Trouble Shooting
Guide Book
www.lgeaircon.com
EE0CVVT-01A
2010
Trouble Shooting
Guide Book
Trouble Shooting Guide Contents
Basic Part
PAGE 5
Search with Error Code number
1. Basic Part 5
1.1 Unit conversion (Energy / Pressure) 6
Troubleshooting
Guide for each
1.2 NOMENCLATURE 7
PAGE 43
Error Code
1.3 LGMV Guideline 13
1.4 Temperature vs pressure of refrigerant 14
1.5 P-h Diagram 15
1.6 Cycle Circuit & Sensor 16
1.7 Outdoor Wiring Diagram 30
Component Check
PAGE 172
Electrical
2. Troubleshooting Guide for each Error Code (Refer page 4) 43
Solution Check
3.3 How to check Multi V Space control box? 187
PAGE 199
3.4 How to check indoor unit PCB? 190
3.5 How to check other electric components 191
Test functions
PAGE 277
B- Trouble shooting 217
C- Technical bulletin 258
R: Reserved
Error Error Error Error Error Error Error
Page Page Page Page Page Page Page
code code code code code code code
01 45 41 102 81 121 102 161 105 201 168 241 170
02 45 42 104 82 122 102 162 102 202 168 242 170
03 45 43 104 83 R 123 105 163 102 203 168 243 170
04 47 44 105 84 124 105 164 105 204 169 244 170
05 49 45 105 85 125 148 165 105 205 168 245 170
06 50 46 105 86 132 126 148 166 148 206 168 246 170
07 50 47 105 87 133 127 148 167 148 207 168 247
08 R 48 105 88 128 104 168 148 208 169 248 R
09 51 49 107 89 129 104 169 95 209 168 249
10 52 50 108 90 130 105 170 98 210 168 250 171
11 53 51 109 91 131 R 171 83 211 168 251 171
12 52 112 92 132 105 172 107 212 169 252 171
13 53 113 93 133 102 173 155 213 168 253 171
R
14 54 114 94 134 102 174 155 214 168 254
15 55 95 135 105 175 155 215 168 255
16 R 56 96 136 105 176 155 216 169 256
R
17 57 97 137 148 177 155 217 168 257
18 58 98 138 148 178 218 168 258
1. Basic Part
R
19 59 116 99 139 148 179 219 168 259
20 60 117 100 134 140 79 180 156 220 169 260
21 65 61 R 101 134 141 104 181 157 221 168 261
22 73 62 118 102 134 142 135 182 158 222 168 262
23 77 63 103 134 143 95 183 223 168 263
R
24 79 64 104 135 144 98 184 224 169 264
25 83 65 119 105 137 145 95 185 225 168 265
26 84 66 R 106 139 146 98 186 226 168 266
27 R 67 120 107 145 147 83 187 227 168 267 R
R
28 85 68 108 R 148 107 188 228 169 268
R
29 86 69 109 147 149 83 189 229 168 269
30 70 122 110 147 150 107 190 230 168 270
R
31 71 123 111 147 151 151 191 231 168 271
32 88 72 R 112 R 152 88 192 232 169 272
33 88 73 124 113 148 153 88 193 159 233 273
34 95 74 126 114 148 154 79 194 159 234 274
35 98 75 127 115 148 155 114 195 235 275
36 76 128 116 149 156 135 196 236 R 276
37 77 129 117 149 157 104 197 R 237 277
R
38 78 130 118 105 158 104 198 238 278
39 79 131 119 R 159 105 199 239 279
40 100 80 R 120 105 160 R 200 160 240 170 280
Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
Component Check
Electrical
Solution Check
1.2.2 Multi V Plus Outdoor Unit (R410A)
Test functions
006 _LG Air Conditioners System Basic Part_ 007
1.2.3 Multi V Plus II Outdoor Unit (R410A) 1.2.5 Multi V Space Outdoor Unit (R410A)
Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
Component Check
Electrical
1.2.4 Multi V Plus II Outdoor Unit (R410A)
Solution Check
1.2.6 Multi V Space II Outdoor Unit (R410A)
Test functions
008 _LG Air Conditioners System Basic Part_ 009
1.2.7 Multi V Sync Outdoor Unit (R410A) 1.2.9 Multi V Mini Outdoor Unit (R410A)
Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
Component Check
Electrical
1.2.8 Multi V Sync II Outdoor Unit (R410A)
1.2.10 Multi V Water II Outdoor Unit (R410A)
Solution Check
Test functions
B: Inverter and Heat Recovery
Abnormal Abnormal
No Item Unit R22,407C 410A Cause & Check Point
condition condition
Basic Part
Overcharging(30Hz),Fan Lock
above 2200 above 3200
1 High Pressure kPa 1100~1800 2000 ~ 3000 Overchaning(25Hz:Plus II)
below 900 below 1800 Ref. Leakage or Ref. Shortage
Low Pressure above 600 above 1300 Overcharging
2 kPa 300~500 600 ~ 1000
(Cooling) below 250 below 400 Ref. Leakage or Ref. Shortage
above 1000 above 1000 Ref. Leakage or Ref. Shortage
3 Indoor LEV Pulse 200~600 200~600
below 200 below 200 Overcharging
4 Outdoor LEV Pulse 1944 - 1344 - Full Open
Troubleshooting
Guide for each
Indoor pipe Overcharging
Error Code
5 ఁ above 0ఁ below -1ఁ above 0ఁ below -1ఁ
[Outlet-inlet] LEV fault
Indoor pipe Ref. Leakage,
6 ఁ 8ఁ~15ఁ above 17ఁ 6ఁ~15ఁ above 17ఁ
Inlet,Outlet Indoor Path. Clogging
Overcharging
High Pressure above 2300 above 3300
Trouble Shooting Guide Book
Component Check
below 120 below 120 Ref. Leakage or Ref. Shortage
Electrical
300~1600 below 200 below 200 Overcharging
10 Outdoor LEV ఁ 200~800
(100~400) above 1800 above 1000 Ref. Leakage or Ref. Shortage
Discharge pipe - Overcharging
11 ఁ above 15ఁ below 15ఁ above 17ఁ below 17ఁ
Tb(condense) LEV fault
above 110ఁ above 110ఁ Ref. Leakage or Ref. Shortage
12 Comp. Discharge T. ఁ 60~100 60~100
below 50ఁ below 50ఁ LEV fault
Suction above 0.5ఁ below 0ఁ below 0ఁ Liquid compression, Overcharging
Solution Check
13 above 0.5ఁ
1.2.12 Multi V Plus Outdoor Unit (R22)
ఁ
Superheat above 7ఁ above 7ఁ Ref. Leakage or Ref. Shortage
above 380V Below 320V Inv. PCB fault,
14 DC Link voltage(Plus II) V
Above 700V Voltage sensor fault
Test functions
- The pressure is relative value.
- The operation ratio of indoor unit is not less than 80% and the value of above table is measured at stable state with LGMV
- The value of above table is not absolute and can be changed according to operation status or installation environment
- The causes of above table are representative and another cause also can exist.
Basic Part
kPa = kgf/cm2 X 101.97
R-22 R-407C
Relative ۀۑۄۏڼۇۀڭ
Temp. ډۋۈۀگ Relative pressure(kPaG) Temp.()
Pressure ۀۍېێێۀۍۋ
ڿۀۏڼۍېۏڼڮ ڿۀۏڼۍېۏڼڮ ڿۀۏڼۍېۏڼڮ
kPaG ێڼڢٻڿۀۏڼۍېۏڼڮ kPaG
ڿۄېیۄڧ ڿۄېیۄڧ ێڼڢ
-30 62.56 -30 86.75 37.87 50 -35.26 -28.35
Troubleshooting
-25 100.11 -25 129.50 72.67 100 -28.52 -21.75
Component Check
15 687.99 15 797.30 654.12 750 13.09 18.85
20 808.69 20 934.41 778.51 850 16.94 22.59
Electrical
25 942.59 25 1086.55 917.87 1000 22.17 27.67
30 1090.55 30 1254.72 1073.36 1150 26.91 32.24
35 1253.46 35 1439.97 1246.28 1300 31.23 36.42
40 1432.25 40 1643.37 1437.87 1550 31.23 36.42
45 1627.89 45 1866.04 1649.67 1750 42.42 47.18
50 1841.36 50 2109.14 1883.24 2000 47.78 52.30
55 2073.75 55 2373.87 2140.33 2250 52.69 56.97
Solution Check
60 2326.16 60 2661.51 2422.98 2550 58.09 62.08
65 2599.83 65 2973.36 2733.60 2850 63.05 66.74
70 2896.07 70 3310.77 3075.22 3200 68.38 71.69
R410A
R-410A
Relative
Temp. Relative pressure(kPaG) Temp.()
pressure
Saturated Saturated Saturated
Saturated Gas kPaG
Liquid Liquid Gas
Test functions
-30 169.62 168.91 170 -30.09 -30.02
-25 229.70 228.81 230 -25.08 -25.01
-20 299.57 298.46 300 -20.06 -19.99
-15 380.23 378.87 380 -15.09 -15.01
-10 472.75 471.09 470 -10.21 -10.12
-5 578.21 576.21 580 -4.98 -4.89
0 697.76 695.38 700 0.04 0.13
5 832.60 829.77 830 4.86 4.96
10 983.94 980.63 980 9.84 9.94
15 1153.09 1149.25 1150 14.88 14.98
20 1341.39 1336.98 1350 20.18 20.29
25 1550.25 1545.26 1550 24.96 25.08
30 1781.19 1775.59 1800 30.36 30.47
35 2035.78 2029.59 2000 34.30 34.42
40 2315.76 2309.03 2300 39.71 39.82
45 2623.00 2615.82 2600 44.62 44.73
50 2959.61 2952.13 2950 49.84 49.95
55 3328.02 3320.49 3400 55.91 56.01
60 3731.18 3724.00 3700 59.61 59.70
65 4173.11 4166.98 4200 65.28 65.34
70 4746.09 4706.31 4700 70.17 70.17
Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
Component Check
Electrical
Solution Check
Test functions
016 _LG Air Conditioners System Basic Part_ 017
1.6.1.3 Main Outdoor Unit (Plus 8~14HP, Plus II 10~16HP) 1.6.1.4 Sub Outdoor Unit (Plus 8/10/12/14 HP)
Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
Component Check
Electrical
Solution Check
Test functions
018 _LG Air Conditioners System Basic Part_ 019
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
021 Basic Part_
1.6.2.2 Heating Mode
1.6.2 Multi V Sync, Sync II
Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
Component Check
Electrical
Solution Check
Test functions
022 _LG Air Conditioners System Basic Part_ 023
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
025 Basic Part_
1.6.4 Multi V Space II (8, 10HP cooling only)
1.6.3 Multi V Space (10HP)
Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
Component Check
Electrical
Solution Check
Test functions
026 _LG Air Conditioners System Basic Part_ 027
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
029 Basic Part_
1.6.8 Multi V Water II H/P (20HP)
1.6.7 Multi V Water II H/P (10HP)
Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
Component Check
Electrical
Solution Check
Test functions
030 _LG Air Conditioners System Basic Part_ 031
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
033 Basic Part_
1.7.1.4 Multi V Plus II 10,12,14,16HP(UW1)
1.7.1.3 Multi V Plus II 8HP(UW1)
2. Troubleshooting
Guide for each
Error Code*
* Includede model :
Multi V Plus, Sync, Sync II, Plus II (Tropical), Water
042 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 043
Error code Error Contents Meaning Main Causes
[Cautions when measuring voltage and current of inverter power circuit] 01 Indoor unit air sensor error
Measuring values may differ depending on measuring tools and measuring circuits since voltage, 1. Indoor unit PCB wrong connection
Indoor unit sensor is
02 Indoor unit pipe inlet sensor error 2. Indoor unit PCB failure
current in the power supply or output side of the inverter has no since waveform. open/short
3. Sensor problem (main reason)
Especially, output voltage changes when output voltage of the inverter has a pattern of pulse wave. 06 Indoor unit pipe outlet sensor error
In addition, measuring values appear largely differently depending on measuring tools.
1) If using a movable tester when checking that output voltage of the inverter is constant (when Error diagnosis and countermeasure flow chart
Basic Part
comparing relative voltage between lines), always use an analog tester. Especially exercise particular
caution if the output frequency of the inverter is low, when using a movable tester, where change of
measured voltage values is large between other lines, when virtually same values appear actually or
Is sensor properly No
where there is danger to determine that failure of the inverter occurred. Connect properly to PCB
connected to PCB?
2) You can use rectification voltmeter ( ) if using commercial frequency tester when measuring
output values of the inverter (when measuring absolute values). Accurate measuring values cannot
Yes
be obtained with a general movable tester (For analog and digital mode).
Troubleshooting
Guide for each
Error Code
Is the resistance value No
Change the sensor
of sensor normal?*
Yes
Trouble Shooting Guide Book
Component Check
Electrical
* In case the value is more than 100 ༮ (open) or less than 100 ȳ(short), Error occurs
Solution Check
CN-ROOM : Indoor air temp sensor
Test functions
Measure the resistance of outlet pipe temp sensor.
044 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 045
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes
Error diagnosis and countermeasure flow chart Error diagnosis and countermeasure flow chart
Basic Part
Does the error happens No Is the drain pan filled
Replace cabled remote No Is Float switch short No
again if the remote half with condensate
controller On measuring its Replace float switch
controller is replaced?* water? (half level of
resistance?
float switch)*
Troubleshooting
Yes
Error Code
No Replace Indoor PCB or
Does the error occurred reconnect the connector
Check connection &
when the cable of remote
transmission cable **
controller is replaced?
Trouble Shooting Guide Book
Component Check
Yes Yes
Replace indoor unit PCB ***
Electrical
Replace Drain Pump
* If there is no remote controller to replace : Use another unit’s remote controller doing well
** Check cable : Contact failure of connected portion or extension of cable are main cause No
Check any surrounded noise ( check the distance with main power cable) Drain pump blocked by Check the drain head height
˧ make safe distance from the devices generate electromagnetic wave foreign particles? and slope***
*** After replacing indoor unit PCB, do Auto Addressing & input unit’s address if connected to central controller.
(All the indoor units connected should be turned on before Auto Addressing
Solution Check
Yes
Checking float
switch
Remove it & clean the pump (Low position short 0 ohm )
Test functions
CN-REMO : Remote controller connection
float
Checking transmission cable connection status
Condensate water
046 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 047
Error code Error Contents Meaning Main Causes
Basic Part
float Error diagnosis and countermeasure flow chart
Troubleshooting
after auto addressing? transmission cable of indoor
Component Check
Float switch connector Yes Replace main PCB fuse after
Yes checking
Electrical
Check the insulation of inverter
No / constant compressor and then
Is main circuit breaker off? replace it
Float switch Housing (CN-FLOAT)
Yes Replace after capacity of
main circuit breaker?
Bad connection of power supply cable
Solution Check
If nothing goes wrong,
Turn on main circuit breaker
Main power supply problem
Check if the
transmission
cable is properly No
Re connect transmission cable
connected
to indoor / outdoor
terminal block?*
[***]Standard of drain pipe head height / slope Yes Outdoor PCB fault
Test functions
Replace after checking
MAX 450
* If the DC voltage between transmission terminal A, B ** If the DC voltage between transmission terminal A, B
of outdoor unit is fluctuate within (-9V~+9V) then of indoor unit is fluctuate within (-9V~+9V) then
transmission from indoor unit is normal transmission from outdoor unit is normal
048 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 049
Error Code Error Contents Meaning Main Causes Error Code Error Contents Meaning Main Causes
Indoor unit outlet pipe Indoor unit outlet pipe temperature Problem in EEPROM inside 1.Error developed in transmission between the micro-
06 Refer to CH02 Indoor unit EEPROM
temperature sensor error sensor open or short 09 Indoor PCB ASS’Y ⇨ processor and the EEPROM on the surface of the PCB.
error
EEPROM 2.ERROR due to the EEPROM damage
Basic Part
same mode
earlier one.
3. Wrong setting of wired remote Error diagnosis and countermeasure flow chart
controller or remote controller fault*
- Replace the indoor unit PCB, and then make sure to do Auto addressing and input the address of central control
Troubleshooting
Guide for each
Is error code
Is operation mode of No
Error Code
No disappeared
outdoor & Indoor units Replace Indoor PCB****
after set operation
same?
mode same?***
Yes Yes
Trouble Shooting Guide Book
END
Component Check
Adjust outdoor main PCB ሲ Wired remote controller
dip switch setting **
Electrical
Solution Check
* Check mode select setting of wired remote controller.
** Outdoor main PCB dip switch no.5 (Cooling) or no.6 (heating) is in On, different mode operation error
may be occurred because the operation mode is fixed by dip switch setting.
Test functions
*** Dissolution method CH07 with remote controller
1) Error removal method : Turn off remote controller by pressing the On/Off button on the cabled remote controller.
The error code will be removed automatically after a few seconds.
With cableless remote controller: Turn off indoor unit, and turn on with the other operation
mode the error will disappeared
2) Immediately change the operation mode after the pressing the On/Off button .
