Heat Pump 220V + 220-240V

R410A(50Hz/60Hz)
0CVV0-01A

P/No. : MFL67474026
Heat Pump

2. External Appearance
■ Heat Pump
General Information of

CHASSIS Model Name Model


*RUN080BLS4
Outdoor Units

*RUN100BLS4
UX5
*RUN120BLS4
*RUN140BLS4

*RUN160BLS4
UX6 *RUN180BLS4
*RUN200BLS4

*RUN220BLS4
UX5
*RUN240BLS4
UX5
*RUN260BLS4

*RUN280BLS4
UX6 *RUN300BLS4
UX5 *RUN320BLS4
*RUN340BLS4

*RUN360BLS4
UX6
*RUN380BLS4
UX6
*RUN400BLS4

UX6
*RUN420BLS4
UX5
*RUN440BLS4
UX5

*RUN460BLS4
UX6 *RUN480BLS4
UX6 *RUN500BLS4
UX5 *RUN520BLS4
*RUN540BLS4

UX6 *RUN560BLS4
UX6 *RUN580BLS4
UX6 *RUN600BLS4

2 _ R410A(50Hz/60Hz)
Heat Pump

3. Nomenclature

ARU N 100 B L S 4

General Information of
Outdoor Units
Serial Number

S : Standard


Air Discharge Type


L : Top Discharge Pro H/P

Electrical Ratings
B: 3Ø, 220-240 V, 50 Hz / 3Ø, 220 V, 60 Hz

Total Cooling Capacity in Horse Power(HP) unit


EX) 8HP → '080' 10HP → '100'

Combination of Inverter Type and


Cooling Only or Heat Pump
N: Inverter and H/P V: Inverter and C/O

ARU : System with Outdoor Unit using R410A for Global


CRU : System with Outdoor Unit using R410A for Brazil only

R410A(50Hz/60Hz) _ 3
Heat Pump

1. Outdoor Unit Function


Category Functions Multi V IV PRO
Defrost / Deicing O
High pressure switch O
Phase protection O
Reliability Restart delay (3-minutes) O
Self diagnosis O
Soft start O
Test Run function X
Convenience Night Silent Operation O
CAC network function Network solution(LGAP) O

Note :
O : Applied,   X : Not applied
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with
separate package.

Outdoor Units
Device Multi V IV PRO
AC Ez (Simple Controller) PQCSZ250S0
AC Smart ll PQCSW320A1E
AC Smart Premium PQCSW421E0A
128 Unit Expansion Kit for AC Smart PQCSE440U0
Option Kit (SD card type) for AC Smart PQCSE341A0 / PQCSE342A0
Central Controller ACP(Advanced Control Platform) PQCPA11A0E / PQCPB11A0E
AC Manager PQCSS520A0E
ACP(Advanced Control Platform) Standard PQCPC22N0
ACP(Advanced Control Platform) Premium PQCPC22A0
AC Manager Plus PQCSSA21E0
DO(Digital Output) Kit PQNFP00T0
LONWORKS Gateway (DC 12V Adapter) PQNFB16A1 / PLNWKB000
BNU LONWORKS Gateway (AC 24 V) PLNWKB100
(Building Network Unit) BACnet Gateway (DC 12V Adapter) PQNFB17B0 / PQNFB17C0
BACnet Gateway (AC 24 V) PQNFB17C1
Installation Refrigerant Charging Kit O (Logical operation)
PDI(power distribution indicator) PQNUD1S00
PDI(power distribution indicator) Premium PQNUD1S40
Cool / Heat Selector PRDSBM
IO Module (ODU Dry Contact) PVDSMN000
Cycle Monitoring LG MV PRCT-FE1
Device Mobile LGMV(Bluetooth) PMVBTQ01

Note :
O : Applied,   X : Not applied
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with
separate package.

