C1: Operation mode auto-change

Component Check

Lock function auto-release

Electrical
“•Œ

~ˆ››G”Œ›Œ™ wkp Case D1: some indoor acc. Pwr. is displayed = 0


Case D2: all indoor acc. Pwr. in one group are displayed = 0
Case D3: Value on ACP and PDI doesn’t match
zŠŒ•ŒGZ j–••ŒŠ›Œ‹G•‹––™Gœ•›G—Œ™UGvœ›‹––™Gœ•›G”–™ŒG›ˆ•GX] Case D4: Value on ACP and Watt meter doesn’t match

Solution Check
OšŒ››•ŽGwkpGˆšGtˆš›Œ™P Case E1: Ventilator communication error
Use PMNFP14A1 PI485 Gateway

Test functions
ZÞ Z_W} …

wtumwX[hX
tˆš›Œ™G⯜☐
p•T–œ›G‹––™GŠ–””U

“•Œ

㤸⥙⣽᷸ 㤸⥙䖐㐐ὤ

216 _LG Air Conditioners System Solution Check_ 217


Case A1: Several indoor unit error (242) Case A1: Several indoor unit error (242)
I. Phenomenon:
Indoor units display error (242), can not control by
simple central controller. ̰ Address wrong setting

Basic Part
ACP can not control a address duplicated indoor unit (20)

r
ro
Er

Troubleshooting
Guide for each
20 21 22 23

Error Code
Trouble Shooting Guide Book

10 11 12 20

r
r ro
E

Component Check
Electrical
II. Reason and Solving:

Indoor units

Solution Check
(242) error
20 24
address wrong setting Y
check and setting
(duplicate, not in-
address again
range)
N
Address re-setting (+ central controllers power reset)

Test functions
indoor unit power Y check power (220V)
supply (not plug-in,
and re-plug in
fuse blow)
N

indoor unit main PCB Y


change main PCB
failure

Outdoor unit Auto- Y Outdoor unit Auto-


addressing fault addressing

218 _LG Air Conditioners System Solution Check_ 219


Case A1: Several indoor unit error (242) Case A1: Several indoor unit error (242)

̰ Indoor main PCB power failure: ̰ Indoor main PCB failure:

Basic Part
Check if the power cord is not plugged in or Fuse is blown out A failure PCB doesn’t sound “Bip” when reset main power.
Check and replace with new one with proper P/No.
You need to set the indoor unit address and do Auto-addressing
on Outdoor unit again.
r
ro

Troubleshooting
Guide for each
Er r

Error Code
r ro
20 21 22 23 E
Trouble Shooting Guide Book

20 21 22 23

Component Check
10 11 12 24

Electrical
10 11 12 24

Solution Check
220V

power cord is not plugged

Test functions
Buzzer

Fuse blown out

220 _LG Air Conditioners System Solution Check_ 221


Case A1: Several indoor unit error (242)
Case A2: all I/U of the same O/U error (242)

̰ Outdoor unit auto-addressing failure: I. Phenomenon:


All I/U that connected to the same O/U display error

Basic Part
Check if the Auto-addressing function return correct number of (242), can not control by central controller.
indoor units.
Incase of incorrect, check the connection line between O/U and
I/U, and indoor unit main PCB.

Troubleshooting
Guide for each
Error Code
Do auto-addressing on this outdoor unit
Trouble Shooting Guide Book

r
ro
Er

Component Check
Electrical
20 21 22 23

10 11 12 24
Same Outdoor unit

Solution Check
Press the switch of the Display number of
outdoor unit (SW02V) connected indoor unit II. Reason and Solving:
for 5 seconds.
In this case, the reasons mostly come from PI485

Test functions
Indoor units
(242) error

Y PI485’s DIP switch


PI485 DIP switch
re-setting
wrong setting

Y
PI485 failure Change PI485

Numbers of indoor unit connection set whose N


addressing is completed are indicated for 30seconds PI485’s comm. cable Y
on 7-segment LED of the outdoor unit PCB. wiring failure re-wiring
(refer to data-book) (Bus_A, Bus_B)

