Professional Documents
Culture Documents
Troubleshooting
Case where alarm code indication is given
Is the YYYYYY
acceleration Can the Can the current
NN NN NN Can the torque NNYYYYYYYYYYY
time correct in acceleration time be limiter (F43) be
relation to the longer? validated? limit be validated?
load?
YYY YYY YYY
YYYYYY
Enter a longer acceleration Enter a larger
time (F07, F08, E10 to E15 Reduce the torque limiter
current limit. (F40, F41, E16 and E17).
and H56).
YYY
Is correct operation obtained? Return the corresponding printed circuit board to us.
NN
Install the inverter separately from the source of noise.
Is there any source of noise near the YYY Take noise suppression measures to the source of
inverter? noise or take noise suppression measures to the
inverter while referring to the user's manual.
NN
Validate the auto-reset function (H04). Is YYY Validate the auto-reset function
acceleration possible? (H04).
NN
Contact us.
-36-
3. Troubleshooting
Case where alarm code indication is given
NN
Replace the control printed circuit board. YEY Return the corresponding
Is correct operation obtained? printed circuit board to us.
NN
(3) Blown fuse The blown fuse alarm is applicable to inverters of 90kW or larger capacities only.
The fuse suppresses secondary disaster such as fire. If the fuse is blown out, operation is impossible. If this alarm is caused, turn the
power off immediately and refer to the following flowchart to determine the cause and replace the inverter.
If this alarm is caused, do not turn the power on again. Contact us.
Is there a grounding fault in the inverter Disconnect cables from the inverter output
Blown fuse output wiring (U, V or W)? YYY terminals (U, V and W) and conduct a Megger
FUS
( Disconnect inverter output cables and
check for continuity to the ground. ) test. Remove grounding faults and replace
with a new inverter.
Is there a grounding fault in the inverter Check similarly to the above description and
output wiring, relaying terminal or motor? YYY remove grounding faults from wiring and
Are there excessive external surges or YYY Take corrective measures against surges and
noises? noises.
NNN
Is there wrong wiring between power
supply terminal wiring of the main circuit YYY IGBT is deteriorated. Replace all IGBTs and
(L1/R, L2/S and L3/T) and inverter output fuses.
wiring (U, V and W)?
NNN
NNN
-37-
3. Troubleshooting
Case where alarm code indication is given
Over-voltage
(4) Over-voltage OV1, 2, 3
NN
Change to the correct value. NO
Is the master/slave setting of
(Refer to the instruction manual
the brake correct?
of the brake.)
YES Change so that three times the
NO deceleration time (F08) is larger than
Replace the brake. Is the brake applied? the measured deceleration time.
YES
YES
NN Is three times the deceleration
Is hunting observed? time (F08) smaller than the
measured deceleration time?
YES
Install the inverter separately from the noise NN
source. Suppress noise of the noise source Is there a noise source near the
NYYY
or take noise suppression measures to the inverter?
inverter while referring to the user's manual.
NN
YYY Can the auto-reset function
Validate the auto-reset function (H04).
(H04) be validated to accelerate?
NN
Contact us.
-38-
3. Troubleshooting
Case where alarm code indication is given
Are fan power supply switching NN Connect the connectors correctly. The fan power supply switching
connectors (CNR and W) Refer to pages 2-14 in the connectors (CNR and W) are applicable
connected correctly? instruction manual. to inverters of 200V class 37kW or larger
capacities or 400V class 75kW or larger
YYY capacities.
Are screws and bolts of the main NN Retighten screws and bolts of the
circuit terminal block tight? terminal block.
YYY
YYY NN
DC common? Is the link voltage correct? Inspect the converter.
NN YYY
If F14 is set at Is restart mode after momentary
Is there a power failure (incl. NN
0 or 1, an LU power failure (function code F14)
momentary power failure)?
alarm is
NN selected?
caused. YYY
YYY
Is the power turned on with the YYY Wait until keypad indication is unlit
control power established
before turning the power on.
(judgment with keypad indication)?