R410A(50Hz/60Hz) _ 1
Heat Pump

2. Specifications
50Hz/60Hz

* : A(Global model), C(Brazil only model)


HP 14 16
Combination Unit *RUN140BLS4 *RUN160BLS4
*RUN140BLS4 *RUN160BLS4
Model Name
Independent Unit

kW 39.2 44.8
Cooling kcal/h 33,700 38,500
Capacity 1) Btu/h 133,800 152,900
(Rated) kW 39.2 44.8
Heating kcal/h 33,700 38,500
Btu/h 133,800 152,900
Cooling kW 10.8 12.3
Input (Rated) 1)
Heating kW 9.92 13.1
Power Factor 6) Rated - 0.93 0.93
Casing Color Warm Gray / Morning Gray Warm Gray / Morning Gray
Heat Exchanger Gold fin Gold fin
Type Hermetically Sealed Scroll Hermetically Sealed Scroll

Outdoor Units
Piston Displacement cm3/rev 62.1 62.1
Number of Revolution rev/min 3,600 3,600
Compressor 6,800 6,800
Motor Output x Number W x No.
Starting Method Direct On Line Direct On Line
Oil Type FVC68D(PVE) FVC68D(PVE)
Type Axial fan Axial fan
Motor Output x Number W 750 x 1 1,200 x 1
m3/min 210 270
Fan Air Flow Rate(High) 7,416 9,535
ft3/min
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Piping Liquid mm(inch) 12.7(1/2) 12.7(1/2)
Connections Gas mm(inch) 28.58(1-1/8) 28.58(1-1/8)
mm (920 × 1,680 × 760) × 1 (1,240 × 1,680 × 760) × 1
Dimensions(W x H x D)
inch (36-7/32 × 66-5/32 × 29-29/32) × 1 (48-13/16 × 66-5/32 × 29-29/32) x 1
kg 193 × 1 208 × 1
Net Weight
lbs 426 × 1 459 × 1
Sound Pressure Level dB(A) 60.0 62.0
Sound Power Level dB(A) 80.0 82.0
High pressure High pressure sensor / High pressure sensor /
- High pressure switch High pressure switch
protection
Protection Over-heat protection / Over-heat protection /
Comperssor/ Fan - Fan driver overload protector Fan driver overload protector
Devices
Over-heat protection / Over-heat protection /
Inverter - Over-current protection Over-current protection
Communication Cable No.xmm (VCTF-SB)
2
2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 6.6 6.0
Refrigerant Precharged Amount
lbs 14.6 13.2
Control Electronic Expansion Valve Electronic Expansion Valve
V, Ø, Hz 220-240, 3, 50 220-240, 3, 50
Power Supply V, Ø, Hz 220, 3, 60 220, 3, 60
Number of maximum connectable indoor units 2) 23(35) 26(40)
Notes:
1. Capacities are based on the following conditions: 2. The numbers in parentheses means maximum connectable indoor units in
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB accordance with outdoor units combination. The recommended ratio is 130%.
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB 3. Wiring cable size must comply with the applicable local and national codes.
- Heating Temperature : Indoor 20°C(68°F) DB / 15°C(59°F) WB 4. Due to our policy of innovation some specifications may be changed without notification.
Outdoor 7°C(44.6°F) DB / 6°C(42.8°F) WB 5. Sound Pressure Level Values are measured at Anechoic chamber. Therefore,
- Piping Length : Interconnected Pipe Length = 7.5m these values can be increased owing to ambient conditions during operation.
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero. 6. Power factor could vary less than ±1% according to the operating conditions.

R410A(50Hz/60Hz) _ 3
Heat Pump

2. Specifications
50Hz/60Hz

* : A(Global model), C(Brazil only model)


HP 18 20
Combination Unit *RUN180BLS4 *RUN200BLS4
*RUN180BLS4 *RUN200BLS4
Model Name
Independent Unit

kW 50.4 56.0
Cooling kcal/h 43,300 48,200
Capacity 1) Btu/h 172,000 191,100
(Rated) kW 50.4 56.0
Heating kcal/h 43,300 48,200
Btu/h 172,000 191,100
Cooling kW 14.6 15.4
Input (Rated) 1)
Heating kW 13.7 15.1
Power Factor 6) Rated - 0.93 0.93
Casing Color Warm Gray / Morning Gray Warm Gray / Morning Gray
Heat Exchanger Gold fin Gold fin
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Outdoor Units

