You are on page 1of 5

IEEE Sponsored 2nd International Conference on Innovations in Information Embedded and Communication Systems

ICIIECS’15

Analysis of Partial Discharge in Underground Cable


Joints
B. Rajalakshmi L. Kalaivani
Dept. of EEE Dept. of EEE
National Engineering College National Engineering College
Kovilpatti-628503, India Kovilpatti-628503, India
rajalakshmi.kvp@gmail.com anuprakad@gmail.com

Abstract - The reliable operation of power network is greatly part in underground transmission system due to 3 types of
reduced by the cable joint failure. Most of the cable joint failure stresses which are supreme in joints. They are the thermal
is due to poor workmanship and insulation degradation. During stress, electrical stress and mechanical stress. Cable joint
cable joint process, different types of insulating materials are failure causes poor workmanship and improper installation.
used. The quality of insulation systems is important in the part of
Estimated dispersion of 37.1%, 5.6%, 1.1% cable failure was
cable network. Partial discharge is a diagnostic tool for detecting
problem in cable joint. This work has been carried out in a resulted from cable joint fault, termination fault and unknown
laboratory on 1.1 kV XLPE, 25 Sq.mm cable and cable joints reason in the North American MV cable system [4].
with different insulations. Partial discharge under different
conditions such as a piece of cable, cable joint without insulation, Partial discharge (PD) is the most important
cable joint with insulation (tape insulation, epoxy resin phenomenon occurs in the cable insulation system. If PD
insulation, epoxy resin grade 103 insulation) and cable joint with measurement is not available, there is no evidence of cable
void are analyzed. Based on the results epoxy resin insulation has damage. To increase the system reliability, PD measurement is
higher Partial Discharge Inception Voltage (PDIV) values and of great significance. Several methods to detect PD in high
shows better performance than other insulations. voltage (HV) cables and their accessories have been described
in the literature [4-6]. The offline PD measurement has an
Keywords - Partial discharge, cross linked polyethylene cable, cable
joint, insulating material, high voltage cable testing. advantage over the other technology. Because, it gives exact
fault location in the cable insulation, cable joint insulation and
I. INTRODUCTION aged cable system. It reports the warning message to the
manager. Based on these informations, it is easy to find out
Cable is the most important power apparatus for the fault in cable joints and rectify it. Catroscopic failure is
transmission of electrical energy. By the rapid urban growth, also avoided by using PD measurements [5].
it is impossible to maintain the number of size of feeder for
over head transmission line approach. As an alternative the II. PARTIAL DISCHARGE IN CABLE JOINT
underground cables become more increasingly to replace the
some of the overhead transmission line for power transmission Most of the failures that occur in the cable systems is
and distribution. Power cable technology had its beginning in due to following reasons: 1. Manufacturing imperfections
the 1880s, when the need for power distribution cables such as voids, Contaminants in insulations, Poor application
became essential. In the late 1960s, power distribution cables of shield material, Protrusion on the shields, Poor application
insulated with Cross Linked Poly Ethylene (XLPE) began of jackets. 2. Poor workmanship during cable joints such as
making their appearance in Canada and United State in 1965. cuts, contamination, missing applied components,
After that, XLPE cable is used all over the world due to misalignment of accessories. These reasons tend to increase
following special features: High dielectric strength, Low the local stress leading to either initial failure or higher rates
dielectric constant, Good dimensional stability and Light of aging. 3. Water ingress due to normal migration through
weight [1-3]. polymeric material, breaks in seal or metallic. It also reduces
the dielectric strength and increase the stress in the area
Cables are joined together under different surrounding the moisture [3].
applications like installation. Development of transient over
current failure occurs not only in the cable but also occurs in PD is defined as “a localized electrical discharge
the cable joints and termination. Cable joint is the weakest that only partially bridges the insulation between conductors
and which may or may not occur adjacent to a conductor”.

