You are on page 1of 9

Building and Environment 150 (2019) 99–107

Contents lists available at ScienceDirect

Building and Environment


journal homepage: www.elsevier.com/locate/buildenv

Measurement of residential HVAC system runtime T


a a a,b,∗
Tianyuan Li , Masih Alavy , Jeffrey A. Siegel
a
Department of Civil and Mineral Engineering, University of Toronto, Toronto, ON, Canada
b
Dalla Lana School of Public Health, University of Toronto, Toronto, ON, Canada

A R T I C LE I N FO A B S T R A C T

Keywords: Recirculating central forced-air heating, ventilation, and air conditioning (HVAC) systems are common in re-
HVAC operation sidential buildings in North America. Runtime, the fraction of time any part of the HVAC system operates, is an
Supply temperature important parameter to evaluate system performance and its impact on building energy use and indoor air
Conditioning mode quality. Different methods have been developed to assess runtime. In this paper, we evaluate the strengths and
Fan-only mode
limitations of existing direct and indirect approaches to access runtime. Using data collected from one study in
System sequencing
Toronto, Ontario and one in Austin, Texas, we improved the algorithm of an indirect method by Thornburg et al.
(2004) which calculates conditioning runtime based on the air temperature in the supply duct. We applied the
improved algorithm to two additional studies in Toronto and compared runtime results from this temperature
method with other direct methods. The results show that the algorithm is reliable with a small annual under-
estimation (1.5–2.5% absolute difference). We also found that runtime varies considerably among similar homes
with the same ambient conditions, thus it is not reliable to use outdoor temperatures to predict runtime. A
further analysis on the real-time temperature and motor signals shows that the accuracy of the algorithm is
influenced by system sequencing (i.e. fan and conditioning unit starting and/or stopping not being coincident in
time) and fan-only operation. Overall, this work illustrates the importance to measure runtime due to its large
variation and that the temperature method is a reliable approach to access runtime in appropriate homes.

1. Introduction that the moisture removal capacity of the cooling coil is influenced by
both cycle length and sequence. Furthermore, when compared to the
Central forced-air heating, ventilation, and air conditioning (HVAC) age of the system, runtime is a better indicator of the wear of the system
systems are the most common types of conditioning systems in re- as it indicates the actual amount of time the system was in operation.
sidential buildings in North America [1,2]. Runtime, the fraction of Unlike many commercial systems that operate continuously for
time the HVAC system operates, is an important parameter for HVAC ventilation purposes, most residential forced-air systems in North
system performance evaluation from various perspectives, including America have varying runtimes because the system cycles on and off to
energy use, filtration performance, latent heat capacity, and main- meet conditioning demands. Variations in runtime of residential sys-
tenance. In North American homes, the energy used by the HVAC tems originate from several factors. Although runtime is not necessarily
system accounts for a large portion of the total energy consumption, a function of climate, it is often influenced by climate and house lo-
[1,2]. As such, knowledge of runtime is essential to understand changes cation. Homes in more extreme climates are likely to have larger con-
in system energy use over time. Runtime is also important from an ditioning systems if sized properly and these larger systems will have
indoor air quality perspective in residences. High efficiency filters are shorter runtimes when ambient temperatures are milder when com-
increasingly utilized in HVAC systems in residential buildings to protect pared to design conditions. Even in similar homes in the same location,
the equipment from fouling and the occupants from partculate matter runtimes can be different because of user preferences (e.g. indoor
exposure [3]. Runtime is essential to calculate the volumetric flow rate temperature set point, window use, use of cooling systems, and use of
of air passing through the filter and to predict particle loading on the fan-only operation without the conditioning unit). In addition, because
filter [4], both of which are important for filtration performance ana- there is very little standardization of residential system design and in-
lyses. In addition, runtime measurements are required to determine the stallation, the flow rate, conditioning unit sizing relative to the load,
cycle length of each conditioning cycle and system sequencing of the motor type, and fan capacity can vary from one similar residence to
conditioning and fan unit operation. Shirey and Henderson [5] found another, resulting in different runtimes.


Corresponding author. Department of Civil and Mineral Engineering, 35 St. George St, Toronto, ON, M5S 1A4, Canada.
E-mail address: jeffrey.siegel@utoronto.ca (J.A. Siegel).

https://doi.org/10.1016/j.buildenv.2019.01.004
Received 20 August 2018; Received in revised form 4 January 2019; Accepted 5 January 2019
Available online 07 January 2019
0360-1323/ © 2019 Elsevier Ltd. All rights reserved.
T. Li et al. Building and Environment 150 (2019) 99–107