222 _LG Air Conditioners System Solution Check_ 223


Case A2: all I/U of the same O/U error (242) Case A2: all I/U of the same O/U error (242)

̰ PI485 DIP switch wrong setting (*) ̰ PI485 failure (*)

Basic Part
The DIP switch wrong setting cause wrong communication The LED doesn’t blink at all (with power supplied)
between controller and indoor units. Æ replace with new one with proper type.
Æ correct and reset PI485 (press Reset button) (plz report to the QA team also)

Check this PI485’s DIP switch

Troubleshooting
Guide for each
Error Code
r
ro
Er
Trouble Shooting Guide Book

20 21 22 23

Component Check
Electrical
10 11 12 24

Reset button

Solution Check
PMNFP14A0,
PMNFP14A1

[1,4,5 ON] (*): incase of using external PI485. See page 245
Multi V, Plus
MPS inverter
PMNFP14A0(1)

Test functions
PMNFP14A0,

[2,4,5 ON]
Multi MPS (*)
PMNFP14A0(1)

LED2G(Yellow), LED3G(Orange)
Normal : LED blinks continuously

(*): incase of using external PI485. See page 245

224 _LG Air Conditioners System Solution Check_ 225


Case A2: all I/U of the same O/U error (242) Case A3: all I/U of the same 485 line error (242)

̰ 485 wiring failure: I. Phenomenon:


Indoor units display error (242), can’t be

Basic Part
Check if the connection to PI485 open or in bad condition. controlled by central controller.
Æ re-wiring

Check this connection

Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

r
ro
Er

Component Check
Electrical
20 21 22 23

10 11 12 24

Solution Check
II. Reason and Solving:

Test functions
Indoor units
(242) error

Wrong connection to Y
controller Re-wiring
(Bus_A, Bus_B)
N
Connection is open
Other Master device Y Set to Slave and re-set
exist ? system.

485 line short-circuit Y


In bad condition or open?
Change the line

226 _LG Air Conditioners System Solution Check_ 227


Case A3: all I/U of the same 485 line error (242) Case A3: all I/U of the same 485 line error (242)

̰ Wrong connection to central controller ̰ Other Master devices exist (Simple central controller)

Basic Part
when connect to central controller, Simple central controller must
RX LED always
bright be set as Slave.

ult

Troubleshooting
a

Guide for each


F

Error Code
22 r
ro
20 21 23
r
Trouble Shooting Guide Book

lE
Master Al

Component Check
10 11 12 2D

Electrical
TX ‫ ׳‬Bus_B
ult
RX ‫ ׳‬Bus_A Fa

Solution Check
a ult
F
DIP switch: 1st ON- Master 1st OFF- Slave

Test functions
+ reset power of all controllers

୔ Notice : Please reset the power after changing the Hardware setting.

Rewiring

228 _LG Air Conditioners System Solution Check_ 229


Case A3: all I/U of the same 485 line error (242) Case A4: indoor unit can’t be controlled by S.C.C
but ACP
̰ Other Master devices exist (Power Distribution Indicator) I. Phenomenon:
Indoor unit can’t be controlled by S.C.C but ACP

Basic Part
when connect to central controller, Power Distribution Indicator
must be set as Slave. II. Reason and Solving:
PI485 (of I/U 2D) doesn’t connect to the proper S.C.C
(Gr.2)
Æ Re-wiring

Troubleshooting
Guide for each
Error Code
22 r
ro
20 21 23
Indoor units can’t
r
lE
be controlled by

Al
Trouble Shooting Guide Book

S.C.C but ACP

10 11 12 2D

Component Check
Not physically Y
connected to proper Re-wiring

Electrical
S.C.C

Master Slave

Office

Solution Check
20 21 22 23

10 11 12 2D

Test functions
Restaurant

Office

20 21 22 23

10 11 12 2D

Restaurant

230 _LG Air Conditioners System Solution Check_ 231


Case B1: impossible to access ACP Web Case B1: impossible to access ACP Web

I. Phenomenon: ACP IP wrong setting


Can not access ACP web.

Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

w•ŽG›Œš›G

Component Check
un

Electrical
II. Reason and Solving: ̰ ACP IP re- setting

Solution Check
ACP IP address 192.168.2.200 192.168.1.200
Problem often comes from ACP IP setting or LAN PC IP address 192.168.1.212 192.168.1.212
cable.
[Before] [After]
Impossible
to access
ACP web

Test functions
Y
ACP’s IP address Re-setting and reboot
wrong setting ACP

ACP power supply Y


Plug-in or change
failure ?

LAN cable failure? Y


Change the line [ACP rebooting]
(cross/ direct/ 80m)

N [refer to manual]
MAC address not Y
Do registration
registered

232 _LG Air Conditioners System Solution Check_ 233


Case B1: impossible to access ACP Web Case B1: impossible to access ACP Web

Wrong LAN cable type cause connection failure. Not register ACP’s MAC address.

Basic Part
PC1 can’t access ACP
wjX
ÆRegister ACP’s MAC address to
nV~X
administrator.

Troubleshooting
Guide for each
Error Code
Hub X]\UX_]UXUY_
nV~GX]\UX_]UXUW
Trouble Shooting Guide Book

wjY
nV~Y

Component Check
Electrical
ACP oœ‰
X]\UX_]UYUY` X]\UX_]UYUZW
nV~GX]\UX_]UYUX nV~GX]\UX_]UYUW
thjaGŸŸŸGŸŸŸ ŸŸŸ

Solution Check
The cross cable should be within 80m length.

Test functions
234 _LG Air Conditioners System Solution Check_ 235
Case B2: ACP access is not stable Case B2: ACP access is not stable

Duplicated IP between ACP and other devices cause access


I. Phenomenon: instable.
ACP Web access is not stable (sometimes was

Basic Part
denied) or very slow.

X]\UX_]UYUY_

Troubleshooting
Guide for each
Error Code
zŠ––“Gshu

oœ‰
X]\UX_]UYUY`
Trouble Shooting Guide Book

ult
Fa
[Access is denied] [Access is slow]

Component Check
Electrical
ACP
X]\UX_]UYUY` X]\UX_]UYUZW
pwGˆ‹‹™ŒššG‹œ—“Šˆ›Œ

Solution Check
̰ ACP IP address re- setting
[Ping test to ACP]

II. Reason and Solving:

Test functions
ACP Web
access is
not stable

Y [refer to manual]
ACP’s IP address Re-setting and reboot
duplicated? ACP

ACP is located near Y


UPS or high voltage Move to other place
source ?
N
Y
Power supply failure? Change other one [ACP rebooting]

236 _LG Air Conditioners System Solution Check_ 237


Case B2: ACP access is not stable Case B2: ACP access is not stable

Duplicated IP check method: Instable access can caused by noise from other equipment.

Basic Part
̰ By high voltage source
1. ACP and PC is in same Router/Hub/Switching equipment

in DOS window oŽG–“›ˆŽŒG›™ˆ•š–™”Œ™

Troubleshooting
WU\”

Guide for each


c:\> arp –a [Enter]

Error Code
hjw
Trouble Shooting Guide Book

zŒ™Œ™G™––” tˆŠ•Œ™ G™––”
XU\”

Component Check
Electrical
&KHFNWR$&3ĜV 0$&$GGUHVV
,IWKLVQXPEHULVQRWWKH$&3ĜV 0$&DGGUHVV

Solution Check
t–™ŒG›ˆ•GYW”
Æ 7KHUHLVRWKHUGHYLFHXVLQJVDPH,3DGGUHVV GXSOLFDWH
̰ By UPS
Ȅ 1RWH$&3ĜV 0$&DGGUHVV&KHFN0HWKRG X”

ult
E\XVLQJ$&3ĜV /&' NH\<RXFDQVHOHFWLQIRUPDWLRQ
WKHQ\RXFDQVHHWKH0$&DGGUHVV
UHIHUWRWKH$&3PDQXDO F a

Test functions
2. ACP and PC is not in same Router/Hub/Switching equipment
‚hjw„ ‚|wz„
Î Request Network Manager about routing table, ARP table and
MAC address \”