NN
Reset the failure and restart operation. To restart without causing an alarm,
Is there power failure (incl. YYY
change F14 data (restart mode after momentary power failure (mode
momentary power failure)?
selection)) to 3, 4 or 5 according to the load type.
NN
Is there a broken device or poor YYY Replace broken devices and
continuity in the power supply
correct poor continuity.
circuit?
NN
Is main circuit power supply NN
terminal wiring (R, S and T) Connect correctly.
connected correctly?
YYY
Is there phaseloss in the YYY
Correct the phaseloss.
incoming power?
NN
Is 73 (electromagnetic contactor) NN Is the wiring of 73 exciting NN
Correct faults.
turned on? coil correct?
YYY YYY
Is the incoming source voltage NN
Replace the power supply printed Return the corresponding
within the specification range? circuit board with a spare part. printed circuit board to us.
YYY
Is there a load requiring large YYY Examine the power supply system
starting current in the same so that specification requirements
power supply system? are satisfied.
NN
Is operation continues even if the YYY Is the power supply NN Examine the power supply
circuit breaker or electromagnetic
transformer capacity correct? transformer capacity.
contactor is turned on?
NN YYY
Does the inverter capacity
Is the DC link voltage in NN code (function code u96) NN Correct the inverter capacity code
consistency with the link voltage
match the inverter being (function code u96).
displayed at the keypad?
used?
YYY YYY
Replace the control printed circuit
board with a spare part.
-39-
3. Troubleshooting
Case where alarm code indication is given
(6) Phaseloss in input
Phaseloss in input *1: Even if there is phaseloss in the input, the Lin alarm is hard to be caused
LLL (*1) with small loads or if a DC reactor is connected.
YYY
Retighten the screws and *2 Phase-to-phase imbalance ratio (%)
bolts at the terminals to the (Max. voltage (V) - Min. voltage (V))
Are screws and bolts at the =
recommended tightening ×67
terminals tight? Average voltage of 3 phases (V)
torques (refer to the
instruction manual).
YYY
Does the phase-to-
Is the source voltage within the YYY Select an inverter of a
phase imbalance ratio
specification range? larger capacity.
(*2) exceed 3%?
YYY
Is single-phase power
connected to the 3- YYY
Check the inverter model.
phase power supply
specification product?
Select the inverter
Install an AC reactor (option). Or matching the power supply
Is an AC reactor (ACR) used? select an inverter of a larger specification.
capacity.
YYY
Install a DC reactor (option for
Is an excessive load caused YYY Is a DC reactor 55kW or smaller capacities,
periodically? used? standard accessory for 75kW or
larger capacities).
YYY
Replace the control printed circuit
board and power supply printed YYY Return the corresponding
circuit board with spare parts. Is printed circuit boards to us.
correct operation obtained?
Measure the ripple waveform of the DC link circuit voltage. If the
Contact us. ripple is large, select an inverter of a larger capacity.
Phaseloss in output
OPL
YYY
Retighten the screws and bolts at
Are screws and bolts at terminals NN terminals to the recommended
tight? tightening torque (refer to the
instruction manual).
YYY
YYY
-40-
3. Troubleshooting
Case where alarm code indication is given
(8) Overheating of the heat sink
Overheating of the heat sink
NO1
YYY
YYY
YYY
NN
Does the mechanical brake NN Reduce the load. (Using overload early warning (E34), reduce the load
operate? before an overload is caused.)
YYYYY
The load may become larger in winter.
Release mechanical brake.
Adjust the fan damper and pump valve.
Is there a broken wire in the NN Is the inverter capacity YYY Replace the control printed circuit
thermistor wiring (power supply code (function code u98)
board with a spare part.
printed circuit board CN18)? correct?
YYY NN
NN
DC common?
YYY
Refer to the maintenance data of the
Are the fan power supply switching YYY NN keypad to check the cumulative run
connectors (CN R and CN W) on the Is the cooling fan locked?
hours of the cooing fan and replace the
power supply printed circuit board correct?
internal fan.
