You are on page 1of 21

CHEK'D APP'D CERT'D

KH.A Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


KH.A
REVISED AS PER SEC COMMENTS IN LETTER # 09-50294-030343 DATED 07.12.09
ISSUED FOR APPROVAL
DESCRIPTION

LV AC CABLE SIZING CALCULATION


A.S

A.S
BY

19.10.09

13.12.09
DATE
NO.

REVISIONS
DESIGNED

BY:- A.S

DATE:- 13.12.09

CHECKED

BY:- A.R/KH.A

DATE:- 13.12.09

OPRG. DEPT

BY

DATE:-

ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT DATE


DOCUMENT TITLE INDEX PLANT DOCUMENT NO. SHEET NO. REV.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OF LV AC CABLE SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL
A C173 CE-113347 01 OF 17 1
CERTIFIED AND CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
DATED

RIYADH SAUDI ARABIA JOB ORDER NO. 1-0931045.02 DOC. CONT. SHT. CE-113302
APP'D CERT'D

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


CHEK'D

KH.A

KH.A

INDEX

SHEET NO. CONTENT


2 Index
03 Reference Documents / Design basis
REVISED AS PER SEC COMMENTS IN LETTER # 09-50294-030343 DATED 07.12.09

04-05 Sizing calculation of ACDB Incomer cables


06-17 Sizing calculation of auxiliary AC cables

Attachments List

Attachment-1 RIYADH Cable Co. Cataloug


ISSUED FOR APPROVAL
DESCRIPTION

A.S

A.S
BY

19.10.09

13.12.09
DATE
NO.

REVISIONS
DESIGNED

BY:- A.S

DATE:- 13.12.09

CHECKED

BY:- A.R/KH.A

DATE:- 13.12.09

OPRG. DEPT

BY

DATE:-

ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT DATE


DOCUMENT TITLE INDEX PLANT DOCUMENT NO. SHEET NO. REV.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OF LV AC CABLE SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL
A C173 CE-113347 02 OF 17 1
CERTIFIED AND CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
DATED
RIYADH SAUDI ARABIA JOB ORDER NO. 1-0931045.02 DOC. CONT. SHT. CE-113302
APP'D CERT'D

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


CHEK'D

KH.A

KH.A

Reference Documents :
1 Transmission Engineering Standard – TES-P-104.03: Cable Sizing & Selection
2 Transmission Engineering Standard – TES-P-119.29: LV Cable Selection & Sizing(600 V & Below)
3 Transmission Material Standard Specification 11-TMSS-10: Power and/or AL. Conductor,600 /1000V rating
4 Dwg. No. CA-113554 – One Line Diagram - 220/127V AC
5 Doc. No. CE-113342 – AC Load Schedule & Aux. TR. Sizing Calculation
6 Dwg. No. CA-113549– Substation Overall layout -Plan
7 Scope of Work and Technical Specification - PTS # 08CN300
REVISED AS PER SEC COMMENTS IN LETTER # 09-50294-030343 DATED 07.12.09

8 RIYADH Cable Co. Catalouge ( attachment-1)


Note :-
All 0.6/1kV Cable Data are referred from RIYADH Cable Co. Catalogues
(for calculation purpose)
ISSUED FOR APPROVAL
DESCRIPTION

Design Basis:-

1 The following type of cables are considered:


a) Power cables – 0.6/1kV, Cu., XLPE insulated, LMDPE sheathed for 630Sqmm cable.
b) Power cables – 0.6/1kV, Cu., XLPE insulated, PVC ST 2 sheathed for other cables

2 The following are the limits of voltage drop considered for design:
AC Circuits:-
a) Auxiliary Transformer to ACDB 0.8 %

b) ACDB to Indoor Lighting panel (ILP) 1.6 %


Lighting Panel (ILP) to Indoor lighting circuits 2.6 %

c) ACDB to Outdoor Lighting Panel (LP-OD) 1.6 %


Lighting panel (LP-OD) to Outdoor lighting 2.6 %
A.S

A.S
BY

d) ACDB to SDB 1.6 %


SDB to SDB various loads 2.6 %
19.10.09

13.12.09
DATE

e) ACDB to Battery charger, Oil filtration sockets, etc… 4.2 %


NO.

REVISIONS
DESIGNED

BY:- A.S

DATE:- 13.12.09

CHECKED

BY:- A.R/KH.A

DATE:- 13.12.09

OPRG. DEPT

BY

DATE:-

ENG'G. DEPT.

BY:-

DATE:-

CERTIFIED.

BY:-

DATE:- AS BUILT DATE


DOCUMENT TITLE INDEX PLANT DOCUMENT NO. SHEET NO. REV.
THIS DRAWING IS NOT
TO BE USED FOR
CONSTRUCTION OF LV AC CABLE SIZING CALCULATION
FOR ORDERING
MATERIALS UNTIL
A C173 CE-113347 03 OF 17 1
CERTIFIED AND
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP
DATED
RIYADH SAUDI ARABIA JOB ORDER NO. 1-0931045.02 DOC. CONT. SHT. CE-113302
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫منطقة أعمال الوسطى‬
LV AC CABLE SIZING CALCULATION

Incomer cable sizing from Aux. Trafo to ACDB ( Q101, Q102,Q103 )

Cable From : 2000KVA AUX. TR


Cable To : ACDB
System Voltage (V) = 220 V
Connected Load (S) = 2000000 VA
Current through the feeder = S/√3xV
= 5249 A
Current considered for design (I) = 5249 A
Cable size selected 6x 1C x 630 mm2 Cu./ Phase
and 3x 1C x 630 mm2 Cu./ Neutral
No. of runs (N) = 6
Underated current carrying capacity of the cable (I c) = 1117 A

Derating Factors
Type of Cable laying : Trefoil touching in cable trench
a) K1 - Air Rating factor at 40˚C = 0.91 (As Per Riyadh cable Co. catalouge table 10)
b) K2 - Group rating factor = 0.87 (As per TES-P-119.29 Cl. 7.1.7.a.i)

Net derating Factor (K) = 0.79


Derated current carrying capacity of the cable = K x Ic x N
= 5306 A

The derated current carrying capacity of the cable is higher than the maximum feeder current --> 1

CE-113347, REV.01 4 of 21
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫منطقة أعمال الوسطى‬

Calculation of Voltage Drop

Unit AC resistance of the cable @ 90 oC (R) = 0.042 W / km


Unit reactance of the cable (X) = 0.091 W / km
Total route length of the cable (L) = 13.5 m
Net Resistance of the cable (Rl = L x R / N x 1000) = 0.0001 W
Net Reactance of the cable (X l = L x X / N x 1000) = 0.0002 W 31.79
Load Power Factor - cos f = 0.85
sin f = 0.53
Total Voltage drop (Vd) = √ 3 x I x [Rl cos f + Xl sin f ]
= 1.71 V
% Voltage drop = Vd x 100 / V
= 0.78 %

Permissible Voltage drop = 0.8 %

The actual voltage drop is lesser than the permissible voltage drop --> 2

Check for Short circuit withstand capacity of the cable

The conductor size is checked for short circuit with the following formulae:
Isc =143 x S / √ t , where
t = Duration of Short circuit = 1 second
S = Cross sectional area of the cable = 630 mm2
Substituting in the above equation, we get
Isc = 90090 A
= 90 KA, for one second
Rated fault withstanding current at the Tranformer = 80.325 KA

Short circuit current withstand capacity of the cable is higher than that at the Tranformer -->3

CE-113347, REV.01 5 of 21
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫منطقة أعمال الوسطى‬

From 1,2 & 3 the design is safe.