978-1-4799-6818-3/15/$31.00 © 2015 IEEE


IEEE Sponsored 2nd International Conference on Innovations in Information Embedded and Communication Systems
ICIIECS’15

PDs are very harmful in solid insulated cables. In most cases, Epoxies are used in various casts and molds,
discharges that are detected during normal operation will lead laminates, plastic tooling, electron microscope, aerospace
to breakdown. The time from PD ignition to final breakdown industry, electronic industry, aircrafts, automobiles, boats and
depends on the discharge type and the place in the cable [6]. other such applications. Being highly useful chemical
A PD phenomenon is random and there is always some compounds, epoxy resins have carved their niche in a number
statistical variation between the times to the breakdown. of industrial applications. Epoxies differ from polyester resins
Depending on the discharge’s type and place the time taken because they are cured by a 'hardener' rather than a catalyst.
breakdown varies from a few hours to a few years. The hardener, often an amine, is used to cure the epoxy by an
‘addition reaction’ where both materials take part in the
Basic structure for a polymeric cable consists of a chemical reaction. Since the amine molecules 'co-react' with
conductor, insulation, a metallic shield and jacket. Cable the epoxy molecules in a fixed ratio, it is essential that the
loading has an influence on PD intensity and magnitude from correct mix ratio is obtained between resin and hardener to
interfacial cavity type defects in polymeric cables. The main ensure that a complete reaction takes place.
factors for these defects, the temperature rise and mechanical
stresses that are caused by cable loading. Cable joints and If amine and epoxy are not mixed in the correct
terminations cause most of the faults in a cable system. They ratios, unreacted resin or hardener will remain within the
have thicker insulation than in the cable so it usually takes matrix which will affect the final properties after cure. To
somewhat longer time for PD to cause a breakdown. The assist with the accurate mixing of the resin and hardener,
insulation screen must be cut off to make a joint or manufacturers usually formulate the components to give a
termination. This causes an uneven distribution of the electric simple mix ratio which is easily achieved by measuring out by
field which means more stress to the insulation [6-10]. There weight or volume. The mixing of resin and hardner is used in
are many defects which can induce PD and many different cable joint insulation [12].
degradation processes that can result.
IV. PARTIAL DISCHARGE MEASUREMENT SYSTEM
The performance of insulating material used in
cable joint can be evaluated by Partial Discharge Inception A. Experimental Setup
Voltage (PDIV) and Partial Discharge Extinction Voltage
(PDEV). PDIV means very first PD observed when the There are a range of techniques used to measure the
voltage is gradually increased from lower level to higher level. PD activity [13]. In this experiment, PD activity is measured
In this work, the PDIV for all conditions are measured [11]. by using coupling capacitor, high voltage test transformer, and
PD meter. The setup used during test is given in figure 1.
III. CABLE JOINT INSULATING MATERIAL
Rating of coupling capacitor is 120 kV, 50 Hz, test
Different types of insulating materials are used for voltage is 144 kV, HV capacitance range is 10000 pF. The
cable jointing [3]. The functions of cable joint insulating testing transformer rated voltage is 2×0.22/100/0.22 kV, rated
compounds are 1. To insulate the conductors and keep them in current 2×22.8/0.1A, rated output is 10 kVA. Coupling
position. 2. To prevent moisture in seal joint. 3. To protect capacitor is used to block DC and only allows AC. Testing
joint from damage. In practical, different types of synthetic transformer is used to produce AC, DC, and impulse voltage.
resins are used such as acrylic resins, epoxy resin,
polyurethanes, poly ester resin etc.

In this experiment, epoxy resin, epoxy resin grade


103 is used for cable jointing. PVC insulation tape is used for
secondary use. The PVC Insulation tapes are made out of Poly
Vinyl Chloride Film. These insulation tapes find wide
application in electrical applications for their good adhesion
and insulation properties. The tape is coated with specially
formulated adhesives that make it resistant to moisture, alkalis
and oils. Advantages are coated with specially formulated
adhesives, excellent insulation property, resistant to moisture,
alkali, high voltage and oils, protect the wire from corrosion
and pressure sensitive tape. Fig. 1. Experimental setup
IEEE Sponsored 2nd International Confference on Innovations in Information Embedded and Com
mmunication Systems
ICIIECS’15

Supply is given to cable by means oof transformer.


