Ethiopian Pharmaceutical Supply Service – EPSS

Supply, Installation and Commissioning of


Networking Infrastructure and Modular Data
Center

DCF and Power Low Level Design


Type of Document:

DCF and Power Low Level Design


Client Name:
EPSS
Prepared by:
IE NETWORK SOLUTIONS PLC

Version:

1.0
Date:
August, 2023

GET THE JOB DONE


IE-EPSS LLD Document

Table of Contents

List of Figures............................................................................................................... iii


List of Table .................................................................................................................. iv
Acronyms ....................................................................................................................... v
1 Introduction ................................................................................................................ 1
1.1 Document Main purpose.......................................................................................................... 1
1.2 Scope ....................................................................................................................................... 1
2 Over View of Modular Data Center............................................................................ 2
2.1 IECombo Series Single Line Micro Data Center ......................................................................... 2
2.2 Cabinet System ........................................................................................................................ 4
2.2.1 Rack Cabinet System ............................................................................................ 4

2.2.2 Cable Trough ........................................................................................................ 6

2.2.3 Aisle Containment of Cabinet ................................................................................ 7

2.2.4 Enclosed Door and aisle ....................................................................................... 7

3 Power Supply System ................................................................................................ 9


3.1 Overall Electrical Design ........................................................................................................... 9
3.1.1 Power Cabinet....................................................................................................... 9

3.1.2 Power Distribution Module .................................................................................. 10

3.2 UPS System ............................................................................................................................ 11


3.2.1 20KVA for HQ distribution racks.......................................................................... 13

3.2.2 Distribution rack UPS .......................................................................................... 14

3.2.3 Intelligent PDU .................................................................................................... 15

3.3 Generator .............................................................................................................................. 15


3.4 Automatic Voltage Regulator ................................................................................................. 16
4 Cooling System ........................................................................................................ 23
4.1 Precision Cooling .................................................................................................................... 23
4.2 Floor Stand Air Conditioner .................................................................................................... 24
5 DCIM .......................................................................................................................... 28

Confidential© 2023 Pa ge |i
IE-EPSS LLD Document

5.1 IE Smart DCIM System Software and Interface. ...................................................................... 29


Monitoring and Management ...................................................................................................... 29
5.2 Environment Sensors ............................................................................................................. 29
5.3 IE Guard Access Control ......................................................................................................... 30
6 Firefighting System .................................................................................................. 32
7 Bill of Materials (BoM) .............................................................................................. 33
8 Document Acceptance Certificate .......................................................................... 37

Confidential© 2023 P a g e | ii
IE-EPSS LLD Document

List of Figures

FIGURE 1:IE-EPSS- DC SOLUTION ............................................................................................................................... 3


FIGURE 2:IE-EPSS- FLOOR PLAN DESIGN FOR DC ....................................................................................................... 4
FIGURE 3: IE-EPSS- RACK CABINET .............................................................................................................................. 6
FIGURE 4:IE-EPSS- TOP CABLE TRAY ........................................................................................................................... 6
FIGURE 5:IE-EPSS- CONVERGED CABINET ................................................................................................................... 7
FIGURE 6: IE-EPSS- CONTAINMENT SYSTEM .............................................................................................................................. 8
FIGURE 7:POWER CABINET .......................................................................................................................................... 10
FIGURE 8:IE-EPSS-POWER DISTRIBUTION MODULE ................................................................................................... 11
FIGURE 9:IE-EPSS- UPS............................................................................................................................................ 13
FIGURE 10: IE-EPSS- 20KVA UPS ............................................................................................................................ 14
FIGURE 11: IE-EPSS- RACK MOUNT UPS ................................................................................................................... 14
FIGURE 12 IE-EPSS- INTELLIGENT PDU ..................................................................................................................... 15
FIGURE 13: IE-EPSS- GENERATOR ............................................................................................................................. 16
FIGURE 14: IE-EPSS- OVER ALL POWER DISTRIBUTION DIAGRAM ................................................................................ 18
FIGURE 15: UPS SCHEDULE DIAGRAM ........................................................................................................................ 19
FIGURE 16: NON CRITICAL SCHEDULE DIAGRAM .......................................................................................................... 20
FIGURE 17 POWER DISTRIBUTION PANEL SCHEDULE DIAGRAM ................................................................................... 21
FIGURE 18POWER DISTRIBUTION FOR EACH RACK ....................................................................................................... 22
FIGURE 19: IE- EPSS- PRECISION AC ........................................................................................................................ 23
FIGURE 20:IE-EPSS- FLOOR STAND AC ...................................................................................................................... 24
FIGURE 21: AC LAYOUT ............................................................................................................................................... 25
FIGURE 22 IE-EPSS- DCIM SYSTEM .......................................................................................................................... 28
FIGURE 23 IE-EPSS- DCIM SCREEN .......................................................................................................................... 29
FIGURE 24 ENVIRONMENT SENSORS............................................................................................................................ 30
FIGURE 25IE-EPSS-PROPOSED ACCESS CONTROL .................................................................................................... 31
FIGURE 26 IE-EPSS- RACK MOUNTED FIRE SUPPRESSION .......................................................................................... 32

