L20A / L30A Series Gas Turbine Generator Specifications

20 14
Nominal Performance
Elevation :0m Ma
Inlet Air Temperature : 15 °C xim
um
Inlet Air Pressure Loss : 0.98 kPa Ou
tpu
Exhaust Gas Pressure Loss : 3.43 kPa (GPB180/180D) t
LHV of Natural Gas Fuel : 35.9MJ/Nm3
(100% CH4)

Typical Steam Condition


Steam Pressure : 0.83 MPaG Heat Rate
Steam Temperature (Saturated) : 177 °C
Feed Water Temperature : 80 °C
Blowdown from HRSG : 0%

L20A Gas Turbine Series

17,970 13,470 8,980


10,690 11,510 13,200
545 517 443
213 188 182
39.7 32.5 24.5
84.0 82.4 77.7
0 15
19,320 17,970 15,080
10,500 10,690 11,380
538 545 565
221 213 193
40.2 39.7 38.8
82.5 84.0 86.7

Lube Oil System Intake Silencer & Filter


- Lube Oil : Turbine Oil ISO VG32 (optional VG46) - Painted Carbon Steel (Outer Skin and Structure)
- Turbine Driven Main Lube Oil Pump - Stainless Steel Inner Punching Metal Sheet
L20A Gas Turbine - Pre-Post Lube Oil Pump - 3 Stage Filter with Insect Screen
- Industrial Single-Shaft - Emergency Lube Oil Pump - Pulse Type Self Cleaning Filter (Option)
- Rotor Speed: 9,420 rpm - Water Cooled Oil Cooler with Temp. Control Valve - Noise Level: 85 dBA at 1m to Filter inlet
Compressor - Oil Reservoir integrated with Baseplate : 5,900 liter Exhaust Silencer Stack (Option)
- 11 Stage Axial Flow - Stainless Steel Piping: Down Stream of Filter Controls
- IGV & 4 Stage VSV - Filter - Microprocessor Based PLC
Combustor - Oil Vapor Fan (CPU, Power Module : Option Redundant)
- 8 Can Combustors Generator - Gas Turbine and Generator Control
- Dual Ignition System - Continuos Duty Rating GT start / Shutdown Control
- Conventional Diffusion (GPB180) - 3 Phase, 3 Wire (Option 4 Wire) Speed / kW / Power Factor Control
(Option De-NOx: Steam Injection) - Voltage: 6.6 kV, 11.0 kV Auto Synchronizing and Auto Sharing
- DLE (Dry Low Emission) (GPB180D) - Power Factor: 90% (Option 85%, 80%) - Touch Panel Operation
- Available Fuel : Natural Gas - IEC Standard, Class F Insulation with F rise - Serial Link User Interface (Option)
Turbine - Exciter: Brushless PMG - SCADA System (Option)
- 3 Stage Axial Turbine Enclosed Package - Redundant Control System (Option)
Coupling Shaft & Cover - Carbon Steel Common Base Frame - Remote Monitoring (Option)
- Flexible Coupling with Shear Pin and Cover - Painted Carbon Steel Acoustic Enclosure Graphics Monitoring
Reduction Gear Box - Noise Level: 85 dBA at 1 m to the side of Enclosure Historical Trend & Event Logger
- Parallel Shaft - Forced Ventilation Fan with Filter Daily and Monthly Reports
Starting and Turning System - Maintenance Stage, Ladder, Beam (Option)
- VFD Motor Drive

GPB180 Typical Package Outlook : mm


6,100
(Reference)

G/T Intake
air inlet Ventilation Air
Enclosure
Vent.Air outlet
10,950
8,900
4,700

G/T Exhaust
gas outlet
3,450

17,250 3,500
19,100