Technical description
Document Details
Executive summary
Instructions to complete a firmware download to both hardware versions of the SPNPM22,
the version with the mini-USB diagnostic port on the faceplate of the module and the version
with the 9 pin RS-232 port on the circuit board of the module.
1 Products concerned
SPNPM22
2 Description
2. Set SW2 poles ‘3’, ‘5’, ‘6’, and ‘8’ to Open on the NPM22 module.
3. Connect an RS-232 cable to the DB9 connector just behind the NPM22 front panel.
NOTE: A flat ribbon cable with DB9 connectors is required if there is no space be-
tween the modules in the MMU. The other end of the cable goes to the PC COM port.
OR
Connect mini-USB to USB cable to the diagnostic port on the front plate of the NPM22.
NOTE: The PC requires a Windows Combined Driver Model (CDM) interface driver,
which can be installed on Windows 2000, XP, VISTA, Windows 7, or Windows 10. In
most situations, Windows Update can be used to automatically locate and download
the device driver for this interface. If Windows Update is unable to locate the correct
driver, then you can download the
FT232R interface driver from the manufacturer's web site - http://www.ftdichip.com.
Currently, the driver file is named per the latest available version of CDM WHQL Certi-
fied.zip. The following application note (from the manufacturer's web site) describes
the driver installation procedure:
"Document Reference No.: FT_000160 FTDI Drivers Installation guide for Windows 7
Application Note AN_119 (latest version)”
4. Configure the COM port to 38, N, 8, and 1 (38K baud, no parity, 8 data bits, and 1 stop bit)
and select no flow control using Hyperterminal software.
5. Insert the NPM22 module in the MMU and wait for the following prompt to appear:
12. Paste (CTRL+V) the file name and path in the Transfer File dialog box.
13. Enter Return to start the transfer and wait for the following prompt to appear:
Hello, enter “~“ and “!” to start XMODEM download
NOTE: Do not remove the NPM22 module until after the above message appears.
14. Remove the NPM22 module and set SW5 pole 1 and all SW2 poles to Closed.
15. Change the baud rate settings and enable the Local/remote diagnostics, if required.
The banner displayed on the serial port show the NPM22 revision.
3 Document management
3.1 Distribution
MyControlSystem
—
www.abb.com/powergeneration
TRADEMARKS The crossed–out wheeled bin symbol on the product and accompa-
nying documents means that used electrical and electronic equip-
Symphony and Symphony Plus are registered or pending
ment (WEEE) should not be mixed with general household waste. If
trademarks of ABB S.p.A.
you wish to discard electrical and electronic equipment (EEE),
Ability is a trademark of ABB. please contact your dealer or supplier for further information.
All rights to copyrights, registered trademarks, and trade- Disposing of this product correctly will help save valuable resources and pre-
marks reside with their respective owners. vent any potential negative effects on human health and the environment,
Copyright © 2019 ABB. All rights reserved. which could otherwise arise from inappropriate waste handling.