Piston Displacement cm3/rev 43.8 × 2 43.8 × 2


Number of Revolution rev/min 3,600 ×2 3,600 ×2
Compressor 4,200 ×2 4,200 ×2
Motor Output x Number W x No.
Starting Method Direct On Line Direct On Line
Oil Type FVC68D(PVE) FVC68D(PVE)
Type Axial fan Axial fan
Motor Output x Number W 1,200 x 1 1,200 x 1
m3/min 270 270
Fan Air Flow Rate(High) 9,535 9,535
ft3/min
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Piping Liquid mm(inch) 15.88(5/8) 15.88(5/8)
Connections Gas mm(inch) 28.58(1-1/8) 28.58(1-1/8)
mm (1,240 × 1,680 × 760) × 1 (1,240 × 1,680 × 760) × 1
Dimensions(W x H x D)
inch (48-13/16 × 66-5/32 × 29-29/32) x 1 (48-13/16 × 66-5/32 × 29-29/32) x 1
kg 250 × 1 260 × 1
Net Weight
lbs 551 × 1 573 × 1
Sound Pressure Level dB(A) 62.0 62.0
Sound Power Level dB(A) 82.0 82.0
High pressure High pressure sensor / High pressure sensor /
- High pressure switch High pressure switch
protection
Protection Over-heat protection / Over-heat protection /
Comperssor/ Fan - Fan driver overload protector Fan driver overload protector
Devices
Over-heat protection / Over-heat protection /
Inverter - Over-current protection Over-current protection
Communication Cable No.xmm (VCTF-SB)
2
2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 6.0 7.6
Refrigerant Precharged Amount
lbs 13.2 16.8
Control Electronic Expansion Valve Electronic Expansion Valve
V, Ø, Hz 220-240, 3, 50 220-240, 3, 50
Power Supply V, Ø, Hz 220, 3, 60 220, 3, 60
Number of maximum connectable indoor units 2) 29(45) 32(50)
Notes:
1. Capacities are based on the following conditions: 2. The numbers in parentheses means maximum connectable indoor units in
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB accordance with outdoor units combination. The recommended ratio is 130%.
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB 3. Wiring cable size must comply with the applicable local and national codes.
- Heating Temperature : Indoor 20°C(68°F) DB / 15°C(59°F) WB 4. Due to our policy of innovation some specifications may be changed without notification.
Outdoor 7°C(44.6°F) DB / 6°C(42.8°F) WB 5. Sound Pressure Level Values are measured at Anechoic chamber. Therefore,
- Piping Length : Interconnected Pipe Length = 7.5m these values can be increased owing to ambient conditions during operation.
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero. 6. Power factor could vary less than ±1% according to the operating conditions.

4 _ R410A(50Hz/60Hz)
Heat Pump

2. Specifications
■ Heat Pump (Standard_Combination model) 50Hz/60Hz

* : A(Global model), C(Brazil only model)


HP 22 24
Combination Unit *RUN220BLS4 *RUN240BLS4
*RUN120BLS4 *RUN120BLS4
Model Name *RUN100BLS4 *RUN120BLS4
Independent Unit

kW 61.6 67.2
Cooling kcal/h 53,000 57,800
Capacity 1) Btu/h 210,600 229,400
(Rated) kW 61.6 67.2
Heating kcal/h 53,000 57,800
Btu/h 210,600 229,400
Cooling kW 16.80 18.60
Input (Rated) 1)
Heating kW 15.90 17.20
Power Factor 6) Rated - 0.93 0.93
Casing Color Warm Gray / Morning Gray Warm Gray / Morning Gray
Heat Exchanger Gold fin Gold fin
Type Hermetically Sealed Scroll Hermetically Sealed Scroll

