Fieldbus system

EtherNet/IPTM compatible
PRODUCT NAME

EX600-SEN1-X1
MODEL/ Series
SI Unit
Model Indication and how to Order
EX600 – S -X1
SI Unit

Protocol Output polarity


Symbol Description Symbol Description
EN EtherNet/IP
TM
1 PNP (-COM.)

Name and Function of Products

No. Description Function


1 Status display LED Displays the status of the unit.
2 Display cover Open for the setting of switch.
3 Display cover tightening screw Loosen to open the display cover.
4 Marker groove Groove to mount a marker.
5 Connector (PCI) Connects the cable of the handheld terminal.
6 Valve plate mounting screw hole Fixes the valve plate.
7 Valve plate mounting groove Groove to insert the valve plate into.
8 Joint bracket Bracket for joining to adjacent units.
9 Unit connector (plug) Transmits signals and power supplies to adjacent units.
10 Connector (BUS IN) Connects the cable for fieldbus inputs.
11 MAC address label Displays the 12 digit MAC address which is different for each SI unit.
12 Seal cap (1 piece) Mounted on to unused connector (PCI).
Mounting and Installation
■Wiring
○Connector pin assignment
Configuration Pin
Signal name
BUS IN number
1 TX+
2 RX+

3 TX-
4 RX-

●Precautions for handling


Be sure to fit a seal cap on any unused connectors. Proper use of the seal cap
enables the enclosure to achieve IP67 specification.
Setting and Adjustment
•Switch setting
(1) Loosen the display cover screw (indicated by arrow).
(2) Open the display cover using a flat head screwdriver, etc.

(3) Set the switch using a small watchmaker's screwdriver with a thin blade, referring to the setting of switch
on the following pages.
(4) After setting the switch, tighten the display cover tightening screw in the reverse order of the above
procedure. (Tightening torque: 0.3 to 0.4 Nm)

●Precautions for handling


• Turn off the power supply whilst setting the switch.
• If there is foreign matter or water droplets around the display cover, clean it off before
opening the cover.
• When setting the switch, do not touch other unrelated parts. This can cause parts
damage or malfunction due to a short circuit.
• All default settings are off or 0. Perform the setting of the switch before using product.
•Configuration memory switch: If the power supply is turned on while the configuration memory switch is
turned on, it performs comparison with the manifold configuration when the
switch is turned off. If there is a difference, an error is output.

Settings1
Content
1
OFF Normal operation mode (default setting)
ON Configuration memory mode
•Timing to memorize the configuration  when power supply for control/input is turned on, with the switch
above turned OFF.
•Timing to compare the configuration  when power supply for control/input is turned on, with the switch
above turned ON.

•Baud Rate switch: Sets the communication speed of the internal bus of the product.

Settings1
Content
2 3
OFF OFF 1 Mbps (default setting)

OFF ON 500 kbps

ON OFF 250 kbps

ON ON 125 kbps
∗: This function is for extension in the future. Use the product with 1 Mbps (default setting).
•IP address setting switch

Settings1 Settings2
IP address
8 1 2 3 4 5 6 7 8
OFF ON OFF OFF OFF OFF OFF OFF OFF 192.168.0.1
OFF OFF ON OFF OFF OFF OFF OFF OFF 192.168.0.2
: : : : : : : : : :
OFF ON OFF ON ON ON ON ON ON 192.168.0.253
OFF OFF ON ON ON ON ON ON ON 192.168.0.254
ON ON OFF OFF OFF OFF OFF OFF OFF 192.168.1.1
ON OFF ON OFF OFF OFF OFF OFF OFF 192.168.1.2
: : : : : : : : : :
ON ON OFF ON ON ON ON ON ON 192.168.1.253
ON OFF ON ON ON ON ON ON ON 192.168.1.254
1
ON/OFF ON ON ON ON ON ON ON ON DHCP mode
2
ON/OFF OFF OFF OFF OFF OFF OFF OFF OFF Remote Control mode
1: The mode to obtain IP address from DHCP server. Obtained IP address is lost when the power supply is cut.
2: The mode to respond to the commands below of BOOTP/DHCP Server provided by Rockwell Automation.
Enable DHCP: IP address etc. can be obtained from BOOTP/DHCP Server.
If the power is supplied again in this state, information including IP address is obtained again.
Disable DHCP: IP address etc. cannot be obtained from BOOTP/DHCP Server.
If the power is supplied again with this condition, previous setting can be held.
•V_SEL switch: The number of outputs (size) occupied by the SI unit is selected.

Settings3
Content SI unit output data size
1 2
OFF OFF Number of occupied valve 32 outputs 4 byte (default setting)
OFF ON Number of occupied valve 24 outputs 3 byte
ON OFF Number of occupied valve 16 outputs 2 byte
ON ON Number of occupied valve 8 outputs 1 byte
∗: Set the number of occupied valve outputs to at least the number of valves used.

•Switch for diagnostics: Allocates the diagnostic data to the input data

Settings3 Diagnostic size set


Mode Content
3 4 for the input
OFF OFF 0 Input data only (default setting) 0 byte
OFF ON 1 Input data + System diagnosis 4 byte
ON OFF 2 Input data + System diagnosis + Unit diagnosis 6 byte
ON ON 3 Reserved -
: Mode 3 is a function for extension in the future. Do not use it now.
•HOLD/CLEAR switch: Sets the output status when the fieldbus has a communication error or is in idling state.
This setting can be made invalid (over-ridden) by the parameter.

Settings3
Content
5
OFF Output is off. (default setting)
ON Holds the output.
: This switch can be enabled and disabled by parameter.

TM
•EtherNet/IP communication setting switch

Settings3
Communication speed full duplex/half duplex setting
6 7 8
OFF ON/OFF ON/OFF Automatic
ON OFF OFF 10 Mbps, half duplex
ON OFF ON 10 Mbps, full duplex
ON ON OFF 100 Mbps, half duplex
ON ON ON 100 Mbps, full duplex

●Precautions for handling


•Handle the switch with care Excessive force can break the switch.
•4, 5, 6, 7 of the Setting1 switch are not used.
•Setting method of IP address by BOOTP / DHCP Server
•When BOOTP / DHCP Server starts up, the Server scans the devices connected to the network.