The control desk is used to control and operatte high voltage
AC test equipments. Computerized PD moniitoring system
gives information about PD.

B. Partial Discharge Meter


c d
The PD meter DTM serves to verify hhigh frequency
PD pulses appearing in the high voltage dieelectrics. Such
discharges may be due to faulty insulation, bbad contact or
dielectrically overstressed areas. The PD meterr is a valuable
instrument for the timely detection of theese disturbing
phenomena and to discard faulty apparatus uunder test. The e
measured PD intensity is displayed either in pC C according to Fig. 2. Test specimen
n for PD analysis
IEC 60270, IS 6209 and, alternatively, in microvvolt
V. RESULTS AND
D DISCUSSION
C. Preparation of Test Specimen
A high voltage supply is given to XLPE cable joint.
The length of armour and inner sheathh is maintained PDIV is measured under follow wing condition by using PD
after cutting. The conductors are joined by crimping type meter and measurement setup: normal cable, cable joint
ferrules using crimping tool. The spacers aare placed on without insulation, cable jointt with insulation, void in
insulated cores. The cable entry portions of the mould is insulation. At the beginning, the test room temperature is 32
cutted and to match the diameter over sheath. The mould is °C. The temperature 32°C is maintained for the whole
placed at the bottom half in position. Ensure the clearance measurement. As per IS 10810 0 part 45, a HV is applied
between jointed phases. Between each jointedd phase mould between a) R and (Y+B+N), b) Y and (R+B+N), c) B and
are as follows: 8mm&6mm -1.1 kV. All the ccores are bind (R+Y+N), d) N and (R+Y+B). The test was carried out in
together with PVC tape. Top and bottom of the plastics mould each phase separately. When a po ositive supply is given to one
is placed on the prepared cable. A foam sheet ttape is used to phase, another phases and neutrall are connected to ground.
block cable entry into plastic mould at both thhe ends. Cable
jointing compound is stirred to make it homoogeneous. The
hardener is added and mixed to a uniform mixtture for at least
5 minutes. Air bubbles are removed during mixing before
pouring. The mixed compound is poured slowly into the
mould, through pouring gate till the mould, poouring gate and
risers are completely filled with compound [14-15].

D. Test Specimen

The test specimen used for analyzing thee PD source is


or R, Y phase
Fig. 3a. PD waveform fo
a) normal cable. b) Cable joint without insulaation c) Cable
joint with tape insulation. d) Cable joint witth epoxy resin The PD wave form fo or R, Y, B, N phases are
insulation. e) Cable joint with epoxy resiin grade 103 captured by using agilent oscilloscope (DSO 6032A) under
insulation, f) Void in tape insulation, epoxy reesin insulation, the condition of cable joint witth epoxy resin insulation is
epoxy resin grade 103 insulation. Test specimeen used during shown in figure 3a, 3b. This oscilloscope is a high resolution
test is shown in figure 2 (a) to (e). and faster response to capture the waveform.

The response of bandwidth is 300 0 MHz, memory is 8 Mbps,


2 port signals that automaticallyy sets the vertical, horizontal
and triggers control. It easily interface into system and
o capture the narrow range of
software upgrades. It’s possible to
partial discharge data. PD wavefform gives the relationship of
a b
IEEE Sponsored 2nd International Conference on Innovations in Information Embedded and Communication Systems
ICIIECS’15

apparent charge magnitude of cable joint with epoxy resin In this condition, PD occurs earlier due to insulating
insulation material surrounding the void which gets easily ionized and it
leads to breakdown. At void condition PDIV values of all
phases are reduced when compared with epoxy resin
insulation.

TABLE II. PDIV FOR EPOXY RESIN INSULATION

R Y B N
Cable condition (kV) (kV) (kV) (kV)

Normal cable 5.2 5.2 5.1 5.0

Cable joint without insulation 2.5 2.5 2.4 2.1


Fig. 3b. PD waveform for B, N phase
Cable joint with tape insulation 2.9 3.0 2.8 2.5
In this test, the voltage level was first increased from
0 kV to 7 kV gradually in 30 seconds. In this duration first Cable joint with epoxy resin insulation 5.1 5.1 4.8 4.8
remarkable discharge value is obtained at 5.2 kV for R, Y
phase, 5.1, 5.0 kV for B, N phase, which is the inception Void in epoxy resin insulation 4.5 4.5 3.8 3.8
voltage level.

