The RC Cubicle contains several electronics modules and may be configured for various auxiliary supply options. RC
modules are the Relay Module (REL), Power Supply Module (PSM), SIM Module (SIM) and Panel Module (PAN), and if
specified at time of order, either one or two I/O Modules (IOM). Module types and serial numbers are identified below
together with the software version and configured auxiliary supply.
During factory testing, the Measurement coefficients recorded in this section are programmed into the Relay Module
whose serial number appears above. If another Relay Module is installed at any time, the OSM Serial Number and the
coefficients stated below must be programmed into its memory.
1/2
Routine Testing
Conduct 300 Close Open Operations: Pass Conduct 2kV OSM Insulation Test: Pass
Conduct Contact Resistance Test: Pass Conduct Partial Discharge Test: Pass
A: 86.8 µOhm (Test Voltage=24kV)
Enter measurement co-efficients and OSM serial number into RC memory using CMS: Pass
Confirm Mechanical Trip Indication: Pass
Confirm RC correctly indicates presence of auxiliary supply: Pass
Confirm GPO active, neutral and earth are correct: Pass
Install battery, confirm RC correctly indicates terminal voltage and charging current: Pass
Conduct RC push button and LED test: Pass
Set IOM into test mode, confirm that energising any input causes all outputs to change state.
Repeat for second IO Module if fitted or use test IOM to confirm operation: Pass
Use CMS to load default settings file. Set all fast keys to the OFF state and set Active Group 1.
Erase all RC data logs: Pass
Confirm a trip operation initiated from operator panel is successful: Pass
Confirm a close operation initiated from operator panel is successful: Pass
Confirm an operation of the Mechanical Trip Ring is successful: Pass
Operate OSM through 4 x instantaneous operations to Lockout with minimum dead times.
Wait 60 seconds and repeat: Pass
Inject 4.0A into each phase individually. Confirm each phase current reading is within range 0A to 8A and
residual current reading is 4A: Pass
Connect each phase in series and inject 50A. Confirm each phase current reading is within range 46A to
54A and residual current reading is within 142.5A to 157.5A: Pass
Inject 6kV individually into each phase, confirm phase voltage reading is within range 5.6kV to 6.4kV for
each phase: Pass
Approval
2/2