Given the diversity of runtimes within an individual home over time Table 1
and between different homes at the same time, several methods are Summary of direct approaches to measure system runtime.
used to measure runtime. These methods can be divided into two # Measurement Parameter Approximate Cost (USD $) Reference
general categories: direct approaches and indirect approaches. While
both categories of methods have been used to assess runtime, the results 1 Motor magnetic field 100–180 [7]
2 Pressure 300–500 –
are conceptually different [6]. The direct approaches use signals that
3 Current or power 100–300 [8,10]
are retrieved directly from the system, and thus they can determine the 4 Modified current or powera 200–600 [9,13]
fan runtime, the fraction of time the fan operates. Some examples in- 5 Smart thermostat records 200–300 [11]
clude using a motor sensor to detect the magnetic field from the fan
a
motor [7], and deploying a current or power transducer on the elec- The modified method uses current or power transducers on both the fan
trical circuit of the fan and sometimes the heating, or cooling unit and on the compressor.
[8,9,10]. Although not truly a direct method, Touchie and Siegel [11]
utilized smart thermostats to assess runtime based on the call for runtime in light commercial or residential buildings. Table 1 sum-
heating, cooling, or fan-only operation. The indirect approaches use an marizes five commonly used methods with the typical costs of the
algorithm to process change in air temperature to calculate con- sensors (labor and training costs are not considered) and example re-
ditioning runtime, the fraction of time the conditioning is operational ferences. The cost estimation is based on sensors which can be used for
(e.g. Ref. [12]). Each of these methods have been previously used to runtime assessment that are available on the US market. As these
assess HVAC runtimes; however, there has been no evaluation on the methods track electrical or pressure signals created by the fan, all of
strengths and limitations of each approach. In addition, most runtime them monitor the fan operating periods, independent of the status of
data are either collected for a relatively short period or have insufficient the conditioning unit. However, because of the difference in measure-
metadata to discern fundamental factors that influence runtime. Fur- ment parameter and the type of sensor used, they have strengths and
thermore, runtime studies in the literature are mainly focused on re- limitations in different areas. Although not truly a direct method, the
latively new homes in the southwestern US in the cooling dominated smart thermostat method is included in summary because it does not
climates (e.g. [8,9,12]). Therefore, there are still gaps in our knowledge require data processing and it has some limitations that are similar to
on both the fan and conditioning runtimes in residences in different the other direct approaches.
climates. The first method utilizes motor sensors, which detect the magnetic
To fill these knowledge gaps, we first address some of the com- field generated from the fan motor during operation. This is the most
plexities associated with residential HVAC systems, and evaluate the definitive method for fan runtime as it records the fan status change
previous approaches to measure runtime. Then, we present an algo- directly. Unlike the other direct methods, this method is not able to
rithm, improved from Ref. [12], for an indirect method to calculate distinguish between heating and cooling modes nor can it differentiate
runtime based on the change in air temperature in the supply register. the fan speed as it only records the time when the fan changes operating
This algorithm offers an opportunity to assess runtime with a simpler status. As motor sensors are specifically designed to detect an alter-
measurement than conventional direct approaches. We further develop nating current magnetic field from fans with permeant split capacitor
the improved algorithm based on direct measurements from in- (PSC) motors, it generally cannot be used on fans with electronically
vestigations in heating-dominated (Toronto, Ontario) and cooling- commutated motors (ECM) that are powered by direct current. In ad-
dominated (Austin, Texas) climates. Runtimes from the improved al- dition, to detect the magnetic field, this sensor has to be placed at a
gorithm are used to explore the temporal variation and the home-spe- specific location on the motor housing, which can be different for every
cificity of runtime measurements. The overall objective of this paper is motor and makes installation challenging in some systems. The second
to provide insights on residential runtimes and to provide a robust and method uses a static pressure measurement in the distribution system to
convenient tool for runtime assessments in future studies. determine the operational status of the fan. As the pressure sensor is not
directly measuring from the motor, it is more flexible in sampling lo-
2. Background cation compared to motor sensors. Unlike the motor sensor, this ap-
proach could differentiate the operating modes based on the pressure
Most North American homes have forced-air recirculating HVAC difference if the fan speed is set to be different in each mode. The third
systems without integrated mechanical ventilation. Conditioning run- approach connects a current or power transducer on one of the fan
times are influenced by the temperature set on the thermostat. Most wires. Similar to the pressure method, this approach is also able to
thermostats also allow the occupants to set the system in fan-only distinguish between operating modes based on the magnitude of cur-
mode, to improve mixing, provide ventilation in systems equipped with rent or power draw. However, proper training and adequate knowledge
an outdoor air intake, or maximize the amount of air that goes through of the fan is required to install the sensor. In addition, access to the fan
the filter. Depending on the configuration of the system, the fan speed wires may not be always available. A modification of this approach uses
can vary under different operation modes. Fan speed is typically set to current or power transducers on both the fan and compressor. As a
accommodate the size of the conditioning unit. In a cooling dominated result, it can differentiate cooling from heating/fan-only operation even
climate, the cooling fan speed is usually set to be higher than the the fan speed is the same for all operation modes. The last approach
heating and the fan-only speeds to account for the larger size of the retrieves system operating information directly from a smart thermo-
cooling equipment. The opposite is true for a heating dominated cli- stat. It is considered to be the most convenient method to assess run-
mate. In addition, systems that are equipped with multi-stage furnaces time; however, smart thermostats are not yet widely used, and even
or compressors have different fan speeds associated with each stage. when they are available, the occupants do not always have access to
Thus, in addition to runtime, it is essential to differentiate between the runtime information because only some thermostat companies share
operating modes if air flow rate or velocity is needed. A further com- data with the homeowner. Moreover, as the smart thermostat is mea-
plication is that different HVAC manufacturers and installers use dif- suring the call for heating, cooling, or fan-only operation; the actual
ferent conventions when controlling the sequencing between the fan system runtime may differ depending on fan and conditioning se-
and conditioning equipment (e.g., turning on the fan after the heat quencing and stage settings on the furnace. This difference may affect
exchanger has been warmed at the beginning of a cycle). Depending on the results of transient analyses and is explored in more details in the
the sequencing, conditioning runtime may be different from fan run- Discussion section.
time [6]. For most of the direct methods, the biggest challenge is the re-
Previous studies have used different direct approaches to determine quirement of system access and operator training to handle a wide