Confidential© 2023 P a g e | iii


IE-EPSS LLD Document

List of Table

TABLE 1: COMPONENT OF SINGLE ROW MICRO DATA CENTER SOLUTION ..................................................................... 3


TABLE 2: CABINET SPECIFICATIONS ............................................................................................................................... 5
TABLE 3: POWER DISTRIBUTION MODULE SPECIFICATIONS: ......................................................................................... 10
TABLE 4: UPS SPECIFICATION ..................................................................................................................................... 12
TABLE 5: INTELLIGENT PDU ELECTRICAL SPECIFICATION: ........................................................................................... 15
TABLE 6: TECHNICAL SPECIFICATION 25 KW IN ROW COOLING.................................................................................... 25
TABLE 7 FIRE SUPPRESSION SPECIFICATIONS .............................................................................................................. 32

Confidential© 2023 P a g e | iv
IE-EPSS LLD Document

Acronyms

UPS----Uninterruptable Power Supply


DCF---- Data Center Facility
PDF----Power Distribution Frame
SDB---Sub Distribution Board
MDB--- Main Distribution Board

Confidential© 2023 Pa ge |v
IE-EPSS LLD Document

1 Introduction

1.1 Document Main purpose


The main purpose of this document is to provide the low-level detailed design for EPSS
DCF renovation design and implementation. This new infrastructure will be deployed in
EPSS HQ located at Addis Ababa.

This document outlines the placement of different DCF products and their design flow.
The information contained in this document provides, among others, detailed design
templates for the new DCF devices that will be deployed. As such, this document will be
used as the foundation for the DCF implementation and ATP test plan will be crafted in
the next phases of the project

1.2 Scope
The scope of this document is limited to provide low level design information related to
the following DCF product as listed in the Bill of Materials (BOM) for the new
infrastructure:

✓ Rack Placement
✓ UPS, AVR & Generator placement and connection.
✓ Power distribution
✓ Air conditioner connection & placement

Confidential© 2023 Pa ge |1
IE-EPSS LLD Document

2 Over View of Modular Data Center

2.1 IECombo Series Single Line Micro Data Center


IECombo intelligent micro module data center is a solution for small data center,
usually the room covers an area of about 30㎡. The IEComb All-In-One micro data
center features: integration; space and time saving; easy installation; high capability;
Intelligent management., etc.

All-In-One cabinet system is equipped with Input ATS; Intelligent power distribution
module; Surge protection; Intelligent monitoring system; Cooling system;
Environment controlling system and fire suppression; access control system. It’s a
highly integrated; complete data center solution.

