Professional Documents
Culture Documents
https://www.facebook.com/MelkatebDesignsheets
by
Mahmoud M. El-Kateb, Ph.D
Structural Engineering Dept.
Faculty of Engineering - Ain Shams University
INDEX (Quick reach)
Load Combinations
Moments of inertia for elastic analysis
Calculation of T & L Section Inertia
Design of Slabs
Design of Beams
Design for Shear
Design of Shear-friction
Design for Torsion
Check of Punching without Shear Rft.
Check of Punching with Shear Rft.
Deflection of Simple R-beams or Slabs
Deflection of Simple T-beams
Deflection of Cantilever Beams or Slabs
Design of Isolated Footings
Design of Combined Footing
Design of Pile Cap
Design of Pile Cap under Moment
Design of Cantilever Retaining Walls
Design of Deep Beam
Calculation of Crack Width
Design of Water section
Development & Splice of Reinforcement
Reinforced Concrete design according to ACI 318-19 By: Dr. Mahmoud El-Kateb
Version 1.3
Project :
1200 mm
250 mm
700 mm
250 mm
Project :
Dimensions
Sec. Tensile RFT Ieff
bw (mm) d (mm)
1 250 650 5 T 16 0.286 Ig
Project :
Ult. Moment Breadth Depth Thick. a (b1.c) Ascalc Asmin Used Required
Sec. Notes
Mu (kN.m) b (mm) d (mm) h (mm) (mm) (mm )
2
(mm )
2
As RFT.
1 216 1000 250 300 41.0 2490 540 2490 T 10 @31 safe
2 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
3 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
4 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
5 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
6 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
7 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
8 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
9 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
10 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
11 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
12 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
13 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
14 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
15 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
16 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
17 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
18 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
19 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
20 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
21 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
22 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
23 20 1000 120 150 7.5 455 270 455 T 10 @172 safe
Reinforced Concrete design according to ACI 318-19 By: Dr. Mahmoud El-Kateb
Version 1.4
* Design of Beams
Project :
None
Comp.
Ult. Moment Breadth Flange Flange Depth a (b1.c) Ascalc Asmin Used Required
Sec. Notes
Mu (kN.m) b (mm) B (mm) side d (mm) (mm) (mm ) (mm )
2 2
As RFT.
1 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
2 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
3 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
4 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
5 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
6 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
7 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
8 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
9 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
10 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
11 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
12 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
13 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
14 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
15 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
16 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
17 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
18 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
19 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
20 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
21 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
22 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
23 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
24 200 250 1200 Comp. 650 10.6 821 547 821 5 T 16 safe
Reinforced Concrete design according to ACI 318-19 By: Dr. Mahmoud El-Kateb