CE-113347, REV.01 6 of 21
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫منطقة أعمال الوسطى‬
LV AC CABLE SIZING CALCULATION
Derating Factors: %VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated C.B


I Selected Cable R X
S.No. From To KW Phase VOLT PF cables I req. Over current current Length %VD Remarks
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp m Ohm/kM Ohm/kM

PANEL : MAIN DISTRIBUTION BOARD BUS-A 220/127V AC


ACDB INDOOR LIGHTING PANEL -1( LOC - FL Current<Derated
1 134.190 3 220 0.85 414.3 2 207.1 XLPE 4C 150 407 0.91 0.7 0.64 259.26 500 52 0.16 0.09 1.56 Current & %VD is <1.6%
BUS-A CONTROL ROOM) Hence Safe

ACDB INDOOR LIGHTING PANEL -2( LOC -AC/DC FL Current<Derated


2 130.770 3 220 0.85 403.7 2 201.9 XLPE 4C 120 355 0.91 0.7 0.64 226.14 500 16 0.20 0.09 0.55 Current & %VD is <1.6%
BUS-A ROOM) Hence Safe

ACDB OUTDOOR LIGHTING PANEL-2 (LOC -380KV FL Current<Derated


3 117.90 3 220 0.85 364.0 2 182.0 XLPE 1C 630 1117 0.91 0.7 0.64 711.53 500 130 0.04 0.09 1.56 Current & %VD is <1.6%
BUS-A GIS ROOM) Hence Safe

FL Current<Derated
ACDB OUTDOOR LIGHTING PANEL -3( LOC -132KV
4 66.06 3 220 0.85 204.0 2 102.0 XLPE 4C 240 551 0.91 0.7 0.64 350.99 320 130 0.10 0.09 1.38 Current & %VD is <1.6%
BUS-A GIS ROOM) Hence Safe

FL Current<Derated
ACDB 300A OIL FILTERATION SOCKET (REACTOR
5 77.74 3 220 0.85 240.0 1 240.0 XLPE 4C 185 469 0.91 0.7 0.64 298.75 320 65 0.13 0.09 1.94 Current & %VD is <4.2%
BUS-A AREA-1) Hence Safe

FL Current<Derated
ACDB
6 SDB-1A (LOC -380KV GIS BLD) 80.75 3 220 0.85 249.3 2 124.7 XLPE 4C 150 407 0.91 0.7 0.64 259.26 320 85 0.16 0.09 1.53 Current & %VD is <1.6%
BUS-A Hence Safe

FL Current<Derated
ACDB
7 SDB-2 (LOC -132KV GIS BLD) 56.087 3 220 0.85 173.2 2 86.6 XLPE 4C 240 551 0.91 0.7 0.64 350.99 320 150 0.10 0.09 1.35 Current & %VD is <1.6%
BUS-A Hence Safe

FL Current<Derated
ACDB PORTABLE 125V DC BATTERY CHARGER
8 62.50 3 220 0.85 193.0 1 193.0 XLPE 4C 120 355 0.91 0.7 0.64 226.14 250 18 0.20 0.09 0.59 Current & %VD is <4.2%
BUS-A (380KV DC SYSTEM BATTERY CHARGER) Hence Safe

FL Current<Derated
ACDB
9 SDB-1B (LOC -380KV GIS BLD) 43.977 3 220 0.85 135.8 2 67.9 XLPE 4C 185 469 0.91 0.7 0.64 298.75 200 175 0.13 0.09 1.47 Current & %VD is <1.6%
BUS-A Hence Safe

FL Current<Derated
ACDB INDOOR LIGHTING PANEL -5( LOC -132KV
10 50.360 3 220 0.85 155.5 2 77.7 XLPE 4C 185 469 0.91 0.7 0.64 298.75 200 165 0.13 0.09 1.59 Current & %VD is <1.6%
BUS-A GIS ROOM) Hence Safe

FL Current<Derated
ACDB
11 TELECOM ROOM ACDB 31.095 3 220 0.85 96.0 1 96.0 XLPE 4C 35 160 0.91 0.7 0.64 101.92 125 26 0.67 0.10 1.22 Current & %VD is <1.6%
BUS-A Hence Safe

FL Current<Derated
ACDB PORTABLE 125V DC BATTERY CHARGER
12 31.250 3 220 0.85 96.48 1 96.5 XLPE 4C 35 160 0.91 0.7 0.64 101.92 125 22 0.67 0.10 1.04 Current & %VD is <4.2%
BUS-A (132KV DC SYSTEM BATTERY CHARGER) Hence Safe

FL Current<Derated
ACDB
13 SGT-1 FANS GROUP-1 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 25 130 0.82 0.7 0.57 74.62 100 60 0.93 0.10 2.20 Current & %VD is <4.2%
BUS-A Hence Safe

FL Current<Derated
ACDB
14 SGT-1 FANS GROUP-2 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 25 130 0.82 0.7 0.57 74.62 100 60 0.93 0.10 2.20 Current & %VD is <4.2%
BUS-A Hence Safe

FL Current<Derated
ACDB
15 SGT-3 FANS GROUP-1 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 25 130 0.82 0.7 0.57 74.62 100 110 0.93 0.10 4.03 Current & %VD is <4.2%
BUS-A Hence Safe

CE-113347, REV.01 7 of 21
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫منطقة أعمال الوسطى‬
LV AC CABLE SIZING CALCULATION
Derating Factors: %VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated C.B


I Selected Cable R X
S.No. From To KW Phase VOLT PF cables I req. Over current current Length %VD Remarks
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp m Ohm/kM Ohm/kM
ACDB FL Current<Derated
16 SGT-3 FANS GROUP-2 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 25 130 0.82 0.7 0.57 74.62 100 110 0.93 0.10 4.03 Current & %VD is <4.2%
BUS-A Hence Safe

ACDB FL Current<Derated
17 SGT-5 FANS GROUP-1 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 50 195 0.82 0.7 0.57 111.93 100 160 0.49 0.10 3.28 Current & %VD is <4.2%
BUS-A Hence Safe

ACDB FL Current<Derated
18 SGT-5 FANS GROUP-2 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 50 195 0.82 0.7 0.57 111.93 100 160 0.49 0.10 3.28 Current & %VD is <4.2%
BUS-A Hence Safe

ACDB 100A WELDING RECEPTACLE AT HVAC FL Current<Derated


19 25.91 3 220 0.85 80.0 1 80.0 XLPE 4C 70 247 0.82 0.7 0.57 141.78 100 30 0.34 0.10 0.65 Current & %VD is <4.2%
BUS-A PACU-1 Hence Safe

ACDB FL Current<Derated
20 48V DC BATTERY CHARGER-1 8.50 3 220 0.85 26.2 1 26.2 XLPE 4C 10 73 0.91 0.45 0.41 29.89 63 25 2.33 0.11 1.05 Current & %VD is <4.2%
BUS-A Hence Safe

ACDB FL Current<Derated
21 HVAC CONTROL PANEL 15.00 3 220 0.85 46.3 1 46.3 XLPE 4C 16 96 0.91 0.7 0.64 61.15 63 10 1.47 0.11 0.47 Current & %VD is <4.2%
BUS-A Hence Safe

ACDB LIGHTING & SOCKETS,ONLINE GAS FL Current<Derated


22 0.425 3 220 0.85 1.3 1 1.3 XLPE 4C 10 73 0.82 0.45 0.37 26.94 32 75 2.33 0.11 0.16 Current & %VD is <4.2%
BUS-A ANALYSER REACTOR-1 Hence Safe