Modular design for easy expansion

✓ Employ the standardized modular design; flexible configuration


according to the IT loading; on-site space.
✓ With internal hot/cold aisle with scalable cooling; low noise
✓ Power distribution and communication capability with allowance for easy
expansion.
✓ Rack-Mounted structure support the standard ICT requirement
Single Row Micro Data Center Solution

Feature of the solution:

✓ Single row solution is consisting of multiple enclosed cabinet


✓ Front and rear side with 200mm cold/hot aisle
✓ Front side with the glass door equipped with access control
✓ Rear side with double opening metal sealed metal door
✓ The in row cooling with N+1 configuration
✓ Rack mounted UPS with 2N configuration n

Confidential© 2023 Pa ge |2
IE-EPSS LLD Document

Figure 1:IE-EPSS- DC Solution

Table 1: Component of Single Row Micro Data Center Solution

1- Precision Cooling 5. Monitoring Screen


2. Power Distribution Cabinet 6. Access Control
3. UPS 7. Fire Suppression
4. IT Cabinet 8. Aisle Containment

Confidential© 2023 Pa ge |3
IE-EPSS LLD Document

Figure 2:IE-EPSS- Floor Plan Design for DC

2.2 Cabinet System


2.2.1 Rack Cabinet System

The cabinet system includes: IT; Network; Integrated cabinet and battery cabinet; all
the cabinet employs the 9-fold profile sheet metal as the frame to make sure the
loading capacity up to 1200kg for static loading. The cabinet with front glass door
and real metal door, all enclosure with IP5X protection.
The Cabinet with features as bellow:

✓ Front door with the glass door and rear door sheet metal double opening
✓ 19’’ standard installation with dimension 600*1000*2000mm
✓ Front with 400mm cold aisle and rear with 400mm hot aisle
✓ With vertical and horizontal cable organizer internally

Confidential© 2023 Pa ge |4
IE-EPSS LLD Document

✓ With PDU vertical mounting, each rack with 2x IESlim Intelligent PDU
✓ Front door with biometric Access control supporting biometric; Password
✓ With caster and earth wiring.
Table 2: Cabinet Specifications

No. Item Specifications


1 Dimension IT Cabinet:
2000mm×600mm×180mm The
cabinet frame with 1000mm width,
the front and rear are attached
with 400mm width aisle The front
door is glass door with access
control supporting biometric
2 Color RAL9005 Black
3 Material High-intensity class A carbon cold
rolled steel plate and zinc-coated
steel plate
4 Containment Front and rear
5 Installation Supporting installation on
concrete floor
6 Static loading 1200KG
7 Dynamic 1000Kg
Loading
8 Protection IP5X

Confidential© 2023 Pa ge |5
IE-EPSS LLD Document

Figure 3: IE-EPSS- rack cabinet

2.2.2 Cable Trough

The “M” Shape cable trough is for organizing the cable on the top of the cabinet; it split
the power and signal cable to realize the LV and HV cable isolation.

Figure 4:IE-EPSS- Top cable tray

Confidential© 2023 Pa ge |6
IE-EPSS LLD Document

2.2.3 Aisle Containment of Cabinet

The containment of cabinet is equipped in each cabinet for optimize the cold and hot
air circulation, with the front and rear door isolated, all the air circulation happened
inside the cabinet to increase the heat exchange rate.

Figure 5:IE-EPSS- Converged Cabinet

2.2.4 Enclosed Door and aisle

The enclosed door and the aisle seal the whole system to isolate any internal and
externally heat exchanging, all the air circulation only happened inside cabinet with
the heat insulation material.

Confidential© 2023 Pa ge |7
IE-EPSS LLD Document

Figure 6: IE-EPSS- containment System

Confidential© 2023 Pa ge |8
IE-EPSS LLD Document

3 Power Supply System

3.1 Overall Electrical Design


The Solution employs the N+1 topology in the electrical design, with the features as
bellow:

a) Dual bus structure support power method backup for the mission critical IT
load

b) Dual UPS connected with dual bus, each UPS offers the whole power
backup

c) Split power management to avoid any single-point failure

3.1.1 Power Cabinet

The Integrated Power Cabinet is used to accommodate the UPS; Cooling; DCIM
monitoring and power distribution module, which is the chief management of the
whole data center power system. In the same time to avoid the rack space
occupation of the IT cabinet. Inside it contains:

✓ 2x 20KVA Rack Mounted UPS


✓ 1 x Power Distribution panel (Rack Mounted type)
✓ 2 x Fire suppression module (Rack mounted type)
✓ 1 x DCIM System

Confidential© 2023 Pa ge |9
IE-EPSS LLD Document

Figure 7:Power Cabinet

3.1.2 Power Distribution Module

The Rack Mounted Power Distribution module is inside the integrated cabinet for the
main power input and output. The module includes the main power input; UPS
in/output; cooling input; PDU and surge protection breakers, with the RS385/SNMP
port for easy communication.