The same operation mode as in the indoor unit started at first other than the defective unit mode (heating /cooling)
**** After replacing the indoor unit PCB, it should be done to do Auto addressing and input the address of central control
050 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 051
Error Code Error Contents Meaning Main Causes Error Code Error Contents Meaning Main Causes
Basic Part
Error diagnosis and countermeasure flow chart
Troubleshooting
Guide for each
Error Code
Is fan motor No
Replace indoor unit fan motor
normal?*
END
Yes
Trouble Shooting Guide Book
Component Check
Electrical
* It is normal when check hall sensor of indoor fan motor as shown below
Solution Check
hundreds kȳ hundreds kȳ
hundreds kȳ hundreds kȳ
Test functions
<Checking connection state of fan motor connector>
** Replace the indoor unit PCB, and then make sure to do Auto addressing and input the address of central control
(Notice: The connection of motor connector to PCB should be done under no power supplying to PCB)
052 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 053
- Compressor checking - Fan checking
Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
wGppSGz GppGaG
Component Check
wGaG
Electrical
*table #1
Solution Check
Test functions
*table #1
Multi B Plus II / Sync II / Multi V MINI Multi V MINI
Multi V Plus/Sync
Water II (1Ȱ) (3Ȱ)
054 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 055
- EEV - EEV
Basic Part
Q
PCB connector
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
Component Check
Electrical
<EEV wiring (Outdoor unit)>
Solution Check
Outdoor unit main LEV Outdoor unit sub cooling LEV Indoor unit LEV
Test functions
* : For this checking, you should make LED circuit by yourself
056 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 057
Troubleshooting Electrical
Basic Part Guide for each Component Check Solution Check Test functions
Error Code
059 Troubleshooting Guide for each Error Code_
- Inverter Compressor’s IPM
Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
Component Check
Electrical
<1 fan UY chassis)>
Solution Check
Test functions
<2 fan system(UW, UW1 chassis)>
060 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 061
- Capacitors and resistor - Replacement procedure of the compressor(Plus II)
Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
Component Check
Electrical
Solution Check
Test functions
062 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 063
Error Code Error Contents Meaning Main Causes
- Replacement procedure of the compressor(Plus II) Plus :21
1. Over current detection at the inverter
Plus II:
compressor (U,V.W)
211,212,213,214
2. IPM overheating.
3. Insulation damage of the compressor
S IPM fault of inverter Defective inverter compressor,
N1 Right / compressor motor damage
Inverter element (IPM) defect
P 21 Comp. compressor 4. Low input voltage at the outdoor
A 5. Inverter compressor terminal disconnected
Basic Part
C or loose.
E N2 Left
6. Inverter PCB / IPM PCB defect
21 Comp.
Troubleshooting
Guide for each
Error Code
78ȳ · 89ȳ · 79ȳ ·
Trouble Shooting Guide Book
Component Check
Electrical
Solution Check
Test functions
064 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 065
Point Checking Part Check
(Function) points
INV - Deviation between phases should be less than 2A.
INV
Plus
Comp. 2. Power & 3. High pressure 4. DC-Link 6. transmission 5. Checking circuit
Running COMP start-relay switch & sensing & circuit to main for reverse phase
Current PCB drive circuit power-relay display circuit PCB of input power
drive circuit
(INV
(COMP COMP
Basic Part
start) part)
(plus)
writing
Troubleshooting
Guide for each
connector
Error Code
1. MICOM
circuit
Trouble Shooting Guide Book
Coil resistance INV, const. speed comp. resistance :INV COMP ˧ 1.2˟·10%(Plus/Sync), 8. CT sensing
(No power) U-V: 1.16·7%ȳ, V-W: 1.19·7%ȳ, W-U: 1.21·7%ȳ(plus II/SyncII/Space II) MINI model : see page 00 circuit
Constant speed COMP : (U-V)1.96˟/(V-W)1.91˟/(U-W)1.99˟·10%)
Component Check
Electrical
9. PWM driving
signal output
circuit
U-W phases resistance V-W phase resistance U-V phase resistance No power 2.Power -Input voltage should be 220V. - Check & replace fuse(3.15A),
Solution Check
at PCB (when power is supplied) T-N voltage (220V)
Insulation -Input resistance should be more than a few ༮ - If resistance value is
resistance Insulation resistance : INV COMP ˧ above 2༯, const. comp : above ༯ (when power is not supplied) 0~100˟ ,
(No power) replace PCB
No transmission 6.Transmiss -Yellow LED should blink. - Check yellow LED blinks or
ion circuit not
to main - When is OFF, check
PCB transmission
Test functions
with main PCB and replace
Comp. connector Comp. conector Cooling fan connector Cooling fan operation
(Plus II)
Inverter compressor Red LED -When red LED blinks. -Check error code displayed at
PCB Error Error displays about inverter compressor PCB main PCB
IPM bolt connecting
066 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 067
Part Part
Check point Check
(Function) (Function) How to check? Counter-measure
points
Basic Part
(Plus)
(Plus)
Troubleshooting
Guide for each
terminal of capacitor
Error Code
DC charging - Charged voltage of between terminals of capacitor - Check input voltage
voltage (= between IPM P-N terminal = DC link terminals) and
(When power is should be more than 450V replace capacitor
supplied) (At the moment of inverter compressor start)
Trouble Shooting Guide Book
Component Check
Magnet Magnet switch -When check resistance of 1st coil of magnet switch, -In case resistance is
N-U :DIODE(0.4V) N-V :DIODE(0.4V) N-W :DIODE(0.4V)
Switch 1st coil resistance should be 0.47 ༮ ˳ or 0 ˟,
Electrical
resistance(a few ༯) resistance(a few ༯) resistance(a few ༯)
(When power is not supplied) Replace Magnet
(Plus) switch
-When magnet switch is on, voltage should be 220V
Sub PCB (When power is not supplied) -When voltage is not
220V, magnet switch
is melt down
- Replace magnet
Solution Check
switch
Test functions
Heat sink ** check point of 1st coil of magnet switch
cooling fan
Magnet switch - While pressing green button of magnet switch, -Replace magnet
(Plus) connection Voltage of each connectors should be 0V or switch
check Resistance should be 0~1˟
(In case power (Warning: power should not be supplied)
is not supplied)
068 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 069
Part Check Part
(Function)
Check point
points (Function)
INV 1. Power &
5. Port from 6. Port from
COMP start-relay 2.220V
3. P port 4. N port Diode Reactor Check voltage
drive circuit connector IPM
PCB & resistance of
(INV each phases
(CH21, (When power
- - -
COMP
Basic Part
part)
CH22) is not supplied) + + +
+ + +
U terminal
Troubleshooting
Guide for each
Error Code
7. On-board
V terminal writing connector
- - -
8. CT sensing circuit
Trouble Shooting Guide Book
9.Power relay
N-U :28kȳ·10% N-V :28kȳ·10% N-W : 28kȳ·10%
W terminal Reverse: N-U :Open N-V :Open N-W : Open
Component Check
10.Comm port
Electrical
& LED Check power
Heat sink supplay and
12. PWM LED 11. PWM driving signal output circuit
cooling fan operation
status
Solution Check
-Input resistance should be more than a few ༮ - If resistance value is
(when power is not supplied) 0~100˟ ,
replace PCB
Test functions
No transmission 10.Transmi -LEDs should blink. - Check LED blinks or not
(Fan, Main PCB) ssion circuit - When is OFF, check
to main, transmission
fan PCB with main, fan PCB
Inverter compressor 12. PWM -When red LED is on. -Check error code displayed at
PCB Error LED PWM is normal main PCB
070 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 071
Part Check Error code Error Contents Meaning Main Causes
How to check? Counter-measure
(Function) points
Plus:22 1. Compressor damage
Capacitor DC charging - Charged voltage of between terminals of capacitor - Check input voltage Plus II: 2. Current sensing sensor (CT) damage
and replace capacitor 221,222,223,224 3. Low input voltage
(To charge DC voltage (= between IPM P-N terminal = DC link terminals)
The current flowing at the CT 4. compressor terminal is disconnected or loose
voltage for (When power is should be more than 450V Over current of
N1 Right sensing circuit is more than the 5. Abnormality at the outdoor / indoor unit fan
inverter S inverter
supplied) (At the moment of inverter compressor start) 22 Comp. allowable maximum value of the 6. Cover or clogging
compressor) P compressor
A current (Outdoor unit covering during cooling mode
Basic Part
C / Filter clogged at the indoor during heating
N2 Left
(Plus II) mode )
E 22 Comp.
7. Defective inverter PCB/IPM PCB
Troubleshooting
* Check values at both
Magnet Magnet switch When magnet switch is on, output voltage should be When output voltage is
Switch 380V (Running) not 380V, Replace PCB
Trouble Shooting Guide Book
(Plus II)
O|T}GaGXUX]ȳ · ^LGVG}T~GaGXUX`ȳ · ^LGV|T~GaGXUYXȳ · ^LP
Component Check
Electrical
Solution Check
Test functions
072 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 073
Part Check Part Check
(Function) points How to check? Counter-measure (Function) points
INV PCB
T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within Standard·10% -Check supply power
and connection (Plus) * Measure the CT current with clamp meter -Multi V SPACE : U(+), U(-), V(+), V(-)
(Terminal - Voltage of 1ɐ(R-N,S-N,T-N) should be within
condition The current difference among
Block, Input 220V·10%. * Multi V PLUS
- Multi / Sync
V PLUS / Sync : R phase phases is less than 0.5A ·10%
power) - Voltage fluctuation should be within 10V
- While stand-by and in operation,
Basic Part
Voltage drop should be within 10V
Troubleshooting
Guide for each
Error Code
Checking points of 3ɐ(R-S) Checking points of 1ɐ(R-N)
Check ȳ - Resistance of R-S,S-T,R-T,R-N,S-N should be -Check short or not of
(In case power more than a few ༮ Control box (Noise filter,
PCB, cables)
Trouble Shooting Guide Book
Component Check
FUSE Check - Voltage of fuse should be within 0~1V -In case of 220V,
disconnection of
Electrical
(Protect over- Fuse is disconnected.
loaded FUSE Replace FUSE
current) (when power is
supplied)
(plus)
3ɐ DIODE
Solution Check
Checking points of R ɐ fuse (Plus)
Check - Resistance of fuse should be within 0~1˟ -In case resistance is ˳,
disconnection of Fuse is disconnected.
FUSE Replace FUSE
(when power is
not supplied)
Nose filter Check voltage -Voltage of each connector (R-R,S-S,T-T) should - In case of 220V
(Noise emit & (When power is be within 0~40V It is disconnected
protect) supplied) Replace noise filter
(Plus) (Plus II)
Test functions
P-U :DIODE(0.4V) P-V :DIODE(0.4V) P-W :DIODE(0.4V)
resistance(a few ༯) resistance(a few ༯) resistance(a few ༯)
074 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 075
Part Check Error Code Error Contents Meaning Main Causes
(Function) points
23(plus)
INV PCB 23(1~4,Plus II)
* Measure the CT current with clamp meter 1. Looseness of DC link terminal
(Plus II) DC voltage charging for 2. Damage in starting relay
S N1 Right Problem in DC charging voltage
*Current < 25A inverter compressor driving 3. Capacitor damage
P 23 Comp. after starting relay turned on
A defect 4. Defective sensing circuit of the
C N2 Left inverter PCB
Basic Part
E 23 Comp.
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
Component Check
Electrical
3ɐ DIODE * After indoor unit turned on and the compressor is not operated,
(Plus II) just before magnetic switch is turned on
the voltage between the 2 terminal as below is more than 270V
Solution Check
Plus / Sync Plus II
Test functions
Part Check
How to check? Counter-measure
(Function) points
076 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 077
Part Check Error Code Error Contents Meaning Main Causes
How to check? Counter-measure
(Function) points
24(Plus Main) 1. High pressure switch defect
T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within 380·10% -Check supply power and 24(1~4,Plus II) 2. Fan defect of indoor unit or outdoor unit
(Terminal - Voltage of 1ɐ(R-N,S-N,T-N) should be within connection condition 3. Check valve of compressor clogged
S N1 Right 4. Pipe distortion due to the pipe damage
Block, Input 220·10%.
P 24 Comp. 5. Refrigerant overcharge
power) - Voltage fluctuation should be within 10V A Excessive rise of Compressor off due to 6. LEV defect at the indoor or outdoor unit .
- While stand-by and in operation, C N2 Left discharge pressure in the high pressure 7. Covering or clogging
Basic Part
Voltage drop should be within 10V. E 24 Comp. outdoor compressor switch in outdoor unit (Outdoor covering during the cooling mode /
Indoor unit filter clogging during the heating mode)
(plus) 8. SVC valve clogging
109 (Sub1) 9. Outdoor PCB defect
140 (Sub2) 10. HR unit valve coil defect(Multi V Sync)
154 (Sub3) 11. HR unit PCB defect(Multi V Sync)
Troubleshooting
Guide for each
Checking points of 3ɐ(R-S) Checking points of 1ɐ(R-N)
Error Code
Check ȳ - Resistance of R-S,S-T,R-T,R-N,S-N should be -Check short or not of
(In case power more than a few ༮ Control box (Noise filter, Is high pressure switch
No
PCB, cables) connector connected Connect securely
is not supplied)
to PCB?*
Trouble Shooting Guide Book
Component Check
FUSE Check -Voltage of fuse should be within 0~1V -In case of 220V,
Is high pressure switch No No
(Protect over- disconnection of Fuse is disconnected. Is high pressure switch
connector short Replace high pressure switch
Electrical
loaded FUSE Replace FUSE terminal short?***
during off time?**
current) (when power is
(plus) supplied) Yes
Yes
Replace connecting cable
Solution Check
Is SVC valve open? Open SVC valve
Check -Resistance of fuse should be within 0~1˟ -In case resistance is ˳,
disconnection of Fuse is disconnected. Yes
FUSE Replace FUSE
(when power is No
not supplied) Is this error appeared Re-check momentary
again after reset? problem or not
Nose filter Check voltage -Voltage (R-R,S-S,T-T) < 0~10V - In case of 220V
Yes
(Noise emit & (When power is If voltage is higer than 10~40V, check resistance It is disconnected
protect)
Test functions
Supplied) (Plus) (Plus II) Replace noise filter
Is high pressure No Replace PCB
more than 2500kPa CH24 : inverter compressor PCB
at manifold gauge? CH109~154 : sub unit PCB
Yes
Is high pressure of No
LGMV similar as Replace high pressure sensor
at manifold gauge?
Yes
078 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 079
* Plus : Connector location of high pressure switch at PCB(Refer electrical component part for Multi V Space)
Is it Multi V Sync?
Inverter compressor PCB SUB outdoor unit PCB
Yes
Basic Part
Is HR unit valve No
Connect HR unit valve connector
connector normal ?
Yes
Troubleshooting
Guide for each
on auto pipe detection? - Refer to HR unit manual pipe detection
Error Code
Yes
Is the pipe detection Checking short or not at connector of high Checking short or not at connector of high
No Set HR unit manual pipe detection
Trouble Shooting Guide Book
Yes
Component Check
Electrical
Is HR unit valve LED turns on
No
when connected indoor unit Replace HR unit PCB
start to operate?
Yes
Solution Check
Is the resistance value of No
Replace HR unit valve coil **** Check resistance of HR unit valve coil : 1.85 k˟(·10%)
HR unit valve coil normal?****
Yes
- HR unit PCB-
Is the HR unit PCB valve No
measures ~220V in port? Replace HR unit PCB
[electric component part]
Test functions
Yes
080 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 081
* Plus II: Connector location of high pressure switch at PCB(Refer electrical component part for Mult V Space) Error Code Error Contents Meaning Main Causes
Plus:
25(Main)
Constant compressor pressure switch Inverter compressor pressire switch 147 (Sub1)
The power supply input voltage
149 (Sub2) Low / over voltage 1. Input voltage is abnormal(T-N)
tolerance is more or less than
171 (Sub3) of main PCB input 2. Outdoor unit main PCB defect
allowable standard
Plus I:,
251,252,253,
Basic Part
254
Troubleshooting
Guide for each
PCB (T-N) 190V~250V ?* is supplied correctly or not
Error Code
Yes
** Checking short or not at connector of high *** Checking short or not at connector of high
Component Check
pressure switch pressure switch
Electrical
Solution Check
* Check voltage at outdoor T/Block(220V)
Test functions
* Check voltage at outdoor T/Block(220V), Plus II
082 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 083
Error code Error Contents Meaning Main Causes
Plus II:
261,262,
263,264 1. U,Vㇵ connect orCOMP fault
S N1 Right At below min.Hz, 2. DC CT sensor fault
Compressor start failure
P 26 Comp. U,V current is lower than 1A 3. INV PCB fault
A 4. IPM component or connector fault
Basic Part
C N2 Left
E 26 Comp.
Troubleshooting
Error diagnosis and countermeasure flow chart
Component Check
Electrical
Solution Check
Test functions
• Measure the CT current with clamp meter
: U(+), U(-), V(+), V(-)
- The current difference among phases is less
than 0.5A ·10%
U(+)U(-)V(+)V(-)
084 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 085
Basic Part
Troubleshooting
Error diagnosis and countermeasure flow chart
Component Check
Electrical
(U-V : 1.16ȳ · 7% / V-W : 1.19ȳ · 7% /U-W : 1.21ȳ · 7%)
Solution Check
Test functions
086 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 087
Error Code Error Contents Meaning Main Causes
Basic Part
Is the resistance value of No
33 (Plus Main) outdoor unit Check sol valve Replace HR unit valve coil
Plus II : normal?**
331,332,
333,334 Compressor is off 1. Temperature sensor defect of constant
Over-increase discharge Yes
because of over-increase (Space:Inv.) compressor discharge pipe?
temperature of constant
Left discharge temperature of 2. Refrigerant shortage/leak
SPACE (Space:Inv.) compressor at
Comp.(N2) constant (Space:Inv.) 3. LEV defect
main constant outdoor and
compressor at main and 4. Liquid injection valve defect Is the outdoor unit
plus sub constant outdoor unit No
sub outdoor unit 5. Check solenoid valve defect(Sync)
Troubleshooting
check sol valve measure ~220V? Replace outdoor unit PCB
Error Code
102,103(Sub2)
152,153(Sub3)
Yes
Component Check
amount correct? Adjust refrigerant amount
[Start up process]
Electrical
Yes * Error is generated if the resistance is more than 5Mȳ (open) and less than 2 ༮ (short)
Yes
Solution Check
Is the resistance of discharge No Replace discharge
temperature sensor normal?* temperature sensor
Test functions
[refer electric component part] Check the resistance
of constant compressor
discharge temperature
Yes sensor
Check another
No No components
Is it cooling mode of Is there pipe
and operation
Multi V Sync ? (strainer etc.) clogging?
conditions
Yes / Take measures
Yes
088 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 089
Check Check
Check points Check points
Loc. Loc.