‚hjw„ ‚|wz„

238 _LG Air Conditioners System Solution Check_ 239


Case C1: Operation mode auto-change Case C1: Operation mode auto-change
Lock function auto-release Lock function auto-release
I. Phenomenon: Not reset S.C.C power after setting DIP switch (to Slave) can cause
Indoor unit operation mode is sometimes auto- malfunction

Basic Part
changed (Cooling/ Heating Æ Fan, AI…)
Æ Always reset power of controller (ACP and S.C.C) after changing
system configuration.

Troubleshooting
Cooling Æ FAN

Guide for each


Error Code
20 21 22 23
Trouble Shooting Guide Book

Reset power. 10 11 12 2D

Component Check
Electrical
Cooling Æ AI

Reset

Solution Check
II. Reason and Solving:

Operation
auto-change

Test functions
[S.C.C rebooting] [ACP rebooting]
Not reset system after Y
changing S.C.C DIP Reset system power
switch
N

S.C.C adapter failure Y


Change new one
or incorrect

N
PI485’s CN_Dry Y
connector was Insert
inserted?
N
485 nodes is arranged Y
in Star topology Re-wiring
(serial)?

240 _LG Air Conditioners System Solution Check_ 241


Case C1: Operation mode auto-change Case C1: Operation mode auto-change
Lock function auto-release Lock function auto-release
One S.C.C unit need 9V, 300mA as standard power supply.
CN_Dry connector must be plugged into PI485 in order to keep
Lower or incorrect spec cause S.C.C malfunction.
Lock function working. (*)

Basic Part
Æ We recommend using adapter (as table below) instead of DC
power from PI485.
Cooling Æ FAN

Troubleshooting
Guide for each
Error Code
20 21 22 23
Cooling Æ FAN
Trouble Shooting Guide Book

20 21 22 23
10 11 12 2D

Component Check
Cooling Æ AI

Electrical
Adapter spec. checking 10 11 12 2D Is CN_Dry connector plugged-in?

Cooling Æ AI
CN_Dry
connector
plug-in

Solution Check
ult
Fa

Test functions
10V, 500mA adapter

d
en
S.C.C 1~4EA S.C.C 5~8EA
1.2A (9V) 2.5A (9V)
m m Note:
o
6708AQ0001B -
R ec Incase of new model PI485 (8pin DIP switch), turn the 5th switch ON

(*): incase of using external PI485. See page 245

242 _LG Air Conditioners System Solution Check_ 243


Case C1: Operation mode auto-change Case D1: some indoor acc. Pwr. is displayed = 0
Lock function auto-release
I. Phenomenon:
We recommend you arrange the wire as a connected serial of
Some indoor accumulated pwr. is displayed = 0
point-to-point 485 nodes (PI485 Gateway) before connecting to

Basic Part
(indoor unit under working normally)
Controller’s 485 port.
Star topology

Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

Component Check
Electrical
AC (13) acc pwr 0 kwh

Solution Check
Bus topology
Join

Test functions
II. Reason and Solving:
Eliminate reason caused by 242 error on I/ U
(refer to the previous part for solving first)

I/U acc. Pwr.