•After selecting the MAC address of EX600, IP address is set.

•IP address is set and added to the list.


LED Display
The status display LED displays the power supply and communication status.
Various kinds of status can be checked as follows:

Display Content
ST(M) Displays the diagnosis status of the unit.
PWR Displays the status of the power supply voltage for control and input.
PWR(V) Displays the status of the power supply voltage for outputs.
MS Displays the module status.
NS Displays the network status.

•SI unit common status


LED display Content

The power supply for control and input is Off.


Off

The unit is in normal operation.


Green LEDs are On

A component failure inside the SI unit.


Red ST(M) LED is On

The power supply voltage for control and input is abnormal.


Red PWR LED is On

The power supply voltage for output is abnormal.


Red PWR(V) LED is On

A unit other than the SI unit has been diagnosed and detected.
Green ST(M) LED is flashing

Either of the following conditions:


•The on/off counter has exceeded the set value.
Red ST(M) LED is flashing •The valve is short circuited or disconnected.

Either of the following conditions:


•Communication error between units has occurred.
Red/green ST(M) LED is flashing • Configuration memory error has occurred.
alternately

•Module status
LED display Content

The power supply for control and input is Off.


MS LED is off

Either of the following conditions:


•The unit has not been configured correctly.
Green MS LED is flashing •Fieldbus is idling.

The unit is in normal operation.


Green MS LED is On

Recoverable error.
Red MS LED is flashing

The element in SI unit is broken.


Red MS LED is On

•Network status
LED display Content

The power supply for control and input is Off, or IP address is not set.
NS LED is Off

The unit received an IP address, but connection is not established.


Green NS LED is flashing

Connection is established.
Green NS LED is On

Connection timeout.
Red NS LED is flashing

IP address is duplicated.
Red NS LED is On
Specification
■Specifications
Model EX600-SEN1
TM
Fieldbus EtherNet/IP (IEEE802.3)
Media 100BASE-TX
Communication speed 10/100 Mbps (Automatic/Manual)
Communication type Full duplex/half duplex (Automatic/Manual)
TM
Communication

EtherNet/IP
Fieldbus protocol
(Conformance version: Composite6)
Input: Unit that can be connected depends on the type
I/O message
Output: Unit that can be connected depends on the type
Setting by SI unit switch: 192.168.0 or 1.1 to 254
IP address setting range
Via DHCP server : Arbitrary address

Vendor ID: 7 (SMC Corporation)


Device information Product type: 12 (Communication Adapter)
Product code: 126
Power supply (control and input) 24 VDC Class2, 2 A
Internal current consumption
120 mA or less
(The power supply for control and input)
Output polarity PNP (-COM.)
Output channel 32 outputs (8/16/24/32 outputs selectable)
Valve output

Solenoid valve with lamp and circuit of protection of surge voltage


Connected load
of 24 VDC 1.5 W (SMC)
Power supply (output) 24 VDC Class2, 2 A
Output for com. error HOLD/CLEAR/Force ON
Protective function Short circuit protection
IP67 (with manifold assembled) ∗
1
Enclosure
-10 to 50 C (Max. surrounding air temperature rating: 50 C) ∗
o o 2
Operating temperature range
o
Storage temperature range -20 to 60 C
Operating humidity range 35 to 85% RH (no condensation)
Environment

Withstand voltage 500 VAC for 1 minute between external terminals and FE
Insulation resistance 500 VDC, 10 MΩ or more between external terminals and FE
10 to 57 Hz: constant amplitude 0.75 mm p-p
2
Vibration resistance 57 to 150 Hz: constant acceleration 49 m/s
for 2 hours each in direction X, Y and Z respectively (De-energized)
2
147 m/s 3 times each in directions of X, Y and Z respectively
Impact resistance
(De-energized)
Pollution degree For use in Pollution Degree 2 Environment (UL508)
Standard CE marking, UL (CSA) , RoHS
Weight 300 g
1: All unused connectors must have a waterproof cap fitted.
2: The UL compliant temperature is 0 to 50 oC.
■Dimensions
Parameter Setting
The product has parameters that can be set for the system, each unit or each channel.
The parameters can be changed using EtherNet/IP and handheld terminal.
There is no order of precedence of the PLC and handheld terminal. The latest parameter settings are used.

■Parameter definition and setting


•System parameters
Parameter
Parameter Default setting
No. Definition Item Content
(H.T. Symbol) setting By By
EIP H.T.
Setting by SI unit switch
becomes valid.
Switch the setting of the Switch ○
OFF/Hold/Forced ON can
Hold/Clear output during communication be set per channel
1 priority setting error or communication idling ○ ○
(Hold/Clear) to follow the setting of the SI Setting by the handheld
unit or the handheld terminal. terminal becomes valid.
Handheld
OFF/Hold/Forced ON can
be set per channel.
•SI unit parameters
Parameter
Parameter Default setting
No. Definition Item Content
(H.T. Symbol) setting By By
EIP H.T.
Power supply
for control Error is generated when Enable Enables. ○
and input control or input power supply
1 ○ ○
voltage voltage goes over approx. 26V
monitor or under 21V. Disable Disables.
(PWRC_Mon)

Power supply Enable Generates an error. ○


Error is generated per unit
for output
when control or output power
2 voltage ○ ○
supply voltage goes over
monitor Does not generate an
approx. 26V or under 20 V. Disable
(PWRO_Mon) error.

Short Circuit Generates error per unit when Enable Generates an error. ○
3 Detection the short circuit of the valve is ○ ○
Does not generate an
(SC_MonOp) detected. Disable
error.
Error is automatically
Auto cleared when the short ○
Restores the status per unit circuit is fixed.
Restart after
after the short circuit
4 short circuit Even when the short ○ ○
detection of the valve short
(SC_RstOp) circuit is fixed, error is not
circuit is cleared. Manual
cleared until the power is
supplied again.

Open Circuit Generates error per channel Enable Generates an error.


