Professional Documents
Culture Documents
Delta 4000+IPF - Mike
Delta 4000+IPF - Mike
Michael M. Evangelista
1
Dos and Don’t’s
2
Safety
3
Safety
4
Safety
5
Power Factor/Dissipation Factor and
Capacitance Test
6
Capacitance Test
7
Capacitance Test
8
Capacitance Test
Capacitance:
9
Capacitance Test
10
Nomenclatures Don’t
11
General Insulation Knowledge
12
‘General Insulation Knowledge’ Do’s
13
General Insulation Knowledge’ Do’s
14
‘General Insulation Knowledge’
Don'ts
Don’t be a bystander.
• Know that you can improve the withstand capability of
insulation.
15
General Testing Knowledge
16
General Testing Knowledge
Do familiarize yourself with history –
bears to remember how we got to where
we are today…
17
‘General testing knowledge’ Do’s
18
Two ways to Measure PF/DF
Ic = V/Xc;
Ic = V x 2∏fC
V= 1 to 10kV
F = DFR
19
‘General testing knowledge’ Do’s
20
‘General testing knowledge’ Do’s
Dielectric representation
• Do keep in mind that a tester may not have control over
how far an insulation system may be segmented for testing
beyond a point.
• - a diagram that identifies each (group of) component(s)
in an asset that will exist at a unique voltage when the asset is
energized.
• The tester must identify if the component is accessible so
that a test lead may be connected.
21
‘General testing knowledge’ Do’s
Dielectric representation
• Insulation between components is depicted by a single capacitor – adequate since
a dielectric representation is simply a guidepost to testing. A dielectric model serves to
predict the electrical behavior of an insulation system so a single capacitor for this type of
diagram would not be adequate.
22
‘General testing knowledge’ Do’s
Test Modes
• The enabling feature of a PF/ DF test instrument that
supports test modes is a “guard circuit”.
• All current resulting from the application of the
instrument’s test voltage will seek to return to the guard point.
• Return paths to the test instrument are provided by up to
3 measuring leads that are connected between the instrument &
the asset under test:
– A “ground” lead
– 2 low voltage leads (R and B)
23
‘General testing knowledge’ Do’s
Test Modes
• GST – Ground
• GST – Guard
• UST
24
‘General testing knowledge’ Do’s
25
‘General testing knowledge’ Do’s
26
An important point to be made about
size
27
‘General testing knowledge’ Don’ts
28
Test Preparation
29
Test Preparation
30
Test Preparation
31
4 consequences of leaving bus
attached to bushings
32
4 consequences of leaving bus
attached to bushings
33
4 consequences of leaving bus
attached to bushings
34
4 consequences of leaving bus
attached to bushings
35
Surface leakage bigger problem on
left or right?
36
‘Test Preparation’ Do’s
37
Failing to short circuit each winding
38
Test Voltage
39
Test Voltage Don’t
41
Analysis
42
Analysis Do’s and Don’ts
43
Analysis Do’s and Don’ts
Don’t ignore capacitance
• In fact, assess capacitance/current first!
• If capacitance/total current has changed from previous, you may
not be testing what you had intended or the physical attributes of
the insulation system has changed notably
45
Analysis Do’s
46
Analysis Do’s and Don’ts
• A lower PF/DF indicates an insulation system in better condition than one with a
higher PF/DF
Do – note that PF/DF can be “too low” – lower than expected or even negative
and this may be indicating a problem depending on when you encounter it
Do – keep in mind that analyzing PF/DF “simply” means looking for a change in
value from previous
47
Analysis Do’s and Don’ts
48
Analysis Do’s and Don’ts
Temperature is a big deal!
49
Analysis Do’s and Don’ts
50
Analysis Do’s and Don’ts
51
Analysis Do’s and Don’ts
52
QUESTIONS???
53
Power Factor Testing
54
Power Factor Testing
What is it?
• A form of AC testing that applies voltage and
measures the leakage/loss current of electrical
insulation.