Connector
resistance
Basic Part
1.85 k˟(·10%)
Troubleshooting
Guide for each
Error Code
Liquid by pass
valve
Trouble Shooting Guide Book
Connector
resistance
Component Check
ྛ - ྜྷ : around 300˟ ྚ - ྞ : around 300˟ ྜ - ྞ : around 150˟
1.85 k˟(·10%)
Electrical
Hot gas by pass
Valve
Connector
resistance
1.85 k˟(·10%)
Solution Check
Test functions
Liquid by pass
valve
Connector
resistance
1.85 k˟(·10%)
090 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 091
* Calculation of additional refrigerant amount * Calculation of additional refrigerant amount
Basic Part
Multi V
Plus,
Plus II
Troubleshooting
Guide for each
Error Code
Multi V
Trouble Shooting Guide Book
Space
Component Check
Electrical
Multi V
Sync II,
HQTCNN/WNVK8U[UVGO
Solution Check
Sync
Test functions
HP 10 20 30 40 50 60
Multi V
Product Charge (kg) 7.3 8.8 16.1 17.6 24.9 26.4
Water II
CF (kg) 0 0 0 0 0 0
HP 4 5 6
Multi V
MINI Product Charge (kg) 3.7 3.7 3.7
CF (kg) -0.5 0 0
092 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 093
Error Code Error Contents Meaning Main Causes
* Calculation of additional refrigerant amount
-Plus, Sync Error happens because of 3 1. High pressure sensor defect
R22 Multi V Plus 34
Over-increase of
times successive 2. Indoor or outdoor unit fan defect
(Main) compressor off due to over- 3. Deformation because of damage of refrigerant pipe
discharge pressure of
143 increase of high pressure 4. Over-charged refrigerant
compressor
(Sub1) by high pressure sensor 5. Indoor / outdoor unit LEV defect
145 7. When blocked
Basic Part
(Sub2) - Outdoor unit is blocked during cooling
169 Error happens because of 3 - Indoor unit filter is blocked during heating
Over-increase of water
(Sub3) times successive 8. SVC valve is clogged
temperature
Plus II: compressor off due to over- 9. PCB defect of outdoor unit
(Multi V Water)
341,342, increase of water 10. Indoor unit pipe temperature sensor defect
343,344 temperature 11. Insufficient water flow rate. (Multi V Water)
Troubleshooting
Guide for each
Error Code
No
Is service valve opened ? Open service valve
Yes
Trouble Shooting Guide Book
Component Check
cable / pipe connection
normal?
Electrical
Yes
Solution Check
HP 5 6 8 10 12 14 16 18 20
Is fan normal?
Heat Product(kg) 4 4.5 10 10 10 10 20 20 20 (Indoor fan during heating
No Replace related parts
(Refer to Error 105~108)
Pump CF(kg) 0 0 -3 -2 -1 -1 -2 -2 -2 Outdoor fan during cooling)
6(380V) Yes
Product(kg) 4 4.5 10 10 10 20 20 20
Cool 10(220V) Is filter blocked
Only (Heating:indoor, No Clean indoor filter (heating)
Test functions
0(380V) Cooling:outdoor /outdoor heat exchanger (cooling)?
CF(kg) 0 0 -2 -1 -1 -2 -2 -2 heat exchanger)?
-3(220V)
Yes
094 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 095
Is it Multi V Sync? Is it Multi V Water?
Yes
Basic Part
Is it heating mode ? of outdoor unit Replace HR unit valve coil Is water flowrate normal? Check water flow rate
check sol valve normal?*
Yes
Yes Yes
Troubleshooting
Yes
Yes
Component Check
No
Electrical
Is HR unit configuration Check HR unit manual pipe address
on auto pipe detection? - Refer to HR unit manual pipe detection
Yes
Solution Check
Yes
Test functions
Yes
Yes
Yes
096 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 097
Error No. Error Contents Meaning Main Causes
Basic Part
compressor indoor unit filter clogging during heating mode)
pressure by the low
-Plus II: 7. SVC valve clogging
pressure sensor Yes Yes
351,352, 8. Outdoor unit PCB defect
353,354 9. Indoor unit pipe sensor defect
10. HR unit valve coil defect(Multi V Sync)
11. HR unit PCB defect(Multi V Sync) is the outdoor unit No
Check sol valve Replace outdoor unit PCB
measure ~220V in port?
Error diagnosis and countermeasure flow chart
Troubleshooting
Yes
Yes
No
Are transmission cable/ check transmission/
Component Check
piping normal? piping correction.
Is HR unit configuration No Check HR unit manual pipe address
Electrical
Yes on auto pipe detection? - Refer to HR unit manual pipe detection
Solution Check
No Yes
Is there pipe crack
or trace of leakage?
Yes
Is fan normal? No Check and replace related parts Is HR unit valve LED turns on No
(in heating outdoor fan,
Weld / reconnect the (error 105~108 reference) when connected indoor unit Replace HR unit PCB
in cooling indoor fan)
cracked portion and start to operate?
recharge refrigerant Yes
Test functions
Yes
No
Is strainer Ok?* Replace the strainer No
Is the resistance value of
Replace HR unit valve coil
HR unit valve coil normal?**
Yes
Yes
Check HR unit coil * In case of frost and high temperature difference between inlet and
No Check indoor unit LEV assembly location outlet of strainer, strainer blocking may happen
Is it Multi V Sync? Check indoor unit PCB (Caution: frost on the outlet area (afterward after half of body)
Check in/outdoor installation condition Yes
Yes
Check for bent or blocked ** Check sol valve coil resistance value : 1.85 k˟(·10%)
Next page from connected pipes
Check blocked HR Unit HR unit valve coil resistance value : 1.85 k˟(·10%)
098 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 099
Error code Error contents Meaning Main causes FUSE Check - Voltage of fuse should be within 0~1V -In case of 220V,
(Protect over- disconnection of Fuse is disconnected.
Plus:40 loaded FUSE
Plus II: Replace FUSE
current) (when power is
401,402,403,404 1. Fuse failure
supplied)
Low current at CT While inverter compressor 2. Defective noise filter
SP N1 Right or operation R phase current 3. R phase connection problem (plus)
A 40 Comp. CT sensor defect drops below 1A or CT short 4. CT sensor failure (inverter PCB
C failure)
Basic Part
N2 Left
E
40 Comp. Checking points of R ɐ fuse
Troubleshooting
not supplied)
Nose filter Check voltage -Voltage of each connector (R-R,S-S,T-T) should - In case of 220V
Yes
(Noise emit & (when power is be within 0~40V It is disconnected
Trouble Shooting Guide Book
Component Check
Replace noise filter
[refer electric component part]
Electrical
Yes
Solution Check
-Space : U, V phase
Yes
Test functions
Check ȳ -Resistance of each connectors (R-R,S-S,T-T) -In case resistance is
(When power should be within 0~10˟ ˳, noise filter is
* Measure the CT current with clamp meter -Multi V SPACE : U(+), U(-), V(+), V(-) Is not supplied) disconnected.
The current difference among Replace noise filter
- Multi V PLUS / Sync : R phase phases is less than 0.5A ·10%
100 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 101
Error code Error contents Meaning Main causes
Plus:
47 (Main constant compressor) 1. Connection of the compressor defect
Compressor
Basic Part
121 (Sub1 constant compressor 1) Sensor measurement discharge pipe temperature sensor
discharge pipe
122 (Sub1 constant compressor 2) valve is abnormal 2. Discharge pipe compressor sensor
temperature
133 (Sub2 constant compressor 1) (Open/Short) of the compressor (open/short) defect
sensor error
134 (Sub2 constant compressor 2) 3. Outdoor PCB defect
162 (Sub3 constant compressor 1)
163 (Sub3 constant compressor 2) Check the resistance inverter
compressor discharge
Plus II: temperature sensor
Check the resistance
471,472,473,474
Troubleshooting
Guide for each
of constant compressor
(Constant compress)
Error Code
discharge temperature
sensor
Error diagnosis and countermeasure flow chart
Trouble Shooting Guide Book
Component Check
Yes
Electrical
Is the resistance of No
Replace sensor
sensor normal?*
Yes
Solution Check
Is sensor resistance No
value same as temperature Replace corresponding outdoor PCB
value of LGMV?
Yes
* Error is generated if the resistance is more than 5Mȳ (open) and less than 2 ༮ (short)
Test functions
Note: Standard values of resistance of sensors at different temperatures (·5% variation)
10 = 362༮ : 25= 200༮ : 50= 82༮ : 100= 18.5༮
102 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 103
Error code Error contents Meaning Main causes Error code Error contents Meaning Main causes
Plus: Plus:
42 (Main) 44 (Main)
1. Bad connection of air temperature
117 (Sub1) 118 (Sub1)
Abnormal value of 1. Bad connection of low pressure connector connector
129 (Sub2) Sensor error of low 130 (Sub2) Sensor error of outdoor air Abnormal value of
sensor 2. Low pressure connector defect (Open/Short) 2. Air temperature connector
158 (Sub3) pressure 159 (Sub3) temperature sensor (Open/Short)
(Open/Short) 3. Outdoor PCB defect defect(Open/Short)
Plus II: Plus II:
3. Outdoor PCB defect
421,422,423,42 441,442,
Basic Part
4 443,444
Troubleshooting
sensor 2. High pressure connector defect(Open/Short)
Error Code
Plus II: 164 (Sub3 H/E A) main & sub outdoor unit heat (Open/Short)
defect(Open/Short)
431,432,433,43 165 (Sub3 H/E B) exchanger (A,B)
3. Outdoor PCB defect
4 Plus II:
451,452,
453,453(H/E A)
Trouble Shooting Guide Book
Is sensor connected No
Component Check
Connect sensor to PCB correctly Plus:
to PCB correctly?
46 (Main)
Electrical
1. Bad connection of air temperature
Yes 120 (Sub1)
connector
132 (Sub2) Compressor suction Abnormal value of
2. Air temperature connector
After replacement of No 161 (Sub3) temperature sensor error sensor (Open/Short)
Replace corresponding defect(Open/Short)
outdoor unit main PCB Plus II:
pressure sensor 3. Outdoor PCB defect
is the system normal? 461,462,
463,464
Yes
Solution Check
Plus:47
END
(constant compressor
of main outdoor unit)
Plus II: Discharge piping temperature
471,472,473,474 Abnormal value of sensor
sensor error of constant(Space: Refer to CH41
(Open/Short)
Inv.) compressor (Main unit)
Left
High pressure SPACE
Comp.(N2)
sensor
Test functions
Piping temperature sensor error
Plus:48 of heat exchanger in main & Abnormal value of sensor
Refer to CH45
(Heat exchanger B) sub outdoor unit heat (Open/Short)
exchanger (B)
Low pressure
sensor
Pressure sensor Error diagnosis and countermeasure flow chart
connection
Plus model on main PCB
Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly??
Yes
No
Is sensor value correct?* Replace sensor
104 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 105
Error Code Error Contents Meaning Main Causes
(plus)
49 (Main) The measured value of the 1. Abnormal input voltage
Outdoor voltage
148(Sub1) sensor is not 2. Outdoor line fuse damage
sensing error
150(Sub2) normal(Open/Short) 3. Outdoor main PCB defect
172(Sub3)
Basic Part
Error diagnosis and countermeasure flow chart
Measure resistance of outdoor air temperature Measure resistance of outdoor suction pipe
sensor Yes
Troubleshooting
temperature sensor
Component Check
* Check Line Fuse of MAIN PCB(Plus) * Check Line Fuse of MAIN PCB(Plus II)
Electrical
Measure resistance of outdoor HEX(A) Measure resistance of outdoor HEX(B)
temperature sensor temperature sensor
Solution Check
Part Check
How to check? Counter-measure
(Function) points
Test functions
T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within 380·10% -Check supply power and
(Terminal - Voltage of 1ɐ(R-N,S-N,T-N) should be within connection condition
Block, Input 220·10%.
power) - Voltage fluctuation should be within 10V
- While stand-by and in operation,
Voltage drop should be within 10V
106 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 107
Error Code Error Contents Meaning Main Causes Error Code Error Contents Meaning Main Causes
Basic Part
Error diagnosis and countermeasure flow chart
Check
No R~S/S~T/T~R phase voltage is 380V · 10%
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V · 10% Is capacity sum of
No Are quantity and capacity No Check transmission cables
Check connection condition and wiring if power is indoor units less than
of indoor units installed between indoor and outdoor
abnormal 130% of outdoor unit
same as the data of LGMV? units
capacity at LGMV?
Yes
Troubleshooting
Yes
Error Code
No Adjust the capacity of indoor
Is main PCB assembly normal? Replace Main PCB assembly
and outdoor unit
Yes
Is SUB DIP switch
Trouble Shooting Guide Book
No
5(SUB1), 6(SUB2) Adjust corresponding DIP switch
Recheck power and ON?*
installation condition
Component Check
Yes
Electrical
Is power of SUB PCB No Is main power really supplied? No Supply main
On? (Check LED blinking) (Terminal Block T-N) power again
Yes Yes
Solution Check
Is transmission
No
cables between outdoor units Re-connect
connected correctly?**
Yes
Test functions
in order(Sub2 Sub1Main) Replace Main or Sub PCB
after power reset?
Yes
End
108 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 109
* Dip switch setting of SUB unit(Plus) * Dip switch setting of SUB unit (Plus II)
Basic Part
Troubleshooting
Guide for each
Error Code
ON ON
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Trouble Shooting Guide Book
Component Check
Electrical
** In order to check transmission ** In order to check transmission
cables between outdoor units, cables between outdoor units,
check in order as below check in order as below
: PCB connectors ˧ : PCB connectors ˧
terminal block ˧ terminal block ˧
transmission cables transmission cables
Solution Check
1 1 1 1
2 2 2 2
3 3
Test functions
*** Press the red button for auto-addressing,
110 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 111
Error Code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes
Basic Part
C
E 52 Comp. Error diagnosis and countermeasure flow chart
Troubleshooting
Yes
Error Code
Yes
Yes End
No No
Is transmission cable Is power supplied
Re-connect transmission cable Supply power
connected correctly? to indoor units?
Component Check
Yes Yes
Electrical
No
Is MAIN PCB normal? Replace MAIN PCB
Replace indoor unit PCB or
Yes transmission PCB
after check defected indoor
Solution Check
* The method of checking MAIN PCB and inverter compressor PCB (If normal, transmission LED blinks)
( Refer electrical component part for Multi V Space)
- Transmission connector & LED in inverter compressor PCB - Transmission connector & LED in MAIN PCB
In case of CH53, almost happened with CH05, the indoor units not operated actually are normal so check with same
method of CH05. and additionally check as shown as below and above flow chart
- Although the quantity of indoor units installed is same as LGMV data there may be a few indoor units with which
the number of transmission is not increased with LGMV
Test functions
- Although the quantity of indoor units installed is not same as LGMV data, and if transmission of the indoor unit
displayed at LGMV is done well then the indoor unit suspected to have some problem (and is not appear at LGMV)
may have following problems
ྙ wrong connection of transmission cable or power cable
ྚ fault of power / PCB / transmission cable
ྛ duplication of indoor unit number
- If transmission is not doing well wholly then the Auto Addressing is not done
(Plus) (Plus) - The case that CH53 appear at indoor unit also Auto Addressing is not done so indoor unit address may be duplicated
*After replacement of indoor unit PCB, Auto Addressing should be done, if central controller is installed then
the central control address also should be input.
in case that only transmission PCB is replaced above process is not needed
112 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 113
Error code Error Contents Meaning Main Causes FUSE Check - Voltage of fuse should be within 0~1V -In case of 220V,
(Protect over- disconnection of Fuse is disconnected.
Plus: FUSE
loaded Replace FUSE
54 (Main)
current) (when power is
110 (Sub1) 1. Inverter PCB defect
Wrong connection of 3Ȱ Wrong connection of 3Ȱ power supplied)
141 (Sub2) 2. No power of R, S, T supplied
power supply cable (Reverse supply cable (Reverse direction /
155 (Sub3) 3. Wrong connection of R, S, T cables (plus)
direction / missing a phase) missing a phase)
Plus II: 4. Main fuse defect
541,542,
Basic Part
543,544
Checking points of R ɐ fuse
Error diagnosis and countermeasure flow chart Check -Resistance of fuse should be within 0~1˟ -In case resistance is ˳,
disconnection of Fuse is disconnected.
FUSE Replace FUSE
Is connection and phase (when power is
No
order of power cables to main / Connect correctly not supplied)
Troubleshooting
sub outdoor unit correct?*
Is connection and phase No Nose filter Check voltage -Voltage of each connector (R-R,S-S,T-T) should - In case of 220V
Connect power cables in
order of power distribution (Noise emit & (when power is be within 0~40V It is disconnected
Trouble Shooting Guide Book
Component Check
Is CH 54 occurred again No
Electrical
after reset MAIN End
circuit breaker?
Yes
Is 3Ȱ Fuse normal? No
[refer electric Replace Fuse
Solution Check
component part]
Yes
Check the diode of inverter
fan PCB and in case of fault
replace inverter fan PCB
[refer electric component part]
Is noise filter
normal? No
Replace NOISE FILTER
[refer electric Check ȳ -Resistance of each connectors (R-R,S-S,T-T) -In case resistance is
Test functions
component part] (When power should be within 0~10˟ ˳, noise filter is
Yes Is not supplied) disconnected.