Version 1.5
Project :
Ult. Shear Normal Breadth Depth Thick. no. of Long. RFT. fVc Vs As Vu max
Sec. Stirrups
Vu (kN) Nu (kN) bw (mm) d (mm) h (mm) bran. (mm )
2
(kN) (kN) S (kN)
1 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
2 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
3 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
4 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
5 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
6 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
7 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
8 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
9 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
10 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
11 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
12 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
13 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
14 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
15 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
16 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
17 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
18 250 100 250 550 700 2 1200 109.0 188.0 0.407 T 10 @192 659
y: Dr. Mahmoud El-Kateb
Notes
safe
safe
safe
safe
safe
safe
safe
safe
safe
safe
safe
safe
safe
safe
safe
safe
safe
safe
Reinforced Concrete design according to ACI 318-19 By: Dr. Mahmoud El-Kateb
Version 1.1
* Design of Shear-friction
Project :
###
###
###
###
Ult. Shear Breadth Thick Coff. of friction Angle fVn (max) Avf fVn
Sec. Used RFT Notes
Vu (kN) b (mm) h (mm) (m) (a) (kN) (mm ) 2
(kN)
1 150 250 700 1 90 1,026 476 178 5 T 12 safe
2 150 250 700 1 90 1,026 476 178 5 T 12 safe
3 150 250 700 1 90 1,026 476 178 5 T 12 safe
4 150 250 700 1 90 1,026 476 178 5 T 12 safe
5 150 250 700 1 90 1,026 476 178 5 T 12 safe
6 150 250 700 1 90 1,026 476 178 5 T 12 safe
7 150 250 700 1 90 1,026 476 178 5 T 12 safe
8 150 250 700 1 90 1,026 476 178 5 T 12 safe
9 150 250 700 1 90 1,026 476 178 5 T 12 safe
10 150 250 700 1 90 1,026 476 178 5 T 12 safe
11 150 250 700 1 90 1,026 476 178 5 T 12 safe
12 150 250 700 1 90 1,026 476 178 5 T 12 safe
13 150 250 700 1 90 1,026 476 178 5 T 12 safe
14 150 250 700 1 90 1,026 476 178 5 T 12 safe
15 150 250 700 1 90 1,026 476 178 5 T 12 safe
16 150 250 700 1 90 1,026 476 178 5 T 12 safe
17 150 250 700 1 90 1,026 476 178 5 T 12 safe
18 150 250 700 1 90 1,026 476 178 5 T 12 safe
19 150 250 700 1 90 1,026 476 178 5 T 12 safe
20 150 250 700 1 90 1,026 476 178 5 T 12 safe
21 150 250 700 1 90 1,026 476 178 5 T 12 safe
22 150 250 700 1 90 1,026 476 178 5 T 12 safe
23 150 250 700 1 90 1,026 476 178 5 T 12 safe
24 150 250 700 1 90 1,026 476 178 5 T 12 safe
25 150 250 700 1 90 1,026 476 178 5 T 12 safe
Reinforced Concrete design according to ACI 318-19 By: Dr. Mahmoud El-Kateb
Version 1.4
Project :
T 10 @219
700mm
700mm
T 10 @161
T 8 @390
250mm OR 250mm
Reinforced Concrete design according to ACI 318-19
Version 2.0
Project :
unbalanced moment
b Mfb
d/
critical perimeter (bo) 2 t
Ult. Load Col. Dims. Slab Cover Critical bo Mft Mfb Size factor
Col.
Vu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m ls
650 300 600 250 30 Auto 2680 30 40 1.00
t+d b+d d CABt CABb Jct Jcb vug vu,AB
1 gqt gqb
Output: (mm) (mm) (mm) (mm) (mm) (mm4) (mm4) (N/mm ) (N/mm2)
2
820 520 220 410 260 6.01E+10 3.05E+10 0.456 0.347 1.10 1.31
Ult. Load Col. Dims. Slab Cover Critical bo Mft Mfb Size factor
Col.
Vu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m ls
650 300 600 250 30 Auto 2680 30 40 1.00
Page 21 of
t+d b+d d CABt CABb Jct Jcb vug vu,AB
2 gqt gqb
Output: (mm) (mm) (mm) (mm) (mm) (mm4) (mm4) (N/mm2) (N/mm2)
820 520 220 410 260 6.01E+10 3.05E+10 0.456 0.347 1.10 1.31
d/ D unbalanced moment
2 Mfx
Ult. Load Col. Dims. Slab Cover Critical bo Mfx Mfy Size factor
Col.
Vu (kN) D (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m ls
420 400 250 30 Auto 1948 30 30 1.00
Deq+d d CABx CABy Jcx Jcy vug vu,AB
1 gqx gqy
Output: (mm) (mm) (mm) (mm) (mm4) (mm4) (N/mm ) (N/mm2)
2
574.5 220 287.2453851 287.2 2.01E+10 2.01E+10 0.400 0.400 0.98 1.32
Ult. Load Col. Dims. Slab Cover Critical bo Mfx Mfy Size factor
Col.