Table 3: Power Distribution Module Specifications:

No. Item Specification


1 AC Main Input Breaker 125A/3P
2 Phase 3 Phase
3 Input Frequency 50Hz/60Hz
4 Input Voltage 380V/400V/415V
5 Surge Protection CLevel:63KA/4P
6 Lighting 63A/4P
7 Manual bypass 100A/2P
8 UPS Input 100A/3P

Confidential© 2023 P a g e | 10
IE-EPSS LLD Document

9 UPS Output 100A/3P


10 PDU Group A 1-8 32A/3P
11 PDU Group B 1-8 32A/1P
12 Air conditioning 50A/3P
Breaker 1,2,3
13 DC Output 10A/1P+2×16A/1P
14 Communication RS485
15 Monitoring Item Input voltage/current/Active
Power/HD/Load Output
voltage/current/power
consumption/loading
capacity/Power factor
-40℃~70℃
16 Dimension mm 440×540×12U
W×D×H)
17 Breaker Brand SCHNEIDER

Figure 8:IE-EPSS-Power Distribution Module

3.2 UPS System


The UPS work as backup power in the whole data center system, the IEWATT UPS
3 in 3 out series cover the range of 20~50KVA, all with the rack mounted 19’’ and
modular design all UPS system are optional both for VRLA or Lithium battery.

Confidential© 2023 P a g e | 11
IE-EPSS LLD Document

Table 4: UPS Specification

No. Item Specification(±192Vdc



1 Nominated Capacity 20kVA
2 Operating frequency 40Hz-70Hz
range 380/400/415Vac,
Nominal voltage (3Ph+N+PE)
3 Operating voltage 138~485Vac
range
4 Input Power Factor ≥0.99
5 Harmonic distortion ≤3% (100%non-linear
(THDi) load )
6 Output Voltage Output Voltage
380/400/415Vac
(3Ph+N+PE)
7 Voltage regulation ±1%
8 Output Frequency 50/60*(1±0.02%)Hz
9 Crest Factor 3:1
10 Overall Efficiency 95.5%
11 THDi THDi ≤2% with linear load
≤4% with non linear
12 Communication port RS232 SNMP/RS485/dry
contact
13 Dimension(W*D*H)mm 800×440×175 (4U)
14 Weight 45 kg
15 Noise <58dB

Confidential© 2023 P a g e | 12
IE-EPSS LLD Document

Figure 9:IE-EPSS- UPS

3.2.1 20KVA for HQ distribution racks

IE proposes Eaton 93E 20kVA UPS with Internal batteries 64x9Ah. 93E delivers up to
98% efficiency.

✓ Technology: Double Conversion (Online) With internal batteries 384VDC


✓ Estimated Runtime 12/28 minutes at full/half load
✓ Scalable runtime with Extended Battery Cabinet
✓ Lower operating costs through 98% efficiency
✓ Up to 35% smaller footprint than competitive solutions
✓ Intelligent Power Manager Software
✓ Single cabinet solution reduces installation, wiring, and maintenance costs
✓ Detachable maintenance bypass options guarantee zero downtime
✓ Patented Eaton Hot Sync® technology to parallel up to 4 UPSs to increase
availability
✓ Large LCD graphically displays UPS status

Confidential© 2023 P a g e | 13
IE-EPSS LLD Document

Figure 10: IE-EPSS- 20KVA UPS

3.2.2 Distribution rack UPS

IE provides tripplite On-line double-conversion UPS pure sine wave AC output to server
and network equipment for remote site active devices deployed on each rack.