5 Detection when the disconnection of the ○ ○
(OC_Mon) valve is detected. Disable Not generated an error. ○

Output setting Clear Turn off the output ○


during
Set output per channel when Hold Hold the output
6 communication ○ ○
communication is abnormal.
fault ∗
1
Turn on the output
(Fault_MD ) ForceON
forcefully
Output setting Clear Turn off the output ○
during Output setting per channel at
7 communicatio the time of communication Hold Hold the output ○ ○
n idling ∗ ∗
1 2
idling Turn on the output
(Idle_MD ) ForceON
forcefully
Parameter
Parameter Default setting
No. Definition Item Content
(H.T. Symbol) setting By By
PLC H.T.

Generates an error.
Memorizes the number of times Enable
Val: 1 to 65000 ∗
4
Valve
the valve is ON. Generates
ON/OFF
8 error per channel when the ○ ○
counter
operation count exceeds the set
(Counter) Does not generate an
value. ∗
3
Disable ○
error.

∗1: This function is valid only when “Hold/Clear priority” of the system parameter is set to Handheld.
∗2: EX600-SEN□ (DeviceNetTM SI unit) and EX600-SMJ□ (SI unit for CC-Link) cannot be set.
∗3: The count is memorized every 30 seconds per channel. When the power supply is turned on again, counting starts from the last value
memorized.
∗4: Times for setting is set value x1000 times.
•Digital output unit parameters
Parameter
Parameter Default setting
No. Definition Item Content
(H.T. Symbol) setting By By
PLC H.T.

Output load Enable Generates an error. ○


Generates error per unit when
short circuit
1 the short circuit of the output ○ ○
detection
equipment is detected. ∗
1 Does not generate an
(SC_MonOp) Disable
error.

Automatically restored
Restart after Restore the setting of short Auto after the error is cleared. ○
output load circuit detection error per unit (Default setting)
2 ○ ○
short circuit after the output equipment
(SC_RstOp) short circuit is cleared. Error continues until the
Manual
power is supplied again.

Open circuit Generates error per channel Enable Generates an error.


3 detection when the disconnection of the ○ ○
(OC_Mon) valve is detected. Does not generate an
Disable ○
error.

Output setting Clear Turn off the output ○


during
Set output per channel when Hold Hold the output
4 communicatio ○ ○
communication is abnormal.
n fault ∗
2
Turn on the output
(Fault_MD) ForceON
forcefully
Output setting Clear Turn off the output ○
during Set the output during
5 communicatio communication idling per Hold Hold the output ○ ○
n idling ∗ ∗
2 3
channel. Turn on the output
(Idle_MD) ForceON
forcefully

Generates an error.
Memorizes the number of Enable
Val: 1 to 65000 ∗
5
Channel times the output equipment is
On/Off ON. Generates error per
6 ○ ○
counter channel when the operation
(Counter) count exceeds the set value
for diagnosis. ∗
5 Does not generate an
Disable ○
error.

∗1: Could be incorrectly recognized as short circuit depending on used load (ex.: lamp load). If detection is incorrect, disable the parameter
setting.
∗2: This function is valid only when “Hold/Clear priority” of the system parameter is set to Handheld.
∗3: EX600-SEN□ (DeviceNetTM SI unit) and EX600-SMJ□ (SI unit for CC-Link) cannot be set.
∗4: The count is memorized every hour. When the power supply is turned on again, counting starts from the last value memorized.
∗5: Times for setting is set value x1000 times.
•Digital I/O unit parameters
Parameter
Parameter Default setting
No. Definition Item Content
(H.T. Symbol) setting By By
PLC H.T.
The power
supply short Enable Generates an error. ○
Generates error per unit when
circuit
the short circuit of the control
1 detection for ○ ○
or input power supply is
control and Does not generate an
detected. Disable
input error.
(SC_MonSs)

Inrush current Enable Ignores excess current.


Ignores excess current per
2 filter ○ ○
unit for 100 msec. after inrush. Does not ignore excess
(Inrush) Disable ○
current
0.1 ms
Input filtering
Sets the time to ignore the 1.0 ms Selects the time for
3 time 1.0 ms ○ ○
input signal change per unit 10 ms filtering.
(Filter_T)
20 ms
Input 1.0 ms
extension Sets the time to hold the input 15 ms Selects the time to hold
4 15 ms ○ ○
time signal per unit. 100 ms the input signal.
(SigExt_T) 200 ms

Output load Enable Generates an error. ○


Generates error per unit when
short circuit
5 the short circuit of the output ○ ○
detection
equipment is detected. ∗
1 Does not generate an
(SC_MonOp) Disable
error.
Automatically restored
Restart after Restore the setting of short Auto after the error is cleared. ○
output load circuit detection error per unit (Default setting)
6 ○ ○
short circuit after the output equipment
(SC_RstOp) short circuit is cleared. Error continues until the
Manual
power is supplied again.

Open circuit Generates error per channel Enable Generates an error.


7 detection when the disconnection of the ○ ○
(OC_Mon) valve is detected. Does not generate an
Disable ○
error.

Output setting Clear Turn off the output ○


during
Set output per channel when Hold Hold the output
8 communication ○ ○
communication is abnormal.
fault ∗
2
Turn on the output
(Fault_MD) ForceON
forcefully
Output setting Clear Turn off the output ○
for Set the output during
9 communication communication idling per Hold Hold the output ○ ○
idling ∗ ∗
2 3
channel. Turn on the output
(Idle_MD) ForceON
forcefully
Parameter
Parameter Default setting
No. Definition Item Content
(H.T. Symbol) setting By By
PLC H.T.

Generates an error.
Memorizes the number of times Enable
Val: 1 to 65000 ∗
5
Output the input or output equipment is
ON/OFF ON. Generates error per
10 ○ ○
counter channel when the operation
(Counter) count exceeds the set value for
diagnosis. ∗
4 Does not generate an
Disable ○
error.

