Air System Sizing Summary for HU GF ENTERANCE LOBBBY

Proect Name: PGIMER Mother and Child Care

Air System Infomation


Air System Name ..HU GF ENTERANCE LOBBBY Number of zones. ..
1
Equipment Class. ******************************************* UNDEF Floor Area ......... 6449.0
Air System Type . ....o-*-.o**
* ***** *~-******* ** ******. SZCAV

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM. Sum of space airflow rates
Space CFM. Individual peak space loads
Calculation Months *************.*************************. J a n to Dec
Sizing Data **************************************************** Calculated

Central Cooling Coil Sizing Data


Total coil load . .
- ********************************************************11.3 Tons Load occurs at . . **************************************************.. Jul 15000
Total coil load 135.1 MBH OA DB/WB ********** ****** 107.0/72.0 F
Sensible coil load. ******************************************************** 125.6 MBH .79.9/ 66.8 F
Coil CFM at Jul 1500 Entering DB /WB. * * * * * * * * * * * * * * * * * * * * * * - - -

6428
************ CFM Leaving DB / WB. 61.4/ 60.1 °F
******************************-******************-

Max block CFM...- - - - - - - - - -----*-****-~-----* 6428 CFM 59.3 F


Sum of peak zone CFM . Coil ADP *************************************************
*****************~----. 6428 CFM Bypass Factor . ******************************************************************
.. 0.100
Sensible heat ratio. * * ************************************** .0.929
Resulting RH.************************** ****************************-********* 57 %
P/Ton - ********************************************-~ 483.9 Design supply temp. . 58.0 F _ ....-.-...-....-...-..-

BTU/(hr-ft).
***************

******************
-24.8 Zone T-stat Check . 1 of 1 OK
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Water flow 10.0 °F rise .

.-*---***. - -

--- . 27.04 gpm Max zone temperature deviation. 0.0 F


**********************************

Central Heating Coil Sizing Data


Max coil load . ************************************* 41.7 MBH Des Htg
-********** Load occurs at . ***********
* ***********************
Coil CFM at Des Htg. **************************~ ************-****-. 6428 CFM 7.7
Max coil CFM.. BTU/(hr-ft). ....---...................-.--..-- ***************.- .

6428
********
*********** CFM Ent. DB/Lvg DB .--
67.2/ 73.4 °F
Water flow@ 20.0 °F drop. **********~*~---~---- .4.17 gpm

Supply Fan Sizing Data


Actual max CFM...
*****~************ ******---**--*-**. 6428 CFM Fan motor BHP. 0.00 BHP
************************************

Standard CFM **************************************************************


.6265 CFM Fan motor kW . . . 0.00 kW
Actual max CFM/t * ********** 1.18 CFM/ft2 Fan static.. *******-**************-**************************************
0.00 in wg

Outdoor Ventilation Air Data


Design airfiow CFM . ***************************** . .600 CFM CFM/person. ******* ** ********************* 10.00 CFM/person
CFM/2 ******************* *** ------. ****** .0.11 CFM/2
Zone Sizing
Project Name: PGIMER Mother and Child Care
Summary for HU GF ENTERANCE LOBBBY

Sizing Calculation Information


Zone and Space
Zone CFM
Sizing Method:
Sum of space airflow rates
****************.

Space CFM Individual peak space loads Calculation Months ********************************* Jan to Dec
Sizing Data . ..Calculated
Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Zone Name Sensible Flow Flow Peak Load Area
(MBH) (CFM) Zone
Zone 1 115.0
(CFM) Load (MBH) (f) CFM/fe
6428 6428 Jul 1500 28.2
Zone Terminal Sizing Data
5449.0 1.18
No Zone Terminal
Sizing Data required for this system.
Space Loads and Airflows

Zone Name Cooling Time Air Heating Floor


Space Name Sensible of Flow Load Area Space
Mult.
Zone 1 (MBH) Load (CFM) (MBH) (fE) CFM/fe
GFENTERANCE LOBBY
115.0 Jul 1500 6428 28.2 5449.0 1.18
System Psychrometrics for HU
Project Name: PGIMER Mother and Child Care GF ENTERANCE LOBBBY

July DESIGN COOLING DAY, 1500


TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Component Temp Humidity Airflow Heat Heat
Location (F) (Ib/ib)| (CFM)| (BTU/hr)
Ventilation Air Inlet 107.0 0.00923
(BTU/hr)
Vent-Retum Mixing 600 18847 6669
Central Cooling Coil Outlet 79.9 0.01141 6428
Central Heating Coil
Outlet 61 4 0.01109 6428 125587 9541
Outlet 1.4 0.01109 6428
Supply Fan Outlet 61.4|
Cold Supply Duct 0.01109 6428
Outlet 61.4
Zone Air 0.01109 6428
Returm Pienum 77.2| 0.01163 6428 106740 16200
Return Fan Outlet 77.2
0.01163 6428
Outlet 77.2 0.01163 6428
Air Densityx Heat Capacity x Conversion Factor: At sea level 1.080; At site altitude
=

Air 1.053 BTU/(hr-CFM-F)


Densityx Heat of Vaporizationx Conversion Factor: At sea level 4746.6; At site altitude
Site Altitude = 708.0 f 4626.4 BTU(hr-CFM)
=

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone Heating Heating
Zone Name Load T-stat Cond Temp Airflow Coil
(BTU/hr) Unit
Zone 1 Mode (BTU/hr) (CFM) (BTU/hr) BTU/hr)
115029 Cooling 106740 77.2 6428
System Psychrometrics for HU GF ENTERANCE LOBBBY
Project Name: PGIMER Mother and Child Care

WINTER DESIGN HEATING


TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Component Temp Humidity Alrflow Heat Heat
Ventilation Air Location (CE) (lb/lb) (CFM) (BTU/hr)L (BTU/hr)
Inlet 44.0 0.00312| 16159
Vent Retum Mixing Outlet 67.2 0.00312 6428
Central Coling Coil Outlet 67.2 0.00312 6428
Central Heating Coil Outlet 73.4 0.00312 6428 41700
Supply Fan Outlet 73.4 0.00312 6428
Cold Supply Duct Outlet 73.4 0.00312 6428
Zone Air
69.6 0.00312 6428 -25541
Retun Plenum
Return Fan
Outlet 69.6 0.00312 6428
Outlet 69.6 0.00312 6428
Air Densityx Heat Capacity x Conversion Factor: At sea level 1.080; At site altitude 1.053
=

Air Densityx Heat of Vaporization x Conversion Factor: At sea level 4746.6; At site altitude BTU/(hr-CFM-F)
Site Altitude = 708.0R
=
4626.4=
BTU(hr-CFM)
TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone Heating Heating
Load T-stat Cond Temp Airflow Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr)
Zone 1 (F)| (CFM) (BTU/hr) (BTU/hr)
28154 Heating -25541 69.6 6428 0
Proiect Name: PGIMER Mother and Child Care Psychrometric Analysis for HU GF
ENTERANCE LORReY

Location: New Delhi, India


Altitude: 708.0 f.
Data for: July DESIGN COOLING
DAY, 1500 0.0200
| 1. Outdoor Air
Mixed Air 0.0175
Central Cooling Coil Outlet
Supply Fan Otlet
Room Air

0.0150

0.0125
-

0.0100

0.0075

0.0050

0.0025

0.0000
30 40 50 60 70 80 90 100 110
Temperature (°F )