TABLE I. PDIV FOR TAPE INSULATION TABLE III. PDIV FOR EPOXY RESIN GRADE 103
INSULATION
R Y B N
Cable condition (kV) (kV) (kV) (kV) R Y B N
Cable condition (kV) (kV) (kV) (kV)

Normal cable 5.2 5.2 5.1 5.0 Normal cable 5.2 5.2 5.1 5.0

Cable joint without insulation 2.5 2.5 2.4 2.1 Cable joint without 2.5 2.5 2.4 2.1
Insulation

Cable joint with tape insulation 2.9 3.0 2.8 2.5 Cable joint with tape insulation 2.9 3.0 2.8 2.5

Cable joint with epoxy resin 4.7 4.7 4.4 4.7


Void in tape insulation 2.7 2.7 2.5 2.3 grade 103 insulation

Void in epoxy resin grade 103 4.0 4.1 3.3 3.5


The PD activity in normal cable and tape insulation is insulation
compared in Table I. Initially the cable is tested without
insulation. PDIV value is very low. This condition leads to From table III, epoxy resin grade 103 is almost
breakdown process. In emergency situations, tape insulation is suitable for cable joint because PDIV value is nearer to
wrapped around the cable joint terminals with suitable normal cable condition. In addition the insulation with void is
clearances. This condition is analyzed and inferred that, the analyzed. In this case, the PDIV values of R, Y, B, N phases
occurrence of PDIV is low due to insulation property. The are reduced from 4.7kV, 4.7kV, 4.4kV, 4.7kV to 4.0kV,
value of PDIV in N phase is lower than other phases. Due to 4.1kV, 3.3kV, 3.5kV. The value of PDIV in B phase is low
some imperfection in insulation, PD occurs which results in due to large size of void is present. Thus fault at any phase can
reduced PDIV. be easily found by means of PD measurement.

From table II, it is inferred that epoxy resin is A standard approach is to compare confidence
suitable for cable joint insulation due to its high PDIV. In this intervals of the Weibull distribution of different sample sets. It
condition, PDIV value is almost same for normal cable is observed from Fig. 4 that the probability of occurrence of
condition. In addition the insulation with void is analyzed. partial discharge (PD) on cable joint with epoxy resin, epoxy
PDIV for R, Y phases are 4.5kV, B, N phases are 3.8kV. resin grade 103 insulation is very low compared to cable joint
without insulation.
IEEE Sponsored 2nd International Confference on Innovations in Information Embedded and Com
mmunication Systems
ICIIECS’15