Replace noise filter
Replace inverter compressor
PCB(CH54), SUB PCB(CH110,141,155)
* Check power cable connection state, **Check power cable connection state, phase order, power
phase (R-S-T) order, power supply state supply state in distribution panel
in control box of product
114 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 115
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes
Basic Part
Error diagnosis and countermeasure flow chart Error diagnosis and countermeasure flow chart
Yes
Troubleshooting
Guide for each
Yes
Error Code
Is inverter PCB assembly No
Replace inverter PCB assembly
Is LGDC Slave Unit No normal?
Recheck power and installation condition
installed?
Trouble Shooting Guide Book
Yes
Yes
Component Check
No
Is Super Sub Unit
Electrical
Recheck power and installation condition
installed ?
Solution Check
Test functions
116 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 117
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes
Basic Part
Error diagnosis and countermeasure flow chart
Is resistance value
Does cooling fan No No
of cooling fan coil correct? No
rotate while compressor Replace cooling fan Is sensor connected
[refer electric Connect PCB to sensor
operation? to PCB correctly?
component part]
Yes Yes Yes
Troubleshooting
Guide for each
Error Code
Replace main PCB Is value of sensor No
Replace sensor
resistance normal?*
No
Is value of sensor Yes
Replace sensor
Trouble Shooting Guide Book
resistance normal?*
Yes
Component Check
Replace inverter fan PCB
Electrical
* If value is 100 ༮ ˦(open) or 100 ȳ ˨(short), error occurs
Replace inverter fan PCB
NB: Resistance value of temperature sensor change according to temperature
It is normal if value shown as below (·5% error)
* Heat sink temperature sensor (·5% tolerance) : 10 = 20.0༮ : 25= 10.0༮ : 50= 3.5༮ : 85= 1.0༮ Heat sink sensor(·5% tolerance) : 10 = 20.0༮ : 25= 10.0༮ : 50= 3.5༮ : 85= 1.0༮
Solution Check
- Position of cooling fan drive connector in main PCB - Heat sink cooling fan
- Temperature sensor location of Heat sink - Measure the resistance of heat sink temperature sensor
Test functions
- Check DC 12V output during inverter - Heat sink temperature
compressor operation sensor connection
118 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 119
Error code Error Contents Meaning Main Causes
Error diagnosis and countermeasure flow chart(Plus II)
1. Fan motor defect / assembly
condition
abnormal
Fan RPM is 10RPM or less
2. Wrong connection of fan motor
Plus II: for 5 sec. when ODU fan
connector
671,672,673,673 starts or 40 RPM or less
(Hall sensor, U,V,W output)
after fan starting.
Basic Part
3. Reversing rotation after RPM target
Outdoor unit FAN apply
LOCK error 4. Fan PCB assembly defect
S N1 Right
After FAN drive signal
P 67 Fan 1. Motor connection defect
If the HALL SENSOR signal
A 2. FAN PCB defect
does not come on for 4 sec.
C N2 Left 3. Motor defect
E 67 Fan
Troubleshooting
Guide for each
Error Code
Error diagnosis and countermeasure flow chart(Plus)
Trouble Shooting Guide Book
Component Check
Yes
Electrical
No
Is the motor normal?* Replace FAN motor
Yes
Solution Check
Replace FAN PCB
* Check Hall sensor of BLDC FAN motor Ha(4),Hb(3) - Gnd(2) : 24MOhm
Ha(4),Hb(3) - Vcc(1) : 11KOhm
Test functions
resistance
16.8ȳ·5% (75)
120 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 121
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes
Constant Speed Constant Speed Constant Speed Compressor CT Inverter input current Micom input voltage isn't 1. Input voltage abnormal (T-N)
Plus II: Plus II:
Compressor CT Sensor Compressor CT Sensor Sensor CT within 2.5V ·0.3V at initial 2. ODU inverter PCB damage
701,702,703,704 711,712,713,714
Error Open/short defect sensor error state of power supply (CT sensing part)
Basic Part
Error diagnosis and countermeasure flow chart
Check
No R~S/S~T/T~R phase voltage is 380V 10%
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V 10%
Check connection condition and wiring if power is
Is constant speed compressor No abnormal
Check constant speed compressor
CT Sensor connection condition
Troubleshooting
Yes
Error Code
No
Yes Is inverter PCB assembly normal? Replace inverter PCB assembly
Yes
Trouble Shooting Guide Book
Component Check
Electrical
Solution Check
Test functions
122 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 123
Error code Error Contents Meaning Main Causes
Basic Part
4.Power line assemble condition
software) 2ms
abnormal
5.Inverter PCB assembly
damage(input current sensing part)
Troubleshooting
Guide for each
Error Code
1.Check Pipe clogging/distortion
2.Check Covering (Indoor/Outdoor Unit)
Is installation No
3.Check EEV connector assemble condition/normal operation
condition normal?
Trouble Shooting Guide Book
Component Check
Check
No R~S/S~T/T~R phase voltage is 380V 10%
Electrical
Is input voltage normal?
R~N/S~N/T~N phase voltage is 220V 10%
Check connection condition and wiring if power is abnormal
Yes
Solution Check
Yes
Test functions
Is inverter PCB assembly No Check inverter PCB assembly IPM normality
normal? Replace inverter PCB assembly
Yes
124 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 125
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes
Basic Part
Error diagnosis and countermeasure flow chart
No Check 15V wire connection
Is input voltage normal?
Check abnormal wiring between Inverter PCB assembly & Reassemble or manage if abnormality found
Is inverter PCB assembly No
bridge diode (misconnection,disconnection)
power wiring normal? Yes
Rewiring if abnormal wiring found
Yes
Troubleshooting
Guide for each
Check No
Is Fan PCB assembly normal?
Error Code
Replace Fan PCB assembly
No R~S/S~T/T~R phase voltage is 380V 10%
Is input voltage normal?
R~N/S~N/T~N phase voltage is 220V 10%
Check connection condition and wiring if power is abnormal Yes
Yes
Trouble Shooting Guide Book
Component Check
bridge R,S,T phase equally?
Yes
Electrical
Is inverter PCB No
Replace inverter PCB assembly
assembly normal?
Yes
Solution Check
Recheck power and
installing condition
Test functions
126 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 127
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes
1.Overload operation
Plus II: Fan DC Link High Fan PCB DC link voltage 1.Input power abnormal Plus II: Fan Over Current Output current is over 5A for
2.Fan Motor defect
761,762,763,764 Voltage Error supplied over 780V 2.Fan PCB assembly defect 771,772,773,774 Error 40ms
3.Fan PCB assembly defect
Error diagnosis and countermeasure flow chart Error diagnosis and countermeasure flow chart
Basic Part
Check
R~S/S~T/T~R phase voltage is 380V 10%
No Is installation No No Check ODU fan motor assemble condition and locking
Is input voltage normal? R~N/S~N/T~N phase voltage is 220V 10%
condition normal? Reassemble or replace if abnormality found
Check connection condition and wiring if power is
Yes abnormal Yes
Troubleshooting
Guide for each
1.Check resistance between each motor output terminal
Error Code
No Are the resistance No No
Is Fan PCB assembly normal? Replace Fan PCB assembly (16.8ൎ5% at 75C)
Between each phase and insulation
2. Check insulation resistance between ODU fan motor
resistance of motor output
terminal (U,V,W) and pipe (over 100Mൎ )
Yes terminal normal?
Replace fan motor if abnormality found
Trouble Shooting Guide Book
Yes
Recheck power and
installation condition
1.Check if color of motor output terminal(U,V,W) connector
Component Check
Is motor wire connection No matched with PCB’s
condition normal? 2.Check wire disconnection and wiring
Electrical
Reassemble or replace if abnormality found
Yes
Yes
Solution Check
Recheck power and
installation condition
Test functions
128 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 129
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes
Basic Part
Error diagnosis and countermeasure flow chart Error diagnosis and countermeasure flow chart
Is fan motor assemble No Check ODU fan motor assemble condition and locking Is fan motor assemble No Check ODU fan motor assemble condition and locking
condition normal? Reassemble or replace if abnormality found condition normal? Reassemble or replace if abnormality found
Troubleshooting
Yes Yes
terminal normal?
Replace fan motor if abnormality found
Yes Yes
Component Check
1. Check if color of motor output terminal(U,V,W) connector
Electrical
Check if connector color matched between fan motor
Is connector color between No Is fan motor connection No matched with PCB’s
hall sensor and PCB
Hall Sensor PCB matched? condition normal? 2. Check wire disconnection and wiring
Reassemble if abnormality found
Reassemble or replace if abnormality found
Yes Yes
Solution Check
Yes Yes
Test functions
130 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 131
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes
Plus II: Main PCB EEPROM 1. No EEPROM
EEPROM Access Error Error occurs when checking 1.EEPROM bad contact/wrong
861,862,863,864 Error 2. EEPROM wrong insertion
Plus II: Fan PCB EEPROM the EEPROM checksum as insertion
871,872,873,874 Error initializing after power is 2.EEPROM Version is different
supplied 3.ODU fan PCB assembly damage
Error diagnosis and countermeasure flow chart
Basic Part
Error diagnosis and countermeasure flow chart
Troubleshooting
Guide for each
No
Error Code
Is EEPROM 24C16? Replace EEPROM with 24C16 No
Is Fan PCB assembly normal? Replace fan PCB assembly
Yes
Trouble Shooting Guide Book
Yes
Recheck power and
installation condition
Recheck power and
Component Check
installation condition
Electrical
Solution Check
Test functions
132 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 133
Error code Error Contents Meaning Main Causes Error code Error Contents Meaning Main Causes
plus: Plus:
Over-increase of constant Compressor is off because of
100,101 (Sub1) 104 (Main)
compressor discharge Over-increase of constant compressor discharge Refer to CH33
102,103 (Sub2) 111 (Sub1)
temperature of Sub outdoor temperature of Sub outdoor unit
152,153 (Sub3) 142 (Sub2) Transmission 1. Loose connection of power cables
Master displays ODU number
156 (Sub3) Error /transmission cables (Open/Short)
which is not communicated.
Plus II: Between 2. Each outdoor unit PCB defect
Slave displays own error number
011˧041 Outdoors 3. Defect of PCB power
Basic Part
011˧042
* Discharge temperature sensor of constant compressor 011˧043
in the sub unit 011˧044
Troubleshooting
Guide for each
Does transmission LED Is PCB input power of
Error Code
No No Check and replace
(Red) of corresponding transformer, PCB power fuse
corresponding parts/
Sub PCB blinks? [refer electric normal? [refer electric Input power
component part] component part]
Yes Yes
Trouble Shooting Guide Book
Component Check
Electrical
Is transmission cables
No
of outdoors connected
Re-connect transmission cables
correctly? [refer electric
component part]
Yes
Solution Check
Replace MAIN PCB
Test functions
LED 8 7 6 5 4
LED 3
LED 2
LED 1
134 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 135
Error diagnosis and countermeasure flow chart(Plus II) Error code Error Contents Meaning Main Causes
-Plus
1. Loose connection of transmission cables
Plus:Transmission error Plus:Transmission error between 2. Transmission cables are open/sort
Plus:105
between outdoor unit Main PCB outdoor Main PCB and fan Main 3. Outdoor Main PCB PCB defect
Plus II:
and fan Main PCB PCB (Fan ˧ outdoor main) 4. Fan Main PCB defect
11˧051
11˧52
Plus II:Transmission error Plus:Transmission error between -Plus II
11˧53
Basic Part
between outdoor unit Inv PCB outdoor Inv PCB and fan PCB 1. Wrong connection between Inverter and
11˧54
and fan PCB (Fan ˧ inv) Fan PCB
2. Fan PCB power not supplied
3. ODU Inv/Fan PCB defect
Troubleshooting
Guide for each
Error Code
Is transmission LED No Is noise filter or fuse No
(yellow) of inverter fan normal ? [refer electric Replace noise filter or fuse
PCB on?* component part]
Yes
Trouble Shooting Guide Book
Yes
Component Check
Electrical
Are transmission cables No
of Main PCB / Fan PCB Re-connect transmission cables
connected normally?
Yes
No
Is green LED of
Solution Check
Replace Main PCB
Main PCB blinks?**
Yes
Test functions
* Location of inverter transmission connector of **Location of PCB transmission connector of
Main PCB and LED Inverter FAN and LED
136 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 137
Error code Error Contents Meaning Main Causes
Plus:106
Plus II:
11˧061 1. Overload operation (Pipe
12˧062 clogging/Covering/EEV
13˧063 IPM protection circuit defect/Ref. overcharge
14˧064 Over current of Main outdoor activation 2. ODU fan motor assemble condition abnormal
Basic Part
fan motor (inverter fan IPM fault) (over current / (Coil disconnection/Short/Insulation damage)
S N1 Right overheating) 3. Fan PCB heatsink assemble condition
P 106 Fan abnormal
A 4. Fan PCB assembly defect
C N2 Left
E 106 Fan
Troubleshooting
Guide for each
Error Code
No
Is it Multi V Space ? Multi V Plus & Sync
Yes
Trouble Shooting Guide Book
Yes
Component Check
㤸㠄㉔Ḱ 㐔䝬㉔ 㢨ᷝ normal? [refer electric Replace inverter fan IPM PCB
component part]
Electrical
Yes
Yes
Solution Check
Is inverter fan motor No
Normal? [refer electric Replace inverter fan motor
component part]
Yes
Test functions
check PWM signal cables
[refer electric component part]
Vcc
Gnd
1 Hb
2 Ha
3 4
138 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 139
Part Check
How to check? Counter-measure Part Check
(Function) points How to check? Counter-measure
(Function) points
Inverter fan
No power
IPM PCB
on PCB
10. Comm. circuit
Basic Part
2. Input circuit of 3ɐ &
1. MICOM LED DC rectifying circuit
4. IPM
9. On-boarding 3. In/Output connector
connector of reactor
2. DC supply terminal
Troubleshooting
Guide for each
(DC310V)
8. Heat sink
Error Code
temperature 4. DC-Link output voltage
sensor connector
7. PWM
Trouble Shooting Guide Book
drive circuit
5. DC-Link electrolytic
capacitor
Component Check
6. SMPS power
Electrical
circuit
3. Outdoor unit fan connectors
Solution Check
3.Outdoor - While Fan operating, in case voltage of filter, fuse
- Check half wave rectifying circuit diode
fan connector - connectors(U-V,V-W,U-W) is 100~300V - Replace connectors & (R-Reactor1: 0.6V, S-Reactor1: 0.6V: -Replace inverter fan
- ˧ Normal inverter T-Reactor1: 0.6V) PCB
4. IPM -- Check Diode(P-N : 0.95V, PCB if not charging
- P-U,P-V,P-W: 0.55V
- N-U,N-V,N-W: 0.55V - Replace inverter IPM
PCB
Test functions
R, S, T, N Reactor 1
Red LED -When red LED blinks, error code happens -Check error code at
about inverter fan PCB main PCB
140 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 141
Error diagnosis and countermeasure flow chart (Plus II)
Multi V Space BLDC FAN PCB
No
Is fan motor assemble Check ODU fan motor assemble condition and locking
4.SW_SEL 6.CN_COMM condition normal? Reassemble or replace if abnormality found
LED01M : PWM Enable 5.SW_DIR [MAIN PCB>FAN PCB] :5,6,8HP
[louver
LED02M : display error [FAN direction] [FAN>COMP PCB] : 10HP
selection]
Yes
Basic Part
7.CN_POWER2 No 1.Check fan motor U,V,W connector connection condition
3.Power supply [louver power supply] Is fan motor wire connection Reassemble wire if abnormality found
condition normal? 2.Check fan motor wire disconnection
Replace ODU fan motor if abnormality found
LED01K
Yes
(FAN>INV
communication)
Troubleshooting
8.SW01M,02M,03M
Error Code
[PCB JIG check] Is fan PCB assemble No Reassemble if abnormality found
9.CN_WIRTE condition normal? 2.Check assemble condition between fan PCB and Heatsink
[on boarding Reassemble heatsink if abnormality found
light]
10.CN_M1S,M2S Yes
Trouble Shooting Guide Book
Component Check
sensor) Is fan PCB assembly normal? Replace fan PCB assembly
Electrical
12.CN_MOTOR1,2
1.CN_POWER
[louver signal output] Yes
[PCB power
supply)
13.CN_FAN
[FAN signal output)
Recheck power and
installation condition]
Solution Check
Situation Monitoring Location How to check? Counter-measure
Power does not turn 1.CN POWER -AC voltage measure 220V -Input voltage (220V)
on -Replace related parts (FAN PCB)
3. Power supply - ZNR01D( barrister ),FUSE burn out
(CH105) checkup
FAN motion disabled 2.CN_DC LIINK -DC 470V~520V displays - Check and replace
-DC 380V and above are normal CAPACITOR
Test functions
- Replace PCB
13.CN_FAN - U,V,W electric flow measurement - Check up and replace
(CH106) stabilize connection and motor
11.CN_SENSOR -Check connectors
(CH67)
(FAN PCB) (FAN PCB)
communication does 6. CN-COMM -Flick LED01K -Check PCB power
not work (CH105) - check connector and PCB (power supply(220V)
supply ,communication) -Check and replace connector
and PCB
Louver does not 4.SW_SEL Check if connector is connected -connect connectors (if there
work -DC24V display check are no louver)
7.CN_POWER2
-Connection status check -Check and Replace trance and
10.CN_M1S,M2S power supply
Connection status check
12.CN_MOTOR1,2 -Check and replace louver
motor and connection part
142 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 143
Multi V Plus II LGDC FAN PCB Error code Error Contents Meaning Main Causes
Plus:107
Plus II:
11˧071
12˧072
13˧073 DC voltage charging Low voltage of Main 1. Bad connection of voltage lead cable of main PCB DC link
14˧074 failure of inverter fan outdoor fan motor 2. Fan main PCB capacitor defect
N motor drive (below 380V) 3. Fan main PCB defect
Basic Part
CN Micom S N1 Right
Write P 107 Fan
A
W C N2 Left
E 107 Fan
V 2. CN FAN Right
Troubleshooting
Guide for each
Error diagnosis and countermeasure flow chart(Plus)
Error Code
1. CN DC Link
CN Heat Sink
Trouble Shooting Guide Book
6. CN Inverter
Communication Is DC LINK cable No
Adjust DC LINK cables
Normal?*
Component Check
DC 15V Power Input 3. CN FAN Left Yes
terminal
Electrical
4. CN Hall Sensor Replace inverter fan PCB
(Right) P
5. CN Hall Sensor
(Left)
Solution Check
Error diagnosis and countermeasure flow chart(Plus II)
Test functions
-Check connectors connection and motor
4/5. CN_HALL
SENSOR(CH67) No
Measure DC_Link voltage
Is DC_Link voltage normal?
