Date: 2/24/2023 Maico Gulf L.L.

C
Company: - PO Box 9014, Al Ghail Industrial Park
Contact: - Ras Al Khaimah, UAE
Project: St Paul hospital Tel. +971 7 2589000
Reference: - Fax. +971 7 2589001

Selection - TW-DT 400 Fan Performance


Product Code On Request 600

Fan Type DIDW Forward Curved


500
Requested Air Volume 8,640 m³/h

Requested Pressure 450 Pa


400
Air Volume 8,640 m³/h

Psta (Pa)
Static Pressure 450 Pa
300
Total Pressure 503 Pa

Velocity Pressure 53 Pa
200
Outlet Velocity 9.34 m/s

Fan Total Efficiency 59.2 % 100


Fan Static Efficiency 53 %

Fan Speed 876 rpm 0

Fan Class 1 10

Air Properties 1.22kg/m³/ 20°C/ 0m/ 50% RH 8


Pabs (kW)

Fan Absorbed Power 2.04 kW 6

Temperature Range -20°C + 85°C 4

Safety Factor 10 % 2

Total Weight 401 kg 0


80
Operating Limits
Tot. Eff. (%)

60
Minimum Speed 350 rpm 40
Maximum Speed 1400 rpm 20

Motor selection 0
0 5000 10000 15000 20000 25000
Electrical Supply 415/3/50 Q - Volume Flow (m³/h)
Motor Rating 3 kW

Energy Class IE3 Sound Performance


Enclosure/Class IP55 / F Hz 63 125 250 500 1k 2k 4k 8k Overall
Lw 84 85 78 73 70 65 61 61 88 dB
Frame Size Sg 132S-6
Lw(A) 58 69 69 70 70 66 62 60 76 dB(A)
Poles number 6
LpA @ 3m 37 48 49 50 49 46 41 39 56 dB(A)
Motor Speed 965 rpm

Full Load Current 6.80 A

Motor Brand WAT

Drive Information
Fan Pulley / Bush / Shaft 112 mm / 1610 / 30 mm

Motor Pulley / Bush / Shaft 100 mm / 1610 / 38 mm

Belts Qty / Length 2 x SPA / 1757 mm

Resultant Speed 862 rpm

Actual Power 1.94 kW

ERP Information
ERP Compliance Exempt

Type

Regulation -
Category of measure -

Selected Accessories
1 x Auto Changeover Panel

Copyright Maico Group 2014 Page 1 of 6


Version: 2.22.2.1702 (Database: 372) July 2023 VIN: D2CFC7D7B5 Date: 2/24/2023 1:18 PM
Date: 2/24/2023 Maico Gulf L.L.C
Company: - PO Box 9014, Al Ghail Industrial Park
Contact: - Ras Al Khaimah, UAE
Project: St Paul hospital Tel. +971 7 2589000
Reference: - Fax. +971 7 2589001

Drawing and Dimensions - TW-DT 400

Key W H L w1 h1 w2 h2
Value [mm] 2100 1000 1270 1700 600 1000 600

Copyright Maico Group 2014 Page 2 of 6


Version: 2.22.2.1702 (Database: 372) July 2023 VIN: D2CFC7D7B5 Date: 2/24/2023 1:18 PM
Date: 2/24/2023 Maico Gulf L.L.C
Company: - PO Box 9014, Al Ghail Industrial Park
Contact: - Ras Al Khaimah, UAE
Project: St Paul hospital Tel. +971 7 2589000
Reference: - Fax. +971 7 2589001

Selection - TW-DT 10-10 Fan Performance


Product Code On Request 600

Fan Type DIDW Forward Curved


500
Requested Air Volume 3,170 m³/h

Requested Pressure 380 Pa


400
Air Volume 3,170 m³/h

Psta (Pa)
Static Pressure 380 Pa
300
Total Pressure 432 Pa

Velocity Pressure 52 Pa
200
Outlet Velocity 9.21 m/s

Fan Total Efficiency 48 % 100


Fan Static Efficiency 42.2 %

Fan Speed 1252 rpm 0

Fan Class 1 3.5


3.0
Air Properties 1.22kg/m³/ 20°C/ 0m/ 50% RH
2.5
Pabs (kW)

Fan Absorbed Power 0.792 kW 2.0


1.5
Temperature Range -20°C + 85°C
1.0
Safety Factor 10 % 0.5
Total Weight 132 kg 0.0
60
Operating Limits
Tot. Eff. (%)

40
Minimum Speed 500 rpm
Maximum Speed 1300 rpm 20

Motor selection 0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
Electrical Supply 415/3/50 Q - Volume Flow (m³/h)
Motor Rating 1.1 kW

Energy Class IE3 Sound Performance


Enclosure/Class IP55 / F Hz 63 125 250 500 1k 2k 4k 8k Overall
Lw 81 81 81 78 71 67 61 57 87 dB
Frame Size Sh 90S-4
Lw(A) 55 65 73 75 71 68 62 56 79 dB(A)
Poles number 4
LpA @ 3m 34 44 52 54 51 47 41 35 58 dB(A)
Motor Speed 1440 rpm