The fan power supply switching
NN connector is applicable to inverters of YYY
200V class 45kW or larger capacities or
400V class 55kW or larger capacities.
Replace the power supply gate printed Remove obstacles.
circuit board and set the fan power supply
switching connector in the correct position.
-41-
3. Troubleshooting
Case where alarm code indication is given
(9) Alarm from external device
YYY
YYY YYY
YYY YYY
Examine the capacity and Replace the control printed circuit board Return the corresponding
%ED of the braking resistor. with a spare part. printed circuit board to us.
Overheat in inverter
OO3
NO
Improve panel ventilation to keep the
Is the ambient temperature of the NO
ambient temperature in order within the
inverter within the specification range?
specification range.
YYY
YYY
YYY
Is the path of cooling wind blocked? Remove obstacles.
NO
-42-
3. Troubleshooting
Case where alarm code indication is given
(11) Motor protection (PTC/NTC thermistor)
Motor protection
OO4
NO
Is the motor equipped with a
cooling fan?
YYY
Is the input voltage of the
Does the cooling fan of the NO YYY Replace the motor
motor cooling fan within the
motor rotate? cooling fan.
specification range?
YYY NO
YYY
Is the wind tunnel of the
cooling fan free from Examine the power supply
clogging? system.
NON
Clean to remove clogging.
YYY
Can the motor sound (carrier
Is the load excessive? YYY YYY Decrease the carrier
frequency: F26) be
(Measure the output current.) frequency (F26).
decreased?
NO NO
Reduce the load. (Using the
Adjust motor constants Is the mechanical brake overload early warning (E34),
NO Do motor constants (P01* to NO
(P01* to 56* and P99*) to applied? reduce the load before an overload
P56* and P99*) match the
those of the motor to be is caused.)
motor to be used?
used.
YYY The load may become larger in winter.
YYY
NO
Perform auto-tuning (P04*) Is auto tuning (P04*) of motor
Release the mechanical brake. Adjust the fan damper and pump valve.
of motor constants. constants performed?
YYY
Are function codes (H26 and H27) NNNO Adjust function codes H26 and H27 according to the
adjusted according to the PTC/NTC thermistor. Check the specifications of the thermistor and
thermistor? calculate the detection voltage again.
YYY
Are connections of the PTC/NTC NNNO Place SW5 on the control Pt circuit board in the PTC/NTC
thermistor and pull-up resistor and
position.
resistance correct?
YYY
Is the thermistor (H26) set though no NNYYY If no thermistor is used, set thermistor (mode selection) (H26)
PTC/NTC thermistor is used? at 0.
NO
* Take care of the torque
boost (F09) setting. Too large
Is the torque boost (F09*) setting too NNYYY Check the torque boost (F09*) setting and adjust to the best
a setting will cause over-
high? value so that operation continues without stalling.
excitation, possibly causing a
burned motor.
NO
YYY
YYY
-43-
3. Troubleshooting
Case where alarm code indication is given
(12) Charge circuit The charge circuit error is applicable to inverters of 200V class, 37kW or larger capacities and 400V
class, 75kW or larger capacities.
error
YYY
YYY
Is the braking unit connected Is the braking resistor turned
Is the resistance correct?
YYY
correctly? off?
YYY
YYY
YYY Wait until the keypad indication is
Is the circuit breaker turned on and turned off
unlit before turning the power on
immediately to check for safety?
again.
NO
YYY
Are the motor constants (P01* to NNNNN Change the motor constants (function codes
P56* and P99*) correct? P01* to P56* and P99*) to those of the motor.
YYY
Are the characteristics of the electronic
thermal relay and the motor overload Change to the correct level. If adjustment fails,
NNNNN
characteristics correct? invalidate the electronic thermal relay (F11* =
(Is the function code data F10*, F12* 0.00) and connect an external thermal relay.
and P99* correct?)
YYY
Is the operation level of the electronic Check the allowable continuous current of the
NNNNNN
thermal relay correct? (Is the function motor again and examine and correct the
code data F11* correct?) function code setting (F11*).
YYY
Return the corresponding printed Adjust the fan damper and pump valve.
circuit board to us.
