You are on page 1of 5

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 17, NO.

3, AUGUST 2002 757

Implementation of an ACE1 Decomposition Method


Naeb-boon Hoonchareon, Member, IEEE, Chee-Mun Ong, Senior Member, IEEE, and
Robert A. Kramer, Senior Member, IEEE

Abstract—Having established feasibility and developed a


method to decompose control area’s 1 into components
attributable to load changes in subareas within the control area,
this paper addresses some of the practical issues with an on-line
implementation of the 1 model and the decomposition
method. Issues examined here include time-varying system condi-
tions, nonlinearities in the governors’ dead bands and AGC loop,
and the impact of load disturbance external to the control area. An
on-line recursive parameter estimation technique with adjustable
forgetting factor to update the 1 model parameters is
proposed.
Index Terms—Area control error (ACE), ancillary services, Fig. 1. Test system with five interconnected control areas.
regulation.

For in reality, the system operating condition will be continu-


I. BACKGROUND ally varying, and our knowledge of the actual condition is at
best partial. Within the AGC and speed governing loops are
A CONTROL area with rapid and widely varying loads not
only incurs substantial costs in providing the necessary
regulation [1], but also the risk of penalty associated with vi-
various kinds of nonlinearities, such as limits and dead bands.
Moreover, in advanced AGC schemes, sophisticated logics
olation of CPS1 and CPS2 [8]. A method to quantify the impact are used to distribute the control effort amongst the regulating
of certain loads on an area’s control performance in terms of units. All of these point to the need to estimate the parameters
CPS1 and CPS2 would help identify responsibility in the event of the ACE models on-line.
where the control area is not in compliance with the control per- When the area’s bias coefficient 10 is set to its fre-
formance standards (CPS) measures, especially when a penalty quency response characteristic , the impact of any external
is involved. Potentially, the method could be useful to pricing re- disturbances on the internal area’s ACE is supposedly small.
lated ancillary services, and also in AGC design to optimize the Estimating the value of on a real-time basis is challenging
control area’s operational efficiency and control performance. [3], because of the complex relationship it has with governor
In the companion paper [2], we examine the feasibility of de- nonlinearities and load characteristics. In any case, with fixed
composing the 1-min average value of area control error (ACE), bias coefficient, the impact on ACE from external disturbances
, of a control area into components, each attributable to should not be ignored. Thus, the impact of external disturbances
load changes in subareas or zones within the control area; de- on the proposed decomposition method has to be studied.
scribe a reduced-order model of ; and devise an algorithm In this paper, we will address practical issues likely to be en-
to decompose into components identifiable to each of countered in the implementation of the decomposition
the defined zones. The decomposed components of may method. First, we establish the robustness of the model
then be used to quantify the impacts of load disturbances in the to a range of values of the AGC/LFC loop gains, synchronizing
corresponding zones on the , CPS1, and CPS2. A dy- torque coefficients, and areas’ frequency response characteris-
namic simulation of the 5-area test system shown in Fig. 1 is tics. Next, we describe an on-line estimation technique for up-
constructed to facilitate the development and testing of the ACE dating the model parameters under time-varying system
model and the decomposition method. conditions. Results showing the tracking capability and noise
A practical implementation of the method to decompose sensitivity of the estimation technique and the efficiency of the
should at the least consider the time-varying nature of combination of model with adaptive parameter identifi-
the system operating condition, nonlinearities within the AGC cation are presented. Finally, we examine the impact of external
and governor responses, and impact of external disturbances. disturbances on the same combination.