✓ Offers network-grade protection against power failures and voltage fluctuations


✓ Zero transfer time between on-line and battery modes for uninterrupted
operation
✓ Optional external battery packs provide additional runtime for applications
requiring it
✓ Add optional WEBCARDLX with latest version of PADM20 for IP-based Auto
Probe feature

ENERGY STAR-certified to save electricity, lower costs, and protect the environment

Figure 11: IE-EPSS- rack mount UPS

Confidential© 2023 P a g e | 14
IE-EPSS LLD Document

3.2.3 Intelligent PDU

The IESlim Series Intelligent PDU includes the management and metered type. With
all output outlet optional. The PDU is equipped with the digital sensor port for
environment sensor connection in each cabinet, serving as a data transferring
station. The intelligent PDU utilize the SNMP-Link platform for management.
Table 5: Intelligent PDU Electrical Specification:

No. Item 20 Outlet


1 Input Rated 32A
Current
2 Input Frequency 50Hz/60Hz
3 Input Port Cable with terminal
4 Output IEC:16×C13+4×C19
Configuration
5 Output Rated 32A
Current
6 Dimension 1830×56×47mm
7 Weight 8.23 kg

Figure 12 IE-EPSS- Intelligent PDU

3.3 Generator
The generator power system for the data center is going to be used as backup power
source and the design is done as such the capacity of the generator will be able to
support the whole data center systems and future requirement. If the utility power is
interrupted the generator power source in the other side will start up automatically
and supply power for the whole data center systems within few minutes. IE-Networks
will provide 80kva Generator.

Features:

✓ Engine(DCEC Cummins 6BT5.9-G2)


✓ 24V charge alternator

Confidential© 2023 P a g e | 15
IE-EPSS LLD Document

✓ Radiator 50℃ max, fans are driven by belt, with safety


✓ Absorber guard
✓ Alternator: single bearing Stamford or Mecca Alter alternator
✓ Dry type air filter, fuel filter, oil filter IP23, insulation class H/H )
✓ Ripple flex exhaust pipe, exhaust siphon, flange, muffler
✓ Main line circuit breaker
✓ Standard automatic control panel
✓ User manual
✓ Batteries, rack and cable
✓ Voltage: 415/230V
✓ Ampere: 230A

Figure 13: IE-EPSS- Generator

3.4 Automatic Voltage Regulator


IE proposes SMFORD AS440 AVR. The AVR provides closed loop control by sensing the
alternator output voltage at the main stator windings and adjusting the exciter stator field
strength. Voltage induced in the exciter rotor, rectified by the rotating diodes, magnetizes
the rotating main field which induces voltage in the main stator windings. A self-excited
AVR receives power from the alternator output terminals.

Confidential© 2023 P a g e | 16
IE-EPSS LLD Document

Confidential© 2023 P a g e | 17
IE-EPSS LLD Document

The bellow design is for power distribution for the data center.

Figure 14: IE-EPSS- over all power distribution diagram

Confidential© 2023 P a g e | 18
IE-EPSS LLD Document

Figure 15: UPS Schedule Diagram

Confidential© 2023 P a g e | 19
IE-EPSS LLD Document

Figure 16: Non critical Schedule Diagram

Confidential© 2023 P a g e | 20
IE-EPSS LLD Document

Figure 17 Power distribution panel Schedule Diagram

Confidential© 2023 P a g e | 21
IE-EPSS LLD Document

Figure 18Power distribution for each rack

Confidential© 2023 P a g e | 22
IE-EPSS LLD Document

4 Cooling System

4.1 Precision Cooling


The IECool Series Precision cooling is specially designed for the micro data center
solution, proper for single or multiple rack solutions, targeting the local hot spot.
Among of them, the rack mounted type with wide range from 7.5~40KW.

Figure 19: IE- EPSS- Precision AC

Confidential© 2023 P a g e | 23
IE-EPSS LLD Document

4.2 Floor Stand Air Conditioner


IE Networks proposes Midea split type Floor stand Air conditioning which is
used to control the temperature of the power room. Unless the heat is removed,
the ambient temperature will rise, resulting in electronic equipment malfunction.
By controlling the air temperature, the computing equipment’s, at the board level
are kept within the manufacturer's specified temperature/humidity range. Air
conditioning systems help to control humidity by cooling the return space air
below to the dew point. 24,000BTU/Hrs. Split-type Floor Stand AC including
Indoor & Outdoor Units.