100
T. Li et al. Building and Environment 150 (2019) 99–107

variety of HVAC systems in residential buildings. To overcome this recorded the air temperature every minute. The collected data are used
challenge, Thornburg et al. [12] introduced an indirect approach, the to explore the impact of sampling locations on runtime calculation.
temperature method, to calculate runtime based on air temperature in Similar to the temperature method of Thornburg et al. [12], our
the supply register. As this approach uses a continuous measurement of improved algorithm, also uses the temperature change to identify the
air temperature by a temperature sensor, access to the AHU is no longer potential conditioning operation periods. However, instead of sub-
required. By examining positive and negative temperature changes, it jective determination, our algorithm distinguishes operating modes
can distinguish between heating and cooling modes, but it cannot based on the rate of change in temperature at each point. The daily
capture fan-only operation as there is generally not enough of a tem- maximum and minimum temperatures in the duct and the outdoor
perature change. This method requires subjective determination to temperature (obtained from a nearby weather station) are also con-
process the temperature signals into runtimes. The algorithm used by sidered in the algorithm to determine operating modes. The algorithm
Thornburg et al. [12] identified potential heating or cooling operation was developed to identify the conditioning cycles based on the sa-
periods based on the magnitude of temperature changes and these tisfaction of three fundamental criteria. First, the rate of change in
potential periods were summarized into hourly runtime averages. The temperature (i.e. the slope) must be greater than a certain threshold
hourly averages were then reviewed by trained personnel to determine consecutively for a certain period of time. Second, the daily maximum
the operation mode based on the outdoor temperature. Because this temperature in the duct must be higher than the maximum outdoor
determination process is subjective, Thornburg et al. [12] acknowl- temperature for heating, and the daily minimum duct temperature must
edged that different technicians may have different interpretations from be lower than the minimum outdoor temperature for cooling. Third,
the same set of data. Therefore, there is a need for a robust algorithm conditioning in the opposite direction cannot happen immediately after
which calculates runtime from a temperature signal in an automated the previous cycle. The first two criteria ensure that only the tem-
process, without manual interventions, to improve the processing speed perature changes caused by system operation are considered by the
of this method, as well as the consistency of the results. algorithm as other factors (e.g. solar radiation, buoyancy driven air-
flow, etc.) can also lead to change in air temperature in the duct. The
third criterion avoids falsely identifying periods at the end of the con-
3. Methodology ditioning cycle due to rapid change in temperature in the opposite di-
rection from conditioning. During the calibration process, three addi-
The development and calibration of the improved temperature al- tional criteria were added to the algorithm to minimize the influence of
gorithm utilized runtime data collected from households from the four variations in system design, large diurnal change in outdoor tempera-
studies. Three of the studies were conducted in a heating dominated ture, and heating and cooling operation on the same day. Once the
climate and one study was in a cooling dominated climate. Table 2 thresholds and criteria were finalized, we applied the algorithm to all
summarizes the name, sample size (# of homes), measurement para- studies listed in Table 2 to calculate runtime. The calibration process is
meters, and purposes of each of the study. In Toronto_A, three homes explained in more details in the following paragraphs.
were monitored for approximately one month in a typical heating The algorithm was first calibrated based on the temperature and
season. Runtime data were collected continuously for 10 months in motor sensor data collected from Toronto_B in an iterative process
Toronto_B (two homes) and for one year in Toronto_Filtration (21 which involves two stages of calibration. First, we compared the daily
homes). In Austin_Asthma, each home was monitored for approxi- runtimes calculated by the improved temperature algorithm to the daily
mately two months in total, one in each of a typical heating and cooling runtimes from the motor signals numerically. The thresholds in the first
season, although the peculiarities of climate in central Texas meant that fundamental criterion were adjusted to minimize the absolute daily
both heating and cooling operation are common in the “heating” runtime difference between the two methods. Through this iterative
season. Of all 84 monitored households, 81 are single-family homes, calibration process, the thresholds for the first fundamental criterion
and 3 are suites in high-rise condominiums. All the homes utilized a were finalized (0.3 °C/min for heating and −0.03 °C/min for cooling)
centralized forced-air HVAC system with heating and cooling units and for at least 5 min consecutively to avoid falsely identifying heating/
the occupants can control the system through thermostats. In all stu- cooling cycles due to sensor uncertainties. We selected 5 min as the
dies, at least one temperature data logger (Onset U12-012, U12-013, or minimum period of time as a typical heating/cooling cycle ranges from
UX100-001) was placed just inside or outside of a supply register. These 5 to 20 min. However, even if the difference is minimized numerically,
data loggers measured and recorded the temperature every minute it does not guarantee that the conditioning cycles were correctly
continuously for the entire study duration. In Toronto_A, Toronto_B, identified. To ensure correct identification of conditioning cycles, we
and Toronto_Filtration, one or multiple direct methods, which were conducted a visual calibration which compares the algorithm and
discussed in the previous section, were deployed simultaneously in the motor sensor results graphically with the temperature profile in the
household with the temperature sensor. The data collected are used for background for more than 150 2-hour operation periods. We checked if
runtime results comparison between different methods. In Toronto_A there was difference in runtime during the 2-hour period with the
and Austin_Asthma, an additional temperature sensor was deployed minimized absolute daily runtime difference and if there was offset
inside the return register and/or in the most-used-room (MUR) and

Table 2
Summary of projects included in this study and their purposes.
Investigation Sample Size (# of Approximate Duration Runtime Approach Purposes
homes) (months)

Toronto_A 3 1 current, temperature Impacts of sampling interval and location of


temperature measurement
Toronto_B 2 10 motor, temperature Algorithm calibration to direct method
Visual calibration in heating climate
Austin_Asthma 58 2 temperature Visual calibration in cooling climate
Algorithm application in cooling climate
Impacts of sampling location
Toronto_Filtration 21 12 motor, pressure, current, thermostat, Comparison between temperature and direct methods
temperature Algorithm application in heating climate

101
T. Li et al. Building and Environment 150 (2019) 99–107

Fig. 1. Supply register temperature profile and operation signals from both motor sensor and temperature algorithm from 2 households a) Toronto_B Site 1 b)
Toronto_B Site 2 during 3-hour period in a typical heating month.