Outdoor Units
Piston Displacement cm3/rev 43.8 + 62.1 62.1 × 2
Number of Revolution rev/min 3,600 ×2 3,600 ×2
Compressor 4200 + 6800 6,800 ×2
Motor Output x Number W x No.
Starting Method Direct On Line Direct On Line
Oil Type FVC68D(PVE) FVC68D(PVE)
Type Axial fan Axial fan
Motor Output x Number W 750 x 2 750 x 2
m3/min 210 x 2 210 x 2
Fan Air Flow Rate(High) 7,416 x 2 7,416 x 2
ft3/min
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Piping Liquid mm(inch) 15.88(5/8) 15.88(5/8)
Connections Gas mm(inch) 28.58(1-1/8) 34.9(1-3/8)
mm (920 × 1,680 × 760) × 2 (920 × 1,680 × 760) × 2
Dimensions(W x H x D)
inch (36-7/32 × 66-5/32 × 29-29/32) x 2 (36-7/32 × 66-5/32 × 29-29/32) x 2
kg 183 x 1 + 178 × 1 183 × 2
Net Weight
lbs 403 x 1 + 392 × 1 403 × 2
Sound Pressure Level dB(A) 61.8 62.0
Sound Power Level dB(A) 82.0 82.0
High pressure High pressure sensor / High pressure sensor /
- High pressure switch High pressure switch
protection
Protection Over-heat protection / Over-heat protection /
Comperssor/ Fan - Fan driver overload protector Fan driver overload protector
Devices
Over-heat protection / Over-heat protection /
Inverter - Over-current protection Over-current protection
Communication Cable No.xmm (VCTF-SB)
2
2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Refrigerant name R410A R410A
kg 5.0 × 2 5.0 × 2
Refrigerant Precharged Amount
lbs 11.0 × 2 11.0 × 2
Control Electronic Expansion Valve Electronic Expansion Valve
V, Ø, Hz 220-240, 3, 50 220-240, 3, 50
Power Supply V, Ø, Hz 220, 3, 60 220, 3, 60
Number of maximum connectable indoor units 2) 35(44) 39(48)
Notes:
1. Capacities are based on the following conditions: 2. The numbers in parentheses means maximum connectable indoor units in
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB accordance with outdoor units combination. The recommended ratio is 130%.
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB 3. Wiring cable size must comply with the applicable local and national codes.
- Heating Temperature : Indoor 20°C(68°F) DB / 15°C(59°F) WB 4. Due to our policy of innovation some specifications may be changed without notification.
Outdoor 7°C(44.6°F) DB / 6°C(42.8°F) WB 5. Sound Pressure Level Values are measured at Anechoic chamber. Therefore,
- Piping Length : Interconnected Pipe Length = 7.5m these values can be increased owing to ambient conditions during operation.
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero. 6. Power factor could vary less than ±1% according to the operating conditions.

R410A(50Hz/60Hz) _ 5
Outdoor Units

UX6
Heat Pump

*RUN160BLS4
*RUN180BLS4
*RUN200BLS4

14 _ R410A(50Hz/60Hz)
3. Dimensions

* : A(Global model), C(Brazil only model)


UX5 + UX5
Heat Pump

*RUN220BLS4
*RUN240BLS4
*RUN260BLS4
3. Dimensions

* : A(Global model), C(Brazil only model)

R410A(50Hz/60Hz) _ 15
Outdoor Units
Heat Pump

4. Electric Characteristics
◆ Wiring of Main Power Supply and Equipment Capacity
1. Use a separate power supply for the Outdoor Unit and Indoor Unit.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain liquid,etc.) when proceeding with the wiring and
connections.
3. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker taking into account
the line voltage drops. Make sure the power-supply voltage does not drop more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use should not be lighter than polychloroprene sheathed flexible cord.
6. Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.

WARNING
• Follow ordinance of your governmental organization for technical standard related to electrical equipment,
wiring regulations and guidance of each electric power company.
• Make sure to use specified wires for connections so that no external force is imparted to terminal connections. If
connections are not fixed firmly, it may cause heating or fire.