ACDB LIGHTING & SOCKETS,ONLINE GAS FL Current<Derated


23 0.425 3 220 0.85 1.3 1 1.3 XLPE 4C 10 73 0.82 0.45 0.37 26.94 32 90 2.33 0.11 0.19 Current & %VD is <4.2%
BUS-A ANALYSER REACTOR-2 Hence Safe

ACDB SGT-1 MK ( Lamp , Heater , Thermostat , FL Current<Derated


24 3.732 1 220 0.85 20.0 1 20.0 XLPE 4C 10 73 0.82 0.45 0.37 26.94 32 60 2.33 0.11 2.22 Current & %VD is <4.2%
BUS-A Moisture-In-Oil Monitor & Receptacle) Hence Safe

ACDB FL Current<Derated
25 SGT-1 PIT PUMP 2.983 3 220 0.85 9.2 1 9.2 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 60 2.33 0.11 0.89 Current & %VD is <4.2%
BUS-A Hence Safe

ACDB FL Current<Derated
26 SGT-2 PIT PUMP 2.983 3 220 0.85 9.2 1 9.2 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 80 2.33 0.11 1.18 Current & %VD is <4.2%
BUS-A Hence Safe

ACDB FL Current<Derated
27 SGT-5 PIT PUMP 2.983 3 220 0.85 9.2 1 9.2 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 160 2.33 0.11 2.37 Current & %VD is <4.2%
BUS-A Hence Safe

ACDB FL Current<Derated
28 SUMP PUMP CONTROL BLD BASEMENT 1.800 3 220 0.85 5.6 1 5.6 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 21 2.33 0.11 0.19 Current & %VD is <4.2%
BUS-A Hence Safe
SUMP PUMP TUNNEL-A1 FL Current<Derated
ACDB
29 (380KV CONTROL CABLES TUNNEL) 3.60 3 220 0.85 11.1 1 11.1 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 60 2.33 0.11 1.07 Current & %VD is <4.2%
BUS-A Hence Safe

ACDB FL Current<Derated
30 REACTOR -1 PIT PUMP 2.98 3 220 0.85 9.2 1 9.2 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 75 2.33 0.11 1.11 Current & %VD is <4.2%
BUS-A Hence Safe

ACDB FL Current<Derated
31 AUXILIARY SUPPLY FOR GT-1 2.914 3 220 0.85 9.0 1 9.0 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 57 2.33 0.11 0.82 Current & %VD is <4.2%
BUS-A Hence Safe

PANEL : MAIN DISTRIBUTION BOARD BUS-B 220/127V AC

CE-113347, REV.01 8 of 21
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫منطقة أعمال الوسطى‬
LV AC CABLE SIZING CALCULATION
Derating Factors: %VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated C.B


I Selected Cable R X
S.No. From To KW Phase VOLT PF cables I req. Over current current Length %VD Remarks
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp m Ohm/kM Ohm/kM
ACDB FL Current<Derated
32 HVAC PANEL-3(LOC -132KV GIS BLD) 210.17 3 220 0.85 648.9 4 162.2 XLPE 1C 630 1117 0.91 0.7 0.64 711.53 800 137 0.04 0.09 1.46 Current & %VD is <1.6%
BUS-B Hence Safe

ACDB INDOOR LIGHTING PANEL -1( LOC - FL Current<Derated


33 134.190 3 220 0.85 414.3 2 207.1 XLPE 4C 150 407 0.91 0.7 0.64 259.26 500 52 0.16 0.09 1.56 Current & %VD is <1.6%
BUS-B CONTROL ROOM) Hence Safe

ACDB INDOOR LIGHTING PANEL -2( LOC -AC/DC FL Current<Derated


34 130.770 3 220 0.85 403.7 2 201.9 XLPE 4C 120 355 0.91 0.7 0.64 226.14 500 16 0.20 0.09 0.55 Current & %VD is <1.6%
BUS-B ROOM) Hence Safe

ACDB OUTDOOR LIGHTING PANEL-2 (LOC -380KV FL Current<Derated


35 117.90 3 220 0.85 364.0 2 182.0 XLPE 1C 630 1117 0.91 0.7 0.64 711.53 500 130 0.04 0.09 1.56 Current & %VD is <1.6%
BUS-B GIS ROOM) Hence Safe

ACDB OUTDOOR LIGHTING PANEL -3( LOC -132KV FL Current<Derated


36 66.06 3 220 0.85 204.0 2 102.0 XLPE 4C 240 551 0.91 0.7 0.64 350.99 320 130 0.10 0.09 1.38 Current & %VD is <1.6%
BUS-B GIS ROOM) Hence Safe

ACDB FL Current<Derated
37 SDB-1A (LOC -380KV GIS BLD) 67.77 3 220 0.85 143.0 2 71.5 XLPE 4C 95 305 0.91 0.7 0.64 194.29 320 85 0.25 0.09 1.24 Current & %VD is <1.6%
BUS-B Hence Safe

ACDB FL Current<Derated
38 SDB-2 (LOC -132KV GIS BLD) 75.449 3 220 0.85 232.9 3 77.6 XLPE 4C 185 469 0.91 0.7 0.64 298.75 320 150 0.13 0.09 1.44 Current & %VD is <1.6%
BUS-B Hence Safe

ACDB OIL FILTERATION SOCKET FOR AUXILIARY FL Current<Derated


39 77.74 3 220 0.85 240.00 2 120.0 XLPE 4C 120 355 0.82 0.7 0.57 203.77 320 10 0.20 0.09 0.20 Current & %VD is <1.6%
BUS-B TRANSFORMER Hence Safe

ACDB 125V DC BATTERY CHARGER-2 FL Current<Derated


40 62.50 3 220 0.85 193.0 1 193.0 XLPE 4C 120 355 0.91 0.7 0.64 226.14 250 18 0.20 0.09 0.59 Current & %VD is <4.2%
BUS-B (380KV DC SYSTEM BATTERY CHARGER) Hence Safe

ACDB OUTDOOR LIGHTING PANEL-1 (LOC -AC/DC FL Current<Derated


41 45.90 3 220 0.85 141.7 1 141.7 XLPE 4C 70 247 0.91 0.7 0.64 157.34 200 16 0.34 0.10 0.61 Current & %VD is <1.6%
BUS-B ROOM) Hence Safe

ACDB FL Current<Derated
42 SDB-1B (LOC -380KV GIS BLD) 43.937 3 220 0.85 135.6 2 67.8 XLPE 4C 185 469 0.91 0.7 0.64 298.75 200 175 0.13 0.09 1.47 Current & %VD is <1.6%
BUS-B Hence Safe

ACDB INDOOR LIGHTING PANEL -3( LOC -380KV FL Current<Derated


43 50.360 3 220 0.85 155.5 1 155.5 XLPE 4C 150 407 0.91 0.7 0.64 259.26 200 70 0.16 0.09 1.58 Current & %VD is <1.6%
BUS-B GIS ROOM) Hence Safe

ACDB INDOOR LIGHTING PANEL -4( LOC -380KV FL Current<Derated


44 50.360 3 220 0.85 155.5 2 77.7 XLPE 4C 150 407 0.91 0.7 0.64 259.26 200 137 0.16 0.09 1.54 Current & %VD is <1.6%
BUS-B GIS ROOM) Hence Safe