between the signals identified by the two methods at the beginning was added in the algorithm to process cooling runtimes when the
and/or end of each cycle. We took notes on the difference and offset to second fundamental criterion cannot be satisfied. The magnitude of this
identify factors which may impact the accuracy of the algorithm. The addition threshold is 10 times greater than the first threshold to elim-
purpose of visual calibration was to ensure that the system operation inate noise caused by the diurnal variation. In addition, similar to the
pattern determined by the improved temperature algorithm was similar heating algorithm, the lowest point of each cycle was used to determine
when compared to the motor sensor results. Through visual calibration, the end of the cooling cycle. Moreover, because there is no typical
we identified system design (e.g. the system flow rate and how far the heating season in Austin, Texas, more than half of the households in the
supply register is from the furnace) can impact the rate of change in air study had heating and cooling operations on the same day. As this
temperature in heating cycles and as a result, affect the accuracy of the problem is prevalent in cooling dominated climates, we designed the
algorithm. Fig. 1a) and b) show the temperature profile, On/Off signal algorithm to identify cooling cycles before heating cycles. We also as-
from the motor sensor, and runtime calculated by the algorithm for a 3- sumed that the occupants would not switch to heating immediately
hour period from the two houses in Toronto_B in a typical heating after a cooling cycle. A minimum time of 25 min between cooling and
month. Both homes utilize a gas furnace for heating. At the beginning of heating operation was determined based on the longest system off time
the heating cycle, the slopes of the temperature profile at both sites between two cooling cycles to minimize the number of falsely identified
were greater than 1 °C/min. Since both slopes were greater than the heating cycles. With the two new criteria added to the algorithm, the
heating threshold (0.3 °C/min), the heating operation can be identified visual calibration results from Austin_Asthma show that the algorithm
by the algorithm. However, near the end of the heating cycle, the two can correctly identify the heating and cooling cycles with varying
systems behaved differently. At Site 1, as the slope of the temperature outdoor temperatures.
changed abruptly from positive to negative, and the algorithm can
identify the end of the cycle based on the same heating threshold. 4. Results
However, at Site 2, the steepness of the slope (i.e. second derivative of
the temperature curve) decreased slowly while the temperature con- In this section, the runtime results from Toronto_B are first discussed
tinued to increase until the end of the heating cycle. This pattern is
to illustrate the accuracy of the algorithm and the potential factors
likely because the location of the supply register at Site 2 was farther which influence the accuracy of the algorithm. Then, we applied the
away from the furnace than Site 1 and/or the air flow rate was smaller,
algorithm to the temperature data collected from Toronto_Filtration.
which resulted in slower heat dissipation in the duct. For Site 2, a The calculated runtime was compared with the results from four other
portion of the heating cycle cannot be identified by the algorithm as the
direct methods including motor sensor, pressure sensor, current trans-
slope of the temperature profile was smaller than the threshold. To ducer, and smart thermostat to further verify the accuracy of this ap-
overcome this challenge, a new criterion was introduced in the algo-
proach. The similarity and difference between the results and potential
rithm for heating. In both sites, it was observed that the fan turns off causes are discussed. In addition, the calculated daily heating and
immediately after the temperature reaches the highest point based on
cooling runtimes from both Toronto_Filtration and Austin_Asthma are
the motor signals. Therefore, we decided to use the peak of the tem- plotted against outdoor temperature to explore the influence of ambient
perature profile to identify the end of the heating cycle regardless of the
condition on runtime and the reasonableness of using outdoor tem-
slope. This new criterion also improves the flexibility of the algorithm perature to estimate runtime.
as the slope of the temperature profile may vary from system to system,
Fig. 2 compares the difference in daily runtimes from the motor
but the peak remains as a good indicator of the end of the heating cycle. sensor signal and temperature method in the two households from
The calibrated algorithm was then applied to the Austin_Asthma
Toronto_B. As discussed previously in Methodology, the temperature
data set to ensure it can work on data collected from homes in a cooling method is not able to capture the periods when the system operates in
dominated climate. While measurements from direct methods are not
fan-only mode; therefore, 118 days when Site 2 operated the fan con-
available for result comparison, visual calibration was conducted for tinuously are excluded (this mode of operation is done in some homes
200 2-hour periods to ensure that the conditioning cycles identified by
to minimize temperature stratification or to achieve more benefit from
the algorithm synchronizes with the temperature profile. The results filtration). As shown in Fig. 2, the difference between the two runtimes
show that the algorithm can identify all the heating cycles, but cannot is almost always greater than zero at both sites, which shows that the
identify some cooling cycles because of the climate of central Texas.
temperature method is underpredicting runtime. This difference could
Due to the large diurnal variation in outdoor temperature, it is possible be an issue with algorithm and also may have a contribution by short
for the minimum duct temperature to be higher than the minimum
periods of fan-only operations not excluded from the dataset. In addi-
daily temperature. As a result, the second fundamental criterion is not tion, it is important to note that the difference between the two
always achieved when system operates in cooling mode in winter. To
methods are greater during the heating months (December–March)
address this challenge, an additional threshold (slope < −0.3 °C/min) when the total runtime is higher because of the increased heating