Vu (kN) D (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m ls
420 400 250 30 Auto 1948 30 30 1.00
Deq+d d CABx CABy Jcx Jcy vug vu,AB
2 gqx gqy
Output: (mm) (mm) (mm) (mm) (mm4) (mm4) (N/mm ) (N/mm2)
2
574.5 220 287.2453851 287.2 2.01E+10 2.01E+10 0.400 0.400 0.98 1.32
Page 22 of
unbalanced moment
Edge columns: Mft
unbalanced moment
b Mfb
d/
2
critical perimeter (bo) t
Ult. Load Col. Dims. Slab Cover Critical bo Mft Mfb Size factor
Col.
Vu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m ls
300 300 600 250 30 Auto 1640 30 70 1.00
t+d b+d/2 d CABt CABb Jct Jcb vug vu,AB
1 gqt gqb
Output: (mm) (mm) (mm) (mm) (mm) (mm4) (mm4) (N/mm2) (N/mm2)
820 410 220 410 102.5 4.12E+10 7.05E+09 0.485 0.320 0.83 1.30
Ult. Load Col. Dims. Slab Cover Critical bo Mft Mfb Size factor
Col.
Vu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m ls
300 300 600 250 30 Auto 1640 30 70 1.00
t+d b+d/2 d CABt CABb Jct Jcb vug vu,AB
2 gqt gqb
Output: (mm) (mm) (mm) (mm) (mm) (mm4) (mm4) (N/mm2) (N/mm2)
820 410 220 410 102.5 4.12E+10 7.05E+09 0.485 0.320 0.83 1.30
Ult. Load Col. Dims. Slab Cover Critical bo Mft Mfb Size factor
Col.
Vu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m ls
300 300 600 250 30 Auto 1640 30 70 1.00
t+d b+d/2 d CABt CABb Jct Jcb vug vu,AB
3 gqt gqb
Output: (mm) (mm) (mm) (mm) (mm) (mm4) (mm4) (N/mm ) (N/mm2)
2
820 410 220 410 102.5 4.12E+10 7.05E+09 0.485 0.320 0.83 1.30
unbalanced moment
Corner columns: Mft
Page 23 of
b unbalanced moment
Mfb
critical perimeter
(bo)
t
Ult. Load Col. Dims. Slab Cover Critical bo Mft Mfb Size factor
Col.
Vu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m ls
150 300 600 250 30 Auto 1120 50 50 1.00
t+d/2 b+d/2 d CABt CABb Jct Jcb vug vu,AB
1 gqt gqb
Output: (mm) (mm) (mm) (mm) (mm) (mm4) (mm4) (N/mm ) (N/mm2)
2
710 410 220 225.0 75.0 1.44E+10 4.03E+09 0.467 0.336 0.61 1.29
Ult. Load Col. Dims. Slab Cover Critical bo Mft Mfb Size factor
Col.
Vu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m ls
150 300 600 250 30 Auto 1120 50 50 1.00
t+d/2 b+d/2 d CABt CABb Jct Jcb vug vu,AB
2 gqt gqb
Output: (mm) (mm) (mm) (mm) (mm) (mm4) (mm4) (N/mm ) (N/mm2)
2
710 410 220 225.0 75.0 1.44E+10 4.03E+09 0.467 0.336 0.61 1.29
Ult. Load Col. Dims. Slab Cover Critical bo Mft Mfb Size factor
Col.