∗1: Could be incorrectly recognized as short circuit depending on used load (ex.: lamp load). If detection is incorrect, disable the parameter
setting.
∗2: This function is valid only when “Hold/Clear priority” of the system parameter is set to Handheld.
∗3: EX600-SEN□ (DeviceNetTM SI unit) and EX600-SMJ□ (SI unit for CC-Link) cannot be set.
∗4: The count is memorized every hour. When the power supply is turned on again, counting starts from the last value memorized.
∗5: Times for setting is set value x1000 times.
•Analog I/O unit parameters (1)
Parameter
Parameter Default setting
No. Definition Item Content
(H.T. Symbol) setting By By
PLC H.T.
The power Generates error per
supply short unit when the short Enable Generates an error. ○
circuit circuit of the input
1 detection for equipment power ○ ○
the input or supply or output
Does not generate an
output device equipment is Disable
error.
(SC_MonSs) detected.
0..10 V
Analog input 0..5 V
Sets the analog input
or output The analog input or
2 or output equipment 1..5 V 1..5 V ○ ○
range output range is selected.
range per channel. 0..20 mA
(Range)
4..20 mA
Offset binary Offset binary. ○
Analog data Sets analog data type
Sign & Magnitude Signed binary.
3 format which is output to ○ ○
(D_Format) PLC per unit. 2S Complement 2’s complement.
Scaled Scale conversion type.
None None ○
Sets analog filtering
Analog 2AVG 2 value average
time per channel.
4 average filter ○ ○
Sampling interval is 4AVG 4 value average
(Filter)
approx. 2 sec.
8AVG 8 value average

Generates error per Enable Generates an error.


Over range
unit when the input
5 detection ○ ○
value exceeds 0.5% Does not generate an
(Over_Rng) Disable ○
of full span. error.

Generates error per Enable Generates an error.


Under range
unit when the input
6 detection ○ ○
value falls below Does not generate an
(Undr_Rng) Disable ○
0.5% of full span. error.
Generates error per
User’s set Generates an error. ∗
2
7 channel when the Enable ○ ○ ○
value upper ∗3
input or output value
limit error Does not generate an
exceeds the set Disable
(Upr_Lmt) error.
value.
Sets the scale upper
Scale upper
limit. Sets error to be Generates an error. ○
limit setting ∗
1
Enable
generated per Val: -32766 to 32767 Val: 1000
(UpLm/Scl)
channel when the
input or output value
exceeds the upper Does not generate an
limit. Disable error.
Val: -32766 to 32767
•Analog I/O unit parameters (2)
Parameter
Parameter Default setting
No. Definition Item Content
(H.T. Symbol) setting By By
EIP H.T.

User’s set Generates an error. ∗


2
Generates error per channel Enable
value lower
when the input or output value
limit error Does not generate an
falls below the lower limit. Disable ○
(Lwr_Lmt) error.

8 Generates an error. ○ ○
Sets the lower limit of scale. Enable ∗*3
Val: -32767 to 32766
Scale lower Sets error to be generated per
limit setting ∗
1
channel when the input or
(UpLm/Scl) output value falls below the Does not generate an

lower limit. Disable error.
Val: 0
Val: -32767 to 32766

Output setting
Val is output. ∗
2
for Enable
Set output per channel when
9 communication ○ ○
communication is abnormal.
error ∗
4
Disable The output is held. ○
(Fault_MA)
Output setting
Val is output. ∗
2
for Enable
Sets output setting per channel
10 communication ○ ○
for communication idling.
idling ∗ ∗
4 5
Disable The output is held. ○
(Idle_MA)
*1: When “Scaled” is selected as the analog data format, the display of H.T. is switched from Upr_Lmt to UpLm/Scl, from Lwr_Lmt to
LwLm/Scl.
*2: Set value shall be set per analog output range within settable range in the table below.
When the analog output range is changed, check the set value and change it to an appropriate value.
*3: Setting via PLC is not available with EX600-SPR□ (SI unit for PROFIBUS).
*4: This function is valid only when “Hold/Clear priority” of the system parameter is set to Handheld.
*5: Some types cannot be used depending on EX600-SDN□ (SI unit for DeviceNet).
Cannot be set for EX600-SMJ□ (SI unit for CC-Link).

Analog Input or Upper and lower setting limit of user setting


Settable range during
output measurement
Lwr_Lmt Upr_Lmt communication error or idling
range
0..10 V 0.00 to +10.45 V +0.05 to +10.50 V 0.00 to +10.50 V
0..5 V 0.00 to +5.22 V +0.03 to +5.25 V 0.00 to +5.25 V
1..5 V +0.75 to +5.22 V +0.78 to +5.25 V +0.75 to +5.25 V
0..20 mA 0.00 to +20.90 mA +0.10 to +21.00 mA 0.00 to +21.00 mA
4..20 mA +3.00 to +20.90 mA +3.10 to +21.00 mA +3.00 to +21.00 mA
•Frequency Counter unit parameters
Parameter
Parameter Default setting
No. Definition Item Content
(H.T. Symbol) setting By By
EIP H.T.
The power
supply short Generates error per Enable Generates an error. ○ ○ ○
unit when the short
circuit
1 circuit of the control
detection for or input power supply Does not generate an
control and is detected. Disable ○ ○
error.
input
None None
Sets frequency
Frequency 2AVG 2 value average ○
filtering time per ○ ○
2 averaging filter 4AVG 4 value average
channel.
8AVG 8 value average

Generates an error.
Generates error per Enable val: ○ ○
User settable Val: 0.0 to 6553.5 6500.0
channel when the
3 value upper
input value exceeds Does not generate an
limit
the set value. Disable error. ○ ○
Val: 0.0 to 6553.5
Generates an error. ○
Generates error per Enable ○ ○
User settable Val: 0.0 to 6553.5 val: 0
channel when the
4 value lower Does not generate an
input value falls
limit Disable error. ○ ○
below the lower limit.
Val: 0.0 to 6553.5
Frequency data
becomes 0Hz, when
Cut off the input value falls Cut off frequency
5 Val: 0 to 1000.0 2.0 ○ ○
frequency below the cut off value
frequency per
channel.
I/O Map
Allocated input/ output bytes of each unit type

Allocated input / output size is changeable according to the diagnosis setting and connected EX600
unit type. The allocated input/ output bytes for each EX600 unit are shown below.
Allocated bytes
Unit type Abbreviation Description
Input Output
EX600-SEN# (32 points) SI Unit (32 points) 0 4
EX600-SEN# (24 points) SI Unit (24 points) 0 3
SI
EX600-SEN# (16 points) SI Unit (16 points) 0 2
EX600-SEN# (8 points) SI Unit (8 points) 0 1
*EX600-SEN# can change the allocated output bytes with switch setting.
*If there is no input byte, input size of master configuration must be set more than 1byte.