Outdoor Units
• Make sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may
include some amount of direct current.

CAUTION
• Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it
may cause an electric shock.
• Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too
large capacity may cause a malfunction of unit or fire.

R410A(50Hz/60Hz) _ 21
Heat Pump

4. Electric Characteristics
◆ 60Hz
Unit Power Supply COMP OFM
Model
Hz Volts Voltage-range MCA TOCA MFA MSC RLA (Cooling) RLA (Heating) kW FLA
8 HP 60 220 Min.:198, Max.:242 31.6 36.0 40 7.0 11.9 10.7 0.75 4.0
10 HP 60 220 Min.:198, Max.:242 32.7 36.0 40 7.0 17.2 16.6 0.75 4.0
12 HP 60 220 Min.:198, Max.:242 43.9 50.0 50 8.0 22.2 20.3 0.75 4.0
14 HP 60 220 Min.:198, Max.:242 44.6 50.0 50 8.0 26.5 24.0 0.75 4.0
16 HP 60 220 Min.:198, Max.:242 45.5 50.0 50 8.0 28.7 31.0 1.20 6.0
18 HP 60 220 Min.:198, Max.:242 63.2 72.0 75 14.0 35.2 32.7 1.20 6.0
20 HP 60 220 Min.:198, Max.:242 64.3 72.0 75 14.0 37.5 36.6 1.20 6.0
22 HP 60 220 Min.:198, Max.:242 78.2 86.0 90 15.0 39.4 36.9 1.50 8.0
24 HP 60 220 Min.:198, Max.:242 86.2 100.0 100 16.0 44.5 40.5 1.50 8.0
26 HP 60 220 Min.:198, Max.:242 87.7 100.0 100 16.0 48.7 44.3 1.50 8.0
28 HP 60 220 Min.:198, Max.:242 89.3 100.0 100 16.0 51.0 51.2 1.95 10.0
30 HP 60 220 Min.:198, Max.:242 105.2 122.0 125 22.0 57.4 52.9 1.95 10.0
32 HP 60 220 Min.:198, Max.:242 107.0 122.0 125 22.0 59.7 56.9 1.95 10.0
34 HP 60 220 Min.:198, Max.:242 108.9 122.0 125 22.0 63.9 60.6 1.95 10.0
Outdoor Units

36 HP 60 220 Min.:198, Max.:242 110.9 122.0 125 22.0 66.2 67.6 2.40 12.0
38 HP 60 220 Min.:198, Max.:242 127.4 144.0 150 28.0 72.7 69.3 2.40 12.0
40 HP 60 220 Min.:198, Max.:242 128.6 144.0 150 28.0 74.9 73.2 2.40 12.0
42 HP 60 220 Min.:198, Max.:242 138.6 158.0 165 29.0 78.8 73.3 2.70 14.0
44 HP 60 220 Min.:198, Max.:242 141.1 158.0 165 29.0 81.1 77.2 2.70 14.0
46 HP 60 220 Min.:198, Max.:242 143.6 158.0 165 29.0 83.3 84.2 3.15 16.0
48 HP 60 220 Min.:198, Max.:242 160.7 180.0 190 35.0 89.8 85.9 3.15 16.0
50 HP 60 220 Min.:198, Max.:242 163.6 180.0 190 35.0 92.1 89.8 3.15 16.0
52 HP 60 220 Min.:198, Max.:242 170.2 194.0 200 36.0 97.2 93.5 3.15 16.0
54 HP 60 220 Min.:198, Max.:242 173.2 194.0 200 36.0 101.4 97.2 3.15 16.0
56 HP 60 220 Min.:198, Max.:242 176.4 194.0 200 36.0 103.6 104.2 3.60 18.0
58 HP 60 220 Min.:198, Max.:242 189.5 216.0 225 42.0 110.1 105.9 3.60 18.0
60 HP 60 220 Min.:198, Max.:242 191.2 216.0 225 42.0 112.4 109.8 3.60 18.0