Vu (kN) b (mm) t (mm) Thick (mm) (mm) Perimeter (mm) kN.m kN.m ls
150 300 600 250 30 Auto 1120 50 50 1.00
t+d/2 b+d/2 d CABt CABb Jct Jcb vug vu,AB
3 gqt gqb
Output: (mm) (mm) (mm) (mm) (mm) (mm ) 4
(mm ) 4
(N/mm ) (N/mm2)
2
710 410 220 225.0 75.0 1.44E+10 4.03E+09 0.467 0.336 0.61 1.29
Page 24 of
By: Dr. Mahmoud El-Kateb
Page 25 of
fvc Utiliz. Magnification
Notes
(N/mm2) ratio factor
1.40 0.94 Safe 1.19
Page 26 of
fvc Utiliz. Magnification
Notes
(N/mm2) ratio factor
1.40 0.93 Safe 1.57
Page 27 of
fvc Utiliz. Magnification
Notes
(N/mm2) ratio factor
1.40 0.92 Safe 2.11
Page 28 of
Page 29 of
Reinforced Concrete design according to ACI 318-19
Version 2.1
Project :
Internal columns:
Ult. Load Magnif. Col. Dims. Thick Cover Shear no. of RFT no. of RFT Dist. bet. legs Dist. bet. legs
Col.
Vu (kN) factor b (mm) t (mm) h (mm) (mm) RFT f legs on (b) legs on (t) on "b" l1 (mm) on "t" l2 (mm)
1 680 1.21 300 700 250 30 10 2 4 200 250
2 680 1.21 300 700 250 30 10 2 4 200 250
3 680 1.21 300 700 250 30 10 2 4 200 250
4 680 1.21 300 700 250 30 10 2 4 200 250
5 680 1.21 300 700 250 30 10 2 4 200 250
Page 30 of
Ult. Load Magnif. Col. Dims. Thick Cover Shear no. of RFT Dist. bet. X S
Col.
Vu (kN) factor D (mm) h (mm) (mm) RFT f legs Legs l (mm) (mm) (mm)
1 650 1.2 500 250 30 10 4 200 110 110
2 650 1.2 500 250 30 10 4 200 110 110
3 650 1.2 500 250 30 10 4 200 110 110
4 650 1.2 500 250 30 10 4 200 110 110
Edge columns:
Ult. Load Magnif. Col. Dims. Thick Cover Shear no. of RFT no. of RFT Dist. bet. legs Dist. bet. legs
Col.
Vu (kN) factor b (mm) t (mm) h (mm) (mm) RFT f legs on (b) legs on (t) on "b" l1 (mm) on "t" l2 (mm)
1 250 1.51 300 700 250 30 10 2 3 200 250
2 250 1.51 300 700 250 30 10 2 3 200 250
3 250 1.51 300 700 250 30 10 2 3 200 250
4 250 1.51 300 700 250 30 10 2 3 200 250
5 250 1.51 300 700 250 30 10 2 3 200 250
Page 31 of
Corner columns:
Ult. Load Magnif. Col. Dims. Thick Cover Shear no. of RFT no. of RFT Dist. bet. legs Dist. bet. legs
Col.
Vu (kN) factor b (mm) t (mm) h (mm) (mm) RFT f legs on (b) legs on (t) on "b" l1 (mm) on "t" l2 (mm)
1 130 2.11 300 700 250 30 10 2 4 200 250
2 130 2.11 300 700 250 30 10 2 4 200 250
3 130 2.11 300 700 250 30 10 2 4 200 250
4 130 2.11 300 700 250 30 10 2 4 200 250
Page 32 of
By: Dr. Mahmoud El-Kateb
Page 33 of
no. of RFT lines Shear stress
Stirrups (D/C)
(n) (D/C)
5 0.68 0.84
5 0.68 0.84
5 0.68 0.84
5 0.68 0.84
Page 34 of
X S no. of RFT Stirrups Shear stress
(mm) (mm) lines (n) (D/C) (D/C)
110 110 5 0.56 0.91
110 110 5 0.56 0.91
