3. MAINTENANCE WORK
341 Regular Inspection
‘Area to be (Checkpoints Procedure
inspected __|
Every day | Pressure Reading ofpressure | Adjust reading to be specified value
Reducing valve | gauge should be correct. | (0.3 Mpa standart.
atair inlet iain must not be Drain if accumulated.
Accumulated more than
limit
level.
Sludge retum line | Sludge and scum are | If either sindge or scum is not being
and scum return | being returned, (Note | retumed, correct according to the
line (NOTE 1) | thatthe returning scum | instructions in (NOTE 2) on page 11
isnot always flowing in
the hose. It flows only
when sewage flows into
the Plant)
Chlorination tablets |The height of tablets in| Remove the top vover, and fully Gil the
inthe chlorinator | the cylinder needs to be | cylinder with the tablets.
(NOTE 2) atleast 1/4 the height of
cylinder.
Every week | Residual chlorine | The residual chlorine | Ifthe residual chlorine concentration
content in treated | concentration must fall_| exceeds 0.Sppm, control the amount of
water ina range of Oto the tablets.
0.5ppm.
Every month | Chlorinator ‘There must Be no Remove the ehlorinator and clean it
(NOTE 3) blockage inthe cylinder.
Discharge pump | Check the mechanical | If leakage rate is 0.5 ce/min or greater,
seal for leakage. ‘make correction according to the
instruction inthe instruction manual of
the discharge pump.~Areato be ‘Checkpoints Procedure
inspected |
Every 2103 | Aeration Discharging of excess | For 30 minutes, prohibit sewage from
months compartment | sludge flowing into the Plant and keep the
Plant inactive. Then, discharge
approximately 75% of the mixture
liquid inthe aeration compartment by
running the discharge pump.
Tris operation must be performed
outside restricted waters. After
discharging, fill the tank with wate,
and restart the Plant.
Check the interior sereen | Ifthe sereen has been fouled up or
for fouling. ‘logged, clean it with freshwater or
clean seawater
Clarification | Check the inside for __ | Ifthe inside is fouled up, clean with
compartment | fouling. freshwater of clean seawater
Every years | Tank, discharge | Inspect the inside of the | Discharge the wastes, and clean the
pump tank, as well asthe | inside. Then, inspect each area. Ifa
components onthe _| problem is found, repair or replace.
accessories.
Pressure Filter shall not be Clean if cogged.
reducing valve | clogged.
[Every3 years Inside ofthe tank | Damaged coating layer | Repair the damaged area with the
inside the tank. coating.
-10-