EtherNet/IPTM compatible
PRODUCT NAME
EX600-SEN1-X1
MODEL/ Series
SI Unit
Model Indication and how to Order
EX600 – S -X1
SI Unit
3 TX-
4 RX-
(3) Set the switch using a small watchmaker's screwdriver with a thin blade, referring to the setting of switch
on the following pages.
(4) After setting the switch, tighten the display cover tightening screw in the reverse order of the above
procedure. (Tightening torque: 0.3 to 0.4 Nm)
Settings1
Content
1
OFF Normal operation mode (default setting)
ON Configuration memory mode
•Timing to memorize the configuration when power supply for control/input is turned on, with the switch
above turned OFF.
•Timing to compare the configuration when power supply for control/input is turned on, with the switch
above turned ON.
•Baud Rate switch: Sets the communication speed of the internal bus of the product.
Settings1
Content
2 3
OFF OFF 1 Mbps (default setting)
OFF ON 500 kbps
ON OFF 250 kbps
ON ON 125 kbps
∗: This function is for extension in the future. Use the product with 1 Mbps (default setting).
•IP address setting switch
Settings1 Settings2
IP address
8 1 2 3 4 5 6 7 8
OFF ON OFF OFF OFF OFF OFF OFF OFF 192.168.0.1
OFF OFF ON OFF OFF OFF OFF OFF OFF 192.168.0.2
: : : : : : : : : :
OFF ON OFF ON ON ON ON ON ON 192.168.0.253
OFF OFF ON ON ON ON ON ON ON 192.168.0.254
ON ON OFF OFF OFF OFF OFF OFF OFF 192.168.1.1
ON OFF ON OFF OFF OFF OFF OFF OFF 192.168.1.2
: : : : : : : : : :
ON ON OFF ON ON ON ON ON ON 192.168.1.253
ON OFF ON ON ON ON ON ON ON 192.168.1.254
1
ON/OFF ON ON ON ON ON ON ON ON DHCP mode
2
ON/OFF OFF OFF OFF OFF OFF OFF OFF OFF Remote Control mode
1: The mode to obtain IP address from DHCP server. Obtained IP address is lost when the power supply is cut.
2: The mode to respond to the commands below of BOOTP/DHCP Server provided by Rockwell Automation.
Enable DHCP: IP address etc. can be obtained from BOOTP/DHCP Server.
If the power is supplied again in this state, information including IP address is obtained again.
Disable DHCP: IP address etc. cannot be obtained from BOOTP/DHCP Server.
If the power is supplied again with this condition, previous setting can be held.
•V_SEL switch: The number of outputs (size) occupied by the SI unit is selected.
Settings3
Content SI unit output data size
1 2
OFF OFF Number of occupied valve 32 outputs 4 byte (default setting)
OFF ON Number of occupied valve 24 outputs 3 byte
ON OFF Number of occupied valve 16 outputs 2 byte
ON ON Number of occupied valve 8 outputs 1 byte
∗: Set the number of occupied valve outputs to at least the number of valves used.
•Switch for diagnostics: Allocates the diagnostic data to the input data
Settings3
Content
5
OFF Output is off. (default setting)
ON Holds the output.
: This switch can be enabled and disabled by parameter.
TM
•EtherNet/IP communication setting switch
Settings3
Communication speed full duplex/half duplex setting
6 7 8
OFF ON/OFF ON/OFF Automatic
ON OFF OFF 10 Mbps, half duplex
ON OFF ON 10 Mbps, full duplex
ON ON OFF 100 Mbps, half duplex
ON ON ON 100 Mbps, full duplex
Display Content
ST(M) Displays the diagnosis status of the unit.
PWR Displays the status of the power supply voltage for control and input.
PWR(V) Displays the status of the power supply voltage for outputs.
MS Displays the module status.
NS Displays the network status.
A unit other than the SI unit has been diagnosed and detected.
Green ST(M) LED is flashing
Recoverable error.
Red MS LED is flashing
•Network status
LED display Content
The power supply for control and input is Off, or IP address is not set.
NS LED is Off
Connection is established.
Green NS LED is On
Connection timeout.
Red NS LED is flashing
IP address is duplicated.