ACDB INDOOR LIGHTING PANEL -5( LOC -132KV FL Current<Derated


45 50.360 3 220 0.85 155.5 2 77.7 XLPE 4C 185 469 0.91 0.7 0.64 298.75 200 165 0.13 0.09 1.59 Current & %VD is <1.6%
BUS-B GIS ROOM) Hence Safe

ACDB PORTABLE 125V DC BATTERY CHARGER FL Current<Derated


46 31.250 3 220 0.85 96.48 1 96.5 XLPE 4C 35 160 0.91 0.7 0.64 101.92 125 22 0.67 0.10 1.04 Current & %VD is <4.2%
BUS-B (132KV DC SYSTEM BATTERY CHARGER) Hence Safe

ACDB 100A WELDING RECEPTACLE AT HVAC FL Current<Derated


47 25.91 3 220 0.85 80.0 1 80.0 XLPE 4C 70 247 0.91 0.7 0.64 157.34 100 195 0.34 0.10 4.20 Current & %VD is <4.2%
BUS-B PACU-2 Hence Safe

ACDB FL Current<Derated
48 48V DC BATTERY CHARGER-2 8.50 3 220 0.85 26.2 1 26.2 XLPE 4C 10 73 0.91 0.45 0.41 29.89 63 25 2.33 0.11 1.05 Current & %VD is <4.2%
BUS-B Hence Safe

CE-113347, REV.01 9 of 21
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫منطقة أعمال الوسطى‬
LV AC CABLE SIZING CALCULATION
Derating Factors: %VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated C.B


I Selected Cable R X
S.No. From To KW Phase VOLT PF cables I req. Over current current Length %VD Remarks
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp m Ohm/kM Ohm/kM
ACDB SGT-2 MK ( Lamp , Heater , Thermostat , FL Current<Derated
49 3.732 1 220 0.85 11.5 1 11.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 32 80 2.33 0.11 1.71 Current & %VD is <4.2%
BUS-B Moisture-In-Oil Monitor & Receptacle) Hence Safe

ACDB SGT-5 MK ( Lamp , Heater , Thermostat , FL Current<Derated


50 3.732 1 220 0.85 11.5 1 11.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 32 160 2.33 0.11 3.42 Current & %VD is <4.2%
BUS-B Moisture-In-Oil Monitor & Receptacle) Hence Safe
SUMP PUMP TUNNEL-B1 FL Current<Derated
ACDB
51 (132KV CONTROL CABLES TUNNEL) 3.600 3 220 0.85 11.1 1 11.1 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 31 2.33 0.11 0.55 Current & %VD is <4.2%
BUS-B Hence Safe

ACDB FL Current<Derated
52 SGT-1 OLTC DRIVE MOTOR 2.890 3 220 0.85 8.9 1 8.9 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 60 2.33 0.11 0.86 Current & %VD is <4.2%
BUS-B Hence Safe

ACDB FL Current<Derated
53 SGT-2 OLTC DRIVE MOTOR 2.890 3 220 0.85 8.9 1 8.9 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 80 2.33 0.11 1.15 Current & %VD is <4.2%
BUS-B Hence Safe

ACDB FL Current<Derated
54 SGT-5 OLTC DRIVE MOTOR 2.890 3 220 0.85 8.9 1 8.9 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 160 2.33 0.11 2.29 Current & %VD is <4.2%
BUS-B Hence Safe

ACDB FL Current<Derated
55 SGT-1 OLTC HEATER SUPPLY 0.170 3 220 0.85 0.5 1 0.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 60 2.33 0.11 0.05 Current & %VD is <4.2%
BUS-B Hence Safe

ACDB FL Current<Derated
56 SGT-2 OLTC HEATER SUPPLY 0.170 3 220 0.85 0.5 1 0.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 80 2.33 0.11 0.07 Current & %VD is <4.2%
BUS-B Hence Safe

ACDB FL Current<Derated
57 SGT-5 OLTC HEATER SUPPLY 0.170 3 220 0.85 0.5 1 0.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 160 2.33 0.11 0.13 Current & %VD is <4.2%
BUS-B Hence Safe

ACDB FL Current<Derated
58 WATER TRANSFER PUMP 2.237 3 220 0.85 6.9 1 6.9 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 60 2.33 0.11 0.67 Current & %VD is <4.2%
BUS-B Hence Safe

ACDB FL Current<Derated
59 LIGHTING SIGN BOARD 0.550 3 220 0.85 1.7 1 1.7 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 300 2.33 0.11 0.82 Current & %VD is <4.2%
BUS-B Hence Safe

ACDB FL Current<Derated
60 GATE HOUSE LIGHTING 0.392 4 127 0.85 2.1 1 2.1 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 290 2.33 0.11 1.95 Current & %VD is <4.2%
BUS-B Hence Safe

ACDB FL Current<Derated
61 AUXILIARY SUPPLY FOR GT-2 2.914 3 220 0.85 9.0 1 9.0 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 105 2.33 0.11 1.52 Current & %VD is <4.2%
BUS-B Hence Safe

PANEL : MAIN DISTRIBUTION BOARD BUS-C 220/127V AC


ACDB FL Current<Derated
62 HVAC PANEL-2(LOC -380KV GIS BLD) 309.22 3 220 0.85 954.7 5 190.9 XLPE 1C 630 1117 0.91 0.7 0.64 711.53 1250 120 0.04 0.09 1.51 Current & %VD is <1.6%
BUS-C Hence Safe

ACDB FL Current<Derated
63 HVAC PANEL-1(LOC -CONTROL BLD) 195.72 3 220 0.85 604.2 2 302.1 XLPE 4C 240 551 0.91 0.7 0.64 350.99 800 40 0.10 0.09 1.25 Current & %VD is <1.6%
BUS-C Hence Safe

ACDB FL Current<Derated
64 300A OIL FILTERATION SOCKET (TRF AREA) 77.74 3 220 0.85 240.0 1 240.0 XLPE 4C 150 407 0.91 0.7 0.64 259.26 320 110 0.16 0.09 3.82 Current & %VD is <4.2%
BUS-C Hence Safe

CE-113347, REV.01 10 of 21
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫منطقة أعمال الوسطى‬
LV AC CABLE SIZING CALCULATION
Derating Factors: %VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated C.B


I Selected Cable R X
S.No. From To KW Phase VOLT PF cables I req. Over current current Length %VD Remarks
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp m Ohm/kM Ohm/kM
ACDB 125V DC BATTERY CHARGER-1 FL Current<Derated
65 62.50 3 220 0.85 193.0 1 193.0 XLPE 4C 120 355 0.91 0.7 0.64 226.14 250 18 0.20 0.09 0.59 Current & %VD is <4.2%
BUS-C (380KV DC SYSTEM BATTERY CHARGER) Hence Safe

ACDB OUTDOOR LIGHTING PANEL-1 (LOC -AC/DC FL Current<Derated


66 45.90 3 220 0.85 141.7 1 141.7 XLPE 4C 70 247 0.91 0.7 0.64 157.34 200 16 0.34 0.10 0.61 Current & %VD is <1.6%
BUS-C ROOM) Hence Safe

ACDB INDOOR LIGHTING PANEL -3( LOC -380KV FL Current<Derated


67 50.360 3 220 0.85 155.5 1 155.5 XLPE 4C 150 407 0.91 0.7 0.64 259.26 200 70 0.16 0.09 1.58 Current & %VD is <1.6%
BUS-C GIS ROOM) Hence Safe

ACDB INDOOR LIGHTING PANEL -4( LOC -380KV FL Current<Derated


68 50.360 3 220 0.85 155.5 2 77.7 XLPE 4C 150 407 0.91 0.7 0.64 259.26 200 137 0.16 0.09 1.54 Current & %VD is <1.6%
BUS-C GIS ROOM) Hence Safe

