In cases of single customers with a maximum demand in
excess of 1.5 MVA, EDD shall provide an 11,000 Volt
incoming switchboard in a ring-main arrangement to be
installed in the distribution sub-station. The customer shall
provide his own 11,000 Volt switchboard, incorporating one or
more incoming 11,000 Volt circuit breaker(s), on which the
customer shall receive the electricity supply. The customer’s
equipment shall be installed in a switch room immediately
adjacent to the distribution substation of EDD with an
interconnecting door lockable only from the distribution
substation.