110 110 5 0.56 0.91
110 110 5 0.56 0.91
Page 35 of
Reinforced Concrete design according to ACI 318-19 By: Dr. Mahmoud El-Kateb
Version 1.7
Project :
PDL+
PLL WDL+ WLL
Span/ Span/
2 2
Working loads: PDL (kN) WDL (kN/m) PLL (kN) WLL (kN/m)
self weight 40 20 50 20
finish+walls 25 10 sustained LL = 25%
Ec = 27806 MPa
n= 7.19
Z= 226.7 mm
Ig = 1.28E+10 mm4
Icr = 5.81E+09 mm4
Ieff = 5.86E+09 mm4
Project :
B
Concrete fc` = 35 MPa C As t
top s
PDL+ PLL
WDL+ WLL
b
h
Span/ Span/
2 2
C As
bottom
Breadth Depth Thickness Span
Sec. Properties of sec: B (mm) b (mm) ts (mm) h (mm) t (mm) L (m)
1 1500 300 140 760 900 10
Working loads: PDL (kN) WDL (kN/m) PLL (kN) WLL (kN/m)
self weight 40 20 30 8
finish+walls 50 10 sustained LL = 25%
Ec = 27,806 MPa
n= 7.19
Z= 167.6 mm
Ig = 3.35E+10 mm4
Icr = 1.71E+10 mm4
Ieff = 1.74E+10 mm4
Project :
PDL+ PLL
WDL+ WLL
Sp
an
Working loads: PDL (kN) WDL (kN/m) PLL (kN) WLL (kN/m)
self weight 2.50 6.25 0 3.00
finish+walls 0.00 3.50 sustained LL = 25%
Ec = 27806 MPa
n= 7.19
Z= 57.7 mm
Ig = 1.30E+09 mm4
Icr = 3.66E+08 mm4
Ieff = 4.69E+08 mm4
Project :
Concrete f c` = 30 MPa
Project :
F1
Column working load Column dim. Extension
Nw (kN) Trans. Long. of P.C (mm)
Smaller 1000 250 500 100
Larger 1500 250 800 100
Page 44 of
0.35 < 0.75 * 1.81 0.26 for smaller column
0.47 < 0.75 * 1.50 0.42 for larger column
5.80 m
T16 @124
900
3.00 m
3.20 m
@200
@124
Page 45 of
T12
T16
1.50 m
T16 @124
6.00 m
Page 46 of
L
R
Distance c.g to
c.g
Dtransver Dtransver B
se se PC
Dlong Dlo
ng
L
PC
Page 47 of
Reinforced Concrete design according to ACI 318-19 By: Dr. Mahmoud El-Kateb
Version 1.6
Project :
Page 48 of
Actual pile load (kN) D/C
484 0.81
4500
Page 49 of
1100
T 20 @159
3000
3200
T 20 @159
4700
Page 50 of
L
R
Number of piles
in the long
direction
b B
P
C
t
L
P
Page 51 of
L
P
C Number of piles
in the short
direction
Page 52 of
Reinforced Concrete design according to ACI 318-19 By: Dr. Mahmoud El-Kateb
Version 1.6
Project :
C
Dims. of P.C cap: B (mm) L (mm) t (mm)
4700 6200 100
Page 53 of
2nd piles row to center, y2 2.25 m 376 110
3rd piles row to center, y3 0.00 m 242.8 242.8
4th piles row to center, y4 0.00 m 242.8 242.8
All Safe
6000
Page 54 of
1200
T 20 @145
4500
4700
T 20 @145
6200
Page 55 of
L
R
Number of piles in
the direction of
moment
Mw
b B
P
C
t
Page 56 of
L
P
C Number of piles in
the
transversedirection
Page 57 of
Reinforced Concrete design according to ACI 318-19 By: Dr. Mahmoud El-Kateb
Version 1.2
Project :
Retained Soil
3.00
2.80
ko = 0.50 C = 0.0 N/mm2
0.50 R
0.00 .
P.