II. ROBUSTNESS OF THE MODEL


Manuscript received March 15, 2000; revised Novemer 5, 2001. This work
was supported by the Northern Indiana Public Service Company (NIPSCO). We begin by first assessing the robustness of the
N. Hoonchareon is with the Dept. of Electrical Engineering, Chulalongkorn model in portraying the actual of a control area over
University, Bangkok, Thailand.
C.-M. Ong is with the School of Electrical and Computer Engineering, Purdue a range of system conditions in the absence of nonlinearities.
University, West Lafayette, IN 47907 USA. Specifically, the performance of the model is examined
R. A. Kramer is with NiSource Energy Technologies, Merrillville, IN 46410 over the following ranges of parameters:
USA.
Publisher Item Identifier 10.1109/TPWRS.2002.801035. 1) effective AGC/LFC loop gain: ;
0885-8950/02$17.00 © 2002 IEEE
Authorized licensed use limited to: AMRITA VISHWA VIDYAPEETHAM AMRITA SCHOOL OF ENGINEERING. Downloaded on August 20,2023 at 08:28:40 UTC from IEEE Xplore. Restrictions apply
758 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 17, NO. 3, AUGUST 2002

TABLE I
RMS ERROR (MW) WITH NO EXTERNAL DISTURBANCES

2) synchronizing torque coefficients: ;


3) area’s frequency response characteristics:
10 ;
where , , and 10 are the nominal values. An AGC/LFC
effective gain of yields approximately 1-min time
constant in the AGC/LFC response. The nominal values of the
Fig. 2. Estimated ACE model parameters under fixed system condition.
bias coefficients 10 for the five control areas are based on
the present rule of thumb of 1% of the peak demand published
by the control areas.
(2)
The test loads applied within the zones 2 and 3 are uncorre-
lated arc furnace loads with temporal fluctuation up to 200 MW
load change within a period of less than 1 min. Zone 1 has a where and are updated at every time step when fresh
conforming load, consisting of a ramp component and a random values of become available. Past information are deem-
variation component. phasized by introducing an exponential weight, or forgetting
Table I summarizes the results of a number of simulation factor , where .
studies. The root mean square (rms) error measure used is the Initial values of and can be conveniently set, that is,
rms of the differences between the actual and the mod- and , where is some large constant [5].
eled , over a 2-h interval of operation. It should be clar-
ified that the term actual here refers to the ob- B. Updating and
tained directly from the SIMULINK simulation of the intercon-
nected system, standing in for the real system. The term modeled Rewriting the model equation given in [2] into the
refers to the computed from the average model form of (2), we have
equation described in the companion paper [2].
The rms error is less than 1 MW in most cases with the worst
rms error under 3 MW. Moreover, the results reveal that the (3)
ability to portray is better in cases where the AGC/LFC
gain and the synchronizing torque coefficients are high, and the where and refer to time steps at the beginning and at
value of area’s bias coefficient is close to the value of area’s fre- the end, respectively, of the th 1-min interval.
quency response characteristics. The accuracy of the modeled Here, the vector is being updated every two
is also somewhat sensitive to dynamic response and par- seconds when new data on the area’s ACE and total load change
ticipating factor of the regulating units. On the whole, the num- become available.
bers in Table I indicate that the model performs well over
the range of the system conditions tested. C. Test Results
On-line estimates of the model parameters are com-
III. ON-LINE ESTIMATION OF THE MODEL PARAMETERS puted from sampling the dynamic simulation every two sec-
The model parameters and are inversely propor- onds. The values of and obtained on-line are verified by
tional to the effective AGC/LFC loop gain which is a function of comparing them with corresponding values obtained from an
the AGC control parameters, the range, and participation factor off-line least square computation.
of the regulating units. For changing operating conditions, the Fig. 2 shows the and in a case where the system condi-
values of and can be updated using a recursive least square tion is not time-varying. Despite the random and rapid changes
(RLS) technique with exponential weights. in the area’s ACE and load, the algorithm performed stably, with
the estimated parameters converging quickly to their respective
A. Recursive Least Square (RLS) Method expected values.
The RLS algorithm for updating and of the ACE model Fig. 3 shows the tracking ability of the method to follow a
can be written as step up and a step down of the AGC gain . Step changes in
AGC gain are used in this test because the correctness of the es-
(1) timated and can be readily verified by formula. The results
Authorized licensed use limited to: AMRITA VISHWA VIDYAPEETHAM AMRITA SCHOOL OF ENGINEERING. Downloaded on August 20,2023 at 08:28:40 UTC from IEEE Xplore. Restrictions apply
HOONCHAREON et al.: IMPLEMENTATION OF AN DECOMPOSITION METHOD 759

