SEL S.p.A.

Via Amendola
51035 Lamporecchio
(PT) ITALY

Instructions for installation of shunt opening release and auxiliary contacts


on TPS switch disconnector

1 2 2) Insert from
behind the plate
of the Operating
Mechanism the
two flathead
bolts M6x12 as
B in the figure.
A

Screw back Bolt


fig 1 being
careful not to
tighten it
completely.
1) Slightly unscrew the screw of Fig. 1 to The lever "A" must be able to rotate a few degrees on
allow the insertion of the bolt "B" of Fig. 2 the same bolt

3 4 4) Fix the coil to


the bracket as
shown in Fig. 4
using the two
countersunk
screws M4x10

3) Fix the coil support holding coil with the two 7


knurled nuts.

5 6

5-6-7) Fix the auxiliary contacts on the back of the plate of the Operating Mechanism, using the two screws
M5x35 the two thicknesses A005385 (to be interposed between the plate of the command and the support
plate of the auxiliary contacts as in fig. 5) and two knurled nuts M5 as in fig 7
Platelets drive of auxiliary contacts are mounted on the switch (item "C" photo 5)

8) The wiring KSCHA010220A is designed to


connect the coil opening + 1 NO contact + 1 aux
KSCHA010220A on changeover see wiring diagram on page 3

TPS-07ist-kit_ed0701-In Pagina 1
SEL S.p.A.
Via Amendola
51035 Lamporecchio
(PT) ITALY

Instructions for installation of shunt opening release and auxiliary contacts


on TPS switch disconnector

9 10 10) Fix the termi-


nal block in the
auxiliary com-
partment, using
the two socked
head screws
M4x16.
Insert it into the
holes provided.
It 'possible that
the two holes
should be
threaded.
9) Connect the wiring to the auxiliary con-
tacts as in electrical diagram .

11 12

11) Insert the wiring in the auxiliary compart- 12) Secure the wiring with PVC cable tie, careful to
ment and connect it to the terminal board. maintain a safe distance from moving parts

13 14

Insert the two heat shrink tubing on wires 14) Connect the coil by the faston terminal plug
01A - 13A of the shunt opening release. predisposed

TPS-07ist-kit_ed0701-In Pagina 2
SEL S.p.A.
Via Amendola
51035 Lamporecchio
(PT) ITALY

Instructions for installation of shunt opening release and auxiliary contacts


on TPS switch disconnector

15 17
16

17) After opening the, the circuit


(if connected properly), cuts off
power to the coil.
Check that this happen, trying to slide
15) Termoretract the jun-
the plunger coil.
ction
If the coil is operated it will be
irremediably damaged.
16a) Close the switch discon-
nector
16b) Supply the circuit of
opening.
The switch should open.

18

SCHEMA ELETTRICO DI COLLEGAMENTO


ELECTRICAL DIAGRAM FOR
CONNECTION OF
KSCHA010220A