-44-
3. Troubleshooting
Case where alarm code indication is given
NO YYY
Are the fan power switching
Is cooling fan ON/OFF control YYY
Is the cooling
connectors (CN R and W) on YYY YYY
(function code H06) selected? fan locked?
the power supply printed
NO circuit board correct?
N0 The fan power switching connector is
Does the internal fan function? applicable to inverters of 200V class
NO
NO 37kW or larger capacities and 400V
class 75kW or larger capacities only.
Replace the power supply gate printed
Refer to the maintenance
circuit board and set the fan power
data at the keypad to
switching connector in the correct
YYY check the cumulative run
position.
hours of the cooling fan.
Replace the internal fan if
necessary.
NO Is the wiring on the main circuit output Within 10min after alarm
side too long? activation?
YYY
YYY NO
Replace the control printed circuit NO
Is the leak current large? Is there a broken wire in the wiring YYY Repair the broken
board with a spare part.
of the internal fan? wire.
YYY
NO
Return the corresponding printed YYY
Install an output circuit filter (OFL). Is the internal fan locked? Remove obstacles.
circuit board to us.
NO
-45-
3. Troubleshooting
Case where alarm code indication is given
(15) Memory error (Er1)
When a memory error occurs, check function code data before turning the power off. If data is correct, merely the backup memory data is
faulty.
Visually inspect the printed circuit board for dust and so on.
If there is an error in the function code data, or if the memory error persists though no error is found, follow the flow chart below to
investigate.
Memory error
EE1
YEY
NN
Check function code data and Replace the control printed circuit Return the corresponding
enter correct data. Then operate. board with a spare part. printed circuit board to us.
! Note When 2 is entered to n00, all function codes including hidden function codes (i01 to i95,
u00 to u99, n00 to n99, k00 to k99 and q01 to q18) are initialized.
Record all function code settings without fail before executing this function , and, after
entering 2 to n00, enter all function codes including hidden function codes (i01 to i95, u00
to u99, n00 to n99, k00 to k99 and q01 to q18) later.
When 2 is entered to u99 (Limited initialization), limited function codes are initialized.
Similarly to the case where 2 is entered to n00, record all function code settings including
i01 to i95, u00 to u99, n00 to n99, k00 to k99 and q01 to q18 without fail before executing
this function, and enter all function codes including hidden function codes (i01 to i95, u00
to u99, n00 to n99, k00 to k99 and q01 to q18) later.
-46-
3. Troubleshooting
Case where alarm code indication is given
NNN
Is there a broken wire or poor YYY Repair the broken wire or poor contact.
contact in the keypad remote After performing alarm resetting, restart
control extension cable? operation.
NNN
Turn the power off temporarily and wait
Is the keypad connector inserted NN until the charge lamp is unlit. Insert the YYY Check parameters and
YYY
securely? keypad connector securely. Is alarm restart operation.
resetting successful after power resetting?
YYY NNN
Turn the power off and wait until Replace the control printed circuit board
the charge lamp is unlit. Turn the or remote control extension cable. Is Alarm (Er2) persists.
power on again. correct operation obtained?
NNN
Take noise suppression measures.
YYY (Check the grounding state, wiring
YYY Is correct data displayed at the Is there a strong effect of
of signal cables, remote control
keypad? noise from the periphery?
extension cable and main circuit
cables and installation method.)
NNN NNN
NN
Replace with another
Replace the keypad, control printed YYY
keypad. Is correct Replace the keypad.
circuit board or remote control extension
operation obtained?
cable. Contact us.
The inverter functions correctly. Continue to Return the corresponding part and
operate. However, if the keypad communication printed circuit board to us.
error persists, replace the keypad, control
printed circuit board or remote control extension
cable. Contact us.
-47-
3. Troubleshooting
Case where alarm code indication is given
(17) CPU error (Er3)
CPU error
ER3
NN
NN
YYY
Is the option card connector
connected correctly to the NN
Connect connectors correctly.
connector of the main body of
the inverter?
