Professional Documents
Culture Documents
CAN
Analyser
CAN Communication analysis
SW version 1.0.0
1 Document information 2
2 Wiring 5
3 Install Device Driver Setup 6
4 Bus monitoring and capture 7
5 Appendix: Check 11
IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
WARNING: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
Example: This type of paragraph contains information that is used to illustrate how a specific function
works.
Image 2.2 Setup after connecting the ECU CAN Analyser interface and T-splice cable for most
ComAp controllers*.
Note: *)
The ~0.1m splice ending with the DB9 connector is used on ID-DCU ComAp controllers in place of the green
Phoenix connector which is used on all other controllers.
Please note that there are no terminating resistors in the T-splice cable nor in the interface itself. It is expected
that the bus itself has correct termination of 120 Ω at each end.
Note: This can be done even when no control unit is connected i.e. in offline mode as the ECU CAN Analyser
HW is independent of the control unit.
The trace files (a.k.a. logs) will be automatically named and the user can select their destination folder by
clicking on the button right of the Output directory text box. Multiple files will be created in case the size
exceeds the maximum allowed limit per file.
The tool offers two logging options. Either 250kbps CAN bus or 125kbps CAN bus can be selected.
250kbps is the default option as majority of ECUs utilize this bus speed.
Listen-only mode is also available through a tick-box. In situations where the ECU CAN Analyser should be
non-intrusive Listen only mode has to be activated as is the case in the figure above. This is the expected
(and default) configuration when capturing data from a bus that has two or more units connected (e.g. ComAp
controller and Engine ECU).
In the rare situation when ECU CAN Analyser is used to capture data from a single unit (e.g. ECU or
controller) this option must not be ticked as the interface must actively acknowledge CAN frames on the bus
otherwise there would be ACK errors detected by the single unit.
Status of the hardware device is visible under Converter. In the example above the ECU Can Analyser is not
plugged in to the PC so the Converter status reads Not connected.
Logging status informs on the active state of the logging session. If this is ongoing the Start time is also
recorded for reference and the Duration is increasing as logging continues.
Received messages indicates a counter of any CAN bus frame seen and logged into the active trace file.
In situations where the ECU CAN Analyser should be non-intrusive Listen only mode has to be activated as
can be seen in the figure below. This is the expected configuration when capturing data from a bus that has
two or more units connected.
In the rare situation when ECU CAN Analyser is used to capture data from a single unit (ECU or controller)
this option must not be ticked as the interface must actively acknowledge CAN frames on the bus otherwise
there would be ACK errors detected by the single unit.
After confirming the configuration and pressing OK PCAN-View will automatically connect to the bus and start
monitoring (but not capturing) the bus traffic.
If data is received from either the controller or ECUs this will be visible in the Receive section of the main
screen.
(Re)Connection or Disconnection from the bus can be performed via the two icons in the top menu if needed.
To start or stop capturing of the bus communication please use the Start, Stop and Save commands from the
Trace menu respectively.
Under normal conditions ticking of all the logging options as seen in the figure below prior to commencing
data capture is recommended.