ACDB PORTABLE 125V DC BATTERY CHARGER FL Current<Derated


69 31.250 3 220 0.85 96.48 1 96.5 XLPE 4C 35 160 0.91 0.7 0.64 101.92 125 22 0.67 0.10 1.04 Current & %VD is <4.2%
BUS-C (132KV DC SYSTEM BATTERY CHARGER) Hence Safe

ACDB FL Current<Derated
70 100A RECEPTACLE FOR TRF AREA 25.91 3 220 0.85 80.0 1 80.0 XLPE 4C 50 195 0.91 0.7 0.64 124.22 100 110 0.49 0.10 3.27 Current & %VD is <4.2%
BUS-C Hence Safe

ACDB FL Current<Derated
71 100A RECEPTACLE FOR REACTOR AREA 25.91 3 220 0.85 80.0 1 80.0 XLPE 4C 50 195 0.91 0.7 0.64 124.22 100 65 0.49 0.10 1.93 Current & %VD is <4.2%
BUS-C Hence Safe

ACDB FL Current<Derated
72 SGT-2 FANS GROUP-1 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 25 130 0.82 0.7 0.57 74.62 100 80 0.93 0.10 2.93 Current & %VD is <4.2%
BUS-C Hence Safe

ACDB FL Current<Derated
73 SGT-2 FANS GROUP-2 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 25 130 0.82 0.7 0.57 74.62 100 80 0.93 0.10 2.93 Current & %VD is <4.2%
BUS-C Hence Safe

ACDB FL Current<Derated
74 SGT-4 FANS GROUP-1 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 35 160 0.82 0.7 0.57 91.84 100 135 0.67 0.10 3.64 Current & %VD is <4.2%
BUS-C Hence Safe

ACDB FL Current<Derated
75 SGT-4 FANS GROUP-2 17.879 3 220 0.85 55.2 1 55.2 XLPE 4C 35 160 0.82 0.7 0.57 91.84 100 135 0.67 0.10 3.64 Current & %VD is <4.2%
BUS-C Hence Safe

ACDB SGT-3 MK ( Lamp , Heater , Thermostat , FL Current<Derated


76 3.732 1 220 0.85 11.5 1 11.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 32 110 2.33 0.11 2.35 Current & %VD is <4.2%
BUS-C Moisture-In-Oil Monitor & Receptacle) Hence Safe

ACDB SGT-4 MK ( Lamp , Heater , Thermostat , FL Current<Derated


77 3.732 1 220 0.85 11.5 1 11.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 32 135 2.33 0.11 2.88 Current & %VD is <4.2%
BUS-C Moisture-In-Oil Monitor & Receptacle) Hence Safe

ACDB FL Current<Derated
78 SGT-3 PIT PUMP 2.983 3 220 0.85 9.2 1 9.2 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 110 2.33 0.11 1.63 Current & %VD is <4.2%
BUS-C Hence Safe

ACDB FL Current<Derated
79 SGT-4 PIT PUMP 2.983 3 220 0.85 9.2 1 9.2 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 135 2.33 0.11 2.00 Current & %VD is <4.2%
BUS-C Hence Safe

ACDB FL Current<Derated
80 SGT-3 OLTC DRIVE MOTOR 2.890 3 220 0.85 8.9 1 8.9 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 110 2.33 0.11 1.58 Current & %VD is <4.2%
BUS-C Hence Safe

ACDB FL Current<Derated
81 SGT-4 OLTC DRIVE MOTOR 2.890 3 220 0.85 8.9 1 8.9 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 135 2.33 0.11 1.93 Current & %VD is <4.2%
BUS-C Hence Safe

CE-113347, REV.01 11 of 21
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫منطقة أعمال الوسطى‬
LV AC CABLE SIZING CALCULATION
Derating Factors: %VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated C.B


I Selected Cable R X
S.No. From To KW Phase VOLT PF cables I req. Over current current Length %VD Remarks
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp m Ohm/kM Ohm/kM
ACDB FL Current<Derated
82 SGT-3 OLTC HEATER SUPPLY 0.170 3 220 0.85 0.5 1 0.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 110 2.33 0.11 0.09 Current & %VD is <4.2%
BUS-C Hence Safe

ACDB FL Current<Derated
83 SGT-4 OLTC HEATER SUPPLY 0.170 3 220 0.85 0.5 1 0.5 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 135 2.33 0.11 0.11 Current & %VD is <4.2%
BUS-C Hence Safe

ACDB FL Current<Derated
84 BOASTER PUMP 2.237 3 220 0.85 6.9 1 6.9 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 60 2.33 0.11 0.67 Current & %VD is <4.2%
BUS-C Hence Safe

ACDB FL Current<Derated
85 AUXILIARY SUPPLY FOR GT-3 2.914 3 220 0.85 9.0 1 9.0 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 133 2.33 0.11 1.92 Current & %VD is <4.2%
BUS-C Hence Safe

ACDB FL Current<Derated
86 AUXILIARY SUPPLY FOR GT-4 2.914 3 220 0.85 9.0 1 9.0 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 161 2.33 0.11 2.33 Current & %VD is <4.2%
BUS-C Hence Safe

SUB-DISTRIBUTION BOARD-1A (BUS-A)

FL Current<Derated
SDB-1A (
87 100A,HIGH VOLTAGE TEST SOCKET-1 25.912 3 220 0.85 80.00 1 80.00 XLPE 4C 25 130 0.91 0.7 0.64 82.81 100 18 0.93 0.10 0.95 Current & %VD is <2.6%
BUS-A) Hence Safe

SDB-1A ( FL Current<Derated
88 100A,RECEPTACLE AT HVAC PACU-3 25.91 3 220 0.85 80.00 1 80.00 XLPE 4C 35 160 0.82 0.7 0.57 91.84 100 35 0.67 0.10 1.37 Current & %VD is <2.6%
BUS-A) Hence Safe

SDB-1A ( FL Current<Derated
89 63A,GAS FILLING RECEPTACLE-1 16.325 3 220 0.85 50.40 1 50.40 XLPE 4C 16 96 0.91 0.7 0.64 61.15 63 30 1.47 0.11 1.55 Current & %VD is <2.6%
BUS-A) Hence Safe

SUMP PUMP TUNNEL-A1 FL Current<Derated


SDB-1A (
90 (380KV CONTROL CABLES TUNNEL) 1.80 3 220 0.85 5.56 1 5.56 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 115 2.33 0.11 1.03 Current & %VD is <2.6%
BUS-A) Hence Safe

SUMP PUMP TUNNEL-A2 FL Current<Derated


SDB-1A (
91 (380KV CONTROL CABLES TUNNEL) 1.80 3 220 0.85 5.56 1 5.56 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 120 2.33 0.11 1.07 Current & %VD is <2.6%
BUS-A) Hence Safe

SDB-1A ( FL Current<Derated
92 380KV LCC (C02-A) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 40 2.33 0.11 0.20 Current & %VD is <2.6%
BUS-A) Hence Safe

SDB-1A ( FL Current<Derated
93 380KV LCC (C02-B) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 40 2.33 0.11 0.20 Current & %VD is <2.6%
BUS-A) Hence Safe

SDB-1A ( FL Current<Derated
94 380KV LCC (C02-C) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 40 2.33 0.11 0.20 Current & %VD is <2.6%
BUS-A) Hence Safe