Diagnosis

The following diagnostic data is allocated to the top of the I/O mapping input data by switching No. 1
and No. 2 of the Setting2 switch.
Switch setting
Mode Diagnostic data Diagnosis size
No1 No2
0 OFF OFF No diagnostic data 0 byte
1 OFF ON System diagnostic 4 bytes
2 ON OFF System diagnostic + Unit diagnostic (for 10 units) 6 bytes
Note 1) The channel diagnostics cannot be allocated to the input map. Use the hand-held unit for
monitoring.
Details of diagnostic information
Details of the diagnostic information are shown on below list.

System diagnosis

1) System diagnosis byte0


Bit Diagnostic content
Analog input, Analog output or Frequency counter falls below user’s setting lower limit
0
value
1 Analog input, Analog output or Frequency counter exceeds user’s setting upper limit value
2 Analog input falls below measurement range
3 Analog input exceeds measurement range
4 Channel ON/OFF counter exceeds setting value
5 Open circuit error detected
6 Short circuit detected on value output or digital output
7 Short circuit detected on input sensor’s power supply

2) System diagnosis byte1


Bit Diagnostic content
0 Power supply voltage for output is outside operating range
1 Power supply voltage for control and sensor is outside operating range
2 Enforced mode is active
3 Communication error between SI Unit and I/O Unit during operation.
4 Communication error between SI Unit and I/O Unit at system starts up.
5 Manifold configuration error.
6 System error
7 Hardware error

3) System diagnosis byte2


Bit Diagnostic content
0~7 (Reserved)

4) System diagnosis byte3


Bit 診断名
0 Error is detected in Digital Input
1 Error is detected in Digital Output
2 Error is detected in Analog Input or Frequency Counter
3 Error is detected in Analog Output
4 Error is detected in SI unit
5 (Reserved)
6 (Reserved)
7 (Reserved)
Unit diagnosis

1) Unit diagnosis byte0


Bit Diagnostic content
0 Error is detected in Unit 0
1 Error is detected in Unit 1
2 Error is detected in Unit 2
3 Error is detected in Unit 3
4 Error is detected in Unit 4
5 Error is detected in Unit 5
6 Error is detected in Unit 6
7 Error is detected in Unit 7

2) Unit diagnosis byte1


Bit Diagnostic content
0 Error is detected in Unit 8
1 Error is detected in Unit 9
2 (Reserved)
3 (Reserved)
4 (Reserved)
5 (Reserved)
6 (Reserved)
7 (Reserved)
Hardware Configuration
■EDS file and icon
EDS file is required to configure the EX600. Furthermore, icons are necessary for the display icon of the EX600
on the configuration.

EDS file: EX600_SEN#.eds


Icon: ex600_1.ico

■Setting using RSLogix5000TM for EtherNet/IPTM


Below is an explanation of the EX600 Series connection method with a Rockwell Automation’ EtherNet/IP™
module.
TM TM
Refer to the manual of RSLogix5000 for EtherNet/IP for a detailed manner of operation.
∗: The screen data shown here is the English version of RSLogix5000TM.

•Select [EtherNet I/P] in [I/O Configuration] folder. Select [New Module].


• [Select Module screen] is displayed. Select [ETHERNET MODULE Generic Ethernet Module], and click on
[OK].
• [Module Properties screen] is displayed. Perform each setting.
(1)Name: Input the description of specific unit.

(2)Comm. Format: Select the data format of Connection Parameters.

(3)IP Address: Input IP Address which is set in SI unit.

(4)Assembly Instance: Set as below.


Description Decimal
Common Format “Data-INT” “Data-SINT”
Input 100 100
Output 150 150
Note)
Configuration 105 105
Note) Configuration other than 105 is possible when Configuration Assembly is not used

(5)Size: Set as below.


Description Decimal
Common Format “Data-INT” “Data-SINT”
Input MAX.32 words Note) MAX.64 byte Note)
MIN.1 words MIN.1 byte
Output MAX.32 words Note) MAX.64 byte Note)
Configuration It is changeable according to the connected unit type.
Connection is not established when configuration size is wrong.
Configuration size is set to 0 byte when configuration assembly is
not used.
Note) It is changeable according to the diagnosis setting and connected unit type.

(1) (4)
(5)

(2)
(3)
■Setting procedure of configuration assembly

The setting of various parameters is possible by using Configuration assembly.


Please refer to the setting procedure of Configuration Assembly taking the unit construction below as an
example.

Unit 0 Unit 1 Unit 2 Unit 3 Unit 4 Unit 5

AMB AMB DMPE DFB DYPE1 SEN

Analog Analog Digital Frequency Digital SI unit


End
I/O I/O I/O Counter Output (32 outputs) Valve
plate
Config size Config size Config size Config size Config size Config size
31 byte 31 byte 9 byte 28 byte 20 byte 26 byte

(1)Calculation of Configuration size


Referring Unit ID list, add Configuration size of the unit which is connected.
AMB(31 byte)+AMB(31 byte)+DMPE(9 byte)+DFB(28 byte)+DYPE1(20 byte)+SEN(32 point) (26 byte)
=145 byte
(2)Setting of Configuration size
Input Configuration size of (1) in the display below.

(2)
(3)Setting of Configuration data
Set Configuration data in order starting from the unit on the end plate unit which is connected.
Refer to unit ID list for setting Unit ID.
Refer to Setting parameter for the details of parameter.

Configuration data Remarks


Byte0 35 (Dec) Unit ID of AMB
Byte1 to 30 Parameter Parameter of AMB
Byte31 35 (Dec) Unit ID of AMB
Byte32 to 61 Parameter Parameter of AMB
Byte62 29 (Dec) Unit ID of DMPE
Byte63 to 70 Parameter Parameter of DMPE
Byte71 40 (Dec) Unit ID of DFB
Byte72 to 98 Parameter Parameter of DFB
Byte99 63 (Dec) Unit ID of DYPE1
Byte100 to 118 Parameter Parameter of DYPE1
Byte119 155 (Dec) Unit ID of SEN1 (32 outputs)
Byte120 to 144 Parameter Parameter of SEN1 (32 outputs)

■Unit ID list
While Configuration Assembly is used, it is necessary to set Unit ID and Configuration size depending on the
type of connected unit and the order of the connection.
Input the addition of the connected unit to the column of Configuration size.