Red NS LED is On
Specification
■Specifications
Model EX600-SEN1
TM
Fieldbus EtherNet/IP (IEEE802.3)
Media 100BASE-TX
Communication speed 10/100 Mbps (Automatic/Manual)
Communication type Full duplex/half duplex (Automatic/Manual)
TM
Communication
EtherNet/IP
Fieldbus protocol
(Conformance version: Composite6)
Input: Unit that can be connected depends on the type
I/O message
Output: Unit that can be connected depends on the type
Setting by SI unit switch: 192.168.0 or 1.1 to 254
IP address setting range
Via DHCP server : Arbitrary address
Withstand voltage 500 VAC for 1 minute between external terminals and FE
Insulation resistance 500 VDC, 10 MΩ or more between external terminals and FE
10 to 57 Hz: constant amplitude 0.75 mm p-p
2
Vibration resistance 57 to 150 Hz: constant acceleration 49 m/s
for 2 hours each in direction X, Y and Z respectively (De-energized)
2
147 m/s 3 times each in directions of X, Y and Z respectively
Impact resistance
(De-energized)
Pollution degree For use in Pollution Degree 2 Environment (UL508)
Standard CE marking, UL (CSA) , RoHS
Weight 300 g
1: All unused connectors must have a waterproof cap fitted.
2: The UL compliant temperature is 0 to 50 oC.
■Dimensions
Parameter Setting
The product has parameters that can be set for the system, each unit or each channel.
The parameters can be changed using EtherNet/IP and handheld terminal.
There is no order of precedence of the PLC and handheld terminal. The latest parameter settings are used.
Short Circuit Generates error per unit when Enable Generates an error. ○
3 Detection the short circuit of the valve is ○ ○
Does not generate an
(SC_MonOp) detected. Disable
error.
Error is automatically
Auto cleared when the short ○
Restores the status per unit circuit is fixed.
Restart after
after the short circuit
4 short circuit Even when the short ○ ○
detection of the valve short
(SC_RstOp) circuit is fixed, error is not
circuit is cleared. Manual
cleared until the power is
supplied again.
Generates an error.
Memorizes the number of times Enable
Val: 1 to 65000 ∗
4
Valve
the valve is ON. Generates
ON/OFF
8 error per channel when the ○ ○
counter
operation count exceeds the set
(Counter) Does not generate an
value. ∗
3
Disable ○
error.
∗1: This function is valid only when “Hold/Clear priority” of the system parameter is set to Handheld.
∗2: EX600-SEN□ (DeviceNetTM SI unit) and EX600-SMJ□ (SI unit for CC-Link) cannot be set.
∗3: The count is memorized every 30 seconds per channel. When the power supply is turned on again, counting starts from the last value
memorized.
∗4: Times for setting is set value x1000 times.
•Digital output unit parameters
Parameter
Parameter Default setting
No. Definition Item Content
(H.T. Symbol) setting By By
PLC H.T.
Automatically restored
Restart after Restore the setting of short Auto after the error is cleared. ○
output load circuit detection error per unit (Default setting)
2 ○ ○
short circuit after the output equipment
(SC_RstOp) short circuit is cleared. Error continues until the
Manual
power is supplied again.
Generates an error.
Memorizes the number of Enable
Val: 1 to 65000 ∗
5
Channel times the output equipment is
On/Off ON. Generates error per
6 ○ ○
counter channel when the operation
(Counter) count exceeds the set value
for diagnosis. ∗
5 Does not generate an
Disable ○
error.
∗1: Could be incorrectly recognized as short circuit depending on used load (ex.: lamp load). If detection is incorrect, disable the parameter
setting.
∗2: This function is valid only when “Hold/Clear priority” of the system parameter is set to Handheld.
∗3: EX600-SEN□ (DeviceNetTM SI unit) and EX600-SMJ□ (SI unit for CC-Link) cannot be set.
∗4: The count is memorized every hour. When the power supply is turned on again, counting starts from the last value memorized.
∗5: Times for setting is set value x1000 times.
•Digital I/O unit parameters
Parameter
Parameter Default setting
No. Definition Item Content
(H.T. Symbol) setting By By
PLC H.T.
The power
supply short Enable Generates an error. ○
Generates error per unit when
circuit
the short circuit of the control
1 detection for ○ ○
or input power supply is
control and Does not generate an
detected. Disable
input error.
(SC_MonSs)
Generates an error.
Memorizes the number of times Enable
Val: 1 to 65000 ∗
5
Output the input or output equipment is
ON/OFF ON. Generates error per
10 ○ ○
counter channel when the operation
(Counter) count exceeds the set value for
diagnosis. ∗
4 Does not generate an
Disable ○
error.
∗1: Could be incorrectly recognized as short circuit depending on used load (ex.: lamp load). If detection is incorrect, disable the parameter
setting.
∗2: This function is valid only when “Hold/Clear priority” of the system parameter is set to Handheld.
∗3: EX600-SEN□ (DeviceNetTM SI unit) and EX600-SMJ□ (SI unit for CC-Link) cannot be set.
∗4: The count is memorized every hour. When the power supply is turned on again, counting starts from the last value memorized.
∗5: Times for setting is set value x1000 times.
•Analog I/O unit parameters (1)
Parameter
Parameter Default setting
No. Definition Item Content
(H.T. Symbol) setting By By
PLC H.T.