Figure 20:IE-EPSS- floor stand AC

Confidential© 2023 P a g e | 24
IE-EPSS LLD Document

Figure 21: AC Layout

Table 6: Technical Specification 25 KW In row Cooling

Indoor Unit IECool-25RA


Total Cooling-kW 25.1
SHR-% 100
Air Volume-m3/h 5000
Mount Type Row
Cooling Type DX
Height-mm 2000(42U)
Depth-mm 1100
Width-mm 300
Weight-kg 260

Confidential© 2023 P a g e | 25
IE-EPSS LLD Document

Reheat-kW 6.0
Outdoor Unit IEFS38AN
Height-mm 695
Depth-mm 990
Width-mm 1407
Leg Height-mm 450
Weight-kg 120
Power Input1) 380V/50-60Hz /3Ph

Key Features

✓ Designed for rack mount, row mount, wall mount or top mount to be
seamlessly integrated into server racks. Customizable to match closed aisle
or open aisle modular data center solution.
✓ Standard monitoring port to be integrated into higher level DCIM system
easily.
✓ Front door and structure customizable to be built into MDC to keep uniform
design style.
✓ Reliability
✓ Developed by professional precision cooling team following proven R&D process
and industry standards.
✓ Designed with recognized components and thorough testing to enhance
reliability level.
✓ Full protection and alarm control system for quick diagnose and reactivate the
unit.
✓ Green & Efficient
✓ Cooling capacity and air flow automatically modulated to match the dynamic
IT output.
✓ Dedicated cooling close to IT heating source saves more than 30% energy
comparing to traditional room cooling solution.
✓ Serviceability
✓ Unit level and components level modularity supports quick replacement and
reduce MTTR.
✓ Swappable fans allow system to remain operational if a replacement is required.
Easy electric box service operation with the slide-out design.

Confidential© 2023 P a g e | 26
IE-EPSS LLD Document

✓ Easy to change G4 air filter guarantees the cleanliness of MDC.


✓ Quick installation with coupled piping connection.

Confidential© 2023 P a g e | 27
IE-EPSS LLD Document

5 DCIM

IE Smart DCIM System is the masterpiece of IEWATT software platform, which is


specially designed for the modular data center scenarios both in hardware and
software. The slim dimension with high function inside make it could take “0” in-rack
space and offers the Comprehensive monitoring and management function in the
same time. I Smart DCIM Hub is a monitoring hub with smart size and versatile
function, the appearance is very tiny make it free to be installed behind power
distribution module to avoid any additional “U” space occupation. Perfect solution
for the spac-tight condition in edge data center.

Figure 22 IE-EPSS- DCIM System

Confidential© 2023 P a g e | 28
IE-EPSS LLD Document

5.1 IE Smart DCIM System Software and Interface.


IE Smart DCIM system is integrated with SNMP-Link platform to manage the
infrastructure in the LAN. Not only the SNMP protocol are available for access
and management, also the RS485

and CANBUS are all connectable. Flexible in expansion. The remote access
are also available via the network in client.

Monitoring and Management


✓ Devices status and parameters, User setting parameters, Web site
information access
✓ All-around alarm information interface, supporting email and Message
✓ Precise energy consumption management
✓ Optional real-time onsite video surveillance
✓ Wifi access support the mobile devices visiting

Figure 23 IE-EPSS- DCIM Screen

5.2 Environment Sensors


The Environment sensors are widely spread in each cabinet to do the real-time detection
of the environment status, including temperature, humidity; smoke ; water leakage and
door status

Confidential© 2023 P a g e | 29
IE-EPSS LLD Document

Figure 24 Environment Sensors

5.3 IE Guard Access Control


IEGuard Access control is a kind of high protection smart locker for the privacy like data
center and some classified area, with the metal cover and high protection IP degree, it
has the intelligent control and management via the internal smart controller.