Check inverter PCB if voltage is below 380V
Communication does 6. CN-COM (CH105) -Flick LED01K - Check DC power input
not work - Check 15V DC power input terminal Yes
- Check Connector - Check and replace connector
and PCB
No
Fan IPM P-N & U,V,W Is Fan PCB assembly normal? Replace fan PCB assembly
Yes
144 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 145
Error code Error Contents Meaning Main Causes
Plus:
Excessive rise of high pressure in Compressor Off due to the high pressure switch
109 Refer to CH24
- Inverter fan main PCB - Inverter fan IPM PCB outdoor unit in outdoor unit
(Sub1)
Basic Part
Wrong connection of 3 phase power cable
110 (Reverse phase / No power in 1 or 2 Refer to CH54
(Reverse phase / Phase omission)
(Sub1) phase)
Troubleshooting
Guide for each
receiving signal from Main outdoor unit
Error Code
Trouble Shooting Guide Book
(Plus)
Component Check
Electrical
Solution Check
Test functions
Check DC Voltage 470~520
(Plus II)
146 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 147
Error code Error Contents Meaning Main Causes
Error code Error Contents Meaning Main Causes
Plus:
113 (Main) 116 Sensor measured value of resistance is
High pressure sensor Refer CH43
125 (Sub1) (Plus Sub1) abnormal (Open / Short)
Outdoor unit
137 (Sub2)
liquid pipe Abnormal sensor 1. Defective temperature sensor connection
166 (Sub3)
(condenser) resistance value 2. Temperature sensor defect(Open / Short)
Plus II: 117 Sensor measured value of resistance is
temperature (Open/Short) 3. Outdoor unit main PCB defect Low pressure sensor Refer to CH42
11˧131 (Plus Sub1) abnormal (Open/Short)
sensor error
12˧132
Basic Part
13˧133
14˧134
118 Outdoor unit air temperature Sensor measured value of resistance is
Refer to CH44
(Plus Sub1) sensor error abnormal (Open / Short)
Error code Error Contents Meaning Main Causes
Plus:
114 (Main sub-cool inlet) 120 Compressor suction pipe Sensor measured of resistance value is
Refer to CH46
115 (Main sub-cool outlet) (Plus Sub1) temperature sensor error abnormal (Open/Short)
Troubleshooting
126 (Sub1 sub-cool inlet)
Error Code
138 (Sub2 sub-cool inlet) 121 (Plus Sub1
139 (Sub2 sub-cool outlet) constant compressor 1) Compressor discharge pipe Sensor measured value of resistance is
Refer to CH41
167 Sub3 sub-cool inlet) 122 (Plus Sub1 temperature sensor error abnormal (Open/Short)
Outdoor unit sub- 1. Defective temperature sensor connecter constant compressor 2)
168 (Sub3 sub-cool outlet) Abnormal sensor
cooling inlet / outlet connection
Trouble Shooting Guide Book
resistance value
temperature sensor 2. Temperature sensor defect(Open / Short)
Plus II: (Open/Short)
error 3. Outdoor unit main PCB defect
11˧141(sub-cool inlet) 123 (Plus Sub1 HEX A) Sub outdoor unit heat exchanger Sensor measured value of resistance is
12˧142 Refer to CH45
124 (Plus Sub1 HEX B) (A,B) pipe sensor error. abnormal (Open/Short)
Component Check
13˧143
14˧144,
Electrical
11˧151(sub-cool outlet) 125 Outdoor liquid pipe (condenser) Sensor measured value of resistance is
11˧152 Refer to CH113
(Plus Sub1) sensor error abnormal (Open/Short)
11˧153
11˧154
126 (Plus Sub1
Error diagnosis and countermeasure flow chart Sub-cool inlet) Outdoor unit sub-cool inlet / outlet Sensor measured value of resistance is
Refer to CH114
127(Plus Sub1 sensor error abnormal (Open/Short)
• Sub-cool circuit in the
Sub-cool outlet)
outdoor unit
Solution Check
Is temperature sensor No 128 Sensor measured value is abnormal
connector connections Check and correct connection High pressure sensor error Refer to CH43
(Plus Sub2) (Open/Short)
are normal?
Yes
129 Sensor measured value is abnormal
Low pressure sensor error Refer to CH42
(Plus Sub2) (Open/Short)
Is the value of temperature No
Replace sensor (Plus)
sensor resistance normal?*
130 Outdoor unit air temperature Sensor measured value is abnormal
Test functions
Refer to CH44
Yes (Plus Sub2) sensor error (Open/Short)
* Sensor resistance 100 ༮ over (open) or 100 ȳ below (short) will generate error (Plus II) (Plus II)
133 (Plus Sub2 Const
compressor1) Compressor discharge pipe Sensor measured value is abnormal
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value Refer to CH41
according to outdoor unit temperature by referring below table (·5% tolerance) 134 (Plus Sub2 Const temperature sensor error (Open/Short)
compressor2)
Air temperature sensor: 10 = 20.7༮ : 25= 10༮ : 50= 3.4༮
Pipe temperature sensor: 10 = 10༮ : 25= 5༮ : 50= 1.8༮
- Liquid pipe temp sensor - Sub-cool inlet temp sensor - Sub-cool outlet temp sensor Sub Outdoor unit heat exchanger
135 (Plus Sub2 HEX A) Sensor measured value is abnormal
(A,B) pipe temperature sensor Refer to CH45
136 (Plus Sub2 HEX B) (Open/Short)
error
148 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 149
Error Code Error Contents Meaning Main Causes Error Code Error Contents Meaning Main Causes
140 Excessive rise in outdoor high Compressor Off due to the high pressure Plus:
Refer to CH24
(Plus Sub2) pressure switch in outdoor unit 151
Function error of 4way 1. Wrong operation of 4way valve because of sludge etc. inflow
Plus II: Function error of
(reversing valve) in 2. No pressure difference because of compressor fault
11˧511 outdoor 4way
Main or Sub outdoor 3. Wrong installation of In/outdoor common pipe
11˧512 (reversing valve)
Outdoor 3 phase power supply units 4. 4way valve defect
141 Wrong wiring at outdoor unit 11˧513
problem (Reverse phase / phase Refer to CH54
(Plus Sub2) (phase reversal / phase omission ) 11˧514
omission)
Basic Part
Error diagnosis and countermeasure flow chart
Transmission error between outdoor units
104 (Main outdoor unit is not receiving sub
142 Transmission error between outdoor
outdoor unit s signals) Refer to CH104
(Plus Sub2) units Is 4-Way valve connecter
147, 149, 171 (Sub outdoor units are not No
receiving main unit signals) connection are properly Reconnect it
connected?
Troubleshooting
Guide for each
Error Code
Yes
143 (Plus Sub1)
Excessive rise in high pressure Compressor Off due to high pressure sensor Refer to CH34
145 (Plus Sub2)
Is 4 Way valve coil No
Change 4 Way valve coil
resistance normal?*
Trouble Shooting Guide Book
Component Check
Is 4 way valve coil connected No
Re-insert 4 way valve coil
to 4 way valve normally?**
Electrical
1. Input Voltage in the installation region =
147 (Plus Sub1) Yes
Low voltage/ High voltage 3phase 380V·10% Refer to CH25
149 (Plus Sub2)
2. Single Phase = 220 ·10%
In case of more than
2 units, does main outdoor No
Refer to CH 51 & make measure
unit recognize
㜼 as more
148 (Plus Sub1) than 2 units? ***
Outdoor voltage sensing error Measured value is abnormal (Open/Short) Refer to CH49
150 (Plus Sub2)
Solution Check
Yes
Yes
Test functions
Magnet switch, corresponding PCB
normally?
[refer electric component part]
Yes
After opposite
mode operation to present No If the same error is occurred in
mode, is the same error near future replace 4way valve
occurred again?
Yes
150 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 151
(Plus) (Plus ȤȤ)
Basic Part
Troubleshooting
Guide for each
Error Code
Main PCB
Trouble Shooting Guide Book
Component Check
Electrical
Solution Check
*** When power is supplied in order as follow (Sub2Sub1Main)
3rd number indicates outdoor quantity at Main PCB 7-segment LED
- Outdoor unit 1set : Model code-capacity(or 10)-..
- Outdoor unit 2set : Model code(Main)-Model code(sub)-capacity(or 20)-..
- Outdoor unit 3set : Model code(Main)-Model code(sub1)- Model code(sub2)- capacity(or 30)- ..
Test functions
**** Check the output voltage of terminal socket ***** Checking method for outdoor unit of 3unit system
during heating operation : 220V (·10%) ྙ Close all the SVC valves of high / low pressure common pipe
ྚ Operate system
ྛ Check the difference of high and low pressure
with LGMV for each unit (Main, Sub1, Sub2)
ྜ If there is a unit in which the difference is not increased
then the 4way valve of that unit is defective
152 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 153
Error Code Error Contents Meaning Main Causes
Error Code Error Contents Meaning Main Causes
Plus:
152,153 Excessive rise of the constant Constant speed compressor Off due to the 173
Refer to CH33
(Plus Sub3) compressor discharge temperature excessive rise in discharge temp (MAIN constant)
174, 175 1. Constant compressor defect
Over-increase of
(sub1 constant 1,2) 2. Discharge temperature sensor defect
temperature
154 Excessive rise in outdoor high Compressor Off due to the high pressure 176, 177 Abnormal staring of 3. Outdoor temperature sensor defect
Refer to CH24 after constant
(Plus Sub3) pressure switch in outdoor unit (sub2 constant 1,2) constant compressor 4. Outdoor main PCB defect
compressor
Plus II: 5. Magnet switch defect
Basic Part
starts
11˧731 6. Wrong connection of constant compressor cables
Outdoor 3 phase power supply 11˧732
155 Wrong wiring at the outdoor 3 phase 11˧733
wiring wrong Refer to CH54
(Plus Sub3) (Reverse phase / Phase omission) 11˧734
(Reverse phase / Phase omission)
Troubleshooting
(Plus Sub3) outdoor units
Error Code
receiving main unit signals) Is resistance value
(insulation & phase to phase)
of corresponding constant No
157 Abnormal resistance value of sensor Replace constant compressor
High pressure sensor error Refer to CH43 compressor normal ?
(Plus Sub3) measurement ( Open / Short ) [refer electric
Trouble Shooting Guide Book
component part]
158 Abnormal resistance value of sensor
Low pressure sensor error Refer to CH42 Yes
(Plus Sub3) measurement ( Open / Short )
Component Check
159 Outdoor unit air temperature Abnormal resistance value of sensor No
Electrical
Refer to CH44 Is cables’ connection
(Plus Sub3) sensor error measurement ( Open / Short ) Adjust connection of cables
of compressor normal? *
Solution Check
163 (Plus Sub3 constant temperature sensor error measurement ( Open / Short ) normal? [refer electric temperature sensor
ompressor2) component part]
Yes
164 (Plus Sub3 HEX A) Pipe sensor error of the main and Abnormal resistance value of sensor
Refer to CH45
165 (Plus Sub3 HEX B) sub units heat exchanger (A,B) measurement ( Open / Short )
Is magnet switch No
normal? [refer
㜼 electric Replace magnet switch
Abnormal resistance value of sensor component part]
Sensor error at the outdoor
166(Plus Sub3) measurement Refer CH113
liquid refrigerant pipe
Yes
Test functions
( Open / Short )
154 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 155
Error Code Error Contents Meaning Main Causes Error Code Error Contents Meaning Main Causes
Basic Part
Error diagnosis and countermeasure flow chart Error diagnosis and countermeasure flow chart
No No
Is temperature sensor
Is water flow rate normal? Check Water flow rate and Power reset Connect temperature sensor on PCB
Connection Condition normal?
Troubleshooting
Guide for each
Error Code
Yes Yes
No
Trouble Shooting Guide Book
Is temperature sensor No
Connect temperature sensor on PCB Is the resistance value of
Connection Condition normal? * Replace temperature sensor
temperature sensor normal?
Yes
Component Check
Yes
Electrical
Replace outdoor unit PCB
No
Is the resistance value of
Replace temperature sensor
temperature sensor normal?
Solution Check
Replace outdoor unit PCB
Sensor of air temperature: 10 = 20.7༮ : 25= 10༮ : 50= 3.4༮
Sensor of piping temperature: 10 = 10༮ : 25= 5༮ : 50= 1.8༮
Test functions
156 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 157
Error Code Error Contents Meaning Main Causes
Error Code Error Contents Meaning Main Causes
Plus II:
Multi V Water II 11˧931 Heat sink
Transmission error Fan PCB heatsink 1. Heatsink temperature sensor defect
182 1. Power cable or transmission cable is not 11˧932 temperature is
between Main PCB can’t receive temperature high 2. Fan PCB assembly defect
Master (11821) connected 11˧933 over 95¶C
(Main PCB Æ Sub signal from Sub PCB 11˧934
Slave1 (12822) 2. Defect of Sub / Main PCB
PCB)
Slave2 (13823)
Plus II: 1. Heatsink temperature sensor
Heatsink
Basic Part
11˧941 Fan PCB heatsink defect(Open/Short)
Temperature
Error diagnosis and countermeasure flow chart 11˧942 temperature sensor
Sensor
2. Wrong connection of temperature sensor
11˧943 error connector
Abnormal
11˧944 3. Fan PCB assembly defect
No
Error diagnosis and countermeasure flow chart
Is Sub Mciom LED blink? Push reset button
Troubleshooting
Guide for each
Error Code
Yes
Is temperature sensor No Check connection of heat sink
inserted to fan PCB? temperature connector
Trouble Shooting Guide Book
No
Is Error disappear ? Instant Error
Yes
Component Check
Yes
No
Electrical
Is temperature sensor Check connection condition of
Replace outdoor unit Main PCB attached to heat sink? heat sink and temperature sensor
Yes
Solution Check
sensor normal? resistance(10kȳ ·5% at 25¶C)
ݬReplace the sensor if
abnormality found
Yes
No
Is fan PCB assembly
㜼 normal? Replace fan PCB assembly
Yes
Test functions
Recheck power and installation
condition
158 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 159
Error Code
Error
Contents
Meaning Main Causes ඖ Auto addressing
1. HR unit’s power cable or transmission cable connection defect
After the Auto operation,
2. After Auto-Addressing, wrong address setting of the indoor
Pipe detection
if the number of the indoor
unit (Defective indoor power / transmission error and PCB Turn on “HR unit Indoor unit
200 units detected is different
error
from the number
defect) Outdoor unit” in the order named ඖ Outdoor unit main PCB
3. Wrong setting of the HR unit’s rotary switch or dip switch
communicating indoor unit
4. HR unit PCB defect
<7 Segment>
Basic Part
H1 01…H1 04
failed to search pipe 1. HR unit’s power cable or transmission cable connection defect
H2 01…H2 04 Wait for 3 minute
connected to HR unit valve 2. After Auto-Addressing, wrong address setting of the indoor
H3 01…H3 04 Pipe
of marked number unit
H4 01…H4 04 detection
(Ex : H1 02 no.2 valve (Defective indoor power / transmission error and PCB defect)
. error
pipe of no.1 HR unit failed 3. Wrong setting of the HR unit’s rotary switch or dip switch
.
to search) 4. HR unit PCB defect
.
Troubleshooting
Press SW02M of the ODU main PCB
Component Check
periodically ?
Yes
Electrical
Yes
Solution Check
Check if all indoor unit is CH05 with
The number of HRU connected is displayed
Operate auto pipe detection after the H.R. unit on (Refer to CH05)
at 7-seg of the ODU main PCB
pipe is sufficiently refrigerated
after resetting outdoor unit
and HR unit 30 minutes before <SW02M> <SW01M>
Yes
Test functions
Is the Auto-pipe detection No Equal number of “IDU No
success? Adjust H.R. unit manual pipe detection and displayed one”?
(is the Error disappeared?) in terms of “wiring”
Yes Check power and communication wiring
Yes between ODU, HRU, IDU
Finish
[NB] If Indoor units/transmission cables of HR unit and cables of power 220V has been changed each other,
transmission parts and indoor will be burnt
160 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 161
ඖ Auto pipe detection ඖ Manual pipe detection
Confirm the IDU auto addressing setting In case of auto pipe detection failure
Basic Part
Turn off “No.1 of SW02M of the HRU” Turn on “No.1 of SW02M of HR unit”
Troubleshooting
Guide for each
Reset the power of HRU PCB Enter central control address into each IDU
Error Code
using its wired remote controller
Confirm the No. 5 DIP S/W of SW01B
of the ODU PCB
Trouble Shooting Guide Book
Component Check
address of IDU connected to the valve
Electrical
In case of changing 5 DIP S/W of SW01B
of the ODU, reset power of the ODU main
PCB. Turn on No.5 of SW01B
of ODU PCB”
Wait for 3 minute
Solution Check
Press SW01V of the ODU main PCB Reset the power of ODU PCB
for 5 second
Test functions
Outdoor unit is operating
for 5~30 minutes. The number of IDU installed is displayed
After ODU stopped, the number of IDU Display error on the ODU PCB / HRU PCB
detected is displayed at 7-seg of the ODU - ODU PCB : HR unit No. Valve No. No
Equal number of
main PCB for 1 minute (Example: H1 01) “IDU and Displayed one”?