102
T. Li et al. Building and Environment 150 (2019) 99–107

calculated from temperature method (y-axis) against the four other


methods (x-axis) listed in Table 2. 43 site-months when a system was
operating continuously in fan-only mode were excluded from the
figure. In addition, 44 site-months were dropped because the direct
methods failed to record runtime due to implementation or sensor
failure. In the figure, 253 site-month are in close proximity ( ± 5%
difference) to the 1:1 relationship line, which suggests that the tem-
perature method results are comparable to the other methods for these
data points. Some exceptions can also be observed. There are 132 site-
months above the 1:1 relationship line which indicates that the run-
times measured by other direct methods are 5%–45% higher than the
runtimes calculated by temperature method. The difference is most
likely caused by system sequencing or periods of fan-only operation,
which is aligned with the observations from Fig. 2. Almost all the
runtimes from the smart thermostat are above the 1:1 line. This dif-
ference is most likely caused by the fact that the smart thermostat is
recording the call for conditioning instead of the actual system re-
sponse, as discussed by Touchie and Siegel [11]. The difference could
also be caused by intentional fan-only operation, as the smart ther-
Fig. 2. Absolute difference in runtimes from motor sensor signal and supply
mostat allows occupants to set a minimum fan-only time for each hour.
temperature method between Site 1 and Site 2 in Toronto B.
There are also 30 site-months below the 1:1 relationship line, which
indicate that the runtimes from the temperature method are greater
demand. This increase in difference is most likely caused by system than the direct methods. This difference is likely to be caused by the
sequencing. Although Fig. 1a) and b) indicate that the fan stopped variations in fan speed caused by operation mode. Because Toronto is in
approximately the same time as the furnaces in both homes, in some of a heating dominated climate, the cooling fan speed in most households
the heating cycles, the fan could continue to operate after the heating is lower than the heating speed. As a result, motor sensors which were
unit is turned off to extract the residual heat to maximize performance. working during heating season may not be able to capture the signals
This offset between the heating unit and fan is usually related to the during cooling seasons due to the weaker electromagnetic signals. Si-
amount of residual heat in the AHU. During the colder months, the milarly, current transducers would not be able to capture the cooling
higher heating demand leads to more frequent heating operation, runtime if it was installed on the wire used for heating/fan-only instead
higher AHU temperatures, and resulted in longer fan runtime after the of cooling (it is not always possible to easily identify the common wire).
heating unit is turned off. Moreover, the higher runtime also amplifies Therefore, the direct method sensors can be sensitive to operating
the runtime difference due to sequencing. Therefore, the difference modes depending on the way they were installed. Overall, paired sign
between the two methods are greater during the colder months. The rank tests with Bonferroni correction (m = 2) suggest that the runtime
detailed implications of system sequencing are explored further in the results from the temperature method are not significantly different
Discussion. Over the study period, the runtime results from the two (p > 0.025) from the other three methods (mean absolute differ-
methods are slightly but significantly different (sign rank test, ence = 1.5%), but are significantly different from the smart thermostat
p < 0.05). However, the difference is mainly attributed to the fan results (p < 0.025) with mean absolute difference of 26.5%.
overrun time in the colder months, and the absolute difference is small In addition to the difference between the direct and indirect ap-
(mean absolute difference = 2.5%) which suggests that the algorithm is proaches, we observed that the runtime at a given site could vary
well-calibrated for these two homes. considerably over time. This variation is likely caused by the change in
To further compare the runtime results from the temperature outdoor temperature and the resulting changes in conditioning de-
method with other direct approaches, we applied the algorithm to the mand. Thus, short-term runtime measurement is not a good re-
21 homes in Toronto_Filtration. Fig. 3 shows the mean monthly runtime presentation of the annual runtime, especially in climates with dis-
tinctive seasons, and it is vital to measure runtime over the long term.
Because of the challenges of runtime measurements, some studies (e.g.
Ref. [14]) used the mean daily or monthly outdoor temperature to es-
timate hours of heating and cooling of each month. To explore the in-
fluence of outdoor temperature and occupant behavior on runtimes in
different climates, and to evaluate the reasonableness of this runtime
estimation method, we plotted the average daily heating and cooling
runtimes from Toronto_Filtration and Austin_Asthma against the mean
daily outdoor temperature in Fig. 4a) and b). In both figures, the black
line represents the average daily conditioning runtime over the year for
all homes in the study.
Two trends observed illustrate the impact of outdoor temperature
on daily runtime. First, the heating runtime increases as the outdoor
temperature decreases, this trend is more obvious in Toronto because it
has a wider range of outdoor temperatures during the heating season.
Second, the cooling runtime increases as a function of the outdoor
temperature, and this trend is more obvious in Austin, which is cooling
Fig. 3. Comparison between mean monthly runtimes calculated by temperature dominated.
algorithm and four other direct methods from 21 homes in Toronto, Ontario. While the trends are similar, the median outdoor temperature for
The sites are differentiated by color. (For interpretation of the references to conditioning are different in the two cities. In Toronto, the median
color in this figure legend, the reader is referred to the Web version of this outdoor temperatures for cooling and heating are 20.8 °C and 4.2 °C,
article.) respectively. In Austin, the median outdoor temperatures for cooling

103
T. Li et al. Building and Environment 150 (2019) 99–107

Fig. 4. Average daily runtime response to daily outdoor temperature in a) Toronto_Filtration and b) Austin_Asthma.