Fig. 3. Tracking capability of the RLS method. Fig. 4. Model performance with 30-MHz governor dead bands included.

demonstrate the ability of the procedure to correctly estimate the


values of and in response to such changes in AGC gain.
The value of the forgetting factor can be adjusted to achieve
a tradeoff between tracking ability and noise sensitivity. A larger
gives better performance in terms of noise sensitivity but
poorer tracking ability, the opposite is true when is smaller.
The test results presented are obtained with . The value
of forgetting factor to use will depend on the real system dy-
namics. The need to employ an adaptive forgetting factor will
be determined from actual experimentation of the method in the
field.

IV. NONLINEARITIES OF THE AGC


The AGC system has various nonlinearities, both within its
control logic and in the generating units. Here, we will examine
the impact of each of the following nonlinearities on the perfor- Fig. 5. Model performance with unit range limits included.
mance of the decomposition method:
1) 5 MW ACE dead bands in the AGC/LFC control logic
of the five control areas;
2) 30-MHz speed governor dead bands on all of the units;
3) rate and range limits of units under AGC control in control
area 1.
The dynamics of the 30-MHz governor dead band is imple-
mented using the backlash representation given in [6]. A unit’s
rate and range limits are incorporated into the models of gov-
ernor and prime mover of the generating unit, as described in
[7].
Our study revealed that the inclusion of the 5 MW ACE
dead bands or the unit rate limits alone on the AGC system has
no significant impact on the accuracy of the modeled and
on the dynamics of the model parameters and . However,
governor dead bands and unit range limits may have significant
effects. Fig. 6. Response to AGC command of regulating units with range limits: unit
Fig. 4 shows the estimated and , and the corresponding 6 6
REG1: 40 MW and unit REG2: 30 MW from baseload operating points.

differences between the actual and the modeled


with just governor dead bands included in the system simu- governor dead bands. The limits on the output response of two
lation. The effect of governor dead bands is observed to be of the units are evident from Fig. 6. Larger errors occur when-
small when the frequency deviation is well within the dead band. ever the regulating units are driven against their range limits be-
Fig. 5 shows the results obtained from a similar run with non- cause of the drop in effective AGC/LFC loop gain. The
linearities from limits imposed on the units’ range instead of model parameters have a reciprocal relation with that effective
Authorized licensed use limited to: AMRITA VISHWA VIDYAPEETHAM AMRITA SCHOOL OF ENGINEERING. Downloaded on August 20,2023 at 08:28:40 UTC from IEEE Xplore. Restrictions apply
760 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 17, NO. 3, AUGUST 2002

TABLE II
RMS ERROR (MW) WITH EXTERNAL DISTURBANCES

responding clock-minute compliance factors of


CPS1 for the same case, as computed using the actual and mod-
eled values of . These results indicate that the decompo-
sition method functions reasonably well in the presence of the
Fig. 7. Actual ACE and modeled ACE under combined nonlinearities. above-mentioned types of nonlinearities.
Many of today’s AGC systems may be equipped with com-
plex control algorithms, including adjustable ACE dead band,
adjustable rate, and range limits. The feasibility of incorporating
the decomposition technique into such AGC systems will have
to be examined on a case-by-case basis.