FL Current<Derated
SDB-1A (
95 380KV LCC (C03-A) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 54 2.33 0.11 0.27 Current & %VD is <2.6%
BUS-A) Hence Safe

CE-113347, REV.01 12 of 21
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫منطقة أعمال الوسطى‬
LV AC CABLE SIZING CALCULATION
Derating Factors: %VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated C.B


I Selected Cable R X
S.No. From To KW Phase VOLT PF cables I req. Over current current Length %VD Remarks
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp m Ohm/kM Ohm/kM

SDB-1A ( FL Current<Derated
96 380KV LCC (C03-B) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 54 2.33 0.11 0.27 Current & %VD is <2.6%
BUS-A) Hence Safe

SDB-1A ( FL Current<Derated
97 380KV LCC (C03-C) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 54 2.33 0.11 0.27 Current & %VD is <2.6%
BUS-A) Hence Safe

SDB-1A ( FL Current<Derated
98 380KV LCC (C04-A) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 68 2.33 0.11 0.34 Current & %VD is <2.6%
BUS-A) Hence Safe

SDB-1A ( FL Current<Derated
99 380KV LCC (C04-B) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 68 2.33 0.11 0.34 Current & %VD is <2.6%
BUS-A) Hence Safe

FL Current<Derated
SDB-1A (
100 380KV LCC (C04-C) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 68 2.33 0.11 0.34 Current & %VD is <2.6%
BUS-A) Hence Safe

SUB-DISTRIBUTION BOARD-1A (BUS-B)

SDB-1A ( FL Current<Derated
101 100A,HIGH VOLTAGE TEST SOCKET-2 25.912 3 220 0.85 80.00 1 80.00 XLPE 4C 70 247 0.91 0.7 0.64 157.34 100 90 0.34 0.10 1.94 Current & %VD is <2.6%
BUS-B) Hence Safe

SDB-1A ( FL Current<Derated
102 HVAC CONTROL PANEL-2(380KV GIS BLD) 20.000 3 220 0.85 61.75 1 61.75 XLPE 4C 25 130 0.91 0.7 0.64 82.81 100 60 0.93 0.10 2.46 Current & %VD is <2.6%
BUS-B) Hence Safe

SDB-1A ( FL Current<Derated
103 EOT CRANE 6.750 3 220 0.85 20.84 1 20.84 XLPE 4C 10 73 0.91 0.45 0.41 29.89 63 25 2.33 0.11 0.84 Current & %VD is <2.6%
BUS-B) Hence Safe

FL Current<Derated
SDB-1A ( SUMP PUMP TUNNEL-A3
104 1.80 3 220 0.85 5.56 1 5.56 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 115 2.33 0.11 1.03 Current & %VD is <2.6%
BUS-B) (380KV O/G CABLES TUNNEL) Hence Safe

SDB-1A ( FL Current<Derated
105 ROLLING SHUTTER MOTOR-1 1.70 3 220 0.85 5.25 1 5.25 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 25 2.33 0.11 0.21 Current & %VD is <2.6%
BUS-B) Hence Safe

SDB-1A ( 380KV OUTDOOR CT'S MISCELLANEOUS FL Current<Derated


106 2.610 3 220 0.85 8.06 1 8.06 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 95 2.33 0.11 1.23 Current & %VD is <2.6%
BUS-B) HEATERS Hence Safe

SDB-1A ( FL Current<Derated
107 380KV LCC (C05-A) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 82 2.33 0.11 0.41 Current & %VD is <2.6%
BUS-B) Hence Safe

SDB-1A ( FL Current<Derated
108 380KV LCC (C05-B) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 82 2.33 0.11 0.41 Current & %VD is <2.6%
BUS-B) Hence Safe

FL Current<Derated
SDB-1A (
109 380KV LCC (C05-C) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 82 2.33 0.11 0.41 Current & %VD is <2.6%
BUS-B) Hence Safe

CE-113347, REV.01 13 of 21
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫منطقة أعمال الوسطى‬
LV AC CABLE SIZING CALCULATION
Derating Factors: %VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated C.B


I Selected Cable R X
S.No. From To KW Phase VOLT PF cables I req. Over current current Length %VD Remarks
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp m Ohm/kM Ohm/kM

SDB-1A ( FL Current<Derated
110 380KV LCC (C06-A) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 96 2.33 0.11 0.48 Current & %VD is <2.6%
BUS-B) Hence Safe

FL Current<Derated
SDB-1A (
111 380KV LCC (C06-B) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 96 2.33 0.11 0.48 Current & %VD is <2.6%
BUS-B) Hence Safe

SDB-1A ( FL Current<Derated
112 380KV LCC (C06-C) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 96 2.33 0.11 0.48 Current & %VD is <2.6%
BUS-B) Hence Safe

SDB-1A ( FL Current<Derated
113 380KV LCC (C07-A) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 110 2.33 0.11 0.55 Current & %VD is <2.6%
BUS-B) Hence Safe

SDB-1A ( FL Current<Derated
114 380KV LCC (C07-B) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 110 2.33 0.11 0.55 Current & %VD is <2.6%
BUS-B) Hence Safe

SDB-1A ( FL Current<Derated
115 380KV LCC (C07-C) CB MOTOR SUPPLY 1.00 3 220 0.85 3.09 1 3.09 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 110 2.33 0.11 0.55 Current & %VD is <2.6%
BUS-B) Hence Safe

SUB-DISTRIBUTION BOARD-1B (BUS-A)

SDB-1B ( FL Current<Derated
116 100A,RECEPTACLE AT HVAC PACU-2 25.912 3 220 0.85 80.00 1 80.00 XLPE 4C 35 160 0.82 0.7 0.57 91.84 100 30 0.67 0.10 1.17 Current & %VD is <2.6%
BUS-A) Hence Safe

FL Current<Derated
SDB-1B (
117 63A,GAS FILLING RECEPTACLE-2 16.325 3 220 0.85 50.40 1 50.40 XLPE 4C 16 96 0.91 0.7 0.64 61.15 63 40 1.47 0.11 2.07 Current & %VD is <2.6%
BUS-A) Hence Safe

SDB-1B ( 380KV OUTDOOR CT'S MISCELLANEOUS FL Current<Derated


118 1.740 3 220 0.85 5.37 1 5.37 XLPE 4C 10 73 0.82 0.45 0.37 26.94 20 95 2.33 0.11 0.82 Current & %VD is <2.6%
BUS-A) HEATERS Hence Safe

SUB-DISTRIBUTION BOARD-1B (BUS-B)

FL Current<Derated
SDB-1B (
119 100A,RECEPTACLE AT HVAC PACU-1 25.91 3 220 0.85 80.00 1 80.00 XLPE 4C 50 195 0.82 0.7 0.57 111.93 100 75 0.49 0.10 2.23 Current & %VD is <2.6%
BUS-B) Hence Safe

SDB-1B ( FL Current<Derated
120 63A,GAS FILLING RECEPTACLE-3 16.325 3 220 0.85 50.40 1 50.40 XLPE 4C 16 96 0.91 0.7 0.64 61.15 63 20 1.47 0.11 1.03 Current & %VD is <2.6%
BUS-B) Hence Safe

SDB-1B ( FL Current<Derated
121 ROLLING SHUTTER MOTOR-2 1.70 3 220 0.85 5.25 1 5.25 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 35 2.33 0.11 0.30 Current & %VD is <2.6%
BUS-B) Hence Safe

SUB-DISTRIBUTION BOARD-2 (BUS-A)

CE-113347, REV.01 14 of 21
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫منطقة أعمال الوسطى‬
LV AC CABLE SIZING CALCULATION
Derating Factors: %VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated C.B