Notes:
1. Voltage range
Voltage supplied to the unit terminals should be within the MCA : Minimum Circuit Amperes (A)
minimum and maximum range MSC : Maximum Starting Current
2. Maximum allowable voltage unbalance between phase is 2% RLA : Rated Load Amperes (A)
3. OFM is measured as the outdoor unit test condition. OFM : Outdoor Fan Motor
4. Select wire spec. based on the larger value of MCA. kW : Fan Motor rated output (kW)
5. MSC means the Max. current during the starting of compressor. FLA : Full Load Amperes (A)
6. Recommended circuit breaker is ELCB MFA : Maximum Fuse Amperes (A)
(Earth Leakage Circuit Breaker)

22 _ R410A(50Hz/60Hz)
Heat Pump

10. Piping Diagrams


10.1 8 / 10 / 12 / 14 / 16 HP (1 Comp.)
Cooling Operation

Indoor Heat Exchanger Indoor Heat Exchanger


Electronic Electronic
Expansion Valve Expansion Valve

M M
Fan Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
M Fan Low Temperature Low Pressure Gas

Outdoor Units
Outdoor
Temperature
Sensor

High Pressure High Pressure


Sensor Switch Gas Pipe

Liquid Pipe

4-Way Valve
Outdoor unit Liquid Pipe
HEX Temperature Charging port Temperature
Sensor
Sensor

Suction
Temperature Oil
Sensor Separator

Low
Pressure Comp
Sensor Discharge
Temperature
Sensor Inverter
Compr
-essor

Accumulator
Heatsink

Sub-cooling Circuit
Outlet Temperature
Sensor
Sub-Cooling HEX

Sub-Cooling

Press ure Sensor Temperature Sensor Check valve Soleno id valve


s

Remarks
Press ure Switch SVC Valve Strainer
EEV

R410A(50Hz/60Hz) _ 195
Heat Pump

10. Piping Diagrams


Heating Operation

Indoor Heat Exchanger Indoor Heat Exchanger


Electronic Electronic
Expansion Valve Expansion Valve

M M
Fan Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
M Fan Low Temperature Low Pressure Gas
Outdoor
Outdoor Units

Temperature
Sensor

High Pressure High Pressure


Sensor Switch Gas Pipe

Liquid Pipe

4-Way Valve
Outdoor unit Liquid Pipe
HEX Temperature Temperature
Sensor Charging port
Sensor

Suction
Temperature Oil
Sensor Separator

Low
Pressure Comp
Sensor Discharge
Temperature
Sensor Inverter
Compr
-essor

Accumulator
Heatsink
Sub-cooling Circuit
Outlet Temperature
Sensor
Sub-Cooling HEX

Sub-Cooling

Press ure Sensor Temperature Sensor Check valve Soleno id valve


s

Remarks
Press ure Switch SVC Valve Strainer
EEV

196 _ R410A(50Hz/60Hz)
Heat Pump

10. Piping Diagrams


Oil Return/ Defrost Operation

Indoor Heat Exchanger Indoor Heat Exchanger


Electronic Electronic
Expansion Valve Expansion Valve

M M
Fan Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
M Fan Low Temperature Low Pressure Gas
Outdoor

Outdoor Units
Temperature
Sensor

High Pressure High Pressure


Sensor Switch Gas Pipe

Liquid Pipe

4-Way Valve
Outdoor unit Liquid Pipe
HEX Temperature Temperature
Sensor Charging port
Sensor

Suction
Temperature Oil
Sensor Separator

Low
Pressure Comp
Sensor Discharge
Temperature
Sensor Inverter
Compr
-essor

Accumulator
Heatsink
Sub-cooling Circuit
Outlet Temperature
Sensor
Sub-Cooling HEX