The power Generates error per
supply short unit when the short Enable Generates an error. ○
circuit circuit of the input
1 detection for equipment power ○ ○
the input or supply or output
Does not generate an
output device equipment is Disable
error.
(SC_MonSs) detected.
0..10 V
Analog input 0..5 V
Sets the analog input
or output The analog input or
2 or output equipment 1..5 V 1..5 V ○ ○
range output range is selected.
range per channel. 0..20 mA
(Range)
4..20 mA
Offset binary Offset binary. ○
Analog data Sets analog data type
Sign & Magnitude Signed binary.
3 format which is output to ○ ○
(D_Format) PLC per unit. 2S Complement 2’s complement.
Scaled Scale conversion type.
None None ○
Sets analog filtering
Analog 2AVG 2 value average
time per channel.
4 average filter ○ ○
Sampling interval is 4AVG 4 value average
(Filter)
approx. 2 sec.
8AVG 8 value average
8 Generates an error. ○ ○
Sets the lower limit of scale. Enable ∗*3
Val: -32767 to 32766
Scale lower Sets error to be generated per
limit setting ∗
1
channel when the input or
(UpLm/Scl) output value falls below the Does not generate an
○
lower limit. Disable error.
Val: 0
Val: -32767 to 32766
Output setting
Val is output. ∗
2
for Enable
Set output per channel when
9 communication ○ ○
communication is abnormal.
error ∗
4
Disable The output is held. ○
(Fault_MA)
Output setting
Val is output. ∗
2
for Enable
Sets output setting per channel
10 communication ○ ○
for communication idling.
idling ∗ ∗
4 5
Disable The output is held. ○
(Idle_MA)
*1: When “Scaled” is selected as the analog data format, the display of H.T. is switched from Upr_Lmt to UpLm/Scl, from Lwr_Lmt to
LwLm/Scl.
*2: Set value shall be set per analog output range within settable range in the table below.
When the analog output range is changed, check the set value and change it to an appropriate value.
*3: Setting via PLC is not available with EX600-SPR□ (SI unit for PROFIBUS).
*4: This function is valid only when “Hold/Clear priority” of the system parameter is set to Handheld.
*5: Some types cannot be used depending on EX600-SDN□ (SI unit for DeviceNet).
Cannot be set for EX600-SMJ□ (SI unit for CC-Link).
Allocated input / output size is changeable according to the diagnosis setting and connected EX600
unit type. The allocated input/ output bytes for each EX600 unit are shown below.
Allocated bytes
Unit type Abbreviation Description
Input Output
EX600-SEN# (32 points) SI Unit (32 points) 0 4
EX600-SEN# (24 points) SI Unit (24 points) 0 3
SI
EX600-SEN# (16 points) SI Unit (16 points) 0 2
EX600-SEN# (8 points) SI Unit (8 points) 0 1
*EX600-SEN# can change the allocated output bytes with switch setting.
*If there is no input byte, input size of master configuration must be set more than 1byte.
Diagnosis
The following diagnostic data is allocated to the top of the I/O mapping input data by switching No. 1
and No. 2 of the Setting2 switch.
Switch setting
Mode Diagnostic data Diagnosis size
No1 No2
0 OFF OFF No diagnostic data 0 byte
1 OFF ON System diagnostic 4 bytes
2 ON OFF System diagnostic + Unit diagnostic (for 10 units) 6 bytes
Note 1) The channel diagnostics cannot be allocated to the input map. Use the hand-held unit for
monitoring.
Details of diagnostic information
Details of the diagnostic information are shown on below list.
System diagnosis
(1) (4)
(5)
(2)
(3)
■Setting procedure of configuration assembly
(2)
(3)Setting of Configuration data
Set Configuration data in order starting from the unit on the end plate unit which is connected.
Refer to unit ID list for setting Unit ID.
Refer to Setting parameter for the details of parameter.
■Unit ID list
While Configuration Assembly is used, it is necessary to set Unit ID and Configuration size depending on the
type of connected unit and the order of the connection.
Input the addition of the connected unit to the column of Configuration size.
bit 2 :(Reserved)
123 Get System diagnosis 2 BYTE
bit 3: Communication error
between SI Unit and I/O Unit
during operation.
TM
(9)EtherNet/IP communication cable
EX9-AC020EN-PSRJ Cable with M12 connector, D code, Socket, Straight 2 m
Revision history
URL http://www.smcworld.com
4-14-1, Sotokanda, Chiyoda-ku, Tokyo 102-0021 Japan
Tel: +81 3 5207 8249 Fax: +81 3 5298 5362
Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.
DeviceNet™ is a trademark of ODVA
The descriptions of products shown in this document may be used by the other companies as their trademarks.
© 2008 SMC Corporation All Rights Reserved