YYY
Is an option-related function
code (o code) entered without NN Install the option card. Enter the
the corresponding option correct function code.
card? Are there setting errors?
NN
NN
-48-
3. Troubleshooting
Case where alarm code indication is given
(19) Option error (Er5)
-49-
3. Troubleshooting
Case where alarm code indication is given
(20) Operation procedure error (Er6)
NN
Is the start check function NN Does the operation command pass through the terminal block (F02 = 1)
NN validated (H96 = 2 or 3)? or is it given through communications (H30, y98)?
-50-
3. Troubleshooting
Case where alarm code indication is given
NN
NN Connect correctly
Is the motor connected correctly? according to the
connection diagram.
YYY
Is the operation command or YYY After performing alarm resetting, repeat auto-tuning
STOP key turned on in tuning? (function code P04*).
NN
Keep BX turned off in tuning.
Is the BX terminal turned on in YYY
After performing alarm resetting, repeat auto-tuning
tuning?
(function code P04*).
NN
Keep DWP turned off in tuning.
Is the DWP terminal turned on in YYY
After performing alarm resetting, repeat-tuning
tuning?
(function code P04*).
NN
YYY
Is the motor of a high speed type YYY Do not use auto-tuning. Do not use automatic torque
used? boost (Change F37* to 1).
NN
Examine the layout so that the wiring between the inverter
Is wiring on the output side of the YYY
and motor becomes shorter. Take every possible
main circuit too long (> 50m)?
measure to reduce the wiring length.
NN
NN
Are the settings of the maximum
output frequency (F03*) and NN
Correct data and repeat auto-tuning (function code P04*).
frequency limiter (high) (F15*)
correct?
NN
Is the load too large? YYY Is the mechanical brake NN
(Measure the output current.) applied?
NN YYY
Release the mechanical
Is the acceleration/deceleration Reduce the load.
NNNNNN brake.
time too short for the load?
(Is the current limit activated?) Adjust the fan damper and The load may be larger
YYY pump valve. in winter.
-51-
3. Troubleshooting
Case where alarm code indication is given
(22) RS485 communication error: communication port 1 (Er8). RS485 communication error: communication port 2 (ErP)
NYYY
Is the host (or PLC) turned off? Do not turn the host (or PLC) off.
NN
In case of Er8: Are function codes (y01 to y10) correct? NNN Correct the settings. (Do not allow
In case of ErP: Are function codes (y11 to y20) correct? duplicate addresses.)
YYY
NNN Correct the setting of devices on the
Is the setting of devices on the host side correct?
host side.
YYY
NN
Is operation command given via RS485?
Use the RJ connector of the NN Is the recommended YYY Is there physical broken
10BASE-T cable complying communication cable wire in the communication
with EIA568. used? cable?
YYY NN
Set the terminator selection switch
for RS-485 communication. (Turn NN Are terminators installed NNNN Check for continuity of the
SW2 and SW3 on the control at both ends of the communication cable and the state
printed circuit board on if the station communication cable? of contact.
is at the end of the network.)
YYY
Are there faults (control software, setting or hardware) in NNN Remove the cause of error on the
the host controller (PLC, PC, etc.)? host controller side.
YYY
Is the communication
NYYY NYYY Separate wiring from
Is there a strong noise source around the inverter? cable tied together with
power cables.
power cables?
NN NNNNNNNNN
Enter the response interval Take noise suppression measures at the inverter
Does the response interval of the device NN (function code y09 (Er8) or y19 and host controller. (Check the grounding state
match the transmission/reception switching and wiring of communication cables and main
(ErP)) according to the
time of the RS232C/RS485 converter? circuit cable and installation method.) Replace
specifications of the device.)
the RS232C/RS485 converter with a
recommended one (insulated type).
YYY
For RS232C: is the recommended communication level NNNN Use the recommended
converter used? communication level converter.
YYY
NNNN Change "operation selection at error occurrence (function code y02
Is communication error detection necessary?
(Er8) or y12 (ErP))" to 3 (continue operation).