Full Load Current 2.60 A

Motor Brand WAT

Drive Information
Fan Pulley / Bush / Shaft 80 mm / 1210 / 25 mm

Motor Pulley / Bush / Shaft 71 mm / 1108 / 24 mm

Belts Qty / Length 1 x SPA / 932 mm

Resultant Speed 1278 rpm

Actual Power 0.843 kW

ERP Information
ERP Compliance Exempt

Type

Regulation -
Category of measure -

Selected Accessories
1 x Auto Changeover Panel

Copyright Maico Group 2014 Page 3 of 6


Version: 2.22.2.1702 (Database: 372) July 2023 VIN: D2CFC7D7B5 Date: 2/24/2023 1:18 PM
Date: 2/24/2023 Maico Gulf L.L.C
Company: - PO Box 9014, Al Ghail Industrial Park
Contact: - Ras Al Khaimah, UAE
Project: St Paul hospital Tel. +971 7 2589000
Reference: - Fax. +971 7 2589001

Drawing and Dimensions - TW-DT 10-10

Key W w1 L H w2 h1 h2
Value [mm] 1200 1000 900 650 500 400 400

Copyright Maico Group 2014 Page 4 of 6


Version: 2.22.2.1702 (Database: 372) July 2023 VIN: D2CFC7D7B5 Date: 2/24/2023 1:18 PM
Date: 2/24/2023 Maico Gulf L.L.C
Company: - PO Box 9014, Al Ghail Industrial Park
Contact: - Ras Al Khaimah, UAE
Project: St Paul hospital Tel. +971 7 2589000
Reference: - Fax. +971 7 2589001

Selection - BOX-D 10-8 B4M Fan Performance


Product Code On Request 700

Requested Air Volume 1,970 m³/h

Requested Pressure 380 Pa

Air Volume 2,016 m³/h 600

Static Pressure 398 Pa

Total Pressure 431 Pa

Velocity Pressure 32.6 Pa 500

Outlet Velocity 7.31 m/s

Specific Fan Power -

Fan Speed 1093 rpm 400

Air Properties 1.22kg/m³/ 20°C/ 0m/ 50% RH


Psta (Pa)

Fan Absorbed Power -

Temperature Range -20 to 55⁰C 300

Motor selection
Electrical Supply 240/1/50

Motor Rating 1.243 kW 200

Enclosure/Class IP20 / F

Poles number 4

Motor Speed 1093-1441 rpm 100

Full Load Current 5.26 A

ERP Information
0
ERP Compliance Exempt
0 1000 2000 3000 4000 5000
Type Q - Volume Flow (m³/h)
Regulation -

Category of measure - Sound Performance


Hz 63 125 250 500 1k 2k 4k 8k Overall
Selected Accessories
Lw 87 85 80 67 63 60 56 50 89 dB
4 x Technopolymer terminal box-IP55 Lw(A) 60 68 72 64 63 61 57 49 75 dB(A)
LpA @ 3m 40 48 51 43 42 41 36 29 54 dB(A)
Values shown are for inlet Lwi and inlet LwiA sound power levels for installation Type D: ducted inlet, ducted outlet. Ratings
include the effects of duct end correction. The sound power levels ratings shown are in decibels, referred to 10⁻¹² watts,
calculated per AMCA International Standard 301.The A-weighted sound ratings shown have been calculated per AMCA
International Standard 301. LpA dBA levels are not licensed by AMCA international.

Certifications
Maico Gulf LLC certifies that the DYNAIR model BOX-D are licensed to bear
the AMCA Seal. The ratings shown are based on tests and procedures
performed in accordance with AMCA Publication 211 and AMCA Publication
311 and comply with the requirements of the AMCA Certified Ratings
Program. Performance certified is for installation type D – Ducted inlet,
Ducted outlet. Performance ratings do not include the effects of
appurtenances (accessories). Speed (RPM) shown is normal. Performance is
based on actual speed of test.

Copyright Maico Group 2014 Page 5 of 6


Version: 2.22.2.1702 (Database: 372) July 2023 VIN: D2CFC7D7B5 Date: 2/24/2023 1:18 PM
Date: 2/24/2023 Maico Gulf L.L.C
Company: - PO Box 9014, Al Ghail Industrial Park
Contact: - Ras Al Khaimah, UAE
Project: St Paul hospital Tel. +971 7 2589000
Reference: - Fax. +971 7 2589001

Drawing and Dimensions - BOX-D 10-8 B4M

Key A B C D E F G H I Wt(GI) Wt(AL)


Value [mm] 600 550 600 289 265 75 160 350 400 36 Kg 26 Kg

Electric Wire Connections

Copyright Maico Group 2014 Page 6 of 6


Version: 2.22.2.1702 (Database: 372) July 2023 VIN: D2CFC7D7B5 Date: 2/24/2023 1:18 PM