Professional Documents
Culture Documents
Power Metering Seminar Dhvtsu
Power Metering Seminar Dhvtsu
Distribution Utilities
10 10 Amperes
20 20 Amperes
100 100 Amperes
200 200 Amperes
320 320 Amperes
480 480 Amperes
• Form Number (FM) - number conforming with the internal
connection diagram shown on EEI Publication No. MSJ-10 or
AEIC-EEI-NEMA standards for Watt-hour Meters. Meters with the
same Form number have identical internal connection regardless of
any brands or manufacturers.
• Without a damping
magnet, a meter would
slowly coast to a stop after
a load was removed. A
more desirable response
would be for the meter
disk to stop immediately
when a load is
discontinued. The
damping magnet provides
the force to accomplish
this task.
Electronic KWh Meter
WATT
ANALOG OUTPUT
KYZ Wh
INTEGRATOR
WATT PULSE RATE
(ANALOG TO PULSE
MULTIPLIER OUTPUT
RATE CONVERTER)
INPUT (2,21/2,3
VOLTAGE
TRANSFORMERS ELEMENT)
INPUTS
Q or VAR
ANALOG OUTPUT
CURRENT KYZ Qh or VARH
INPUTS Q or VAR INTEGRATOR PULSERAE
MULTIPLIER (ANALOG TO PULSE OUTPUT
(2,21/2.3 RATE CONVERTER)
ELEMENT)
VOLT
ANALOG OUTPUT
KYZ Vh
VOLT/VOLTHOUR PULSE RATE
CONVERTER OUTPUT
& INTEGRATOR
REGISTER
ELECTRONIC (L.E.D.)
(+DEMAND)
OR CYCLOMETER
Wattsload = W1 + W2 + W3
• If the common point is one line or at point C.
e'c becomes zero and the formula reduces to :
e'c = 0
Watts load = e'a ia + e'b ib
Watts load = W1 + W2
Instrument Transformer
• Current Transformer - usually rated on a
basis of 5 amperes and 1 amperes secondary
current and used to reduce primary current to
usable levels for transformer-rated meters and
to insulate and isolate meters from high
voltage circuits.
• Current transformers are applied in two very
different functions, metering and/or protection.
Types of Current Transformers
• Demand Metering
• Automated Meter Reading ( AMR )
• Prepaid Metering
• Advance Metering Infrastructure ( AMI )
Demand Metering
• An electric demand meter works on the principle that
customers who require a higher or more intensive level
of service during bursts of peak demand should pay
more for the availability of that service.
• ‐ An electrical load averaged over a specific period of
time.
• Units: kilowatts
• Current X Voltage (Averaged Over Time) = Demand
• Typically Metered for Commercial and Industrial
Customers
• Demand Intervals: 15 or 30 minutes
Various Demand Types
• Maximum Demand (Peak Demand)
The highest demand measured over a selected period
of time ( typically one month).
• Minimum Demand
> The lowest demand measured over a selected
period of time (used only for Power Factor).
• Cumulative Demand
The sum of the previous billing period Max demands. At
the time of demand reset, the Maximum Demand of the
previous billing period is added to the previous
accumulated total of all Maximum Demands.
• Continuously Cumulative Demand
The same as (Cumulative Demand) plus
the present period Max Demand.
• Previous Demand
The Max Demand from the most
recently completed interval
• Projected Demand
The estimated Max Demand the meter
will accumulate by the end of the
current
Demand Calculations
• Block Demand -
Maximum Demand
is based upon the
highest average
demand during any
one demand
interval.
• Rolling Demand –
similar to block
demand, but uses
subintervals to
determine the
Maximum or
Minimum interval.
• Thermal demand ‐
measures average load
with an inherent time
interval and a response
curve which is
based on the heating
effect of the load.
Automated Meter Reading
I. RESIDENTIAL CUSTOMERS
- Form 1S
- Class 100
- Accuracy Class 0.3
- Voltage Rating 240 V
II. LOW VOLTAGE NON – RESIDENTIAL
CUSTOMERS
-Form 1S
-Class 200
-Accuracy Class 0.3
-Voltage Rating 240 V
III. HIGH VOLTAGE CUSTOMERS
-Form 1S, Form 3S, Form 16S, Form 48 A
-Self Contained / Instrument Transformer
Rated
-Class 20 / Class 200
-Voltage Rating 120 V – 480 V
-Demand Metering
-TOU ready
-Reactive Power Metering
-Load Profiling
Distribution Transformers
Distribution Transformers
• The purpose of a distribution transformer is to
reduce the primary voltage of the electric
distribution system to the utilization voltage
serving the customer.
• A distribution transformer is a static device
constructed with two or more windings used
to transfer alternating current electric power
by electromagnetic induction from one circuit
to another at the same frequency but with
different values of voltage and current.
History of Distribution Transformers
Secondary
(X1, X2, X3)
KVA Bushings
Rating
Company Nameplate
Number (Hidden)
• Distribution Transformer Nameplate
Primary
Voltage Rating KVA Rating
Secondary
Voltage
Rating Polarity
(Additive)
Voltage
Rating
per tap Schematic
position Diagrams
Symbols Used in Transformer Voltage Rating
To designate separate
voltages which can be
X obtained by reconnecting13200 GRDY / 7620 V -
Cross the coils of a winding in 120/240 X 139/277 V
series or multiple
combinations
Difference Between 120 / 240 V & 240 / 120 V
HV SIDE
Temporary
Shorting Vm Voltmeter
Wire (Jumper)
LV SIDE
• W0 = V1Ic = Pcore
Short Circuit Test
Winding Loss
Standard Distribution Transformer
Losses
• Transformer impedance determines the voltage
drop attributable to the transformer when carrying
load.
Excessive transformer impedance can cause low
voltage on secondary and service lines as well
Common Distribution
Transformer Connections
SINGLE-PHASE 240V, LINE-TO-GROUND
SECONDARY SYSTEM
A
N
H1 H2
X3 X1
X2
a
b
X1 X1
X3 X3
X2 X2
a
b
c
INSULATED PHASE BARE GROUNDED
CONDUCTORS PHASE CONDUCTOR
B b
SECONDARY VOLTAGES
N c Vab = 240V
a Vbc = 240V
A C
Vca = 240V
PRIMARY VECTORS SECONDARY VECTORS
WYE, DELTA CONNECTION FOR 3-PHASE,
CORNER-GROUNDED DELTA SECONDARY
A
B
C
N
H1 H2 H1 H2 H1 H2
X1 X3 X1 X1
X3 X3
X2 X2 X2
a
b
c
INSULATED PHASE BARE GROUNDED
CONDUCTORS PHASE CONDUCTOR
B b
SECONDARY VOLTAGES
N c Vab = 240V
a Vbc = 240V
A C
Vca = 240V
PRIMARY VECTORS SECONDARY VECTORS
DELTA , DELTA CONNECTION FOR 3-PHASE, DELTA
SECONDARY
DELTA , WYE CONNECTION FOR 3-PHASE, WYE
SECONDARY
WYE , WYE CONNECTION FOR 3-PHASE, WYE
SECONDARY
New Technology on Distribution
Transformer