I Selected Cable R X
S.No. From To KW Phase VOLT PF cables I req. Over current current Length %VD Remarks
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp m Ohm/kM Ohm/kM

SDB-2 ( FL Current<Derated
122 100A,RECEPTACLE AT HVAC UNITS -1 25.912 3 220 0.85 80.00 1 80.00 XLPE 4C 35 160 0.82 0.7 0.57 91.84 100 35 0.67 0.10 1.37 Current & %VD is <2.6%
BUS-A) Hence Safe

FL Current<Derated
SDB-2 (
123 63A,GAS FILLING RECEPTACLES # 1,2,3 16.325 3 220 0.85 50.40 1 50.40 XLPE 4C 25 130 0.91 0.7 0.64 82.81 63 70 0.93 0.10 2.34 Current & %VD is <2.6%
BUS-A) Hence Safe

SDB-2 ( FL Current<Derated
124 EOT CRANE 6.750 3 220 0.85 20.84 1 20.84 XLPE 4C 16 96 0.91 0.7 0.64 61.15 63 95 1.47 0.11 2.03 Current & %VD is <2.6%
BUS-A) Hence Safe

SDB-2 ( FL Current<Derated
125 ROLLING SHUTTER MOTOR DOOR-1 1.70 3 220 0.85 5.25 1 5.25 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 90 2.33 0.11 0.76 Current & %VD is <2.6%
BUS-A) Hence Safe

SDB-2 ( FL Current<Derated
126 SUMP PUMP-1&2 132KV GIS BASEMENT 3.60 3 220 0.85 11.11 1 11.11 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 80 2.33 0.11 1.43 Current & %VD is <2.6%
BUS-A) Hence Safe

SDB-1A ( SUMP PUMP TUNNEL-B2 FL Current<Derated


127 1.80 3 220 0.85 5.56 1 5.56 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 195 2.33 0.11 1.74 Current & %VD is <2.6%
BUS-B) (132KV O/G CABLES TUNNEL) Hence Safe

SUB-DISTRIBUTION BOARD-2 (BUS-B)

SDB-2 ( FL Current<Derated
128 100A,RECEPTACLE AT HVAC UNITS -2 25.912 3 220 0.85 80.00 1 80.00 XLPE 4C 70 247 0.82 0.45 0.37 91.14 100 65 0.34 0.10 1.40 Current & %VD is <2.6%
BUS-B) Hence Safe

SDB-2 ( FL Current<Derated
129 100A,RECEPTACLE AT HVAC UNITS -3 25.912 3 220 0.85 80.00 1 80.00 XLPE 4C 70 247 0.82 0.45 0.37 91.14 100 55 0.34 0.10 1.18 Current & %VD is <2.6%
BUS-B) Hence Safe

FL Current<Derated
SDB-2 (
130 63A,GAS FILLING RECEPTACLES # 4,5,6 16.325 3 220 0.85 50.40 1 50.40 XLPE 4C 16 96 0.91 0.7 0.64 61.15 63 45 1.47 0.11 2.32 Current & %VD is <2.6%
BUS-B) Hence Safe

SDB-2 ( FL Current<Derated
131 HVAC CONTROL PANEL-2(132KV GIS BLD) 2.00 3 220 0.85 6.17 1 6.17 XLPE 4C 10 73 0.91 0.45 0.41 29.89 63 40 2.33 0.11 0.40 Current & %VD is <2.6%
BUS-B) Hence Safe

FL Current<Derated
SDB-2 (
132 SUMP PUMP-3 132KV GIS BASEMENT 1.80 3 220 0.85 5.56 1 5.56 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 90 2.33 0.11 0.80 Current & %VD is <2.6%
BUS-B) Hence Safe

SDB-2 ( FL Current<Derated
133 ROLLING SHUTTER MOTOR DOOR-2 1.70 3 220 0.85 5.25 1 5.25 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 40 2.33 0.11 0.34 Current & %VD is <2.6%
BUS-B) Hence Safe

SDB-1A ( SUMP PUMP TUNNEL-B3 FL Current<Derated


134 1.80 3 220 0.85 5.56 1 5.56 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 155 2.33 0.11 1.38 Current & %VD is <2.6%
BUS-B) (132KV O/G CABLES TUNNEL) Hence Safe

HVAC PANEL-1

CE-113347, REV.01 15 of 21
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫منطقة أعمال الوسطى‬
LV AC CABLE SIZING CALCULATION
Derating Factors: %VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated C.B


I Selected Cable R X
S.No. From To KW Phase VOLT PF cables I req. Over current current Length %VD Remarks
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp m Ohm/kM Ohm/kM
FL Current<Derated
135 HVAC-1 PACU-1A (DUTY) 68.300 3 220 0.85 210.87 1 210.87 XLPE 4C 150 407 0.82 0.7 0.57 233.62 320 62 0.16 0.09 1.89 Current & %VD is <2.6%
Hence Safe

FL Current<Derated
136 HVAC-1 PACU-2A (DUTY) 73.470 3 220 0.85 226.83 1 226.83 XLPE 4C 185 469 0.82 0.7 0.57 269.21 320 92 0.13 0.09 2.59 Current & %VD is <2.6%
Hence Safe

FL Current<Derated
137 HVAC-1 PACU-1B (STANDBY) 68.300 3 220 0.85 210.87 1 210.87 XLPE 4C 150 407 0.82 0.7 0.57 233.62 320 62 0.16 0.09 1.89 Current & %VD is <2.6%
Hence Safe

FL Current<Derated
138 HVAC-1 PACU-2B (STANDBY) 73.470 3 220 0.85 226.83 1 226.83 XLPE 4C 185 469 0.82 0.7 0.57 269.21 320 92 0.13 0.09 2.59 Current & %VD is <2.6%
Hence Safe

FL Current<Derated
139 HVAC-1 ELECTRIC DUCT HEATER (AC/DC ROOM) 45.000 3 220 0.85 138.93 1 138.93 XLPE 4C 70 247 0.91 0.7 0.64 157.34 200 30 0.34 0.10 1.12 Current & %VD is <2.6%
Hence Safe

SUPPLY FAN- TUNNEL A1 FL Current<Derated


140 HVAC-1 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 60 2.33 0.11 0.67 Current & %VD is <2.6%
(380KV CONTROL CABELS TUNNEL) Hence Safe

FL Current<Derated
EXHAUST FAN- TUNNEL A1
141 HVAC-1 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 60 2.33 0.11 0.67 Current & %VD is <2.6%
(380KV CONTROL CABELS TUNNEL) Hence Safe

SUPPLY FAN- TUNNEL B1 FL Current<Derated


142 HVAC-1 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 50 2.33 0.11 0.55 Current & %VD is <2.6%
(132KV CONTROL CABELS TUNNEL) Hence Safe

EXHAUST FAN- TUNNEL B1 FL Current<Derated


143 HVAC-1 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 50 2.33 0.11 0.55 Current & %VD is <2.6%
(132KV CONTROL CABELS TUNNEL) Hence Safe

HVAC PANEL-2

FL Current<Derated
144 HVAC-2 PACU-1A (DUTY) 100.090 3 220 0.85 309.01 1 309.01 XLPE 4C 240 551 0.82 0.7 0.57 316.27 400 35 0.10 0.09 1.12 Current & %VD is <2.6%
Hence Safe

FL Current<Derated
145 HVAC-2 PACU-2A (DUTY) 100.090 3 220 0.85 309.01 2 154.51 XLPE 4C 185 469 0.82 0.7 0.57 269.21 400 120 0.13 0.09 2.30 Current & %VD is <2.6%
Hence Safe