Sub-Cooling

Press ure Sensor Temperature Sensor Check valve Soleno id valve


s

Remarks
Press ure Switch SVC Valve Strainer
EEV

R410A(50Hz/60Hz) _ 197
Heat Pump

10. Piping Diagrams


10.2 18 / 20 (2 Comp.)
Cooling Operation

Indoor Heat Exchanger Indoor Heat Exchanger


Electronic Electronic
Expansion Valve Expansion Valve

M M
Fan Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Outdoor Units

Low Temperature Low Pressure Gas


Outdoor M Fan
Temperature
Sensor

High Pressure High Pressure Gas Pipe


Sensor Switch

Liquid Pipe

4-Way Valve Liquid Pipe


Outdoor unit Temperature
HEX Temperature Charging port Sensor
Sensor

Suction
Temperature Oil Oil
Separ Separ
Sensor -ator -ator

Low
Pressure Compressor1 Compressor2
Sensor Discharge Discharge
Temperature
Sensor Inverter Temperature Inverter
Compr Sensor Compr
-essor1 -essor2

Accumulator

Heatsink
Sub-cooling Circuit
Outlet Temperature
Sensor
Sub-Cooling HEX

Sub-Cooling

Press ure Sensor Temperature Sensor Check valve Soleno id valve


s

Remarks
Press ure Switch SVC Valve Strainer
EEV

198 _ R410A(50Hz/60Hz)
Heat Pump

10. Piping Diagrams


Heating Operation

Indoor Heat Exchanger Indoor Heat Exchanger


Electronic Electronic
Expansion Valve Expansion Valve

M M
Fan Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid

Outdoor Units
Low Temperature Low Pressure Gas
Outdoor M Fan
Temperature
Sensor

High Pressure High Pressure


Sensor Switch
Gas Pipe

Liquid Pipe

4-Way Valve Liquid Pipe


Outdoor unit Temperature
HEX Temperature Sensor
Charging port
Sensor

Suction
Temperature Oil Oil
Separ Separ
Sensor -ator -ator

Low
Pressure Compressor1 Compressor2
Sensor Discharge Discharge
Temperature Temperature Inverter
Sensor Inverter
Compr Sensor Compr
-essor1 -essor2

Heatsink
Accumulator

Sub-cooling Circuit
Outlet Temperature
Sensor
Sub-Cooling HEX

Sub-Cooling

Press ure Sensor Temperature Sensor Check valve Soleno id valve


s

Remarks
Press ure Switch SVC Valve Strainer
EEV

R410A(50Hz/60Hz) _ 199
Heat Pump

10. Piping Diagrams


Oil Return/ Defrost Operation

Indoor Heat Exchanger Indoor Heat Exchanger


Electronic Electronic
Expansion Valve Expansion Valve

M M
Fan Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas
Outdoor M Fan
Outdoor Units

Temperature
Sensor

High Pressure High Pressure Gas Pipe


Sensor Switch

Liquid Pipe

4-Way Valve Liquid Pipe


Outdoor unit Temperature
HEX Temperature Charging port Sensor
Sensor

Suction
Temperature Oil Oil
Separ Separ
Sensor -ator -ator

Low
Pressure Compressor1 Compressor2
Sensor Discharge Discharge
Temperature
Sensor Inverter
Temperature Inverter
Compr Sensor Compr
-essor1 -essor2
Accumulator

Heatsink
Sub-cooling Circuit
Outlet Temperature
Sensor
Sub-Cooling HEX

Sub-Cooling

Press ure Sensor Temperature Sensor Check valve Soleno id valve


s

Remarks
Press ure Switch SVC Valve Strainer
EEV

200 _ R410A(50Hz/60Hz)
Heat Pump

11. Wiring Diagrams


11.2 12 / 14 / 16 HP
Outdoor Units

202 _ R410A(50Hz/60Hz)
Heat Pump

11. Wiring Diagrams


11.3 18 / 20 HP

Outdoor Units

R410A(50Hz/60Hz) _ 203
Heat Pump

12. Field Wiring


12.1 50Hz / 60z
◆ Example Connection of Communication Cable
■ Single Outdoor Unit

Power supply Voltage range(V)