and heating are 27.2 °C and 10 °C, respectively. This difference (6.4 °C Table 3
for cooling and 5.8 °C for heating) shows that in the colder climate, Daily mean runtime (standard deviation) calculated from supply, return and
people tend to use cooling at lower outdoor temperatures. As a result, MUR temperature using the temperature algorithm in Austin_Asthma homes.
the daily runtime under the same mean outdoor temperature varies Operation mode Sampling location
between cities with different climates. In addition, variability is ob-
served in the same city for a given outdoor temperature. This variability Supply (n = 58) Return (n = 50) MUR (n = 14)
is likely caused by factors including system sizing relative to load and
Heating 4.61 (3.63) 4.77 (4.94) 3.41 (2.41)
user operation. Moreover, fan-only operation, which is determined by Cooling 17.0 (9.45) 16.5 (10.7) 10.8 (10.7)
user preference and not necessarily by outdoor temperature are not
reflected in the figures above, could have a greater influence on the
daily runtimes. Thus, the outdoor temperature is not particularly useful return and MUR temperature are not significantly different
for accurate runtime estimation for individual homes because of the (p > 0.0125) from the runtimes calculated based on supply tempera-
variations between climates and among homes in the same climate ture. Thus, temperatures in the return register and MUR can also be
[11]. However, the outdoor temperature data is easily and readily ac- used to calculate runtime. However, it is important to note that the
cessible compared to other direct or indirect methods, so it still may be change in temperature in the return register and MUR are very small,
useful for average runtime estimations for a population of homes when sometimes less than 1 °C. As the algorithm uses the slopes in tempera-
the other measurements are not available, but care should be taken ture profile to identify conditioning cycles, the results could be easily
when using it to determine runtime for a particular home. affected by air temperature changes near the sampling location due to
air movement and human activities.
5. Discussion To further verify the accuracy of this approach, the runtimes cal-
culated based on return and MUR temperatures are compared to daily
In this section, we explore the impacts of sampling locations, sam- runtime results from a direct approach in a heating dominated climate
pling frequency, and system sequencing on the accuracy of the algo- during heating season. In Toronto_A, a current transducer (CT) and two
rithm. The limitations and implications of the temperature method are temperature sensors, one in the return register and one in the MUR
also discussed. were deployed in all homes for one typical heating month. The absolute
difference between results from the CT and return temperature, CT and
5.1. Impact of sampling location MUR temperature are −17% (Std. dev = 8.66%) and −8.3% (Std.
dev = 0.5%), respectively. It is worth noting that the temperature
The impact of sampling location on the accuracy of temperature method underestimated the runtimes in both cases by 8–17% and there
algorithm is assessed through two comparisons, between measurements is even considerable difference between the MUR and return results,
in two different supply registers, and between a supply register and a which is different from the results in Austin_Asthma. This difference is
location with room temperature. To compare daily runtimes calculated likely due to the fact that the thresholds used in the return and MUR
from different supply registers, we applied the algorithm to eight runtime calculation were calibrated based on the Austin_Asthma da-
households in Austin_Asthma, where an additional temperature sensor taset. Because the magnitudes of the slopes are so small, the algorithm
was deployed in a separate supply register. The mean absolute differ- is very sensitive at detecting changes in the air temperature. As a result,
ence in daily cooling and heating runtime is 0.01% (Std. dev = 2.2%) the return and MUR algorithm is not very accurate for runtime calcu-
and 0.1% (Std. dev = 1.1%). These results show that the location of the lation in a heating climate like Toronto because it strongly depends on
supply register has very limited impact on the conditioning runtime the temperature distribution within the space (which itself is often a
results. Thus, the temperature sensor can be deployed in any supply function of runtime because of mixing). The small changes in tem-
register in the house to measure runtime, although care should be taken perature also introduced more uncertainty to the runtime result.
to avoid registers with little or no flow because of damper operation or Therefore, the return register or MUR are not the ideal locations for
duct design issues. sampling. While indoor temperature can be used to estimate con-
The temperature sensors were also deployed at other sampling lo- ditioning runtimes, the results should be verified by results comparison
cations in the Austin_Asthma study. The temperature sensor was placed and visual inspection before being used for further analyses.
in the return register in 14 sites and in the most-used room (MUR, e.g.,
the living room) in 50 sites (some of the sites had both return and MUR 5.2. Impacts of sampling frequency
sensors installed). The calculated daily runtimes and standard devia-
tions are summarized in Table 3. Paired sign rank tests with Bonferroni To evaluate the impact of sampling frequency, an identical tem-
correction (m = 4) were used to avoid a significant association by perature sensor which recorded temperature at 1.25-min interval was
chance when performing multiple tests on the same dataset. The results deployed in the same supply register besides the sensor recording at 1-
suggest that both heating and cooling runtime calculated based on the min interval in the 3 homes in Toronto_A. Two additional data sets with

104
T. Li et al. Building and Environment 150 (2019) 99–107

Table 4
Mean daily runtime and standard deviation calculated at different sampling interval from Toronto_B.
Operation mode Sampling interval

1 min 1.25 min 2 min 2.5 min

Heating 15.6% ± 16.0% 16.0% ± 16.5% 15.7% ± 16.2% 16.4% ± 17.1%


Cooling 2.55% ± 5.52% 2.75% ± 6.03% 2.63% ± 5.68% 2.80% ± 6.05%

2-min and 2.5-min sampling intervals were generated by eliminating heat exchanger. Because of this 5-minute overrun, the temperature al-
every other observation of the measured data from both sensors. The gorithm underpredicts the runtime (the average hourly runtimes by the
mean daily runtime and standard deviation calculated from these four motor signal and by the temperature method are 70.5% and 42.6%,
datasets are summarized in Table 4. Within the same dataset, the large respectively). After the first hour, the system was operating less fre-
standard deviation in heating indicates the variations in daily runtimes quently likely because of decrease in heating demand. This less frequent
in the two households over the course of the study, which is aligned operation resulted in a lower supply plenum temperature and shorten
with our previous observations. Comparison between the datasets the fan overrun time. As a result, the fan operation is more synchro-
shows that the runtimes calculated at 1.25, 2, and 2.5-min interval are nized with heating unit and the accuracy of the algorithm is improved
similar to the 1-min interval results. Thus, the sampling frequency has a (the average hourly runtimes by motor signal and temperature method
small impact on runtime prediction and the temperature sensors can be are 24.6% and 23.0%, respectively). Thus, the algorithm is more ac-
deployed at lower sampling frequency for a longer time. However, the curate when the temperature in the supply plenum is lower for a given
sampling interval should still be shorter than the length of the con- system.
ditioning cycles (usually varies between 5 and 20 min) to avoid missing The other pattern we identified from Fig. 5 is the point of inflection,
changes in the air temperature in the supply register. which is the point where the second derivative of the temperature
profile is negative. It can be easily identified on the supply temperature
profile if there is a sudden increase in the slope of the temperature
5.3. Impacts of sequencing of the system
profile before it decreases again. We found that in this case (Fig. 5), the
point of inflection occurs at the time the fan turns off, because there is
Comparison and visual calibration between the methods indicate
no more air movement in the duct and the rate of temperature decrease
that conditioning operations are generally not entirely coincident with
diminishes. It is worth noting that the occurrence of point of inflection
fan operations because of system sequencing. In other words, con-
on the temperature profile depends on the duration of fan overrun time.
ditioning runtime of a system may be different from fan runtime, or the
If the fan turns off immediately after the heating unit (e.g., Fig. 1a and
two runtimes may be similar in duration, but have an offset. Therefore,
b), the fan overrun time is short and there will be no visible point of
system sequencing could considerably affect the accuracy of the tem-
inflection on the temperature profile. However, if the fan overrun time
perature method, which calculates the conditioning runtime based on
is longer, the point of inflection will be more obvious (as shown in
temperature changes.
Figs. 5–7) and it will be a better indicator for the time when the fan
In heating mode, the fan usually continues operating after the
turns off. For this reason, in addition to the peak temperature, the point
heating unit is turned off to extract residual heat from the heat ex-
of inflection can be used for future improvements of the temperature
changer to maximize its performance. To evaluate the impact of se-
method for fan runtime calculations.
quencing, we examined the potential factors which could influence the
The heating demand could have a greater impact on the fan overrun
fan overrun time. The length of the fan overrun time is found to be
time if a furnace has more than one stage. These furnaces often first
related to the air temperature in the system. Fig. 5 shows an example of
operate at the lower output level to satisfy the heating demand for a
this phenomenon from Toronto_B Site 1 for a 2-hour period. As shown
certain period of time. If the room is not heated to the desired tem-
in Fig. 5, the peak temperature recorded in the supply register was
perature during the first stage, the furnace will stop and then start the
greater than 50 °C during the first 45 min. As explained earlier, the peak
second stage to operate at its full capacity to satisfy the demand faster.
in temperature of every cycle indicates the time when the gas burners
Because the furnace is not operating at its full capacity from the be-
turned off. After the peak, as indicated by the motor signal, the fan
ginning, the cycle length of a two-stage furnace is usually longer than a
continued operating for another 5 min to extract residual heat from the