Unit Unit part number Unit ID Configuration size [byte]


EX600-SEN1 (32 outputs) 155 26
EX600-SEN1 (24 outputs) 154 20
SI unit
EX600-SEN1 (16 outputs) 153 14
EX600-SEN1 (8 outputs) 152 8
Digital output unit EX600-DYPE1 (24 outputs) 63 20
Digital I/O unit EX600-DMPE (8 inputs/8 outputs) 29 9
Analog I/O unit EX600-AMB (2 inputs / 2 outputs) 35 31
Frequency Counter unit EX600-DFB (4 inputs) 40 28
■EtherNet/IPTM configuration assembly
Configuration format
EX600-SEN1-X1 (max.26 bytes) Configuration size by
Byte Bit
Parameter Setting value coils setting
Unit ID 8 coils setting: 152 (Dec), 98 (Hex)
16 coils setting:153 (Dec), 99 (Hex)
0 -
24 coils setting:154 (Dec), 9A (Hex)
32 coils setting:155 (Dec),9B (Hex)
0 Reserved 0
1 Short circuit detection 0:disable, 1:enable
2 Reserved 0
3 Restart after short circuit 0:disable, 1:enable
Power supply voltage 0:disable, 1:enable
1 4
monitor (Control/Input)
Power supply voltage 0:disable, 1:enable
5
monitor (Output)
6 Hold /Clear 0: Via switch, 1: Via software
7 Reserved 0
0 (Ch0) ON/OFF counter 0:disable, 1:enable
2 ~ ~ ~
7 (Ch7) ON/OFF counter 0:disable, 1:enable 8 coils setting
0 (Ch0) Open circuit detection 0:disable, 1:enable is allocated
3 ~ ~ ~ from byte 0
7 (Ch7) Open circuit detection 0:disable, 1:enable to byte 7.
(Ch0) Output setting during 0: hold
0
communication Fault 1: depend on fault value
4 ~ ~ ~
(Ch7) Output setting during 0: hold
7
communication Fault 1: depend on fault value
0 (Ch0) Fault value 0: clear, 1:ON
5 ~ ~ ~
7 (Ch7) Fault value 0: clear, 1:ON
(Ch0) Output setting during 0: hold
0
communication Idle 1: depend on fault value
6 ~ ~ ~
(Ch7) Output setting during 0: hold
7
communication Idle 1: depend on fault value
0 (Ch0) Idle value 0: clear, 1:ON
7 ~ ~ ~
7 (Ch7) Idle value 0: clear, 1:ON
0 (Ch8) ON/OFF counter 0:disable, 1:enable
8 ~ ~ ~
7 (Ch15) ON/OFF counter 0:disable, 1:enable
0 (Ch8) Open circuit detection 0:disable, 1:enable
~ ~ ~ 16 coils setting
9
(Ch15) Open circuit 0:disable, 1:enable is allocated
7
detection from byte 0
(Ch8) Output setting during 0: hold to byte 13.
0
communication Fault 1: depend on fault value
10 ~ ~ ~
(Ch15) Output setting during 0: hold
7
communication Fault 1: depend on fault value
EX600-SEN1-X1 Configuration size
Byte Bit
Parameter Setting value
0 (Ch8) Fault value 0: clear, 1:ON
11 ~ ~ ~
7 (Ch15) Fault value 0: clear, 1:ON
(Ch8) Output setting during communication 0: hold
0
Idle 1: depend on fault value
12 ~ ~ ~
(Ch15) Output setting during communication 0: hold
7
Idle 1: depend on fault value
0 (Ch8) Idle value 0: clear, 1:ON
13 ~ ~ ~
7 (Ch15) Idle value 0: clear, 1:ON
0 (Ch16) ON/OFF counter 0:disable, 1:enable
14 ~ ~ ~
7 (Ch23) ON/OFF counter 0:disable, 1:enable
0 (Ch16) Open circuit detection 0:disable, 1:enable
15 ~ ~ ~
7 (Ch23) Open circuit detection 0:disable, 1:enable
(Ch16) Output setting during communication 0: hold
0
Fault 1: depend on fault value
16 ~ ~ ~
(Ch23) Output setting during communication 0: hold 24 coils setting
7
Fault 1: depend on fault value is allocated
0 (Ch16) Fault value 0: clear, 1:ON from byte 0
17 ~ ~ ~ to byte 19.
7 (Ch23) Fault value 0: clear, 1:ON
(Ch16) Output setting during communication 0: hold
0
Idle 1: depend on fault value
18 ~ ~ ~
(Ch23) Output setting during communication 0: hold
7
Idle 1: depend on fault value
0 (Ch16) Idle value 0: clear, 1:ON
19 ~ ~ ~
7 (Ch23) Idle value 0: clear, 1:ON
0 (Ch24) ON/OFF counter 0:disable, 1:enable
20 ~ ~ ~
7 (Ch31) ON/OFF counter 0:disable, 1:enable
0 (Ch24) Open circuit detection 0:disable, 1:enable
21 ~ ~ ~
7 (Ch31) Open circuit detection 0:disable, 1:enable
(Ch24) Output setting during communication 0: hold
0 32 coils setting
Fault 1: depend on fault value
is allocated
22 ~ ~ ~
from byte 0
(Ch31) Output setting during 0: hold to byte 25.
7
communication Fault 1: depend on fault value
0 (Ch24) Fault value 0: clear, 1:ON
23 ~ ~ ~
7 (Ch31) Fault value 0: clear, 1:ON
(Ch24) Output setting during communication 0: hold
0
24 Idle 1: depend on fault value
~ ~ ~
EtherNet/IP Objects
System diagnostic objects (Class: 102d, 66h)
Instance Attribute
Access Name Data type Description
(decimal) (decimal)
Input data size of I/O
100 Get Input data size UINT
mapping
Output data size of I/O
101 Get Output data size UINT
mapping

Number of units in the


109 Get Number of units USINT
manifold

0: Update the configuration


110 Get/Set Re-register BOOL
memory.
0: Via switch setting
121 Get / Set Hold / Clear BOOL
1: Via software setting
bit 0: Analog input, Analog
output or Frequency
counter falls below user’s
setting lower limit value.

bit 1: Analog input, Analog


output or Frequency
counter exceeds user’s
setting upper limit value.