- HRU PCB : ‘200’
Yes
Equal number of IDU No
and displayed one? Turn off No.5 of SW01B Check the central control address of IDU
in terms of “piping” Check the piping among ODU, IDU, HRU
of ODU PCB and HRU
Yes
162 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 163
ඖ HR Unit PCB
Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
Component Check
Green LED blinking :
Electrical
Communication OK
Solution Check
Test functions
164 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 165
ඖ Manual addressing of valves on HR unit PCB
(with SW01M, SW03M, SW04M)
Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
Component Check
Electrical
T vaGu
T k aGu
SW01M SW03M SW04M
Solution Check
No.1 of SW01M
T v aGuUXGGz~WXtGGGGGJX
T k GaGlGGGGllwyvtGG
G^TzlnU
SW01M SW03M SW04M
T v azGGGGXWGGGGG
Test functions
nGoGGGGGGG
GGGGGGGG
SW03M
GJXG GGz~WZtGzV~
SW01M SW04M
T k GaGkGGGGGGG
SW03M z~WZtGzV~GG GGG^Tzln SW03M
TvGaGzGGGGXGGGGG
nGsGGGGGGG
GGGGGGGG
GJXG GGz~W[t SW04M
SW01M SW03M Tk GaGkGGGGGGG
SW04M z~W[tGzV~GG GGG^Tzln SW04M
No.1 of SW01M
TvGaGuUGXGGz~WXtGGGGG
GGGJX
Tk GaG“XX” GG^TzlnG
SW01M SW03M SW04M
166 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 167
Error Code Error Contents Meaning Main Causes Error Code Error Contents Meaning Main Causes
201(HR unit1) 205(HR unit2) HR unit liquid 1. Defective connection in HR unit power supply and
1. Defective temperature sensor connection 204(HR unit1) 208(HR unit2) transmission transmission
209(HR unit3) 213(HR unit4) pipe Abnormal value of sensor transmission connection
2. Temperature sensor defect(Open/Short) 212(HR unit3) 216(HR unit4) error between error between
217(HR unit5) 221(HR unit6) temperature measurement ( Open / Short ) 2. Wrong setting of the HR unit Rotary switch and
3. Defective HR unit PCB 220(HR unit5) 224(HR unit6) the HR unit and the HR unit and
225(HR unit7) 229(HR unit8) sensor error Dip switch
228(HR unit7) 232(HR unit8) outdoor unit outdoor unit
3. Defective HR unit PCB
HR unit
202(HR unit1) 206(HR unit2)
Error diagnosis and countermeasure flow chart
Basic Part
Sub-cooling 1. Defective temperature sensor connection
210(HR unit3) 214(HR unit4) Abnormal value of sensor
inlet pipe 2. Temperature sensor defect(Open/Short)
218(HR unit5) 222(HR unit6) measurement ( Open / Short )
temperature 3. Defective HR unit PCB
226(HR unit7) 230(HR unit8)
sensor error
H.R. unit green No
HR unit LED (communication LED) blinks Check H.R. unit input power (220V·10%)
203(HR unit1) 207(HR unit2) periodically ?
Sub-cooling Abnormal value of sensor 1. Defective temperature sensor connection
211(HR unit3) 215(HR unit4) Yes
discharge pipe measurement 2. Temperature sensor defect(Open/Short)
219(HR unit5) 223(HR unit6)
Troubleshooting
temperature ( Open / Short ) 3. Defective HR unit PCB Yes
Error Code
Check installation status of communication line
Check H.R. unit Rotary switch and and connected pipe
Dip Switch setting outdoor unit ˩HR unit ˩outdoor unit
Error diagnosis and countermeasure flow chart
Trouble Shooting Guide Book
Yes Yes
Component Check
Is the sensor connected to no
Reconnect sensor to PCB
Electrical
HR unit PCB properly? Replace HR unit PCB
yes
Solution Check
yes transmission parts and indoor will be burnt
* Sensor resistance 100 ༮ over (open) or 100 ȳ below (short) will generate error
Test functions
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (·5% tolerance)
Air temperature sensor: 10 = 20.7༮ : 25= 10༮ : 50= 3.4༮
Pipe temperature sensor: 10 = 10༮ : 25= 5༮ : 50= 1.8༮
168 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 169
Error Code Error Contents Meaning Main Causes Error Code Error Contents Meaning Main Causes
Basic Part
1. NOISE occurs
1) Check transmission cables are connected correctly or not 2. CNU defect
2) If central controller is connected to total network, check IP of CNU, central controller Central controller 3. Temporary error of Timing mismatch
3) Replace CNU 251 Length of received data : 0
Receive Zero Error 4. A/C product defect
5. PI485 communication cable open or
connection defect
Error Code Error Contents Meaning Main Causes
Troubleshooting
Guide for each
1. Defective CNU 1. NOISE occurs
Central controller data Central controller to CNU data
Error Code
241 2. Center controller initialization 2. CNU defect
transmission error (Sending error) transmission failure
failure Central controller Setting address and actual address 3. Temporary error of Timing mismatch
252
Wrong Address Error are different each other 4. A/C product defect
5. PI485 communication cable open or
Central controller receive Error CNU to Central controller on time 1. Defective CNU connection defect
242
Trouble Shooting Guide Book
(Data receiving error ) data receiving error 2. Central controller initialization error
Component Check
Central controller receive buffer 2. CNU defect
243 CNU is longer than data length 2. Defective CNU
overflow (In excess data receive) Central controller 3. Temporary error of Timing mismatch
defined at protocol 3. transmission noise error 253 No response from air conditioner
Electrical
Disconnection Error 4. A/C product defect
5. PI485 communication cable open or
1. Defective CNU connection defect
Central controller receive time out transmission failure
244 2. Initialization failure of central
(Receiving time : 3sec ˦) between central controller and CNU
controller
Solution Check
time controller 1) Check system setting address of central controller and actual address is matched or not
2) Re-start service program(engine) of central controller
3) Replace CNU
Data receiving failure of central 1. CNU defect
246 Central controller Receive Timeout controller from CNU within 2. Initialization failure of central
designated time controller
Test functions
170 _LG Air Conditioners System Troubleshooting Guide for each Error Code_ 171
3.1 How to check main control box?
(a) Plus
Basic Part
2 6
4
3
5
Troubleshooting
Guide for each
Error Code
1
Component Check
Electrical
No. Part Check
How to check? Counter-measure
(Function) points
3. Electric
1 T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within 380·10% -Check supply power
(Terminal - Voltage of 1ɐ(R-N,S-N,T-N) should be within 220·10%. and connection
Block, - Voltage fluctuation should be within 10V condition
Input - While stand-by and in operation,
Component Check
power)
Solution Check
Voltage drop should be within 10V
Test functions
Check ȳ - Resistance of R-S,S-T,R-T,R-N,S-N should be -Check short or not of
(In case more than a few ༮ Control box (Noise
power filter, PCB, cables)
is not - Resistance of T-N should be within 40~50˟ - Replace transformer
supplied) (Main transformer of outdoor)
2 FUSE Check - Voltage of fuse should be within 0~1V -In case of 220V,
(Protect disconnection Fuse is disconnected.
over- of FUSE Replace FUSE
loaded (when power
current) is supplied)
172 _LG Air Conditioners System Electrical Component Check_ Electrical Component Check_ 173
(a) Plus (a) Plus
3 Nose filter Check voltage -Voltage of each connector (R-R,S-S,T-T) should - In case of 220V 5 EOCR Time, Current -Rotary switch setting should be correct
(Noise emit & (When power be within 0~40V It is disconnected (Cut off over- Rotary (Current:30~40A, Time:5sec)
Basic Part
protect) is Replace noise filter loaded switch Setting
Supplied) current to
protect TIME
constant
compressor)
Current(A)
Troubleshooting
Connection -R cable and T cable should be connected each other
out circuit to
drive valves
Check ȳ -Resistance of each connectors (R-R,S-S,T-T) -In case resistance is 8. JIG transmission
(In case power should be within 0~10˟ ˳, noise filter is connector
Component Check
Is not supplied) disconnected. 18. 7- segment display
Replace noise filter 13. Central control signal &
Electrical
on-board writing circuit
4 Magnet Magnet switch -When check resistance of 1st coil of magnet switch, -In case resistance is 1. MICOM circuit
9. Pressure, temperature sensor
switch 1st coil resistance should be 0.47 ༮ ˳ or 0 ˟, circuit
(When power is not supplied) Replace Magnet 15. FAN transmission circuit
When magnet switch is on, voltage should be 220V switch
17. Outdoor option setting switch
(When power is not supplied)
-When voltage is not 14. compressor transmission circuit
Solution Check
220V, magnet switch
is melt down 16. Auto-Addressing
- Replace magnet 11. I/D˩O/D transmission
switch circuit
4. Power Trans In
connector
12. O/D˩O/D transmission
circuit
Test functions
6. AC 220V power 5. AC voltage sensing circuit 7. Power Trans Out connector
connector for (T-N input voltage check)
** check point of 1st coil of magnet switch central control
Magnet switch -While pressing green button of magnet switch, - Replace magnet Defect Check point How to check? Counter-measure
connection Voltage of each connectors should be 0V or switch
No power 2.Power terminal -Input voltage should be 220V. -Check fuse(3.15A), T-N voltage
check Resistance should be 0~1˟
at PCB (when power is supplied) -If resistance is 0~100˟ , replace
(In case power (Warning: power should not be supplied)
2.Power terminal -Input resistance should be more than PCB
is not supplied)
a few ༮(when power is not supplied)
7.Transformer -Output voltage should be 14V,9V -Check transformer and connection
No trans- 11.I/D˩O/D -DC voltage of connectors should be -Replace PCB, transformer and
mission 12.O/D˩O/D various (-7V~+7V) check connection points
14.Inverter -Yellow LED should blink. -Check Main / Inverter compressor PCB
compressor and
15.Inverter fan -Green LED should blink connection points
-Check Main / Inverter fan PCB
In case 3. AC 220V -Voltage of PCB should be 220V at LGMV -Replace PCB and check connection points
PCB AC output to drive -Replace PCB and check connection points
power valves and -Output voltage should be showed as
output is below
others
0
Sensor(5V), Cooling fan(12V),LEV(12V)
Basic Part
(Supplies is not supplied) connection points
2.4 ˟ 0.25 ˟
power to PCB
and
transmission)
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
42 ˟
Component Check
voltage 2nd side : 14V, 9V(AC) and check 1 4
3
Electrical
(when power is connection points
supplied)
Solution Check
1 T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within 380·10% -Check supply power
(Terminal - Voltage of 1ɐ(R-N,S-N,T-N) should be within 220·10%. and connection
Block, - Voltage fluctuation should be within 10V condition
Input - While stand-by and in operation,
power)
Voltage drop should be within 10V
Test functions
Checking points of 3ɐ(R-S) Checking points of 1ɐ(R-N)
Basic Part
Inverter
protect) is Replace noise filter PCB Comm.
Supplied) LED
Reset button
Const. Comp.
Central controller
Troubleshooting
High Pr. Switch
Check ȳ -Resistance of each connectors (R-R,S-S,T-T) -In case resistance is Const. Comp. Liquid Valve
Inv discharge,
Inv. Comp. Liquid Valve
HEX1, HEX 2
(In case power should be within 0~10˟ ˳, noise filter is
Component Check
AC Fan Power Supply
Sensors
Is not supplied) disconnected. Const. Comp.
Magnetic Switch
Electrical
Replace noise filter Hot Gas Sol. Valve
Outdoor air,
Constant Comp Heater Suction temp.,
3 Magnet Magnet switch -When check resistance of 1st coil of magnet switch, -In case resistance is Constant comp.
Inv. Comp Heater
switch 1st coil resistance should be 0.47 ༮ ˳ or 0 ˟, 4-Way Valve
discharge
sensor
(Constant (When power is not supplied) Replace Magnet
speed When magnet switch is on, voltage should be 220V switch 220V Power
compressor) (When power is not supplied)
Input
Solution Check
220V, magnet switch Jig Power High Pressure
Terminal, 220V Constant Comp. Sensor
is melt down Current Sensor Low Pressure
Sensor
- Replace magnet
Communication
switch terminal
Test functions
No power 2.Power terminal -Input voltage should be 220V. -Check fuse(3.15A), T-N voltage
** check point of 1st coil of magnet switch
at PCB (when power is supplied) -If resistance is 0~100˟ , replace
2.Power terminal -Input resistance should be more than PCB
4 CT Current Current to -Check wiring a few ༮(when power is not supplied)
Sensor Constant
Compressor
No trans- I/D˩O/D -DC voltage of connectors should be -Replace PCB and
mission O/D˩O/D various (-7V~+7V) check connection points
14.Inverter -Yellow LED should blink. -Check Main / Inverter compressor PCB
compressor and
connection points
Basic Part
DC voltage not supplied) should be more than a few ༮ less than normal spec.
for inverter
compressor)
3 * Check values at both
terminal of capacitor
4 2
Troubleshooting
Guide for each
Error Code
DC charging - Charged voltage of between terminals of - Check input voltage and
voltage capacitor replace capacitor
(When power is (= between IPM P-N terminal = DC link
1 supplied) terminals)
Trouble Shooting Guide Book
Component Check
PCB start-relay switch & sensing & circuit to main for reverse phase
drive circuit power-relay display circuit PCB of input power
Electrical
drive circuit
Solution Check
1 T/BLOCK Check voltage - Voltage of 3ɐ(R,S,T) should be within 380·10% - Check supply voltage
(Terminal (When power - Voltage of 1ɐ(R-N,S-N,T-N) should be within & connection points
block, Power is supplied) 220·10%. Check noise filter, 1. MICOM
input) - Voltage fluctuation should be within 10V fuse circuit
- While standby and in operation,
Voltage drop should be within 10V
9. PWM driving
signal output
circuit 8. CT sensing circuit
Test functions
Phenomena Check point How to check? Counter-measure
Checking points of 3ɐ(R-S) Checking points of 1ɐ(R-N)
No power 2.Power -Input voltage should be 220V. - Check & replace fuse(3.15A),
2 REACTOR Resistance of - Resistance of reactor should be within 1~3˟ - In case resistance is at PCB (when power is supplied) T-N voltage (220V)
(DC voltage connectors & (When power is not supplied) ˳, coil is -Input resistance should be more than a few ༮ - If resistance value is 0~100˟ ,
connection (when power is not supplied) replace PCB
stabilization) - Voltage between terminals of reactor should be disconnected.
condition No 6.Transmission -Yellow LED should blink. - Check yellow LED blinks or not
within 0~1V (When power is supplied) Replace reactor
transmission circuit to main - When is OFF, check transmission
PCB with main PCB and replace
Malfunction of 9.PWM signal -Green LED should blink. - Replace PCB
inverter cable -Check IC port coupler
compressor of PWM drive
(when power is
not supplied) 1-2 Diode : 1.0V 2-3 Diode : 1.4V
Inverter Red LED -When red LED blinks. -Check error code displayed at
compressor Error displays about inverter compressor PCB main PCB
***Reactor for INV compressor Reactor for INV Fan PCB Error
5 Inverter 1. MICOM circuit 10. Comm. circuit 7 Inverter 1. PWM signal connector
fan PCB fan
Basic Part
IPM PCB
4. IPM
9. On-boarding 2. Input circuit of 3ɐ &
lighting connector DC rectifying circuit
8. Heat sink
3. In/Output connector
temperature
of reactor
sensor connector
2. DC supply terminal
Troubleshooting
Guide for each
7. PWM (DC310V)
Error Code
drive circuit 4. DC-Link output voltage
6. SMPS power
Trouble Shooting Guide Book
Component Check
Phenomena Check point How to check? Counter-measure
Electrical
Phenomena Check point How to check? Counter-measure
No power 2.3ɐ power - Input voltage of 3ɐ 4 wires should be -Check supply voltage, noise
on PCB Input circuit 3ɐ 380V, 1ɐ 220V Reactor 1 filter, fuse Inverter fan 1.PWM signal - Check 9pin connectors - Replace cables & check
R, S, T, N
- Check half wave rectifying circuit diode -Replace inverter fan PCB is not rotating 2.Fan DC power - DC voltage should be charged of 310V soldering condition of PCB
(R-Reactor1: 0.6V, S-Reactor1: 0.6V: 3.Outdoor - While Fan operating, in case voltage of - Replace connectors & inverter
T-Reactor1: 0.6V) fan connector connectors(U-V,V-W,U-W) is 100~300V PCB if not charging
˧ Normal
4. IPM - Check Diode(P-N : 0.95V, - Replace inverter IPM PCB
Solution Check
P-U,P-V,P-W: 0.55V
N-U,N-V,N-W: 0.55V
No 10. Transmission -Yellow LED should blink. -Check yellow LED blinks or not
transmission circuit with main -When is OFF / ON continuously, Check DIODE(P-U : 0.5V)
PCB
Test functions
check transmission with main PCB
Inverter fan Red LED -When red LED blinks, error code happens -Check error code at main PCB
PCB error about inverter fan PCB 8 IPM Check voltage
& resistance
of
6 3ɐ Check voltage & each phases
DIODE resistance of (When power
each phases is not
(when power is supplied)
not supplied)
P-U :DIODE(0.4V) P-V :DIODE(0.4V) P-W :DIODE(0.4V)
resistance(a few ༯) resistance(a few ༯) resistance(a few ༯)
P-U :DIODE(0.4V) P-V :DIODE(0.4V) P-W :DIODE(0.4V)
resistance(a few ༯) resistance(a few ༯) resistance(a few ༯)
Basic Part
4
3
1 700 DC
Link
Troubleshooting
Guide for each
Error Code
DC 15V
Output N- Phase
terminal Terminal
PFC
R- Phase
On-boarding
Trouble Shooting Guide Book
(To Diode)
terminal
R- Phase
Terminal
(From Noise
filter)
Component Check
T- Phase
Electrical
Terminal
(From Noise
filter)
Solution Check
REACTOR Resistance of - Resistance of reactor should be within - In case resistance is
(DC voltage connectors & 1~3˟ ˳, coil is disconnected. Phenomena Check point How to check? Counter-measure
stabilization) connection (When power is not supplied) Replace reactor
condition - Voltage between terminals of reactor should No power 2.Power -Input voltage should be 220V. -T-N voltage (220V)
be within 0~1V (When power is supplied) at PCB (when power is supplied)
-Input resistance should be more than a few -If resistance value is 0~10,
༮ (when power is not supplied) replace PCB
Test functions
No transmission 10.Transmissio -LEDs should blink. - Check LED blinks or not
(Main PCB) n circuit to - When is OFF, check
3ɐ DIODE Check voltage & main, fan PCB
-In case the measured value is different from the (Fan PCB) transmission with main, fan
resistance of PCB
table, set multi tester to resistance mode
each phases
and measure. If the value is small (0 ȳ) or high
(when power is
(hundreds M ȳ), PCB needs to be
not supplied) replaced. Inverter 12. PWM LED -When red LED blinks. -Check error code displayed
- In case that bridge diode is damaged, check if compressor PCB PWM is normal at main PCB
inverter PCB assembly (IPM) is needed to be Error
replaced.