Confidential© 2023 P a g e | 30
IE-EPSS LLD Document

Key Features:

✓ IP55 Protection degree


✓ Less than 1.5 second finger recognition.
✓ Standalone mode complete setup and programmable for the user adding and
delete
✓ Full metal covers more robust
✓ Audio-visual indication for acceptance.
✓ Relay outputs for electric lock and alarm.

Figure 25IE-EPSS-proposed Access Control

Confidential© 2023 P a g e | 31
IE-EPSS LLD Document

6 Firefighting System

The rack mount fire extinguisher is design to protect critical electrical IT


components within the cabinets. Built in with the FM200 gas, releasing valves,
activation sensors and controllers, the compact system is ideal for the micro
modular data center applications.

• Pertinence: Covering internal cabinet area to protect the devices


• Rapid Action: Non-pipe design; transient eruption to cover whole cabinet
• Rack Mounted: Easy replacement in 19’’ cabinet
• Network connect: Each module with communication port for real-time management

Figure 26 IE-EPSS- Rack mounted fire suppression

Table 7 Fire suppression Specifications

Confidential© 2023 P a g e | 32
IE-EPSS LLD Document

7 Bill of Materials (BoM)

SI-IE-EPSS-ITF-BOQ
No Uo Qt
Item Type Feature
. M y.

ITF DCI Item


1 Head Quarter(HQ)
1. lu
Main Data Center 1
1 m
1.1
.1 Cabinet and Aisle Containment
Standards 42U cabinet 600mm*1000 mm
dimension with 200mm cold & 200 mm
hotasile containment
With vertical and horizontal cable manager
2x fixed shelf with 100kg weight
Front glass door for complete 42U height
visibility & Rear Split Steel door,The Front
Rack and Containment system Rack doors provided with Biometric Access Set 4
Control with 02 nos. of Electromagnetic lock
per door
Each Rack with LED light for status display
Aisle containment system casement to create
micro data center aisle containment.Thermally
insulated cold aisle chamber,The front with
400mm
1.1
.2 Power Distribution Panel
Rack Mounted Power Distribution Panel inside
the electrical Cabinet
125A Main Input capacity, with essential
MCCB including UPS in/output; cooling
Power Distribution Panel(inside
MCCB; PDU MCCB; Surge protection
the power cabinet) Set 1
MCCB; Manual Bypass MCCB
With the surge protection and intelligent
sampling module inside for detect the
electrical status
RS485 communication with the DCIM system
1.1
.3 UPS and Battery
20KVA/20KW Rack Mounted UPS; Double
conversion and IGBT technology: Full IGBT
20KW UPS(inside the power Rectifier /Battery Charger and IGBT based
Set 2
cabinet) Inverter
Rack Mounted 3U Height; N+N connection
topology

Confidential© 2023 P a g e | 33
IE-EPSS LLD Document

Nominal output voltage: 380/400/415V (3-


phase with Neutral);Nominal output
frequency: 50 Hz
Battery: 40 pcs 24AH/12V battery for 15mins
backup time at full load for each UPS
Communication & monitoring software:
usb/intelligent slot (dry contact card/ modbus
card/ rs 485 card)
1.1
.4 PDU
PDU; Inteligent function with sensor ports in
each one; the outlets include 20 pcs C13+4 pcs
Intelligent PDU Pcs 8
C 19; With meter for all the electrical status
and LCD display; each IT cabinet with2
1.1
.5 Air Conditioner
25KW precision cooling Inrow Type;DX
(Variable) type in N+1 Topology
With Inbuilt Heater and Humidifier to cater IT
load to 25KW
Inverted type Compressor equipped with pre-
set high- and low-pressure switches for
protection against high condensing and low
Air Conditioner evaporating temperatures Pcs 2
Direct Drive FAN, High efficiency, external
rotor electronically commutated (EC) motor
with integrated electronics
With microprocessor-based controller. It can
be programmed to control the function of
every device within the unit via I/O
With the outdoor units matched to the cooling
capacity
1.1
.6 Environment and Power Monitoring system(DCIM)
The EMI system including the monitoring
console and the environment sensors, the
DCIM console based on network SNMP
communication portal, supporting local and
remote access ;with 10-inch-wide touch screen
HMI display with a very user-friendly
· Smoke sensor x 5
EMI and DCIM · Temperature sensor x 5 Set 1
· Humidity sensor x 5
· Water leak sensor x 2
Software system with following
· Local Web based access
· Remote access via the network
· Mobile App access
1.1
.7 Fire detection and Suppression System