=0

Y
I/ U address wrong
Re-setting
d setting?

men
m
co
Re
244 _LG Air Conditioners System Solution Check_ 245
Case D1: some indoor acc. Pwr. is displayed = 0 Case D2: all indoor acc. Pwr. in one group are
displayed = 0
I. Phenomenon:
Setting range of indoor unit address on PDI is wrong. All indoor accumulated pwr. in same group are

Basic Part
displayed = 0
Æ PDI re-setting (refer manual) (indoor unit under working normally)

Troubleshooting
Guide for each
Error Code
20 21 22 23
Trouble Shooting Guide Book

10 11 12 13

Component Check
Pwr. = 0 kwh

Electrical
(Start) Æ (End) AC (10) acc pwr 0 kwh
(10) Æ (12) lt AC (11) acc pwr 0 kwh

au
AC (12) acc pwr 0 kwh

F AC (13) acc pwr 0 kwh

Solution Check
(Start) Æ (End)
(10) Æ (13)

Test functions
[ER-02 no pulse]

[Display only total acc. pwr]

246 _LG Air Conditioners System Solution Check_ 247


Case D2: all indoor acc. Pwr. in one group are Case D2: all indoor acc. Pwr. in one group are
displayed = 0 displayed = 0
Wrong connection with Watt meter cause malfunction.
II. Reason and Solving:

Basic Part
Eliminate reason caused by 242 error on I/ U
(refer to the previous part for solving first)

20 21 22 23

Troubleshooting
All I/U acc.

Guide for each


Error Code
Pwr. = 0

10 11 12 13
Y
Trouble Shooting Guide Book

Connection with watt


Re-wiring 0 kwh 0 kwh 0 kwh 0 kwh
meter wrong?

Component Check
N
Watt meter

Electrical
485 connection to Y
Re-wiring
ACP wrong?

CN_WATTMETER Check the connection (+, - )

Solution Check
The Start and End address of the power indicator refers to
the first and last address of the indoor unit group. ž›ŒG ž›Œ
‰“ˆŠ’ ‰“ˆŠ’
Ex) Indoor address "72", "73", "74", "75" ‫ݵ‬ ‚žˆ››G”Œ›Œ™„ ‚wkp„

ult
Start address: 72 End address: 75.
Fa

Test functions
ž›ŒG ž›Œ
‰“ˆŠ’ ‰“ˆŠ’
‚žˆ››G”Œ›Œ™„ ‚wkp„

248 _LG Air Conditioners System Solution Check_ 249


Case D2: all indoor acc. Pwr. in one group are Case D3: Value on ACP and PDI doesn’t match
displayed = 0
Wrong connection with ACP cause malfunction. I. Phenomenon:
Data on ACP and PDI is not same

Basic Part
II. Reason and Solving:
ACP with version lower than 3.30.3e has poor
function of data update from PDI
20 21 22 23

Troubleshooting
Guide for each
Æ up-grade ACP to 3.30.3e version

Error Code
Check the connection 10 11 12 13
Bus_A, Bus_B
Trouble Shooting Guide Book

0 kwh 0 kwh 0 kwh 0 kwh

Component Check
Electrical
CN_OUTFAN

iœš†h h

Solution Check
iœš†i i

a ult
F

Test functions
iœš†h h
iœš†i i

250 _LG Air Conditioners System Solution Check_ 251


Case D4: Value on ACP and Watt meter doesn’t match Case D4: Value on ACP and Watt meter doesn’t match

I. Phenomenon:
Total accumulated pwr. on ACP doesn’t II. Reason and Solving:

Basic Part
match to Watt meter. Setting of Watt meter in PDI is wrong.

Troubleshooting
Guide for each
Error Code
a ult
F
1 w/ pulse
Trouble Shooting Guide Book

Component Check
Electrical
2 W/ P

Solution Check
2 w/ pulse

Test functions
252 _LG Air Conditioners System Solution Check_ 253
Case E1: Ventilator communication error Case E1: Ventilator communication error

I. Phenomenon: PI485 DIP switch wrong setting


ACP can’t control ventilator.

Basic Part
Display error 485 cable wrong connection.

Troubleshooting
TX ˩ Bus_A LED02G, 03G

Guide for each


Error Code
RX ˩ Bus_B alternately blink
Trouble Shooting Guide Book

Component Check
Electrical
DIP switch
3,4 ON

Solution Check
II. Reason and Solving:

Vent. error
[Correct]

Test functions
address wrong setting Y
check and setting
(duplicate, not in-
address again
range)
N

PI485 DIP switch Y


Re-setting
wrong setting?