YYY
NNN
-52-
3. Troubleshooting
Case where alarm code indication is given
(24) Data save error due to under-voltage (ErF)
While data is saved at shutdown, does YYY Check the DC link circuit voltage Remove the cause of the
the voltage drop due to quick discharge
drop time at shutdown. quick discharge.
of the DC link circuit voltage or the like?
NN
Press the RESET key to reset the alarm.
Is there a strong effect of noise from YYY Eliminate the noise
Restore the original frequency and PID
surrounding devices? source.
commands at the keypad and restart operation.
NN
Does the error occur every time when NN Check for errors in the external sequence circuit such
the power is turned on? as the power shutdown circuit.
YYY
NN
-53-
3. Troubleshooting
Case where indication of other than the alarm code is given
(1) "- - - -" center bar indication
Is LED monitor (display selection) E43 NYYY To display other monitoring items, enter
is changed to 10 or 12 while PID
a value other than 10 and 12 to E43.
control is inactive (J01 = 0)?
NNN
NNN
NNN
Is there a broken wire or poor YYY
contact in the keypad remote Repair the broken wire or poor contact.
control extension cable?
NNN
Turn the power off temporarily and
Is the keypad connector inserted NN
check that the charge lamp is unlit.
securely?
Insert the keypad connector securely.
YYY
NNN
YYY
-54-
3. Troubleshooting
Case where indication of other than the alarm code is given
Underscore indication
____
In the program mode of the keypad, refer to menu 5 "Maintenance Data" and select 5_01 to check the DC link voltage.
200VDC or smaller voltages (200V class) or 400VDC or smaller voltages (400V class) cause this indication.
Brackets indication
[ ]
NN
YYY
-55-
3. Troubleshooting
Case where no alarm code indication is given
Abnormal motor operation
(1) The motor fails to rotate
Is the charge lamp lit and Are the earth leakage Turn the earth leakage breaker and
breaker and
The motor fails to rotate. is there LCD indication of electromagnetic contactor on and turn the
electromagnetic contactor
the keypad? turned on? main power on.
YYY YYY
Is the voltage at the main Check for voltage drop, phaseloss, phase-
Turn the earth leakage breaker and YYY
Control power auxiliary circuit power supply
to-phase imbalance, connection faults,
electromagnetic contactor on and terminals (L1/R, L2/S and
input only? poor contact and so on and take
turn the main power on. L3/T) correct? corrective measures.
YYY
Remove the cause of the alarm YYY Is a short bar or DC
Is the keypad indication
and perform alarm resetting and reactor connected
in the alarm mode? Connect the short bar or DC reactor.
operate. across terminals PI and
P(+)?
YYY The power supply gate printed circuit
If no fault is found, continue to Operation command input: board is broken. The cause of breakage
operate. keypad or control circuit may be in breakage of the main circuit.
terminal Contact us.
Are the FWD and REV YYY Supply only one rotation
terminal commands
command input.
supplied simultaneously?
Keypad Control circuit
terminal
YYY
YYY YYY
Cancel operation commands and frequency commands
Is the frequency setting smaller than
Press ∧ YYY having higher priority. Examine relevant settings.
the starting frequency or stopping
to enter the speed.
frequency?
Enter a frequency setting equal to or larger than the starting
frequency (F23*) and stop frequency (F25). Or change the
starting frequency (F23*) or stop frequency (F25) to a correct
Refer to the I/O check menu of the
value.
keypad. Is a frequency setting given?
YYY
Are the peak limit (F15) and bottom limit Change to the correct Enter the frequency
(F16) settings of the frequency limiter
correct?
setting. setting.
YYY
Check the data of function codes (E01 to E09, E98 and
Is the coast-to-stop command (BX)
E99). Use the I/O check to check the input state and
turned on?
remove the coast-to-stop command.
YYY
Is the data of function codes (F04*, F05*, Change the V/F setting according to the
H50 to H53, H65) and H66 correct? motor.
YYY
YYY
Is the motor connected correctly? Correct wiring errors.