Ic
Insulation
Vs
55
Power factor Testing
What is it ?
• Power factor testing is a type of insulation
testing used to evaluate the integrity of
electrical insulation.
CHL
CHG CLG
56
Facts about Insulation
Ic
= = Capacitor =
Vs
57
Facts about Insulation
Cos (90) = 0
58
Facts about Insulation
59
Facts about Insulation
Ic Ic
IT
Vs Vs IR Vs
IR
60
Why perform Power Factor/
Dissipation Factor Testing ?
61
Power Factor Testing
Is used for:
Evaluating the nature and quality of electrical insulation
materials and systems.
Revealing contamination, fractures, and punctures.
Detection of defects which accompany the aging of
insulation.
62
What is Power Factor?
Ic
IR Vs
63
What is Dissipation Factor ?
Ic
IR Vs
64
Power Factor Testing
POWER FACTOR
DISSIPATION FACTOR
65
Power Factor/ Dissipation Factor
Relative losses?
PF:
• Relative losses means the amount of energy lost
to heat compared to the total amount of energy
present across the system
• IR/IT
DF:
• Relative losses means the amount of energy lost
compared to the amount of electrical energy
stored by the insulation
• IR/IC
66
Power Factor Testing
67
Power Factor Testing
68
Power Factor vs Dissipation
Factor
69
Nomenclatures Don’t
70
Where Is Power Factor Used?
71
Where is Power Factor Used?
72
Power Factor /Dissipation
Factor Testing
Equipment failure
Unscheduled downtime/lost revenue
Inefficiency
73
Power Factor/Dissipation Factor
Testers Can Be Used To Evaluate
Transformers
Circuit breakers
Rotating machinery
Insulating liquids
HV bushings
Surge arresters
HV coils
74
Tests that can be performed
75
Power Factor Testing
H CHL L
=
CHG CLG
76
Power Factor Testing
Modeling of a Transformer
77
Power Factor Testing
Delta 4000
Four Leads
• High Voltage Lead (Black Lead)
• Red Lead
• Blue Lead
• Ground Lead
78
Power Factor Testing
79
Power Factor Testing
80
Power Factor Testing
81
Power Factor Testing
82
Power Factor Testing
83
Power Factor Testing
Guard
84
Power Factor Testing Measurement
Ungrounded Specimen Test Ground Red Blue
× × √
× √ ×
× √ √
Resonating Inductor
87
Power Factor Testing
88
89
90
91
92
Tan delta measurement setup
Lo
A
Ground CHL
CL CH
93
Power Factor Testing
Trend results
Compare absolute value to maximum value set by
manufacturer.
Compare absolute value to typical values for similar
equipment type.
94
Applicable Standards
IEEE C57.12.90
• Standard test code
IEEE 62-1995 (to be replaced by C57.152)
• Field test guide
IEC 60076
• International standard
Etc...
95
Typical power factor limits for oil insulated
transformers and bushings (IEEE)
Power transformers,
0.2-0.4% 0.3-0.5% > 0.5%
oil insulated
IEEE 62-1995 states; “The power factors recorded for routine overall tests on
older apparatus provide information regarding the general condition of the
ground and inter-winding insulation of transformers and reactors. While the
power factors for most older transformers will also be <0.5% (20C), power
factors between 0.5% and 1.0% (20C) may be acceptable; however, power
factors >1.0% (20C) should be investigated.”
