INCOMING 34.

5kV
LINE FROM MERALCO

MAIN DISTRIBUTION
MDP-1 460V, 3Ø = 98.6A = 62.85kW
FUSE CUTOUT 35kV LA MDP-2
8.0 AWG / 600V IPRI 460V, 3Ø = 128.69A = 82.02kW
THHN COPPER WIRE, ISEC 230V, 3Ø = 257.39A
STRANDED (PER PHASE) POLE MOUNTED DISTRIBUTION TRANSFORMER MDP-3 460V, 3Ø
3-167kVA, 34.5kV, 200kV BIL, 5 TAPS MDP-SHOP IPRI 460V, 3Ø = 90.71A = 61.43kW
MAIN TR 460V, 3Ø, ISEC 230V, 3Ø = 157.22A
HV BUSHING = 1, LV BUSHING = 4
460V, 30kV BIL 100AT, ITCB DCY 460V, 3Ø = 403.61A = 273.33kW
Ipri = 8.38A NEMA 3R TOTAL CURRENT = 721.61A
Isec = 628.81A TOTAL POWER = 479.63kW
CT AS kVA = (479.63kW / 0.8) / 3 = 599.53kVA = 3 x 333kVA
0.6kV 50 / 51 Kwh Wh PF A
25kA / 1 SEC 100AT
800 / 5A 5IN TOTAL CURRENT = 753.07A
2PT MAIN,
15VA, 60Hz 3Ø, ITCB SIZE OF CONDUCTOR = (753.07A + 49.2A(1.25)) = 814.57A
VT USE = 2 x 500MCM, 600V THHN COPPER WIRE
2 x 500MCM, 600V SIZE OF CIRCUIT BREAKER = 753.07A + 100%(99) = 852.07A = 850AT
THHN COPPER WIRE, STRANDED 0.6kV
(PER PHASE) 600V/120V 38mm² 75AT, 3Ø, 50AT, 3Ø,
50VA, 60Hz ITCB ITCB
MERALCO
ISOLATION 800AT, 3Ø,
BREAKER ITCB
SPARE SPARE

NOTE:
MAIN DISTRIBUTION
LOW VOLTAGE SWITCHGEAR 1250AF, SET THE MAIN BREAKER SETTINGS PROTECTION FROM 1250AT TO
460V, 3Ø NEMA 3R 3Ø, ACB 850AT IN CASE OF ADDITIONAL LOAD FOR THE FUTURE. CHECK THE
CT AS MAIN CIRCUIT BREAKER CAPACITY, THEN CHANGE THE PROTECTION
0.6kV 50 / 51 Kwh Wh PF A SETTINGS.
25kA / 1 SEC
1200 / 5A 5IN 2PT
15VA, 60Hz
VT
0.6kV
600V/120V
50VA, 60Hz

250MCM, 600V 800AT, 3Ø, 800AT, 3Ø, 600AT, 3Ø


THHN COPPER ITCB ITCB ITCB
WIRE, STRANDED
(PER PHASE)

MDP-3
2 x 350MCM / 600V 460V, 3Ø,
THHN COPPER 600AT, 3Ø
250kVA, 600AT, ITCB
WIRE, STRANDED ITCB
DRY-TYPE NEMA 3R
(PER PHASE)
440V/220V 2 x 250MCM / 600V
TR-B STEP-DOWN THHN COPPER
3Ø, 60Hz,4.9% Z WIRE, STRANDED
Ipri = 328.04A (PER PHASE) 250AT, 3Ø 75AT, 3Ø 75AT, 3Ø 80AT, 3Ø 250AT, 3Ø 25AT, 3Ø 20AT, 3Ø 30AT, 3Ø
Isec = 627.55A ITCB ITCB ITCB ITCB ITCB ITCB ITCB ITCB