Fig. 5. Temperature profile, On/Off signals recorded by motor sensor and Fig. 6. Temperature profile, On/Off signals from both motor sensor and tem-
calculated by the temperature method from Site 1, Toronto_B. Note fan con- perature method from Site 1, Toronto_Filtration when the system is operating in
tinues to run after heating cycle ends. two-stage heating.

105
T. Li et al. Building and Environment 150 (2019) 99–107

Fig. 7. Temperature profile, On/Off signals from both smart thermostat and Fig. 8. Temperature profile, On/Off signals from both pressure signal and
temperature method from Site 13, Toronto_Filtration. The fan operated before temperature method from Site 1, Toronto_Filtration. The system is operating in
the heating unit turned on. cooling mode.

single stage furnace if the second stage engages. Fig. 6 shows an ex- the fan is designed to operate at the end of the cycle.
ample of the temperature profile of a two-stage furnace in study Tor- When the system is operating in cooling mode, there are generally
onto_Filtration for a 2-hour period. The system was operating in the two types of system sequencing: one is the compressor and the fan stop
first stage and the measured temperature was lower than 40 °C from at the same time, and the other is the fan continues operating after the
17:00–18:30. This pattern is expected because of the mild outdoor compressor is off to benefit from the cold coil. Fig. 8 shows an example
weather (2 °C). At 18:40, the second-stage engaged to meet the heating of cooling sequence from Site 1 in Toronto_Filtration. As indicated in
demand. It is indicated in the temperature profile as the slope of the the graph, the pressure signal indicates that the fan continued to run for
profile first decreased then increased. Because of the engagement of the 2–4 min after the temperature in system reached the lowest point. In
second stage, the heating cycle was longer than usual, and the mea- this system, the fan overrun time had limited impact on the accuracy of
sured temperature was approximately 10 °C higher. Due to the higher the algorithm because the fan started 2–4 min late at the beginning of
temperature, the fan overrun time also increased at the end of the cycle. each cycle. As a result, the conditioning runtime and the fan runtime
During this 2-hour period, the temperature algorithm under-predicted were similar in duration in this system.
the runtime by 3% compared to the motor sensor results (43% and 46%, It is also worth to mention that the comparison between fan and
respectively). However, a greater difference is expected if the second conditioning runtime can be used to evaluate the operation of cooling
stage engages more often due to a higher heating demand. Overall, the systems. Running the fan continuously after the compressor is off de-
algorithm tends under-predict runtime for two-stage (or multi-stage) grades the moisture removal capacity of the cooling coil because the
furnaces, as a higher temperature is usually reached in the system when moistures condenses on the coil surface during the cooling cycle eva-
the second stage engages and results in longer fan overrun time. porates back into air stream before it has a chance to drain from the coil
In addition to fan overrun time at the end of the cycle, from Fig. 6 [5]. This is a bigger concern on higher efficiency coils with smaller
also identified a short delay in motor signal at the beginning of the spaces between the heat exchanger fins. A well-designed system, par-
cycle. The delay could be caused by the different response time of the ticularly in a climate where latent removal is important, should stop the
sensors, but it is more likely because most natural gas furnaces delay fan operation before the surface temperature of the cooling coil be-
the fan until the heat exchanger has been warmed by the burners to comes higher than the wet-bulb temperature of the entering air to
avoid circulation of cold air through the house. The delay is generally prevent evaporation from occurring. In well-designed systems, the
shorter than 2 min, and it slightly offsets the underprediction of runtime conditioning runtime shoudl be similar in duration when compared to
by the temperature method. fan runtime. In other systems, the fan overrun time could be longer and
There are also rare cases where the fan may come on before the result in underprediction of fan runtime. Overall, for both heating and
burner cycle. This is often an option for homes with smart thermostats cooling, the examples discussed in this section show that the con-
and it is done to circulate the air in the home to promote thermal ditioning runtime can be different from fan runtime due to system se-
mixing. In this case, the temperature algorithm underpredicts the run- quencing and fan-only operation, and resulted in the algorithm un-
time because the air temperature no longer represents fan operation. derpredicting the fan runtime.
Fig. 7 shows an example of the fan starting before the gas burners at
Site 13 from Toronto_Filtration. According to the smart thermostat re-
6. Conclusion
sults, the fan was operating five minutes prior to the burners at the
beginning of each cycle. The algorithm was not able to capture the fan
The improved temperature algorithm, which calculates runtime
operation and under-predicted the runtime by 23% over the 2-hour
based on the changes in air temperature in the supply duct, is an al-
period.
ternative, convenient, and reliable approach to assess runtime in re-
Similar to the overrun pattern that we have identified previously
sidential buildings, even though it calculates conditioning runtime in-
from other sites, the fan at Site 13 also operated independent of the gas
stead of fan runtime. The greatest strengths of this method are that it
burners at the end of the cycle, likely for the same reasons as in the
does not require access to the AHU or specially-trained personnel and it
other homes with gas furnaces. It is worth noting that this period of fan
can differentiate between heating and cooling modes. Overall, com-
operation was not identified by the smart thermostat because the smart
pared to the direct runtime measurement methods, the improved tem-
thermostat reads the call for heating or cooling set by the occupants
perature algorithm slightly underpredicts runtimes in heating domi-
instead of the real system response. Since the fan operation was trig-
nated climates due to the influence of system sequencing. In cooling
gered by the furnace controls, it is not captured by the smart thermo-
dominated climates, especially for well-designed systems, the algorithm
stat. Therefore, the smart thermostat could also underpredict runtime if
provides similar runtime results to the direct methods. It is more