V. IMPACT OF EXTERNAL DISTURBANCES


To determine the sensitivity of the control area’s ACE to ex-
ternal load disturbances and its impact on the decomposition
technique, sizable random load variations are simultaneously
applied to control areas 2–5 in Fig. 1. The load in control area 1
remains the same as described earlier.
Table II presents the rms errors of the modeled for
various system conditions previously shown in Table I; but this
time, with load disturbances also applied in the external areas.
Fig. 8. Difference between the two curves given in Fig. 7. A comparison of the results given in Tables I and II will
show that when , the accuracy of the modeled
is only slightly affected by external load disturbances.
This observation agrees with the theory that external load
disturbances should not affect the ACE of a control area when
its frequency bias coefficient is set equal to its frequency
response characteristic.
Second, the larger the difference between the area’s 10
and , the larger the impact of external disturbances on the local
ACE and on the accuracy of the modeled . This is also
evident from the differential equation governing the behavior
of ACE given in the companion paper [2]. When the difference
is large, the influence of frequency error on ACE
becomes significant.
Although control area 1 has fairly strong ties with its external
areas and the external load disturbances applied are sizable, the
impact of the external disturbances on its ACE and the decom-
Fig. 9. Clock-minute compliance factor under combined nonlinearities. position algorithm is not large. The rms errors of all of the cases
studied are small. This is due, in part, to the fact that the differ-
loop gain. In such situations, we observed that the use of a con- ence of control area 1 is small relative to similar dif-
stant forgetting factor in the RLS could not provide acceptable ferences of the neighboring areas. Had it not been the case, the
tracking ability and noise sensitivity. impact of external disturbances would be larger. A large differ-
Fig. 7 shows the actual and the modeled for ence between the frequency bias setting and the actual value of
the case where all of the above-mentioned nonlinearities are the frequency response characteristic is not uncommon in prac-
present. To facilitate a comparison, the difference between the tice, especially when 10 is determined as some fraction of
two curves of Fig. 7 is shown in Fig. 8. Fig. 9 shows the cor- peak demand and when the effective value of the frequency re-
Authorized licensed use limited to: AMRITA VISHWA VIDYAPEETHAM AMRITA SCHOOL OF ENGINEERING. Downloaded on August 20,2023 at 08:28:40 UTC from IEEE Xplore. Restrictions apply
HOONCHAREON et al.: IMPLEMENTATION OF AN DECOMPOSITION METHOD 761

nonlinear system conditions. Test results showed good conver-


gence, tracking ability, and noise sensitivity. The accuracy of
the decomposition method with adaptive parameter identifica-
tion is less affected by ACE dead bands and units’ rate limits,
but more so by governor dead bands and units’ range limits.
Finally, the impact of external disturbances on implementa-
tion of the decomposition technique is found to be negligible
Fig. 10. Root mean square of sliding m-minute average frequency error
when the difference between the area’s and 10 is small
obtained from the simulation. and/or when system frequency deviates within a narrow range.

