: Basic Parameters

01.00 Maximum Output Frequency (Fmax) Unit: Hz


Settings 50.00 to 600.0 Hz Factory Setting: 60.00
This parameter determines the AC motor drive’s Maximum Output Frequency. All
the AC
motor drive frequency command sources (analog inputs 0 to +10V and 4 to 20mA) are
scaled
to correspond to the output frequency range.
Please note that output frequency may be not in this setting range due to
parameter setting:
1. Pr.00.10 is set to 0: when enabling Pr.07.03 (Slip Compensation) in V/f mode, it
may be not
in this setting range.
2. Pr.00.10 is set to 1: The AC motor drive will auto compensate slip in vector
mode, so it also
may be not within this setting range.
Related parameters: 00.10 (Control Method), 04.12(Min AVI Frequency),
04.14(Max AVI
Frequency), 04.16(Min ACI Frequency), 04.18(Max ACI Frequency), 04.19(ACI/AVI2
Selection), 04.21(Min AVI2 Frequency), 04.23(Max AVI2 Frequency) and 07.03(Slip
Compensation (Used without PG) (Motor 0))
V/F 曲 線
Output
Frequency
Analog Input
Signal 0V(4mA) 10V(20mA)
01.00
Max. Output
Frequency
01.01 Maximum Voltage Frequency (Fbase) (Motor 0) Unit: Hz
Settings 0.10 to 600.0Hz Factory Setting: 60.00
This value should be set according to the rated frequency of the motor as
indicated on the
motor nameplate. Maximum Voltage Frequency determines the v/f curve ratio. For
example, if
the drive is rated for 460 VAC output and the Maximum Voltage Frequency is set to
60Hz, the
drive will maintain a constant ratio of 7.66 V/Hz (460V/60Hz=7.66V/Hz). This
parameter value
must be equal to or greater than the Mid-Point Frequency (Pr.01.03).
Call 1(800)985-6929 for Sales deltaacdrives.com sales@deltaacdrives.com Call
1(800)985-6929 for Sales deltaacdrives.com
pter 4 Parameters|
4-46 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14
If this parameter setting is less than the rated frequency of the motor, it
may cause over
current and damage the motor or trigger the over current protection.
If this parameter setting is greater than the rated frequency of the motor,
it may cause
insufficient motor torque.
Related parameters: Pr.01.02(Maximum Output Voltage (Vmax) (Motor 0)),
Pr.01.03(Mid-Point
Frequency (Fmid) (Motor 0)), Pr.01.04(Mid-Point Voltage (Vmid) (Motor 0)),
Pr.01.05(Minimum
Output Frequency (Fmin) (Motor 0)) and Pr.01.06(Minimum Output Voltage (Vmin)
(Motor 0)).
01.02 Maximum Output Voltage (Vmax) (Motor 0) Unit: V
Settings 115V/230V series 0.1 to 255.0V Factory Setting: 220.0
460V series 0.1 to 510.0V Factory Setting: 440.0
This parameter determines the Maximum Output Voltage of the AC motor drive.
The Maximum
Output Voltage setting must be smaller than or equal to the rated voltage of the
motor as
indicated on the motor nameplate. This parameter value must be equal to or greater
than the
Mid-Point Voltage (Pr.01.04).
If the output voltage of the AC motor drive is smaller than this setting,
the output voltage can’t
reach this setting due to input voltage limit.
If this setting is greater than the rated voltage of the motor, it may cause
over current of the
motor output to damage motor or trigger the over current protection.
If this setting is smaller than the rated voltage of the motor, it may cause
the insufficient motor
torque.
Related parameters: Pr.01.01(Maximum Voltage Frequency (Fbase) (Motor 0)),
Pr.01.03(Mid#Point Frequency (Fmid) (Motor 0)), Pr.01.04(Mid-Point Voltage (Vmid)
(Motor 0)),
Pr.01.05(Minimum Output Frequency (Fmin) (Motor 0)) and Pr.01.06(Minimum Output
Voltage
(Vmin) (Motor 0)).
01.03 Mid-Point Frequency (Fmid) (Motor 0) Unit: Hz
Settings 0.10 to 600.0Hz Factory Setting: 1.50
This parameter sets the Mid-Point Frequency of the V/f curve. With this
setting, the V/f ratio
between Minimum Frequency and Mid-Point frequency can be determined. This parameter
must be equal to or greater than Minimum Output Frequency (Pr.01.05) and equal to
or less
than Maximum Voltage Frequency (Pr.01.01).