You are on page 1of 2

TestObject

Device SN: 201102082 Version: V3.8.6.14


Device Model: K3163i Test Time: 2023-08-24 14:47
User: Company:

Device Info
Name/Description: Manufacture:
Device Type: Serial/Model:
Device Address:
Substation Name:
Substation Address:

System Nominal Parameters


VNom Sec (L-L): 110.000V INom Sec : 1.000A
VNom Prim (L-L): 10.500kV INom Prim : 0.700kA
FNom: 50.000Hz

1.System Config

Test Parameter
Output Type: Power Amp Binary Type: Relay Contact
Current: 6*35A Voltage: 4*310V

2.AC Test

Test Parameter
Amplitude Angle Frequency
V A- 63.509V 0.000° 50.000Hz
N
V B- 63.509V 240.000° 50.000Hz
N
V C- 63.509V 120.000° 50.000Hz
N
IA 0.000A 0.000° 50.000Hz
IB 0.000A 240.000° 50.000Hz
IC 0.000A 120.000° 50.000Hz
V X- 0.000V 0.000° 50.000Hz
N
I A(2) 0.000A 0.000° 50.000Hz
I B(2) 0.000A 240.000° 50.000Hz
I C(2) 0.000A 120.000° 50.000Hz

Variable Active Group Output Quantity Step Limit


Variable1 √ Group1 V A-N,V B-N,V C-N Frequency 4.100Hz 55.000Hz
Variable2 x Group2 IA Amplitude 1.000A 2.000A

Test Result
Result Trigger Logic: Or
Change Mode: From-Action
InPut Action Time
1 241.88ms
2 No Trip
3 No Trip
4 No Trip
5 No Trip
6 No Trip
7 No Trip
8 No Trip

Variable Action Value


Group1 V A-N Frequency 45.900Hz
Group1 V B-N Frequency 45.900Hz
Group1 V C-N Frequency 45.900Hz