NCES
REFEREN
1. Eichhorn R. M (1981), ‘A criticall comparison of XLPE and EPR for
use as electrical insulation on underground
u power cabbles’, IEEE
Transcations on dielectric and Elecctrical insulation, Vol. 16, No. 6, pp.
469-482.
2. Boggs .S .A (2002), ‘Mechanism for f degradation of TR-XLPE impulse
strength during service aging’, IE EEE Transations on power delivery,
Vol. 17, No. 2, pp. 308-312.
3. Carlos Katz, Michael L. Walker, Robert
R J. Keefe, Vitaliy Yaroslavskiy,
L.Walker (2008), ‘Comparative Laboratory
L Evaluation of Premolded
Joints for Medium Voltage Cab bles’, IEEE Transactions on Power
Delivery, Vol. 23, No. 2, pp. 516-522.
4. Aschwanden. Th, Hahn. H, Heiman nn. Th, Laurent. M, Ritter. L (1998),
‘On-site partial discharge measurem ments on premoulded cross-bonding
joints of 170 kV XLPE and EPR cables’,
c IEEE Transactions on Power
Delivery, Vol. 13, No. 2, pp. 330-335.
5. Hao. L, Hunter. J. A, Lewin. P. L, Michel. M, Walton. C (2013),
‘Autonomous classification of PD D sources within three-phase 11 kV
PILC cables’, IEEE Transactio ons on Dielectrics and Electrical
PDIV(kV) Insulation, Vol. 20, No. 6, pp. 21177-2124.
6. Chien-Kuo Chang, Ruay-Nan Wu W (2011), ‘The Use of Partial
Figure 4. Weibull probability plot for cable joint with diffferent insulation Discharges as an Online Monitoriing System for Underground Cable
Joints’, IEEE Transactions on Pow wer Delivery, vol. 26, No. 3, pp.
1585-1591.
VI. CONCLUSION 7. Hao. L, Lewin. P. L (2010), ‘Parrtial discharge source discrimination
using a support vector machine’, IE EEE Transactions on Dielectrics and
Electrical Insulation, Vol. 17, No. 1,
1 pp. 189-197.
In this work, a study has been made abbout the use of
PD measurements as a part of a medium voltaage cable joint 8. Ahmed. H, Srinivas. N. N (1998), ‘On-line partial discharge detection
life cycle management process. The theory behind PD, their in cables’, IEEE Transactions on Dielectrics
D and Electrical Insulation ,
measurement in XLPE cable joints with differrent insulation, Vol. 5, No. 2 pp. 214-217.
9. Chandima Ekanayake , Hui Ma, C. Jeffery Chan, Saha, K Tapan
artificial fault in the insulation and expeeriences from (2013), ‘Pattern recognition tech hniques and their applications for
laboratory have been studied. Based on thesse studies the automatic classification of artificiial partial discharge sources’, IEEE
following conclusions are drawn. Transactions on Dielectrics and Electrical
E Insulation, Vol. 20, No. 2,
pp. 468-478
Cable failure probability is high at the beginning and 10. Chatterjee. B, Chakravorti. S, Dey.D D, Munshi. S (2010), ‘Cross-
wavelet transform as a new paradig gm for feature extraction from noisy
at the end of cable life. The main reasons for faiilures on newly partial discharge pulses’ , IEEE Transactions on Dielectrics and
installed cables joints are improper selectionn of insulating Electrical Insulation, Vol. 17, No. 1,
1 pp. 157-166.
materials and bad workmanship. The rise of failure probability 11. Edward Gulski , Frank Petzold HubertH Schlapp, Paul P. Seitz Ben
at the end of cable life is mainly caused by cablle aging. Cable Quak (2008), ‘Advanced Solution for f On-site Diagnosis of Distribution
Power Cables’, IEEE Transactio ons on Dielectrics and Electrical
aging depends on many internal and externaal factors. The Insulation Vol. 15, No. 6, pp. 1145-1149.
temperature, voltage stress, moisture and void present in the 12. Brazier. L. G (1946), ‘Joints, sealinng ends and accessories for pressure
insulating material are shown to be the main faactors affecting cable’, jjour.IEE, Vol. 93 PII, pp. 415-34.
4
the speed of insulation degradation. The qualityy of installation 13. Davies. A. E, Lewin. P. L, Tian. Y (2002), ‘Comparison of on-line
partial discharge detection meth hods for HV cable joints’, IEEE
and installation conditions has a big influence oon the lifetime Transactions on Dielectrics and Ellectrical Insulation, Vol. 9, No. 4, pp.
of the cable and its joints and terminations. PDDs are a sign of 604-615.
insulation deterioration. The harmfulness of P PD depends on 14. Short. H. D (1949), ‘A theoretical and practical approach to the design
the discharge source location, defect type aand insulating of h.v cable joints’, IEEE Transcaation on power delivery Vol. 68, pp.
1275-83.
material types. Selection of insulating material is used in the 15. Mcallister. D, Radcliffe. W .S (197 76), ‘Joints incorporating mechanical
cable joint as a very important task. connectors and joint refilling for 60
00/1000V cables’, IEE conference.

During cable operation interruption costs can be


minimized and cable replacement can be optim mized with the
help of continuous and periodic PD measurem ments. When, a
fault occurs this opens the possibility forr off-line PD
measurements which are also beneficial in decciding when a
cable system has reached its end of life stage or not.

You might also like