4 Inverter
fan PCB 10 11
Basic Part
10 11 12 6 12
9
5 8 7
7 8 5
Troubleshooting
Guide for each
Error Code
4
3 6 3
Trouble Shooting Guide Book
Component Check
1 1
2
Electrical
Phenomena Check point How to check? Counter-measure
Solution Check
check* and Fan PCB
NO Name Function NO Name Function
* IPM check: [CN CD_LINK] 1 T/BLOCK 3 phase 4 line power input 1 T/BLOCK 3 phase 4 line power input
After
disconnecting Excessive electric blockade
all connector 2 FUSE 2 FUSE Excessive electric blockade(30A)
(30A)
3 Noise filter Block and discharge noise 3 Noise filter Block and discharge noise
Test functions
- - - 4 MAIN PCB
product
No 10. Transmission -Yellow LED should blink. -Check yellow LED blinks or not
5 FAN PCB BLDC FAN control 5 FAN PCB BLDC FAN control
transmission circuit with -When is OFF / ON continuously,
Inverter PCB check transmission with main
6 COMP PCB BLDC COMP control 6 COMP PCB BLDC COMP control
PCB
Basic Part
1.CN06 7.CN_POWER2
[MAIN>COMP 3.Power supply [louver power supply]
Communication]
LED01K
(FAN>INV
12. LED01,02K communication)
8.SW01M,02M,03M
Troubleshooting
Guide for each
5.CN04 [PCB JIG check]
Error Code
11. Function key [high pressure switch 9.CN_WIRTE
& Power-Relay] [on boarding light]
10.CN_M1S,M2S
2.CN_DC LINK [louver signal input]
Trouble Shooting Guide Book
Component Check
[PCB power 12.CN_MOTOR1,2
supply) [louver signal output]
Electrical
13.CN_FAN
[FAN signal output)
9.CN02 8.CN IIPM 7.CN GATE1,2
[DC LINK sensor] Situation Monitoring Location How to check? Counter-measure
10.CN14
Power does 1.CN POWER -AC voltage measure 220V -Input voltage (220V)
[COMP output sensor]
Solution Check
not turn on
3. Power supply (CH105) - ZNR01D( barrister ),FUSE burn out -Replace related parts
checkup
Monitoring
Situation How to check? Counter-measure FAN motion 2.CN_DC LIINK -DC 470V~520V displays - Check and replace CAPACITOR
Location
disabled -DC 380V and above are normal - Replace PCB
PCB power does not 4.CN01 -input voltage must be 220V (power on) -LINE FUSE(3.15A)
turn on 13.CN_FAN(CH106) - U,V,W electric flow measurement Check up and replace connection
(CH52) manage after checking input
11.CN_SENSOR(CH67) stabilize and motor
-input resistance is over ༮.(power off) voltage 220V
-Check connectors
-replace PCB if the resistance is
Test functions
0~100˟ communicat 6. CN-COMM -Flick LED01K -Check PCB power supply(220V)
ion does (CH105) - check connector and PCB (power -Check and replace connector and
not work supply ,communication) PCB
Communication does 1.CN06 -yellow LED(LED01,02K)must flick. -check communication and FAN
not work 2.CN09 PCB and MAIN PCB if the yellow
Louver does 4.SW_SEL -Check if connector is connected - connect connectors (if there are no
(CH52) LED is flick or OFF (check
not work louver)
connection and replace PCB)
7.CN_POWER2 -DC24V display check -Check and Replace trance and
COMP malfunction 10.CN14 -constant COMP output U(-),V(-),W -replace after checking PCB and power supply
COMP if the difference is over 2A
10.CN_M1S,M2S -Connection status check -Check and replace louver motor
9.CN02 -DC voltage within 470V~520V and connection part
-replace after checking CAPACITOR
and PCB 12.CN_MOTOR1,2 - Connection status check - Check and replace louver motor
8.CNIPM -check connection status and connection part
7.CN_GATE
(CH21 Replace and check motor and
connection
CH22 *BLDC motor monitoring method
CH23) 1 2
3 4 Ha(4),Hb(3) - Gnd(2) : 24MOhm
Ha(4),Hb(3) - Vcc(1) : 11KOhm
Deficiency error 3.CN05 -3 point power line (noise filter latter part) - Readjust and Replace after Vcc Gnd
(CH54) over 380V checking FUSE, input power , Hb Ha
connection line
Basic Part
Value of main PCB
5. Sensing part main display Value Main PCB
5 sec later after power input,
[pipe] PCB in (At the
outdoor moment that 4X Main model name
6.CN_REMO unit power is 50 Sub1(when connected)
[remote control supplied) 50 Sub2(when connected)
power &
communication] XX Total operation capacity in Hp
Troubleshooting
Guide for each
(Ex: 20 Hp 20)
Error Code
7.CN_HVB
12.CN_DRAIN [plasma] 25 Normal state
[Drain pump 11.CAPACITOR 9.CN_VANE1,2 8.CN_DISP Others : PCB checking mode
Output part_220v] [internal$ external]] [louver operation] [reception part PCB 22 In case of R22 refrigerant
10.CN_LEV connection port] R410A: 41
Trouble Shooting Guide Book
* Outdoor unit communication PCB front side Outdoor unit communication PCB backside
Component Check
* When there is
communication error(U01Y)
Electrical
1 8
2 7
14.CN_A5 3 6
[indoor PCB 4 5
connection] DIODE MODE measurement
8-1,2,3,4 : 1.2V
5-1,2,3,4 : 0.7V
Communication
Solution Check
Connection (A,B)
Monitoring
Situation How to check? Counter-measure Outdoor
Location
PCB, remote control 13.CN_POWER -input voltage must be 220V.(power on) -manage and check input voltage 220V sub unit
power does not come - Barrister (ZNR01N),FUSE,,PCB check -replace and check relate parts PCB display
on Value Sub PCB
(When power
Communication does 14.CN_A5 -check connection -readjust and check connection is supplied)
not work
LED 8 7 6 5 4
communication -Check connection PCB latter U01Y -Replace and check IC(DIODE) display
Test functions
PCB -- green LED flick (flick initially) -Replace after checking communication condition) LED 3
PCB and indoor unit PCB power supply
LED 2
Outdoor unit motor 1.CN_MOTOR -Error CH10(FAN LOCK) when it does not -replace and check motor and
does not work operate after remote control operation connection LED 1
11.CAPACITOR -DC 310V is recharged Replace CAPACITOR
Basic Part
main display Value
PCB in (At the
outdoor moment that
unit power is
ON supplied)
1. Main unit
Troubleshooting
DIP RE Function Method / description
Error Code
1 X Cooling operation control No. 1 ON push RED button 3 times for 3 sec.
display 01, 0F by turns (#1 indoor unit OFF)
Push BLACK button for 3 sec.
Trouble Shooting Guide Book
Component Check
display 02, 0F by turns (#2 indoor unit OFF)
(go on…)
Electrical
1 O SAVE MODE No.1 ON RESET
/ Target high pressure down, target low pressure up
Solution Check
3 O Inverter compressor BACKUP No.3 ON RESET
Factory setting value is displayed in 7 segment on PCB for 24sec.
operation / while inverter compressor failure, operate more than indoor unit All dip switches must be set properly before step 1.
capacity (SINGLE:70K,SERIES:110K)
3,4 O MAIN UNIT BACKUP No.3, No.4 ON RESET / when MAIN unit failure
Test functions
5 O Cooling operation LOCK No.5 ON RESET / locking cooling operation mode
7 X Forced oil return operation No.7 ON Push BLACK button for 2 sec. display 01(Oil return)
2. Sub unit
DIP RE Function Method / description
s/w SET
Outdoor unit
PCB DIP ඞ Dip switch Setting ඞ
switch
Basic Part
1 2 3 4 5 6 7 8 9 10 11 12 13 14
ON
8 7 6 8 7 6
OFF
1. Main unit
Troubleshooting
Guide for each
Error Code
No. RESET Function Dip Switch
Component Check
Target high pressure Up, target low pressure down
Electrical
4 0 Longest Pipe length No.1, No.2 , ON
Solution Check
7 0 Forced Cooling operation No.5 ON
10 0 Snow No.8 ON
Test functions
13 0 Outdoor unit fan low static No.12 ON
pressure compensation
Outdoor unit ඞ Dip switch Setting ඞ Inverter compressor drive current (When compressor is starting)
PCB DIP
- Driving current fluctuation of Inv. compressor should be less than 2A(Plus)
switch
Basic Part
1 2 3 4 5 6 7 8 9 10 11 12 13 14
ON
8 7 6 8 7 6
OFF
Troubleshooting
Guide for each
Error Code
No. RESET Function Dip Switch Check current of U phase Check current of V phase Check current of W phase
Component Check
Electrical
3. Settings of corresponding outdoor unit
Compressor
1 0 Inverter comp. back-up No.3 ON Check resistance of INV,constant compressor
Solution Check
INV, const. speed comp. resistance :INV COMP ˧ 1.2˟·10%(Plus),
2 0 Unit back-up No.4 ON
U-V: 1.16·7%ȳ, V-W: 1.19·7%ȳ, W-U: 1.21·7%ȳ(plus II)
3 X Pump out No.10, No.14, ON :Constant speed COMP : (U-V)1.96˟/(V-W)1.91˟/(U-W)1.99˟·10%)
Test functions
Resistance between U-W Resistance between V-W Resistance between U-V
4. Solution Check
LEV
Outdoor unit main LEV Outdoor unit sub cooling LEV Indoor unit LEV
Basic Part
3rd part 1. Multi-
Multi-V + Simple Central Controller
LonTalk/ BACnet
2. CAC(Single,Multi) + Simple Central Controller
BMS
Ethernet
Troubleshooting
(TCP/IP)
Error Code
CNU AC Smart
Server SCC
LonWorks BACnet ACP D.C
4. Eco-
Eco-V + Simple Central Controller
Trouble Shooting Guide Book
EIA-485
Component Check
506 6
5. Multi-
Multi-V + ACP + Simple Central Controller
Electrical
Telemetering apparatus
PI485 Interface PDI
SGL Dry Gu|#frqwdfw
contact
UART 6. Multi-
Multi-V + CAC + ACP + Simple Central Controller
LGAP
LG’s A/C
Solution Check
Outdoor unit
7. Multi-
Multi-V + Eco-
Eco-V + CAC + ACP + Simple Central Controller
Indoor unit
Multi V
Remote
Multi MPS Single CAC Ventilator
8. Multi-
Multi-V + Eco-
Eco-V + AC Manager + ACP
controller
Test functions
200 _LG Air Conditioners System Solution Check_ 201
㶢 Multi-V+ Simple central controller. 1ea [ 1 Line wiring ] 㶢 Multi-V+ Simple central controller. 2ea [ 1 Line wiring ]
Rotary DIP PI485 Indoor unit Rotary DIP PI485 Indoor unit
Basic Part
switch switch Controller DIP switch Outdoor – Indoor unit connection address switch switch Controller DIP switch Outdoor – Indoor unit connection address
setting setting setting (*) setting setting setting setting (*) setting
Troubleshooting
Guide for each
Master Series 2
Error Code
[0] 1,2 ON Series 2 [04] … [07] [0] 1,2 ON [04] … [07]
& &
IDU IDU
Series 2 [09] … [0B] Series 2 [10] … [13]
Trouble Shooting Guide Book
Component Check
PI485 PI485
Electrical
Solution Check
(*): incase of using external PI485. See page 257 㶢 Multi-V+ Simple central controller. 3ea [ 1 Line wiring ]
ඟ Process
ྙ Indoor address Setting Rotary DIP PI485 Indoor unit
must be not duplicated switch switch Controller DIP switch Outdoor – Indoor unit connection address
setting setting setting (*) setting
ྚ Install PI485, Wiring RS485 line(Bus Method)
Test functions
ྛ PI485 Dipswitch Setting
Power on [00] … [03]
Check PI485 Red LED blinking. It must equal to number of connected I/U ODU
[0] 1,2 ON Master [04] … [07]
ÆIf different, Check outdoor Auto_addressing Series 2
ྜ Setting Rotary switch on Simple central controller. &
IDU
same to the 1st digit of connected indoor unit address [10] … [13]
Series 2
ྜྷ Setting Dip switch on Simple central controller Slave
[1] 2 ON
Turn the power ON: No need [14] … [1F]
PI485
After 3 Minutes (Searching Time)
Simple central controller must recognize all indoors [20] … [23]
(you can check by pushing total On + Total Off + 13)
[2] 2 ON Slave
If not recognize all indoors, repeat upper process [24] … [2F]
Rotary DIP PI485 Indoor unit Rotary DIP PI485 Indoor unit
Basic Part
switch switch Controller DIP switch Outdoor – Indoor unit connection address switch switch Controller DIP switch Outdoor – Indoor unit connection address
setting setting setting (*) setting setting setting setting setting
[00]
[00] … [03] [01]
[02]
Troubleshooting
ODU
Error Code
[0] 1,2 ON Series 2 [04] … [07] [0] 1,2 ON
& PMNFP14A0, [03]
IDU
[10] … [13] [04]
Trouble Shooting Guide Book
Series 2
[05]
[1] 2 ON Slave [1,4,5 ON]
No need [14] … [1F]
Component Check
or
PI485 [06]
Electrical
[20] … [23] [2,4,5 ON]
(*)
[2] 1,2 ON Master Max. 16 indoor unit
[24] … [2F]
Solution Check
(*): incase of using external PI485. See page 257
(*) The DIP switch setting must follow to below table:
Test functions
204 _LG Air Conditioners System Solution Check_ 205
㶢 Multi V + CAC (Multi/ Single) + Simple central controller. 2ea 㶢 Ventilator + Simple central controller. 1ea
Rotary DIP PI485 Indoor unit Rotary DIP PI485 Indoor unit
Basic Part
switch switch Controller DIP switch Outdoor – Indoor unit connection address switch switch Controller DIP switch Outdoor – Indoor unit connection address
setting setting setting setting setting setting setting (*) setting
Troubleshooting
Guide for each
& PHNFP14A0
Error Code
Master [0] 1,3 ON
[0] 1,2 ON
Multi V IDU
[04]
Series 2
[04] … [07]
Trouble Shooting Guide Book
[3,4 ON]
No need
PI485
[09]
[1] 2 ON Slave
Component Check
[10]
Electrical
PMNFP14A0, [11] [0C]
[12]
[1,4,5 ON]
[13]
or
[14]
Solution Check
[15]
[2,4,5 ON]
ඟ Process
(*)
[16] ྙ Dipswitch setting on Eco-V Main PCB, Power On
ྚ Eco-V address Setting.
ྛ Install PI485, Wiring RS485 line (Bus Method)
Test functions
ྜ PI485 Dipswitch Setting
(*): incase of using external PI485. See page 257 Power on
(**) The DIP switch setting must follow to below table: Check PI485 Yellow LED blinking.
ྜྷ Setting Rotary switch on Simple C.C.
ྞ Setting Dip switch on Simple C.C. and Power on.
ྟ wait for 3 Minute (Searching Time)
(you can check by pushing total On + Total off + 13)
Rotary DIP PI485 Indoor unit Rotary DIP PI485 Indoor unit
Basic Part
switch switch Controller DIP switch Outdoor – Indoor unit connection address switch switch Controller DIP switch Outdoor – Indoor unit connection address
setting setting setting (*) setting setting setting setting (*) setting
[00] [00]
PHNFP14A0
Troubleshooting
Guide for each
PHNFP14A0
Error Code
[0] 1,3 ON Master [0] 1,3 ON Master
[0F] [0F]
[3,4 ON]
Trouble Shooting Guide Book
[3,4 ON]
[10] [10]
[1] 3 ON Slave [1] 1,3 ON Master
Component Check
Electrical
[1F] [1F]
Solution Check
ඟ Process
ྙ Dipswitch setting on Eco-V Main PCB, Power On
ྚ Eco-V address Setting.
ྛ Install PI485, Wiring RS485 line (Bus Method)
Test functions
ྜ PI485 Dipswitch Setting
Power on
Check PI485 Yellow LED blinking.
ྜྷ Setting Rotary switch on Simple C.C.
ྞ Setting Dip switch on Simple C.C. and Power on.
