Table 4d3a and 4d3b
Ambient temperature: 30 °C
CURRENT-CARRYING CAPACITY (amperes): Conductor operating temperature: 70 °C
Single-core armoured Conductor cross- 2 cables, Reference Methods C & F (clipped direct, on tray or free air)
70°C thermoplastic sectional area DC 2 cables, single-phase AC 3 or 4 cables, three-phase AC
insulated cables (non-
touching spaced* trefoil and touching flat and touching flat and spaced*
magnetic armour)
(COPPER 1 2 3 4 5 6 7
CONDUCTORS) (mm2) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m)
R X Z R X Z R X Z R X Z R X Z
Reproduced from
BS7671:2018 Wiring 50 0.93 0.93 0.22 0.95 0.92 0.30 0.97 0.80 0.190 0.82 0.79 0.26 0.84 0.79 0.34 0.86
Regulations 70 0.63 0.64 0.21 0.68 0.66 0.29 0.72 0.56 0.180 0.58 0.57 0.25 0.62 0.59 0.32 0.68
95 0.46 0.48 0.20 0.52 0.51 0.28 0.58 0.42 0.175 0.45 0.44 0.25 0.50 0.47 0.31 0.57
120 0.36 0.39 0.195 0.43 0.42 0.28 0.50 0.33 0.170 0.37 0.36 0.24 0.43 0.40 0.30 0.50
150 0.29 0.31 0.190 0.37 0.34 0.27 0.44 0.27 0.165 0.32 0.30 0.24 0.38 0.34 0.30 0.45
185 0.23 0.26 0.190 0.32 0.29 0.27 0.39 0.22 0.160 0.27 0.25 0.23 0.34 0.29 0.29 0.41
240 0.180 0.20 0.180 0.27 0.23 0.26 0.35 0.175 0.160 0.23 0.20 0.23 0.30 0.24 0.28 0.37
300 0.145 0.160 0.180 0.24 0.190 0.26 0.32 0.140 0.155 0.21 0.165 0.22 0.28 0.20 0.28 0.34
400 0.105 0.140 0.175 0.22 0.180 0.24 0.30 0.120 0.130 0.195 0.160 0.21 0.26 0.21 0.25 0.32
500 0.086 0.120 0.170 0.21 0.165 0.23 0.29 0.105 0.145 0.180 0.145 0.20 0.25 0.190 0.24 0.30
630 0.068 0.105 0.165 0.195 0.150 0.22 0.27 0.091 0.145 0.170 0.135 0.195 0.23 0.175 0.22 0.28
800 0.053 0.095 0.160 0.185 0.145 0.21 0.25 0.082 0.140 0.160 0.125 0.180 0.22 0.170 0.195 0.26
1000 0.042 0.091 0.155 0.180 0.140 0.190 0.24 0.079 0.135 0.155 0.125 0.165 0.21 0.165 0.170 0.24