Main PCB DIP switch Y


Re-setting
wrong setting?

485 wrong Y
Re-wiring
connection?

254 _LG Air Conditioners System Solution Check_ 255


Case E1: Ventilator communication error Appendix:

I. Using external PI485 (PMNFP14A0/ PMNFP14A1) for Multi V System


Main PCB DIP switch wrong setting

Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book

Component Check
Electrical
0: apply PMNFP14A0,
X: not apply PMNFP14A1
PI485 setting method
For Multi V system

Solution Check
[1,4,5 ON]
1,4 ON
Example:
[Correct]
Only the combination Plus II Outdoor unit, Plus II indoor units and
Wide wired remote controller doesn’t require external PI485 in order to
Be sure to reset PCB after setting use Lock function (All/ Mode/ Fan/ Temp. lock)

II. Jumper (CN_Dry) or 5th switch of 8pin DIP switch PI485 setting in order

Test functions
to use Lock function

256 _LG Air Conditioners System Solution Check_ 257


Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
259 Solution Check_
Technical bulletin
C. Technical bulletin

258 _LG Air Conditioners System


Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
261 Solution Check_
Technical bulletin

260 _LG Air Conditioners System


Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
263 Solution Check_
Technical bulletin

262 _LG Air Conditioners System


Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
265 Solution Check_
264 _LG Air Conditioners System
Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
267 Solution Check_
Technical bulletin

266 _LG Air Conditioners System


Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
269 Solution Check_
Technical bulletin

268 _LG Air Conditioners System


Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
271 Solution Check_
Technical bulletin

270 _LG Air Conditioners System


Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
273 Solution Check_
Technical bulletin

272 _LG Air Conditioners System


Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
275 Solution Check_
Technical bulletin

274 _LG Air Conditioners System


Trouble Shooting Guide Book
Technical bulletin
Trouble Shooting Guide Book

5. Test functions
(Plus II, Sync II)

276 _LG Air Conditioners System Test functions_ 277


Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
279 Test functions_
(Sync II)

(Sync II)

278 _LG Air Conditioners System


Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
281 Test functions_
5.1 Sensor checking
5. Test functions

280 _LG Air Conditioners System


Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
283 Test functions_
5.2 Auto charging

282 _LG Air Conditioners System


Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
285 Test functions_
5.3 Auto refrigerant checking

284 _LG Air Conditioners System


Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
287 Test functions_
5.4 Pump down

286 _LG Air Conditioners System


Trouble Shooting Guide Book
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
289 Test functions_
288 _LG Air Conditioners System
5.5 Pump out
Trouble Shooting Guide Book
5.6 Vacuum mode 5.8 Pipe Searching (Sync, Sync II)
Automatic Pipe Searching

Confirm the IDU auto addressing setting

Basic Part
Turn off “No.1 of SW02M of the HRU”

Check the proper setting of


No. 2 & 3 of SW02M of the HRU
(Model of HRU & number of IDU)

Troubleshooting
Guide for each
Error Code
Reset the power of HRU PCB

Confirm the No. 5 DIP S/W of SW01B


Trouble Shooting Guide Book

of the ODU PCB


- Outdoor temp is over 15୅ : ON

Component Check
- Outdoor temp is below 15 ୅ : OFF

Electrical
In case of changing 5 DIP S/W of SW01B
of the ODU, reset power of the ODU main
PCB.

Wait for 3 minute

Solution Check
Press SW01V of the ODU main PCB
for 5 second

The number of HRU connected is displayed


at 7-seg of the ODU main PCB, and
5.7 Static pressure compensation mode then ’88’ is displayed

Test functions
This function secures the air flow rate of ODU, in case static pressure has been
Outdoor unit is operating
applied like using duct at fan discharge of ODU.
for 5~30 minutes.