96
Key Fault Detection
97
THE MEGGER DELTA 4000
98
Delta 4000
12-kV Insulation Diagnostic System
99
Delta 4000 system
Two units;
Control module with measurement circuitry (14 kg)
HV step-up module (22 kg)
Two versions;
Delta4110 – External computer model
Delta4310 – On-board computer model
Two user modes;
Automatic with PowerDB
Manual with Delta Control
Two unique new methods;
• ITC
• VDD DELTA 4110 DELTA 4310
100
Internal or external computer
(Delta4310)
101
Delta4000 key features
102
Delta4000 – Test capabilities
103
Delta4000 test modes
104
Delta 4000 key specification
Output voltage
0-12 kV
Frequency range
1-500 Hz
Output current
300 mA, 4 minutes
100 mA continuous
Measurements
Voltage
Current
Capacitance
Power factor
Dissipation factor (tan delta)
Inductance
Power (Watts loss)
Measurement accuracy (Capacitance/Inductance/PF/Tan Delta)
± 0.5%
105
Two Software User Modes
106
Manual control
107
Automatic testing using PowerDB
108
Noise in substations
Induced AC (50/60Hz)
Induced DC
Corona discharge
HVDC equipment
DC offset from (varying) ground potential (mainly in HVDC
substations)
Other disturbancies (RF, power transients etc)
109
Traditional temperature correction
111
Temperature correction – Bushings
(manufacturers data)
1.8
5_O_C
1.6 7_GO_25_765
9_CTF_20_60
1.4 11_CT_KF_85_330
13_B
1.2
15_F
1 17_L_LC_LI_LM
19_OF_OFI_OFM
0.8 21_S_SI_SIM
23_T_U
0.6
25_COT_COS_SOT
0.4 27_ERC
29_PRC
0.2 31_POC
33_P_PA_PB
0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60
112
Tan Delta vs Temperature –
Conclusions from a project
Tan delta values are affected by variation of temperature. In most cases (but
not all), tan delta value increases with increase in temperature. Rate of
change is different for different makes and age of the transformers and
bushings
The temperature correction factors (for recalculating measured tan delta to
20° C reference temperature) are different for different makes. Hence
temperature correction factors as given in e.g. IEEE/C57.12.90 can not be
applied to these components “Application of Temperature Correction
Factors for Dissipation Factor Measurements
for Power Transformers – A Case Study”
Power Grid Corporation of India Limited
113
Individual/Intelligent Temperature
Correction (ITC)
114
ITC validation using full (IDAX/MODS)
modelling
7.00
6.00
5.00
Tan delta (DFR 21)
4.00 Tan delta (DFR 27)
Tan delta (DFR 34)
3.00
Tan delta (DFR 49)
2.00 Measured
IEEE 57
1.00
0.00
0 20 40 60 80
Temp. Cap. Tand (%), Individual ITC tand (%) IEEE C57.12.90 IEEE tand (%)
(°C) (pF) measured Corr. factor @20°C Corr. factor @20°C
21 1978 0.329 1.04 0.31 1.02 0.32
26 1976 0.367 1.20 0.31 1.14 0.32
34 1978 0.516 1.53 0.34 1.37 0.38
49 1974 0.832 2.70 0.31 1.91 0.44
115
ITC temperature correction curves for typical
transformers at various age/condition
116
Voltage Dependence Detection (VDD)
118
Delta4000 Optional Accessories
119
Delta4000 Optional Accessories
Capacitor kit
• Allows for field “Quick check” of both
Capacitance and Dissipation/Power Factor
HV TTR Capacitor
• Allows for HV TTR measurement
Resonating Inductor
• Allows for extended current output and
capacitance range (50/60 Hz testing)
120
Delta4000 Optional Accessories
CAL4000 - Calibration Box for Delta4000
• Designed for in-house calibration
• Same unit as used for factory calibration
121
Delta4000 Optional Accessories
Reference Standard
• Can be used for Delta4000 HV unit
calibration
• Defined capacitance and dissipation
factor
• Traceable to national standards
• For general calibration and verification
purposes
122
Delta4000 – Calibration
123
Part of the Megger transformer
testing tool-box!