M.I. 50mm² 3.5mm² 3.5mm²


600AT, 3Ø 600AT, 3Ø
ITCB ITCB 1x50kVA,
2 x 350MCM / 600V OIL-TYPE
MDP-2 & 4
400AT, 3Ø THHN COPPER 460V/230V
460V, 3Ø, WIRE, STRANDED
ITCB TR-C STEP-DOWN SPARE SPARE SPARE SPARE
(PER PHASE) PC5(VFD) MONORAIL
3Ø, 60Hz,4.9% Z LOWERATOR
3/0 AWG, THHN CU, 600V CRANE
Ipri = 62.76A ACTUAL LOAD :
Isec = 125.51A ACTUAL LOAD 5.5A
500AT, 3Ø : 6.6A
MDP-1 ITCB
460V, 3Ø, 250AT MAIN,
250AT, 3Ø 175AT, 3Ø 175AT MAIN, 2 x 250MCM / 600V
250AT, ITCB 3Ø, ITCB
ITCB ITCB 3Ø, ITCB THHN COPPER
NEMA 3R
WIRE, STRANDED
G (PER PHASE) 125AT MAIN, 75AT MAIN,
PRECUT 5 PRECUT 3 ~ 3Ø, ITCB 3Ø, ITCB NOTE:
DIESEL GENERATOR 2-14mm² 2-22mm²
125AT, 3Ø 125AT, 3Ø 75AT, 3Ø 50AT, 3Ø 50AT, 3Ø 50AT, 3Ø ACTUAL LOAD ACTUAL LOAD 250kW, 0.8pf, 60Hz, + 1-8.0mm² + 1-8.0mm² ALL 1Ø, 230V LOADS MUST BE
ITCB ITCB ITCB ITCB ITCB ITCB : 58.4A : 30A 125AT, 3Ø 125AT, 3Ø 32AT, 3Ø 480V, 375.88 FLA THHN CU THHN CU BALANCE IN 3Ø, 230V POWER SUPPLY.
ITCB ITCB ITCB

LP-A LIGHTING LP-B LIGHTING


38mm² 38mm² 14mm²
PANEL (MACHINE) PANEL (OFFICE)
38mm² 38mm² 62.68A 94.54A
NEMA 3R NEMA 3R
SPARE QF3 SPARE SPARE SPARE
AIR COMPRESSOR W/ DRYER 2 AIR COMPRESSOR W/ DRYER 2 1000AT, 3Ø
ACTUAL LOAD : CHARGING MOBILE
3.6A 20HP, 54FLA 20HP, 54FLA ITCB
BATTERY INVERTER 1: 10KVA
BATTERY INVERTER 2: 8KVA 2 x 175mm²
BATTERY INVERTER 3: 5.04KW

500kVA, DRY-TYPE
460V/440V MULTI-TAP
3Ø, 60Hz
ISOLATION TRANSFORMER
125AT, 3Ø 125AT, 3Ø 100AT, 3Ø 50AT, 3Ø 40AT, 3Ø 25AT, 3Ø
ITCB ITCB ITCB ITCB ITCB ITCB

2 x 175mm²

2 x 175mm² 175mm²
IF2 IF3 Autopack Logsaw Autotransfer SPARE
& 125AT, 3Ø 800AT, 3Ø 150AT, 3Ø 40AT, 3Ø 500AT, 3Ø
ACTUAL LOAD : ACTUAL LOAD : ACTUAL LOAD : ITCB ITCB ITCB ITCB ITCB
44.6A 30A Conveyor 5A
ACTUAL LOAD :
6A
60mm²
JRT ACCU. REWINDER JRT LOGSAW BT ACCU.
BT/KT LOGSAW

125AT, 3Ø 200AT, 3Ø
ITCB ITCB

250AT, 3Ø
ITCB

CORE MAKER

250kVA, DRY-TYPE
440V/370V MULTI-TAP
3Ø, 60Hz
ISOLATION TRANSFORMER

250AT, 3Ø
ITCB

TO DCY
SIMOTION
(DC BUS)