sponse characteristic is lower than the theoretical value because REFERENCES


a significant number of the governors are operating well within [1] P. D. Handerson, H. Klaiman, J. Ginnetti, T. Snodgrass, N. Cohn, S.
their dead bands. Bloor, and L. S. VanSlyck, “Cost aspects of AGC, inadvertent energy,
and time error,” IEEE Trans. Power Syst., vol. 5, pp. 111–118, Feb. 1990.
If the area’s frequency response characteristic could be es- [2] N. Hoonchareon, C. M. Ong, and R. A. Kramer, “Feasibility of decom-
timated, e.g., by some on-line estimation method, then setting posing ACE for apportioning regulation and load-following costs,”,
10 to the estimated would lessen the area’s AGC reaction vol. 17, Aug. 2002.
[3] T. Kennedy, S. M. Hoyt, and C. F. Abell, “Variable, nonlinear tie-line
to external load disturbances. In doing so, the cost of over-reg- frequency bias for interconnected systems control,” IEEE Trans. Power
ulation and extraneous fluctuations in frequency and ACE may Syst., vol. 3, pp. 1244–1253, Aug. 1988.
also be reduced. A control policy that requires monitoring and [4] N. Cohn, Control of Generation and Power Flow on Interconnected
Power Systems. New York: Wiley, 1966.
control of the frequency response characteristic of each control [5] L. Ljung and T. Soderstrom, Theory and Practice of Recursive Identifi-
area would ensure a fairer distribution of the control responsi- cation. Cambridge, MA: MIT Press, 1983.
bility among the control areas. Indeed, in the most recent version [6] IEEE Working Group on Prime Mover and Energy Supply Models for
System Dynamic Performance Studies, “Dynamic models for fossil fu-
of NERC Policy 1 [8], NERC is recommending that a control eled steam units in power system studies,” IEEE Trans. Power Syst., vol.
area sets its frequency bias as close as practical to the area’s 6, pp. 753–761, May 1991.
frequency response characteristic. [7] IEEE Committee Report, “Dynamic models for steam and hydro
turbines in power system studies,” IEEE Trans. Power App. Syst., vol.
PAS-9, pp. 1904–1915, Nov./Dec. 1973.
VI. DISCUSSION [8] North American Electric Reliability Council, “Policy 1 generation con-
trol and performance,”, Version 1a, Feb. 2000.
Although the results presented were obtained from simula- [9] N. Jaleeli and L. S. VanSlyck, “Control performance standards and pro-
tion, the similarity of the system frequency dynamics in the sim- cedures for interconnected operation,” EPRI, Palo Alto, CA, EPRI Rep.
TR-107 813, Apr. 1997.
ulated system to those experienced in the real system may pro-
vide another check on the validity of the result presented. Fig. 10
shows the plots of the rms of the sliding average frequency er-
rors from our simulations. The shape of these curves is not un- Naeb-boon Hoonchareon (M’01) received the B.Eng. (Hons) degree in elec-
like measured frequency characteristic curves used in determi- trical engineering from Chulalongkorn University, Bangkok, Thailand, in 1993,
and the M.S.E.E. and Ph.D. degrees from Purdue University, West Lafayette,
nations of the relevant targeted bound in the NERC’s CPS: in IN, in 1996 and 2000, respectively.
the CPS1 and in the CPS2 [9]. Of the two curves, the one Dr. Hoonchareon is now with the Dept. of Electrical Engineering, Chula-
with nonlinearities is slightly flatter for average time windows longkorn University. His research interests include interconnected power sys-
tems operation, modern automatic control, and optimization.
greater than 10 s. This agrees with previous observations by
others that the problem with inadvertent energy exchange over
longer periods is accentuated by the effects of nonlinearities.
To follow up, we are planning to conduct a field implemen- Chee-Mun Ong (S’73–M’74–SM’80) received the B.E. (Hons) degree in elec-
tation and testing of these methods, and developing a method trical engineering from the University of Malaysia in 1967, and the M.S. and
to perform on-line estimation of the area’s frequency response Ph.D. degrees from Purdue University, West Lafayette, IN, in 1968 and 1974,
respectively.
characteristic. During the periods 1968–1973 and 1976–1978, he was a Lecturer at the Uni-
versity of Malaya. In 1969 and 1970, he was a UNESCO Fellow with the Central
Electricity Generating Board and the English Electric in the U.K. In 1978, he
VII. CONCLUSIONS joined the School of Electrical Engineering, Purdue University, first as an As-
This paper examines the issues related to the implementation sistant Professor, and then in 1985, as a Professor. His interests are in power
systems and electrical drives.
of a method to decompose to components identifiable Dr. Ong is a Fellow of the Institution of Electrical Engineers, and a registered
with changes in loads in subareas of the control area. Acceptable Professional Engineer of Indiana.
performance of the decomposition technique over a wide range
of system conditions is demonstrated. Our results show that the
accuracy of the decomposition is affected to varying degrees
Robert A. Kramer (M’85–SM’91) received the B.S. and M.S. degrees in
by the effective AGC/LFC gains, the area’s frequency response physics, and the M.S. and Ph.D. degrees in nuclear engineering, all from
characteristics, the tie strength, the dynamic response of units, Purdue University, West Lafayette, IN.
and outside load disturbances. Currently, he is Manager of Technical Support at Northern Indiana Public
Service Company (NIPSCO), Merrillville, IN, where he is responsible for the
Also presented is a RLS algorithm to update the introduction of new technology into the gas and electric functions of the utility,
model parameters for purposes of handling changing and as well as providing support on various technical and competitive issues.
Authorized licensed use limited to: AMRITA VISHWA VIDYAPEETHAM AMRITA SCHOOL OF ENGINEERING. Downloaded on August 20,2023 at 08:28:40 UTC from IEEE Xplore. Restrictions apply

You might also like