Confidential© 2023 P a g e | 34
IE-EPSS LLD Document

1U, can be filled with 3kg fire extinguishing


Fire detection systems agent (FM200), glass ball trigger, suitable for Pcs 8
1~2 cabinets
1.1
.8 CCTV camera
High quality imaging with 4 MP resolution
Clear imaging against strong backlight due to
120 dB WDR technology
DS-2CD2143G2-I(2.8mm)(O- Efficient H.265+ compression technology
Pcs 1
STD) Water and dust resistant (IP67) and vandal
resistant (IK10)
Focus on human and vehicle targets
classification based on deep learning
1.
Rack Cabinet
2
42U 800x1000mm 19" INORAX-ST SERIES
Pcs 1
CSS-X-4280A SERVER CABINET
LOW NOISE ROOF FAN TRAY for Floor
Standing Cabinet with 4 fans-for Inorax-ST Pcs 1
CSA-X-2002 series
19" 1U HEAVY DUTY FIXED SHELF Pcs 2
CCA-X-1010 d=800mm (for 1000 mm depth cabinets)
CCA-0-7017 EARTHING KIT 300mm Pcs 1
Vertical, Basic Pdu, 6xIEC C13 Sockets, With
Circuit Breaker, 16A, 3x1,5mm² 2,5m Cable, Pcs 2
PB-C06-010-116-1A2PE With IEC 60309 Commando Plug
15U 600X650mm DOUBLE SECTION
Pcs 16
WS3D-X-156HA WALLMOUNT CABINET
1.4 UPS
"Eaton 93E 20kVA UPS; With backfeed
93E20KMBSBI protection;u Pcs 1
MBS; Internal batteries 64x9Ah"
Warranty For 3 years Pcs 1
1.5 Generator
1ESP: 90KVA/72KW; PRP: 80KVA/64KW
Cummins 4BTA3.9-G11 with Stamford
UCI224G Silent type, 3
TC90T Pcs 1
phase 4 wires, 50Hz, 415/240V, genset comes
with Chint breaker, battery, charger, DSE7320
controller and silencer.
1.
AVR
6

Confidential© 2023 P a g e | 35
IE-EPSS LLD Document

Sensing Input:
Voltage: 100 VAC to 130 VAC 1 phase or 190
VAC to 264 VAC 1 phase1
Frequency: 50 Hz to 60 Hz nominal Power
Input:
Voltage: 100 VAC to 264 VAC 1 phase only
Frequency: 50 Hz to 60 Hz nominal
UC1224G Pcs 1
Power Output
Voltage: maximum 82 VDC at 200 VAC input
Current :continuous 4 A2 ,transient 7.5 A for
10 seconds
Resistance: 15 Ω minimum (10 Ω minimum
when power input less than 175 VAC)
Regulation:+/- 1.0% RMS3

Accessories
1 Power requirments

40x40cm wall mount


MCCB - 175A
Power distribution Board 1 MCB - 2 x 63A 3ph Pcs 1
MCB - 2 x 32A 3ph
MCB - 2 x 16A 1ph
MCB - 2 x 10A 1ph
25
Cable
Power cable 3 x 2.5mm m 0
13
Cable
Power cable 3 x 6 mm m 0
2 AC
7KW precision cooling system
AC Pcs 1
Floorstand

Confidential© 2023 P a g e | 36
IE-EPSS LLD Document

8 Document Acceptance Certificate

Name Name

Title Title

Company Company

Signature Signature

Date Date

Name Name

Title Title

Company Company

Signature Signature

Date Date

Name Name

Title Title

Company Company

Signature Signature

Date Date