3 Phase 3 Wires Frequency
Outdoor Indoor
[Outdoor Unit] 60Hz 220V 220V
(Main Switch) R S T
(L1) (L2) (L3)
50Hz 220-240V 220-240V
Switch

ELCB
Power supply
1Phase 2Wires

L N
Power Line
(3 Wires Cable)
ELCB Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Outdoor Units

Pull Box Pull Box Pull Box


(Installer option) (Installer option) (Installer option)

Power Line Power Line Power Line Power Line


(2 Wires Cable) (2 Wires Cable) (2 Wires Cable) (2 Wires Cable)

Communication Line
(3 Wires Cable)

[Indoor Units]

WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the
power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this sys-
tem consists of the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and
off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.

Between Indoor and Master Outdoor unit

Master
SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
Outdoor Unit

3(A) 4(A) 3(A) 4(A) 3(A) 4(A)

The GND terminal at the main PCB is a ‘-’ terminal for day contact,
it is not the point to make ground connection.

204 _ R410A(50Hz/60Hz)
Heat Pump

12. Field Wiring


■ Series Outdoor Unit
■ When the power source is connected In series between the units.

Power supply
3 Phase 3 Wires
[Master] [Slave]
(Main Switch) R S T
(L1) (L2) (L3)
Switch

ELCB
Power supply
1Phase 2Wires

L N
Power Line
(3 Wires Cable)
ELCB Power Line
(2 Wires Cable)
Commu
Communication Line
W
(2 Wires Cable)

Pull Box Pull Box Pull Box


(Installer option)
ption) (Installer option) (Installer
aller option)

Outdoor Units
Voltage range(V)
Power Line Power Line Power Line Power Line
Po Frequency
(2 Wires Cable) (2 Wires Cable) (2 Wires Cable) (2 Wires Cable) Outdoor Indoor
60Hz 220V 220V
50Hz 220-240V 220-240V
mmunication Line
Communication
(3 Wires Cable)

[Indoor Units]

WARNING
When the MCA (sum of the maximum current) is over than 150A, the power source do not use in series between the
outdoor units.

■ When the power source is supplied to Each outdoor unit individually.

Power supply
3 Phase 3 Wires
[Master] [Slave]
(Main Switch) R S T R S T
(L1) (L2) (L3) (L1) (L2) (L3)
Switch Switch

ELCB ELCB
Power supply
1Phase 2Wires

L N

Power Line
ELCB Power Line
(3 Wires Cable)
(2 Wires Cable)
Communication Line
(2 Wires Cable)

Pull Box Pull Box Pull Box


(Installer option) (Installer option) (Installer option)

Voltage range(V) Power Line Power Line Power Line Power Line
Frequency (2 Wires Cable) (2 Wires Cable) (2 Wires Cable) (2 Wires Cable)
Outdoor Indoor
60Hz 220V 220V
50Hz 220-240V 220-240V Communication Line
(3 Wires Cable)

[Indoor Units]

R410A(50Hz/60Hz) _ 205
Heat Pump

12. Field Wiring

WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the
power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this sys-
tem consists of the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and
off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.

Between Indoor and Master Outdoor unit

Master Master
SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
Outdoor Unit
Outdoor Units

Outdoor unit

3(A) 4(B) 3(A) 4(B) 3(A) 4(B) SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
Slave1
Outdoor Unit

The GND terminal at the main PCB is a ‘-’ Slave2


terminal for dry contact. SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
Outdoor Unit
It is not the point to make ground
connection.
• Make sure that terminal number of master
and slave outdoor units are Slave3
matched.(A-A,B-B) SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
Outdoor Unit

206 _ R410A(50Hz/60Hz)
Heat Pump

12. Field Wiring


◆ Example Connection of Communication Cable
[BUS type] [STAR type]
• Connection of communication cable must be installed • Abnormal operation can be caused by communication
like below figure between indoor unit to outdoor unit. defect, when connection of communication cable is
installed like below figure(STAR type).

Outdoor Units

R410A(50Hz/60Hz) _ 207