bit 2: Analog input falls below


122 Get System diagnosis 1 BYTE lower measurement
range.

bit 3: Analog input exceeds


1 upper measurement
range.

bit 4: Channel ON/OFF


counter exceeds setting
value.

bit 5: Open circuit is


detected.
bit 0: Power supply voltage
for output is outside
operating range.

bit 1: Power supply voltage


for control and sensor is
outside operating range.

bit 2 :(Reserved)
123 Get System diagnosis 2 BYTE
bit 3: Communication error
between SI Unit and I/O Unit
during operation.

bit 4: Communication error


between SI Unit and I/O Unit
at system starts up.

bit 5: Manifold configuration


error.
bit 6 : System error

bit 7 : Hardware error


System diagnostic objects (Class: 102d, 66h)
Instance Attribute
Access Name Data type Description
(decimal) (decimal)
bit 0 :Error is detected in digital
input

bit 1 :Error is detected in digital


output

bit 2 :Error is detected in analog


input or frequency
125 Get System diagnosis 4 BYTE counter

bit 3 : Error is detected in


analog output

bit 4 : Error is detected in SI


unit

bit 5…bit 7 : (Reserved)


bit 0 :Error is detected in Unit 0

bit 1 :Error is detected in Unit 1

bit 2 :Error is detected in Unit 2

bit 3 : Error is detected in Unit 3


Unit diagnosis
156 Get BYTE
1 bit 4 : Error is detected in Unit 4

bit 5 : Error is detected in Unit 5


1
bit 6 : Error is detected in Unit 6

bit 7 : Error is detected in Unit 7


bit 0 :Error is detected in Unit 8
Unit diagnosis
157 Get BYTE bit 1 :Error is detected in Unit 9
2
bit 2…bit 7 : (Reserved)
bit 0 :Unit 0 is connected

bit 1 : Unit 1 is connected

bit 2 : Unit 2 is connected

bit 3 : Unit 3 is connected


Unit diagnosis
174 Get BYTE
3 bit 4 : Unit 4 is connected

bit 5 : Unit 5 is connected

bit 6 : Unit 6 is connected

bit 7 : Unit 7 is connected


bit 0 : Unit 8 is connected
Unit diagnosis
175 Get BYTE bit 1 : Unit 9 is connected
4
bit 2…bit 7 : (Reserved)
Unit diagnostic objects (Class: 103, 67h)
Instance Attribute
Access Name Data type Description
(decimal) (decimal)
102 GET Unit type USINT Unit ID is shown.
bit 0: Analog input, Analog output
or Frequency counter falls
below user’s setting lower
limit value.

bit 1: Analog input, Analog output


or Frequency counter
exceeds user’s setting upper
limit value.

bit 2: Analog input falls below


lower measurement range.
108 GET Unit diagnosis 5 BYTE bit 3: Analog input exceeds upper
measurement range.

bit 4: Channel ON/OFF counter


exceeds setting value.

bit 5: Open circuit is detected.

bit 6: Short circuit is detected at


output.

bit 7: Short circuit is detected at


sensor supply.
bit 0 :Error is detected at channel
1…10
(Note)
0

bit 1 :Error is detected at channel


1

bit 2 :Error is detected at channel


2

bit 3 : Error is detected at channel


3
Channel diagnosis
110 GET BYTE
1 bit 4 : Error is detected at channel
4

bit 5 : Error is detected at channel


5

bit 6 : Error is detected at channel


6

bit 7 : Error is detected at channel


7
bit 0 :Error is detected at channel
8
Channel diagnosis
111 GET BYTE bit 1 :Error is detected at channel
2 9

bit 2 :Error is detected at


channel 10

bit 3 : Error is detected at channel


11

bit 4 : Error is detected at channel


12

bit 5 : Error is detected at channel


13

bit 6 : Error is detected at channel


14

bit 7 : Error is detected at channel


15
(Note) The instance number from 1 to 10 is allocated to the Unit No. from 0 to 9.
Unit diagnostic objects (Class: 103, 67h)
Instance Attribute
Access Name Data type Description
(decimal) (decimal)
bit 0 :Error is detected at channel 16

bit 1 :Error is detected at channel 17

bit 2 :Error is detected at channel 18

bit 3 : Error is detected at channel 19


Channel diagnosis
112 GET BYTE
3 bit 4 : Error is detected at channel 20

bit 5 : Error is detected at channel 21

bit 6 : Error is detected at channel 22

1…10 bit 7 : Error is detected at channel 23


(Note) bit 0 :Error is detected at channel 24

bit 1 :Error is detected at channel 25

bit 2 :Error is detected at channel 26

bit 3 : Error is detected at channel 27


Channel diagnosis
113 GET BYTE
4 bit 4 : Error is detected at channel 28

bit 5 : Error is detected at channel 29

bit 6 : Error is detected at channel 30

bit 7 : Error is detected at channel 31


(Note) The instance number from 1 to 10 is allocated to the Unit No. from 0 to 9.
Channel diagnostic objects (Class: 119d, 77h)
Instance Attribute
Access Name Data type Description
(decimal) (decimal)
bit 0: Analog input, Analog
output or Frequency
counter falls below
user’s setting lower
limit value.

bit 1: Analog input, Analog


output or Frequency
counter exceeds
user’s setting upper
limit value.

bit 2: Analog input falls


below lower
measurement range.
1…10 100…131 Channel diagnosis
Get BYTE bit 3: Analog input exceeds
(Note1) (Note2) Ch0…Ch31 upper measurement
range.

bit 4: Channel ON/OFF


counter exceeds
setting value.

bit 5: Open circuit is


detected.

bit 6: Short circuit is


detected at output.