CC
0.00 2.00 0.00
2.00
Foundation soil C= 0.0 N/mm2 f = 30 o
Page 58 of
Stabilizing force from: kN Horizontal force from: kN
Weight of wall 18.75 Active earth pressure on wall 23.52
Weight of footing (RC+PC) 25.00 Active earth pressure on footing 9.15
Weight of soil on active side 0.00 Active surcharge pressure 2.20
Weight of soil on passive side 15.75 Passive earth pressure on wall -1.13
Surcharge 0.00 Passive side pressure on footing -3.38
Total weights: S= 59.50 Driving force: S = 30.37
Over-turning check:
Stabilizing moment from: kN.m Over-turning moment from: kN.m
Weight of concrete 60.16 Active earth pressure 35.94
Weight and pressure of soil 15.28 Active surcharge pressure 3.63
S= 75.44 S = 39.57
Calculation of Rft. :
Mu (kN.m) c (mm) d (mm) As (mm2) As min
For Wall 40.1 50 200 542 450 5 f 12 /m
For Base 52.5 75 425 329 900 8 f 12 /m
Page 59 of
Shear on base: Vu = 37.7 kN < Vc = 153 kN Safe
Page 60 of
Reinforced Concrete design according to ACI 318-19 By: Dr. Mahmoud El-Kateb
Version 1.1
Project :
Wu = 120.0 kN/m
Mu = 240.0 kN.m
Vu = 240.0 kN.m
Safe dimensions
Web RFT = T 10 @ 209 2 Legs , Vertical
T 10 @ 209 2 Legs , Horizontal
T 10 @209
2T 16
4.00
Reinforced Concrete design according to ACI 224R-01 By: Dr. Mahmoud El-Kateb
Version 1.7
Project :
Comp. side
Thickness
Z
N.A
Tens. side
Breadth
INPUT DATA:
Breadth (B) = 1000 mm
Thickness (t) = 300 mm
Tension RFT. = 8 T 16 = 1608 mm2 Acceptable
Tension RFT. Cover to c.g = 50 mm
RFT in perpendiculatr dir. = 8 T 12 (Two way slabs
Short / Long span = 1 Span: Simple only)
Page 63 of
Compression RFT. = 8 T 12 = 905 mm2
Compression RFT. Cover = 50 mm
Mservice = 50 kN.m
Nservice = 20 kN Tension
Exposure condition: Humidity, moist air, soil
Reasonable crack width = 0.30 mm ACI 224R-01, Table 4.1
Exposure: Normal enviroment, exposure to liquid with pH > 5 ACI 350M-06
Structural system: One way member Clause 10.6.4
OUTPUT DATA:
Modular ratio (n) = 7.8
Neutral Axis depth (Z) = 64 mm
Tens. Steel stress (fs) = 144 MPa Acceptable
b= 1.27 ACI 350M-06, Eq. (10-6)
Page 64 of
Reinforced Concrete design according to ACI 350M-06 By: Dr. Mahmoud El-Kateb
Version 1.0
Project :
Comp. side
Thickness
Z
N.A
Tens. side
Breadth
INPUT DATA:
Breadth (B) = 1000 mm
Thickness (t) = 300 mm Length of member = Greater than 12 m
Mservice = 50 kN.m Mstr = 70 kN.m
Nservice = 20 kN Tension Nstr = 28 kN
Exposure: Normal enviroment, exposure to liquid with pH > 5 Clause 10.6.4
Structural system: One way member Clause 10.6.4
Sd = 1.93 Enviromental durability factor, Eq. (9-8)
REQUIRED DESIGN STRENGTH:
Mstrength = 135.0 kN.m Clause 9.2.6
Nstrength = 54.0 kN Clause 9.2.6
Tension RFT. Cover to c.g = 50 mm
Required As = 1583 mm2 As,min = 750 mm2 each face
Choose Tension RFT. = 8 T 16 = 1608 mm2 Acceptable
Compression RFT. = 8 T 12 = 905 mm 2
Project :
Page 67 of
Confinement condition:
Other cases
T yr = 1
Development Length, Ldc = 19 db for db 16 = 304 mm Clause 25.4.9.1
Page 68 of
Page 69 of
Page 70 of
Page 71 of
Page 72 of