ྟ wait for 3 Minute (Searching Time)
(you can check by pushing total On + Total off + 13)
Basic Part
switch switch Controller DIP switch Outdoor – Indoor unit connection address switch switch Controller DIP switch Outdoor – Indoor unit connection address
setting setting setting (*) setting setting setting setting (*) setting
Troubleshooting
Guide for each
PMNFP14A1 Series 2
Error Code
[0] 1,3 ON [04] … [07] [04] … [07]
&
IDU
[1,4,5 ON] Series 2 [10] … [13]
Trouble Shooting Guide Book
PHNFP14A0 [08]
[0] 2 ON Slave No need
[14] … [1F]
Component Check
PI485
Electrical
[0C]
[3,4 ON]
[1] 2 ON Slave
Solution Check
㶢 Air conditioner + Ventilator 㶢 Multi-V+ ACP + Simple central controller. [ 2 Line wiring ]
+ Simple central controller [2 line wiring]
Rotary DIP PI485 Indoor unit
Rotary DIP PI485 Indoor unit switch switch Controller DIP switch Outdoor – Indoor unit connection address
switch switch Controller DIP switch Outdoor – Indoor unit connection address setting setting setting (*) setting
setting setting setting (*) setting
Test functions
[00] … [03]
[00] … [03]
ODU
[0] 2 ON Slave Series 2 [04] … [07]
[0] 1,2 ON &
[04] … [07]
IDU
Series 2 [10] … [13]
No need
PI485 [14] … [1F]
PHNFP14A0 [00]
[0] 1,3 ON [1] 2 ON Slave
[0F]
[3,4 ON]
Basic Part
switch switch Controller Outdoor – Indoor unit connection address switch switch Controller DIP switch Outdoor – Indoor unit connection address
DIP switch
setting setting setting setting setting setting (*) setting
setting (*)
ODU
Series 2 [00] … [03] PMNFP14A0, [00] … [03]
&
Troubleshooting
Guide for each
IDU
Error Code
[04] … [07] [04] … [07]
Series 2 [1,4,5 ON]
No need
PI485
or [08]
[09]
Trouble Shooting Guide Book
PMNFP14A0,
[2,4,5 ON] [0F]
[0] 2 ON Slave [0] 2 ON Slave
[10]
Component Check
(*)
[11] [10]
[1,4,5 ON]
Electrical
PHNFP14A0
[12]
or
Solution Check
㶢 Multi-V+ CAC + ACP + Simple central controller. [ 2 Line wiring ] 㶢 Multi-V+ ACP + Simple central controller. [ 2 Line wiring ]
Rotary DIP PI485 Indoor unit Rotary DIP PI485 Indoor unit
switch switch Controller DIP switch Outdoor – Indoor unit connection address switch switch Controller DIP switch Outdoor – Indoor unit connection address
setting setting setting (*) setting setting setting setting (*) setting
Test functions
[00] PMNFP14A0,
[00]
[3,4 ON]
Basic Part
wGX [_\G
wG[ ZÞ Z_W}
Troubleshooting
Guide for each
Error Code
…
wp[_\
…
Trouble Shooting Guide Book
Component Check
Electrical
~G wkp
juv|{mhu
㶢 Power Distribution Indicator
Solution Check
Test functions
214 _LG Air Conditioners System Solution Check_ 215
Not connect to Central controller
zGY jGGGUGvGGGGX]
B. Trouble shooting
Basic Part
OGwkpGG|P
Troubleshooting
Guide for each
ZÞ Z_W} … Case A4: indoor unit can’t be controlled by S.C.C but ACP
Error Code
Case B1: impossible to access ACP Web
Case B2: ACP access is not stable
Trouble Shooting Guide Book
Component Check
…
Electrical
Solution Check
OGwkpGGtP Case E1: Ventilator communication error
Use PMNFP14A1 PI485 Gateway
Test functions
ZÞ Z_W} …
wtumwX[hX
tG⯜☐
pTGGU
…
㤸⥙⣽᷸ 㤸⥙䖐㐐ὤ
Basic Part
ACP can not control a address duplicated indoor unit (20)
r
ro
Er
Troubleshooting
Guide for each
20 21 22 23
Error Code
Trouble Shooting Guide Book
10 11 12 20
r
r ro
E
Component Check
Electrical
II. Reason and Solving:
Indoor units
Solution Check
(242) error
20 24
address wrong setting Y
check and setting
(duplicate, not in-
address again
range)
N
Address re-setting (+ central controllers power reset)
Test functions
indoor unit power Y check power (220V)
supply (not plug-in,
and re-plug in
fuse blow)
N
Basic Part
Check if the power cord is not plugged in or Fuse is blown out A failure PCB doesn’t sound “Bip” when reset main power.
Check and replace with new one with proper P/No.
You need to set the indoor unit address and do Auto-addressing
on Outdoor unit again.
r
ro
Troubleshooting
Guide for each
Er r
Error Code
r ro
20 21 22 23 E
Trouble Shooting Guide Book
20 21 22 23
Component Check
10 11 12 24
Electrical
10 11 12 24
Solution Check
220V
Test functions
Buzzer
Basic Part
Check if the Auto-addressing function return correct number of (242), can not control by central controller.
indoor units.
Incase of incorrect, check the connection line between O/U and
I/U, and indoor unit main PCB.
Troubleshooting
Guide for each
Error Code
Do auto-addressing on this outdoor unit
Trouble Shooting Guide Book
r
ro
Er
Component Check
Electrical
20 21 22 23
10 11 12 24
Same Outdoor unit
Solution Check
Press the switch of the Display number of
outdoor unit (SW02V) connected indoor unit II. Reason and Solving:
for 5 seconds.
In this case, the reasons mostly come from PI485
Test functions
Indoor units
(242) error
Y
PI485 failure Change PI485
Basic Part
The DIP switch wrong setting cause wrong communication The LED doesn’t blink at all (with power supplied)
between controller and indoor units. Æ replace with new one with proper type.
Æ correct and reset PI485 (press Reset button) (plz report to the QA team also)
Troubleshooting
Guide for each
Error Code
r
ro
Er
Trouble Shooting Guide Book
20 21 22 23
Component Check
Electrical
10 11 12 24
Reset button
Solution Check
PMNFP14A0,
PMNFP14A1
[1,4,5 ON] (*): incase of using external PI485. See page 245
Multi V, Plus
MPS inverter
PMNFP14A0(1)
Test functions
PMNFP14A0,
[2,4,5 ON]
Multi MPS (*)
PMNFP14A0(1)
LED2G(Yellow), LED3G(Orange)
Normal : LED blinks continuously
Basic Part
Check if the connection to PI485 open or in bad condition. controlled by central controller.
Æ re-wiring
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
r
ro
Er
Component Check
Electrical
20 21 22 23
10 11 12 24
Solution Check
II. Reason and Solving:
Test functions
Indoor units
(242) error
Wrong connection to Y
controller Re-wiring
(Bus_A, Bus_B)
N
Connection is open
Other Master device Y Set to Slave and re-set
exist ? system.
̰ Wrong connection to central controller ̰ Other Master devices exist (Simple central controller)
Basic Part
when connect to central controller, Simple central controller must
RX LED always
bright be set as Slave.
ult
Troubleshooting
a
Error Code
22 r
ro
20 21 23
r
Trouble Shooting Guide Book
lE
Master Al
Component Check
10 11 12 2D
Electrical
TX ׳Bus_B
ult
RX ׳Bus_A Fa
Solution Check
a ult
F
DIP switch: 1st ON- Master 1st OFF- Slave
Test functions
+ reset power of all controllers
Notice : Please reset the power after changing the Hardware setting.
Rewiring
Basic Part
when connect to central controller, Power Distribution Indicator
must be set as Slave. II. Reason and Solving:
PI485 (of I/U 2D) doesn’t connect to the proper S.C.C
(Gr.2)
Æ Re-wiring
Troubleshooting
Guide for each
Error Code
22 r
ro
20 21 23
Indoor units can’t
r
lE
be controlled by
Al
Trouble Shooting Guide Book
10 11 12 2D
Component Check
Not physically Y
connected to proper Re-wiring
Electrical
S.C.C
Master Slave
Office
Solution Check
20 21 22 23
10 11 12 2D
Test functions
Restaurant
Office
20 21 22 23
10 11 12 2D
Restaurant
Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
wGG
Component Check
un
Electrical
II. Reason and Solving: ̰ ACP IP re- setting
Solution Check
ACP IP address 192.168.2.200 192.168.1.200
Problem often comes from ACP IP setting or LAN PC IP address 192.168.1.212 192.168.1.212
cable.
[Before] [After]
Impossible
to access
ACP web
Test functions
Y
ACP’s IP address Re-setting and reboot
wrong setting ACP
N [refer to manual]
MAC address not Y
Do registration
registered
Wrong LAN cable type cause connection failure. Not register ACP’s MAC address.
Basic Part
PC1 can’t access ACP
wjX
ÆRegister ACP’s MAC address to
nV~X
administrator.
Troubleshooting
Guide for each
Error Code
Hub X]\UX_]UXUY_
nV~GX]\UX_]UXUW
Trouble Shooting Guide Book
wjY
nV~Y
Component Check
Electrical
ACP o
X]\UX_]UYUY` X]\UX_]UYUZW
nV~GX]\UX_]UYUX nV~GX]\UX_]UYUW
thjaGG
Solution Check
The cross cable should be within 80m length.
Test functions
234 _LG Air Conditioners System Solution Check_ 235
Case B2: ACP access is not stable Case B2: ACP access is not stable
Basic Part
denied) or very slow.
X]\UX_]UYUY_
Troubleshooting
Guide for each
Error Code
zGshu
o
X]\UX_]UYUY`
Trouble Shooting Guide Book
ult
Fa
[Access is denied] [Access is slow]
Component Check
Electrical
ACP
X]\UX_]UYUY` X]\UX_]UYUZW
pwGG
Solution Check
̰ ACP IP address re- setting
[Ping test to ACP]
Test functions
ACP Web
access is
not stable
Y [refer to manual]
ACP’s IP address Re-setting and reboot
duplicated? ACP
Duplicated IP check method: Instable access can caused by noise from other equipment.
Basic Part
̰ By high voltage source
1. ACP and PC is in same Router/Hub/Switching equipment
Troubleshooting
WU\
Error Code
hjw
Trouble Shooting Guide Book
zG t G
XU\
Component Check
Electrical
&KHFNWR$&3ĜV 0$&$GGUHVV
,IWKLVQXPEHULVQRWWKH$&3ĜV 0$&DGGUHVV
Solution Check
tGGYW
Æ 7KHUHLVRWKHUGHYLFHXVLQJVDPH,3DGGUHVVGXSOLFDWH
̰ By UPS
Ȅ 1RWH$&3ĜV 0$&DGGUHVV&KHFN0HWKRG X
ult
E\XVLQJ$&3ĜV /&' NH\<RXFDQVHOHFWLQIRUPDWLRQ
WKHQ\RXFDQVHHWKH0$&DGGUHVV
UHIHUWRWKH$&3PDQXDO F a
Test functions
2. ACP and PC is not in same Router/Hub/Switching equipment
hjw |wz
Î Request Network Manager about routing table, ARP table and
MAC address \
hjw |wz
Basic Part
changed (Cooling/ Heating Æ Fan, AI…)
Æ Always reset power of controller (ACP and S.C.C) after changing
system configuration.
Troubleshooting
Cooling Æ FAN
Reset power. 10 11 12 2D
Component Check
Electrical
Cooling Æ AI
Reset
Solution Check
II. Reason and Solving:
Operation
auto-change
Test functions
[S.C.C rebooting] [ACP rebooting]
Not reset system after Y
changing S.C.C DIP Reset system power
switch
N
N
PI485’s CN_Dry Y
connector was Insert
inserted?
N
485 nodes is arranged Y
in Star topology Re-wiring
(serial)?
Basic Part
Æ We recommend using adapter (as table below) instead of DC
power from PI485.
Cooling Æ FAN
Troubleshooting
Guide for each
Error Code
20 21 22 23
Cooling Æ FAN
Trouble Shooting Guide Book
20 21 22 23
10 11 12 2D
Component Check
Cooling Æ AI
Electrical
Adapter spec. checking 10 11 12 2D Is CN_Dry connector plugged-in?
Cooling Æ AI
CN_Dry
connector
plug-in
Solution Check
ult
Fa
Test functions
10V, 500mA adapter
d
en
S.C.C 1~4EA S.C.C 5~8EA
1.2A (9V) 2.5A (9V)
m m Note:
o
6708AQ0001B -
R ec Incase of new model PI485 (8pin DIP switch), turn the 5th switch ON
Basic Part
(indoor unit under working normally)
Controller’s 485 port.
Star topology
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
Component Check
Electrical
AC (13) acc pwr 0 kwh
Solution Check
Bus topology
Join
Test functions
II. Reason and Solving:
Eliminate reason caused by 242 error on I/ U
(refer to the previous part for solving first)
Y
I/ U address wrong
Re-setting
d setting?
men
m
co
Re
244 _LG Air Conditioners System Solution Check_ 245
Case D1: some indoor acc. Pwr. is displayed = 0 Case D2: all indoor acc. Pwr. in one group are
displayed = 0
I. Phenomenon:
Setting range of indoor unit address on PDI is wrong. All indoor accumulated pwr. in same group are
Basic Part
displayed = 0
Æ PDI re-setting (refer manual) (indoor unit under working normally)
Troubleshooting
Guide for each
Error Code
20 21 22 23
Trouble Shooting Guide Book
10 11 12 13
Component Check
Pwr. = 0 kwh
Electrical
(Start) Æ (End) AC (10) acc pwr 0 kwh
(10) Æ (12) lt AC (11) acc pwr 0 kwh
au
AC (12) acc pwr 0 kwh
Solution Check
(Start) Æ (End)
(10) Æ (13)
Test functions
[ER-02 no pulse]
Basic Part
Eliminate reason caused by 242 error on I/ U
(refer to the previous part for solving first)
20 21 22 23
Troubleshooting
All I/U acc.
10 11 12 13
Y
Trouble Shooting Guide Book
Component Check
N
Watt meter
Electrical
485 connection to Y
Re-wiring
ACP wrong?
Solution Check
The Start and End address of the power indicator refers to
the first and last address of the indoor unit group. G
Ex) Indoor address "72", "73", "74", "75" ݵ G wkp
ult
Start address: 72 End address: 75.
Fa
Test functions
G
G wkp
Basic Part
II. Reason and Solving:
ACP with version lower than 3.30.3e has poor
function of data update from PDI
20 21 22 23
Troubleshooting
Guide for each
Æ up-grade ACP to 3.30.3e version
Error Code
Check the connection 10 11 12 13
Bus_A, Bus_B
Trouble Shooting Guide Book
Component Check
Electrical
CN_OUTFAN
ih h
Solution Check
ii i
a ult
F
Test functions
ih h
ii i
I. Phenomenon:
Total accumulated pwr. on ACP doesn’t II. Reason and Solving:
Basic Part
match to Watt meter. Setting of Watt meter in PDI is wrong.
Troubleshooting
Guide for each
Error Code
a ult
F
1 w/ pulse
Trouble Shooting Guide Book
Component Check
Electrical
2 W/ P
Solution Check
2 w/ pulse
Test functions
252 _LG Air Conditioners System Solution Check_ 253
Case E1: Ventilator communication error Case E1: Ventilator communication error
Basic Part
Display error 485 cable wrong connection.
Troubleshooting
TX ˩ Bus_A LED02G, 03G
Component Check
Electrical
DIP switch
3,4 ON
Solution Check
II. Reason and Solving:
Vent. error
[Correct]
Test functions
address wrong setting Y
check and setting
(duplicate, not in-
address again
range)
N
485 wrong Y
Re-wiring
connection?
Basic Part
Troubleshooting
Guide for each
Error Code
Trouble Shooting Guide Book
Component Check
Electrical
0: apply PMNFP14A0,
X: not apply PMNFP14A1
PI485 setting method
For Multi V system
Solution Check
[1,4,5 ON]
1,4 ON
Example:
[Correct]
Only the combination Plus II Outdoor unit, Plus II indoor units and
Wide wired remote controller doesn’t require external PI485 in order to
Be sure to reset PCB after setting use Lock function (All/ Mode/ Fan/ Temp. lock)
II. Jumper (CN_Dry) or 5th switch of 8pin DIP switch PI485 setting in order
Test functions
to use Lock function
5. Test functions
(Plus II, Sync II)
(Sync II)
Basic Part
Turn off “No.1 of SW02M of the HRU”
Troubleshooting
Guide for each
Error Code
Reset the power of HRU PCB
Component Check
- Outdoor temp is below 15 : OFF
Electrical
In case of changing 5 DIP S/W of SW01B
of the ODU, reset power of the ODU main
PCB.
Solution Check
Press SW01V of the ODU main PCB
for 5 second
Test functions
This function secures the air flow rate of ODU, in case static pressure has been
Outdoor unit is operating
applied like using duct at fan discharge of ODU.
for 5~30 minutes.
After ODU stopped, the number of IDU Display error on the ODU PCB / HRU PCB
detected is displayed at 7-seg of the ODU - ODU PCB : HR unit No. Valve No.
main PCB for 1 minute (Example: H1 01)
- HRU PCB : ‘200’
Yes
Basic Part
Turn on “No.1 of SW02M of HR unit”
Troubleshooting
Guide for each
Error Code
Enter central control address into each IDU
using its wired remote controller
Trouble Shooting Guide Book
Component Check
corresponding with the central control
Electrical
address of IDU connected to the valve
Solution Check
Reset the power of ODU PCB
Test functions
The number of IDU installed is displayed
No
Equal number of
“IDU and Displayed one”?
Yes
Turn off No.5 of SW01B Check the central control address of IDU
of ODU PCB and HRU
Indoor unit
MEMO
- Pipe Inlet Temp.
- Pipe Outlet Temp.
Outdoor unit
- Suction Temp.
- Subcooling Circuit Inlet Temp.
- Subcooling Circuit Outlet Temp.
- Liquid Pipe Temp.
- Hex Temp.