After ODU stopped, the number of IDU Display error on the ODU PCB / HRU PCB
detected is displayed at 7-seg of the ODU - ODU PCB : HR unit No. ૟ Valve No.
main PCB for 1 minute (Example: H1 01)
- HRU PCB : ‘200’

Equal number of IDU No


and displayed one?
in terms of “piping” Check the piping among ODU, IDU, HRU

Yes

Completion of the auto pipe detection Retry auto pipe detection

290 _LG Air Conditioners System Test functions_ 291


5.8 Pipe Searching (Sync, Sync II) 5.8 Pipe Searching (Sync, Sync II)
Manual Pipe Searching

In case of auto pipe detection failure

Basic Part
Turn on “No.1 of SW02M of HR unit”

Reset the power of HRU PCB

Troubleshooting
Guide for each
Error Code
Enter central control address into each IDU
using its wired remote controller
Trouble Shooting Guide Book

Manually set the address of each valve

Component Check
corresponding with the central control

Electrical
address of IDU connected to the valve

Turn on No.5 of SW01B


of ODU PCB”

Solution Check
Reset the power of ODU PCB

Wait for about 5 minutes

Test functions
The number of IDU installed is displayed

No
Equal number of
“IDU and Displayed one”?

Yes

Turn off No.5 of SW01B Check the central control address of IDU
of ODU PCB and HRU

Completion of the manual pipe detection Retry manual pipe detection

292 _LG Air Conditioners System Test functions_ 293


Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
295 Test functions_
5.9 Manual setting example
5.8 Pipe Searching (Sync, Sync II)

294 _LG Air Conditioners System


Trouble Shooting Guide Book
Appendix #1 : Resistance Value of temperature sensor Appendix #1 : Resistance Value of temperature sensor

Pipe Temperature Sensor Pipe Temperature Sensor

Indoor unit Indoor unit


- Pipe Inlet Temp. - Pipe Inlet Temp.
- Pipe Outlet Temp. - Pipe Outlet Temp.

Outdoor unit Outdoor unit


- Suction Temp. - Suction Temp.
- Subcooling Circuit Inlet Temp. - Subcooling Circuit Inlet Temp.
- Subcooling Circuit Outlet Temp. - Subcooling Circuit Outlet Temp.
- Liquid Pipe Temp. - Liquid Pipe Temp.
- Hex Temp. - Hex Temp.

Air Temperature Sensor Air Temperature Sensor

- Indoor unit Air temp. - Indoor unit Air temp.


- Outdoor unit Air temp. - Outdoor unit Air temp.

Comp. Discharge Temperature Comp. Discharge Temperature


Sensor Sensor

- Inverter Comp. discharge temp. - Inverter Comp. discharge temp.


- Constant Comp. discharge temp. - Constant Comp. discharge temp.

* Refer: Resistance value maybe * Refer: Resistance value maybe


change according to temperature change according to temperature
of temp sensor, It shows according of temp sensor, It shows according
to criteria of current temperature to criteria of current temperature
(·5% margin) (·5% margin)
Appendix #1 : Resistance Value of temperature sensor

Pipe Temperature Sensor

Indoor unit
MEMO
- Pipe Inlet Temp.
- Pipe Outlet Temp.

Outdoor unit
- Suction Temp.
- Subcooling Circuit Inlet Temp.
- Subcooling Circuit Outlet Temp.
- Liquid Pipe Temp.
- Hex Temp.

Air Temperature Sensor

- Indoor unit Air temp.


- Outdoor unit Air temp.

Comp. Discharge Temperature


Sensor

- Inverter Comp. discharge temp.


- Constant Comp. discharge temp.

* Refer: Resistance value maybe


change according to temperature
of temp sensor, It shows according
to criteria of current temperature
(·5% margin)
MEMO MEMO
MEMO MEMO
Multi V Trouble Shooting Guide Book

Publisher LG Electronics Airconditioning Company, CAC Biz Team


Issued date December 2009
Adress LG Twin Towers, 20, Yeouido-dong, Yeongdeungpo-gu, Seoul 150-721, Korea
Web www.lgeaircon.com

All rights are reserved by LG Electronics.