bit 7: Short circuit is


detected at sensor
supply.
(Note1) The instance number from 1 to 10 is allocated to the Unit No. from 0 to 9.
(Note2) The attribute number from 100 to 131 is allocated to the channel No. from 0 to 31.
Unit parameter setting objects
Class Instance Attribute Name Data
(decimal) (decimal) (decimal)
Access Description
(Corresponding Unit) type
Short circuit detection at
sensor supply
0 :Disable
100 -Digital Input BOOL
1 :Enable
-Analog Input
-Analog output
-Frequency Counter
Short circuit detection at
output
0 :Disable
101 BOOL
1 :Enable
-SI unit,
-Digital Output
Over range detection
0 :Disable
102 BOOL
1 :Enable
-Analog Input
Under range detection
0 :Disable
103 BOOL
1 :Enable
- Analog Input
Inrush current filter
0 :Disable
104 BOOL
1 :Enable
-Digital Input
Restart after short circuit
1…10
120 Get / Set 0 :Manual
(Note) 105 BOOL
-SI unit 1 :Auto
-Digital Output
0 :0.1msec
Input filtering time
1 :1msec
106 USINT
2 :10msec
-Digital Input
3 :20msec
0 :1msec
Input extension time
1 :15msec
107 USINT
2 :100msec
-Digital Input
3 :200msec
Analog data format 0 :Offset binary
1 :Signed binary
108 USINT
-Analog input 2 :2’S complement
-Analog output 3 :Linear scaling
Power supply voltage monitor
for control / input 0 :Disable
109 BOOL
1 :Enable
-SI unit
Power supply voltage monitor
for output 0 :Disable
110 BOOL
1 :Enable
-SI unit
(Note) The instance number from 1 to 10 is allocated to the Unit No. from 0 to 9.
Channel parameter setting objects
Class Instance Attribute Name Data
(decimal) (decimal) (decimal)
Access Description
(Corresponding Unit) type
Open circuit
detection 0 :Disable
121 -SI unit
BOOL
1 :Enable
-Digital output
ON/OFF counter
detection
0 :Disable
122 -SI unit
BOOL
1 :Enable
-Digital input
-Digital output
ON/OFF counter
setting value Set the maximum
counter value. Settable
123 -SI unit
UINT
value is
-Digital input (1~65000) x 1000 times
-Digital output
User setting value
upper limit detection
0 :Disable
124 -Analog input
BOOL
1 :Enable
-Analog output
-Frequency Counter
User setting upper
limit value
2 byte AD value via analog
125 -Analog input
UINT
data format
-Analog output
-Frequency Counter
1…10 100…131
Get / Set User setting value
(Note1) (Note2)
lower limit detection
0 :Disable
126 -Analog input
BOOL
1 :Enable
-Analog output
-Frequency Counter
User setting lower
limit value
2 byte AD value via analog
127 -Analog input
UINT
data format
-Analog output
-Frequency Counter
Output setting during
communication fault
0 :Hold
131 -SI unit
BOOL
1 :Via output value
-Digital output
-Analog output
Digital output value
during
communication fault 0 :Clear
132 BOOL
1 :ON
-SI unit
-Digital output
Analog output value
during
2 byte AD value via analog
133 communication fault UINT
data format
-Analog output
Channel parameter setting objects
Class Instance Attribute Name Data
Access Description
(decimal) (decimal) (decimal) (Corresponding Unit) type
Output setting during
communication fault
0 :Hold
134 -SI unit
BOOL
1 :Via output value
-Digital output
-Analog output
Digital output value during
communication fault
0 :Clear
135 BOOL
1 :ON
-SI unit
-Digital output
Analog output value during
communication fault 2 byte AD value via
136 1…10 100…131
Get / Set
UINT
analog data format
(Note1) (Note2)
-Analog output
Analog input filter 0 :None
1 :2 value average
-Analog input 2 :4 value average
137 USINT 3 :8 value average
4 :16 value average
5 :32 value average
6 :64 value average
Analog input or output 3 : 0...10V
range 4 : 0...5V
138 USINT 5 : 1...5V
-Analog input 6 : 0...20mA
-Analog output 7 : 4...20mA
Set the cut off
Cutoff frequency frequency value.
1…10 100…131
142 (Note1) (Note2)
Get / Set UINT
Settable value is
-Frequency Counter
0~1000.0 Hz.
(Note1) The instance number from 1 to 10 is allocated to the Unit No. from 0 to 9.
(Note2) The attribute number from 100 to 131 is allocated to the channel No. from 0 to 31.
Monitor ON/OFF counter value objects
Class Instance Attribute Name Data
Access Description
(decimal) (decimal) (decimal) (Corresponding Unit) type
Monitor present ON/OFF
counter value
Present ON/OFF
1…10 100…131
139 (Note1) (Note2)
Get
-SI unit
UDINT counter value is
monitored.
-Digital output
-Digital input
(Note1) The instance number from 1 to 10 is allocated to the Unit No. from 0 to 9.
(Note2) The attribute number from 100 to 131 is allocated to the channel No. from 0 to 31.

Update Error Log.txt objects


Class Data
Instance Attribute Access Name Description
(decimal) type
0: Update the error log.txt file in
140 1 102 Get/Set Update error log.txt Byte
the FTP server
Accessories
For the selection of accessories, refer to the catalog.
(1)Valve plate
EX600-ZMV1
Enclosed parts: Round head screw (M4x6), 2 pcs.
Round head screw (M3x8), 4 pcs.

EX600-ZMV2 (Specified for SY series)


Enclosed parts: Round head screw (M4x6), 2 pcs.
Round head screw (M3x8), 4 pcs.

(2)End plate bracket


EX600-ZMA2
Enclosed parts: Round head screw (M4x20), 1 pc.
P tithe screw (M4x14), 2 pcs.
EX600-ZMA3 (Specified for SY series)
Enclosed parts: Round head screw (M4x20) with washer, 1 pcs.
P tithe screw (M4x14), 2 pcs.

(3)Intermediate support bracket


EX600-ZMB1…for direct mounting
Enclosed parts: Round head screw (M4x5), 2 pcs.
EX600-ZMB2…for DIN rail mounting
Enclosed parts: Round head screw (M4x6), 2 pcs.
(4)Seal cap (10 pcs.)
EX9-AWES…for M8
EX9-AWTS…for M12

(5)Marker (1 sheet, 88 pcs.)


EX600-ZT1

(6)Y Junction connector


PCA-1557785 2xM12 (3 pin) – M12 (5 pin)

TM
(9)EtherNet/IP communication cable
EX9-AC020EN-PSRJ Cable with M12 connector, D code, Socket, Straight 2 m
Revision history

URL http://www.smcworld.com
4-14-1, Sotokanda, Chiyoda-ku, Tokyo 102-0021 Japan