YYY
-56-
3. Troubleshooting
Case where no alarm code indication is given
Abnormal motor operation
(2) The motor rotates but the speed does not increase
The motor rotates at about the low slip frequency and the
speed does not increase. While operation continues, an
OL1 or OLU alarm trip is caused.
NN
Is the load too large? (Measure the output YYY Is the mechanical NN
Reduce the load.
current.) brake applied?
YYY
YYY Is the torque boost NN Reduce the torque boost amount
Is the current limit applied?
amount (F09*) correct? (F09*).
YYYYYNN YYYYY
Change the current limiter (mode
Current limiter (mode YYY level) F44 to a correct value or, if
selection): Is F43 set at current limit operation is
2? unnecessary, change F43 to 0
(inactive).
NNYYYY
YYYYYYY
Is the torque limit level data YNN Change function code settings (F40, F41,
correct? E16 and E17) to correct values or cancel.
YYYYYY
Are the bias and gain settings for the frequency setting
correct? NN
Change the bias and gain settings to
(Check the data of F18, C50, C32, C34, C37, C39, C42 and correct values.
C44.)
YYY
-57-
3. Troubleshooting
Case where no alarm code indication is given
Abnormal motor operation
Operation command =
The motor rotates in reverse to terminal block Are the function code settings
Enter function codes (E98 and E99).
the command. (E98 and E99) correct?
YYY
Operation command = keypad
Standard YYY
YYY
YYY
YYY
YYY
-58-
3. Troubleshooting
Case where no alarm code indication is given
Abnormal motor operation
(4) Speed fluctuation or current fluctuation (hunting, etc.) during operation at constant speed
YYY
Is an external frequency Is noise added to the YYY Enter a larger frequency setting filter
YYY
command potentiometer signal cable connected to constant to function codes C33, C38
used? the external device? and C43.
NN
Effects of noise from the circumstances
are probable. Route the main circuit
Is the main circuit wiring YYY cables as separately as possible from
routed near the control
the control circuit wiring. Change the
circuit wiring?
control circuit wiring to shielded or
NN twisted cables.
NN NN
NN
NN
NN
If load fluctuation is large, the motor speed also varies. Check the motor constants
again. After checking the constants, perform auto-tuning.
If the problem persists, contact us.
-59-
3. Troubleshooting
Case where no alarm code indication is given
Abnormal motor operation
Is the carrier frequency NNYYY Change the carrier frequency (F26) to a larger
setting (F26) low? value. Change F27 to the correct value.
NN
YYY
Is the ambient temperature of NN Are motor constants (P01 to YES Change the motor constants to
the inverter high? P08) correct? correct values.
NN
YYY
NN
Reduce the load to reduce the
YYY temperature of the inverter. (In
Is the load too large?
case of the fan and pump, reduce
frequency limiter (high) F15.)
NN
Is the installation accuracy of Perform discrete operation of the Adjust the jump frequency
the load good enough to NN motor to identify the cause of function (C01 to C04) and
cause resonance with the resonance. Improve characteristics avoid continuous operation at
installation base? of the cause side. frequencies causing
resonance.
YYY
Contact us.
-60-
3. Troubleshooting
Case where no alarm code indication is given
Abnormal motor operation
(6) The motor does not accelerate or decelerate in the specified acceleration/deceleration time
The motor does not accelerate or
decelerate in the specified
acceleration/deceleration time
YYYYYYY
NN
Is the data of current limiter
Does the current limit operation NN Is the data of current limiter YYY NN Change the current limiter (mode
(mode level) F44 set at a correct
suppress frequency rise? (mode selection) F43 set at 2? level) F44 to a correct value.
value?
YYYYYYY NN YYYYYYYY
YYYYYY
Change function codes (F40, F41, E16 and
E17) to correct values or cancel.
Is the torque limit switching NN
signal used?
Is the automatic deceleration YYY Enter longer deceleration time (F08, E11,
control active? E13 and E15).
NNYYYY
Reduce the load.
Is the load too large? YYY NN
Is the mechanical brake applied? (In case of the fan or pump, reduce
(Measure the output current.)
frequency limiter (high) F15.)