106
T. Li et al. Building and Environment 150 (2019) 99–107

accurate and reliable than indirect approaches which use the daily or References
monthly outdoor temperature to estimate runtimes. For annual runtime
calculation, the algorithm underestimates the runtime by 1.5–2.5% [1] EIA, Energy Consumption Survey (RECS): Table HC1.1 Fuels Used and End Uses in
annually compared to other methods used in this work. In addition, we U.S. Homes by Housing Unit Type, (2015) Feb-2017. [Online]. Available: https://
www.eia.gov/consumption/residential/data/2015/hc/php/hc6.1.php , Accessed
found that air temperature measurements from the supply register can date: 11 April 2018.
provide the most accurate results and the sampling frequency has a [2] Statistics Canada, Households and the Environment Survey, (Mar. 2015).
small impact on the accuracy of the algorithm, as long as the sampling [3] B Stephens, A. Novoselac, J.A. Siegel, The effects of filtration on pressure drop and
energy consumption in residential HVAC systems (RP-1299), HVAC R Res. 16 (3)
interval is shorter than the conditioning cycle length. Because this (May 2010) 273–294.
temperature method determines the conditioning runtime instead of fan [4] J.A. Siegel, Primary and secondary consequences of indoor air cleaners, Indoor Air
runtime, fan-only operation, which is dependent on the user preference 26 (1) (Feb. 2016) 88–96.
[5] D.B. Shirey, H.I. Henderson, Dehumidification at part load, ASHRAE J. 46 (4) (Apr.
and independent on conditioning needs, can influence the accuracy of 2004) 42–49.
the method. Thus, knowledge of the occupant preference is required [6] T. Li, J.A. Siegel, Impacts of HVAC sequencing on runtime, Indoor Air 2018,
before choosing the most suitable approach to measure runtime. Philadelphia, PA, USA, 2018.
[7] S. Giri, M. Berges, Virtual metering of electrical appliances through analysis of data
Overall, our results show that the newly proposed temperature method
from contactless sensing, 2015 IEEE Global Conference on Signal and Information
is a robust tool that can be utilized to further enhance our knowledge of Processing, GlobalSIP, 2015, pp. 348–352.
residential systems runtime and its impacts on thermal comfort, HVAC [8] K.S. Cetin, P.C. Tabares-Velasco, A. Novoselac, Appliance daily energy use in new
energy use, and indoor air quality. residential buildings: use profiles and variation in time-of-use, Energy Build. 84
(Supplement C) (Dec. 2014) 716–726.
[9] B Stephens, J.A. Siegel, A. Novoselac, Operational characteristics of residential and
light-commercial air-conditioning systems in a hot and humid climate zone, Build.
Acknowledgements Environ. 46 (10) (Oct. 2011) 1972–1983.
[10] D. Kosar, S. Scott, H. Vadnal, P. Glanville, Field monitoring of rooftop unit (RTU)
heating runtimes and gas usage for selected commercial buildings, ASHRAE Trans.
This work was funded by the National Sciences and Engineering 120 (1) (Jan. 2014).
Research Council (NSERC: RGPIN-2014-06698) and the measurements [11] M. Touchie, J.A. Siegel, Residential HVAC runtime from smart thermostats: char-
acterization, comparison, and impacts, Indoor Air 28 (6) (Nov. 2018) 905–915.
in the Austin homes were funded by the Department of Housing and [12] J.W. Thornburg, C.E. Rodes, P.A. Lawless, C.D. Stevens, R.W. Williams, A pilot
Urban Development (HUD: TXHHU0023-13). Tianyuan Li was partially study of the influence of residential HAC duty cycle on indoor air quality, Atmos.
supported by a Canada Graduate Scholarship-Master's Program and Environ. 38 (11) (Apr. 2004) 1567–1577.
[13] K.S. Cetin, A. Novoselac, Single and multi-family residential central all-air HVAC
Masih Alavy was partially supported by an Alexander Graham Bell system operational characteristics in cooling-dominated climate, Energy Build. 96
NSERC Canada Graduate Scholarships-Doctoral Program. We gratefully (Jun. 2015) 210–220.
acknowledge the participation of all the homeowners in the investiga- [14] C. Chen, B. Zhao, C.J. Weschler, “Indoor exposure to ‘outdoor PM10’: assessing its
influence on the relationship between PM10 and short-term mortality in U.S. cities,
tions cited here.
Epidemiology 23 (6) (Nov. 2012) 870–878.

107

You might also like