124
125
Power factor/dissipation factor (tan
δ) testing
Perfect insulation/ideal
capacitor – Dissipation factor
=0
More leakage, higher
dissipation factor – A resistor
has 100% dissipation
If the dissipation in the
transformer/bushing/cable is
too high you may get self-
generated heating and the
component may explode
(thermal runaway)
Dissipation factor is a quality
parameter for the insulation
Traditionally measured at
50/60 Hz and 1-10 kV
126
Tan delta measurement setup
Lo
A
Ground CHL
CL CH
127 127
Delta4000 test modes
128
UST measurements
129
GST measurements
130
CHL: UST-R
OUT
V IN1
A
IN2
GND
CHL
CL CH
131
CHL+CH: GST-GND
OUT
V IN1
IN2
A
GND
CHL
CL CH
132
CH: GSTg-RB
OUT
2
V IN1
IN2
GND
A
CHL
CL CH
133
Tip-Up Test
134
Power Factor Testing
Tip-up Test
135
Tip-up testing
“Tip-up” test
• Tests performed at varied voltage levels
• Primarily used for dry (non-oil) insulation (rotating machines)
• Oil-immersed insulation generally exhibits flat dissipation values
over a wide voltage range (no voltage dependence)
• Indicates ionization (PD) due to voids in dry insulation, and high
stress locations under oil
136
Exciting current measurements
137
Key Fault Detection
139
Exciting current measurements
140
Exciting current measurements
141
Exciting current measurements
142
HV Ratio Testing
DELTA
Test Set
Measure the
TTR capacitor
alone (C1)
Measure the
DELTA
Test Set
capacitor in
series with the
transformer
windings (C2)
Calculate the
ratio as; N =
C1 / C2
143
EXCITATION CURRENT TEST
144
Transformer Excitation Current
Tests
145
Connection
NOTE: Transformer excitation current tests are performed on the high voltage
winding to minimize the excitation current. Problems in the low voltage
windings will still be detected by this method.
The secondary windings are left floating with the exception of a wye or zig-zag
secondary. In this case the neutral bushing remains grounded as it is in normal
service.
146
Connection
147
Connection
148
Test Procedure
• Test voltages should be as high as possible, but limited to 10 kV, without exceeding the rating of the line-to-
line voltages on delta connected transformers and line-to ground on wye connected transformers. Also
note that in many cases the maximum applied voltage is limited by the maximum current output
• Test voltage must always be the same as prior tests if any comparisons are made.
• All transformer excitation current tests are conducted in the UST test mode (normally UST-R, using Red
low voltage lead).
• For routine testing, transformers with load tap changers should have tests performed in at least one raise
and one lower position off of neutral. The no-load tap changer should be in the normal in service position.
• For new transformers, excitation tests should be performed in every tap position for both the load and
noload tap changers.
• The more information that is recorded at the time of testing will ensure the best comparison of results at
the next routine test.
149
Test Procedure
• Test voltages should be as high as possible, but limited to 10 kV, without exceeding the rating of the line-to-
line voltages on delta connected transformers and line-to ground on wye connected transformers. Also
note that in many cases the maximum applied voltage is limited by the maximum current output
• Test voltage must always be the same as prior tests if any comparisons are made.
• All transformer excitation current tests are conducted in the UST test mode (normally UST-R, using Red
low voltage lead).
• For routine testing, transformers with load tap changers should have tests performed in at least one raise
and one lower position off of neutral. The no-load tap changer should be in the normal in service position.
• For new transformers, excitation tests should be performed in every tap position for both the load and
noload tap changers.
• The more information that is recorded at the time of testing will ensure the best comparison of results at
the next routine test.
150
Test Results
• Compare test results to previous tests on the same transformer, or to manufacturers’ data if available.
• Tests can also be compared to similar type units. It is essential that identical
test voltages be used for repeat tests on a transformer.
• Fluctuation in the test voltage will produce inconsistent current readings. Three phase transformers should have
the individual windings energized at both ends if the original test appears abnormal.
• Transformer excitation current tests on the high voltage winding should detect problems in the secondary winding
if they exist. Winding resistance testing in addition to the excitation tests could be helpful in isolating either a core
or winding defect.
• Test results on three phase transformers, especially wyeconnected windings, could produce high but similar
readings on two phases compared to the third phase.
151
Power Factor Testing
152
Power Factor Testing
153
Power Factor Testing
154
Power Factor Testing
155
156
Thank You!!!
157