NNYYYY YYY
The load may become
larger in winter.
Release the mechanical brake.
The motor generation torque is * Take care of the torque boost setting (F09). Too
Increase torque boost (F09). YYY
insufficient. Increase the large a setting will cause excessive excitation,
Does the motor start?
torque boost (F09) to adjust. possibly causing motor burnout.
NNYYYYY
YYYYYYYY
Enter a larger frequency setting filter
Is noise added to the signal YYY
constant at function codes (C33, C38
cable of the external device?
and C43).
NNYYYYY
Noise effects of surrounding devices are probable.
Is the main circuit wiring routed YYY Route the main circuit cables as separately as
near the control circuit wiring? possible from the control circuit wiring. Change
control circuit wiring to shielded or twisted cable.
NNYYYYY
Does inverter noise cause YYY Connect a capacitor across the output
malfunction of the frequency terminals of the potentiometer or install a
command potentiometer? ferrite core around the signal cable.
NNYYYYY
Is the V2/PTC selection switch in NN Place the V2/PTC selection switch on the
the PTC position (thermistor control printed circuit board in the V2
input mode)? position.
YYYYYYY
-61-
3. Troubleshooting
Case where no alarm code indication is given
Abnormal motor operation
(7) The motor fails to restart after momentary power failure though the power is restored
The motor fails to restart after
momentary power failure though
the power is restored
YYY
Is the setting of restart mode after YYY Change the setting of restart mode after momentary power failure
momentary power failure (mode
(mode selection) to 3, 4 or 5.
selection) F14 set at 0, 1 or 2?
NN
YYY
YYY
Contact us.
-62-
3. Troubleshooting
Case where no alarm code indication is given
Trouble on inverter setting operation
(1) The keypad shows no indication
Are the main power Are the earth leakage Turn the earth leakage
supply and auxiliary breaker and breaker and
control power supply electromagnetic electromagnetic contactor
turned on? contactor turned on? on and supply main power.
YYS
Y ES
Check for voltage drop,
Is the voltage at the phaseloss, phase-to-phase
Is the control power main circuit power imbalance, connection
installed? terminals (L1/R, L2/S faults, poor contact and so
and L3/T) correct? on and take corrective
measures.
YYS YYS
Is a short bar or DC
reactor connected Connect a short bar or DC
across terminals P1 and reactor.
P(+)?
YYS
Remove the keypad and
install (connect) correctly. A contact fault is probable.
Is the keypad installed Replace with another Retighten the mounting screws
(connected) correctly? keypad, if you have any, of the short bar or DC reactor
and check if indication is connected across terminals P1
given. and P(+).
YYS
Is the voltage of the
YYS Review the power
Auxiliary power input? auxiliary power supply
supply system.
correct?
YYS
Inspect the Is the converter YYS
DC common?
converter. correct?
YYS
Replace the power supply gate Failure of the keypad is
printed circuit board and set probable. Replace the
CN R ・ CN W keypad and return the
the fan power switching
(CN321 to 322) corresponding part to
connector (CN R/W) in the
correct position. us.
Repair the main circuit and Is the main circuit YYS Is the wiring at 73
replace the power supply (IGBT and diode) auxiliary contact
gate printed circuit board. correct? correct?
YYS
-63-
3. Troubleshooting
Case where no alarm code indication is given
Trouble on inverter setting operation
(2) The menu is not displayed
Is the setting of keypad menu NN Change the E52 setting so that the
selection (E52) correct? necessary menu is displayed.
YYY
Is inverter operation in
progress?
YYY
YYY
Is data protection (F00) set at YYY Change F00 to 0 and change the
1? setting of the desired function code.
NN
Is edit permission command Check the data of function codes E01 to E09, E98 and E99.
19 "WE-KP" assigned to a NN Refer to I/O check at the keypad menu to check the signal
control terminal X1-X9 and is input. Next, change F00 from 1 to 0 or change the setting of
the terminal turned off? the edit permission command "WE-KP" to turn it on.
YYY
YYY
YYY YYY
-64-