FL Current<Derated
146 HVAC-2 PACU-3A (DUTY) 100.090 3 220 0.85 309.01 1 309.01 XLPE 4C 240 551 0.82 0.7 0.57 316.27 400 70 0.10 0.09 2.24 Current & %VD is <2.6%
Hence Safe

FL Current<Derated
147 HVAC-2 PACU-1B (STANDBY) 100.090 3 220 0.85 309.01 1 309.01 XLPE 4C 240 551 0.82 0.7 0.57 316.27 400 35 0.10 0.09 1.12 Current & %VD is <2.6%
Hence Safe

FL Current<Derated
148 HVAC-2 PACU-2B (STANDBY) 100.090 3 220 0.85 309.01 2 154.51 XLPE 4C 185 469 0.82 0.7 0.57 269.21 400 120 0.13 0.09 2.30 Current & %VD is <2.6%
Hence Safe

CE-113347, REV.01 16 of 21
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫منطقة أعمال الوسطى‬
LV AC CABLE SIZING CALCULATION
Derating Factors: %VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated C.B


I Selected Cable R X
S.No. From To KW Phase VOLT PF cables I req. Over current current Length %VD Remarks
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp m Ohm/kM Ohm/kM
FL Current<Derated
149 HVAC-2 PACU-3B (STANDBY) 100.090 3 220 0.85 309.01 1 309.01 XLPE 4C 240 551 0.82 0.7 0.57 316.27 400 70 0.10 0.09 2.24 Current & %VD is <2.6%
Hence Safe

SUPPLY FAN- TUNNEL A2 FL Current<Derated


150 HVAC-2 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 120 2.33 0.11 1.33 Current & %VD is <2.6%
(380KV CONTROL CABELS TUNNEL) Hence Safe

EXHAUST FAN- TUNNEL A2 FL Current<Derated


151 HVAC-2 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 16 96 0.91 0.45 0.41 39.31 20 120 1.47 0.11 0.85 Current & %VD is <2.6%
(380KV CONTROL CABELS TUNNEL) Hence Safe

SUPPLY FAN- TUNNEL A3 FL Current<Derated


152 HVAC-2 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 115 2.33 0.11 1.28 Current & %VD is <2.6%
(380KV O/G CABLES TUNNEL) Hence Safe

FL Current<Derated
EXHAUST FAN- TUNNEL A3
153 HVAC-2 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 115 2.33 0.11 1.28 Current & %VD is <2.6%
(380KV O/G CABLES TUNNEL) Hence Safe

HVAC PANEL-3

FL Current<Derated
154 HVAC-3 PACU-1A (DUTY) 132KV GIS HALL 65.170 3 220 0.85 201.20 1 201.20 XLPE 4C 120 355 0.82 0.7 0.57 203.77 320 50 0.20 0.09 1.71 Current & %VD is <2.6%
Hence Safe

FL Current<Derated
155 HVAC-3 PACU-2A (DUTY) 132KV GIS HALL 65.170 3 220 0.85 201.20 1 201.20 XLPE 4C 120 355 0.82 0.7 0.57 203.77 320 55 0.20 0.09 1.88 Current & %VD is <2.6%
Hence Safe

FL Current<Derated
156 HVAC-3 PACU-3A (DUTY) 132KV GIS BASEMENT 70.880 3 220 0.85 218.83 1 218.83 XLPE 4C 150 407 0.82 0.7 0.57 233.62 320 40 0.16 0.09 1.27 Current & %VD is <2.6%
Hence Safe

FL Current<Derated
157 HVAC-3 PACU-1B (STANDBY) 132KV GIS HALL 65.170 3 220 0.85 201.20 1 201.20 XLPE 4C 120 355 0.82 0.7 0.57 203.77 320 50 0.20 0.09 1.71 Current & %VD is <2.6%
Hence Safe

FL Current<Derated
158 HVAC-3 PACU-2B (STANDBY) 132KV GIS HALL 65.170 3 220 0.85 201.20 1 201.20 XLPE 4C 120 355 0.82 0.7 0.57 203.77 320 55 0.20 0.09 1.88 Current & %VD is <2.6%
Hence Safe

FL Current<Derated
159 HVAC-3 PACU-3B (STANDBY) 132KV GIS BASEMENT 70.880 3 220 0.85 218.83 1 218.83 XLPE 4C 150 407 0.82 0.7 0.57 233.62 320 40 0.16 0.09 1.27 Current & %VD is <2.6%
Hence Safe

FL Current<Derated
SUPPLY FAN- TUNNEL B2
160 HVAC-3 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 190 2.33 0.11 2.11 Current & %VD is <2.6%
(132KV O/G CABLES TUNNEL) Hence Safe

EXHAUST FAN- TUNNEL B2 FL Current<Derated


161 HVAC-3 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 190 2.33 0.11 2.11 Current & %VD is <2.6%
(132KV O/G CABLES TUNNEL) Hence Safe

SUPPLY FAN- TUNNEL B3 FL Current<Derated


162 HVAC-3 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 160 2.33 0.11 1.78 Current & %VD is <2.6%
(132KV O/G CABLES TUNNEL) Hence Safe

CE-113347, REV.01 17 of 21
CONSTRUCTION OF NEW HITEEN (#9005) 380/132KV BSP

Saudi Electricity Company ‫الشركة السعودية للكهرباء‬


Central Operating Area ‫منطقة أعمال الوسطى‬
LV AC CABLE SIZING CALCULATION
Derating Factors: %VD = (Voltage Drop / Supply Voltage) x 100
VOLTAGE DROP LIMIT k1 = Variation in air temperature -Indoor: 40°C VOLTAGE DROP (3Ph) = √3 x I x L ( R COS Φ + X SIN Φ )
ACDB TO VARIUOS LOADS 4.2 % k1 = Variation in air temperature -Outdoor: 50°C VOLTAGE DROP (1Ph) = 2 x I x L ( R COS Φ + X SIN Φ )
ACDB TO OLP/ILP 1.6 % k2 = Group rating factor I = Current in Amp.
ACDB TO SDB 1.6 % Cables are laid on racks L = Route length in meter.
SDB TO VARIOUS LOADS 2.6 % System Voltage = 220 / 127 VAC

No. of DERATING FACTORS derated C.B


I Selected Cable R X
S.No. From To KW Phase VOLT PF cables I req. Over current current Length %VD Remarks
K1 K2 Amp
Amp per ph. Amp Type Core mm² Amp All Amp m Ohm/kM Ohm/kM

EXHAUST FAN- TUNNEL B3 FL Current<Derated


163 HVAC-3 2.237 3 220 0.85 6.91 1 6.91 XLPE 4C 10 73 0.91 0.45 0.41 29.89 20 160 2.33 0.11 1.78 Current & %VD is <2.6%
(132KV O/G CABLES TUNNEL) Hence Safe

TELECOM ROOM ACDB

TELECOM FL Current<Derated
164 SMK PANELS LIGHT & HEATER 10.36 3 220 0.85 32.00 1 32.00 XLPE 4C 16 96 0.91 0.7 0.64 61.15 40 20 1.47 0.11 0.66 Current & %VD is <2.6%
ACDB Hence Safe

TELECOM FL Current<Derated
165 FMK PANELS LIGHT & HEATER 10.36 3 220 0.85 32.00 1 32.00 XLPE 4C 16 96 0.91 0.7 0.64 61.15 40 25 1.47 0.11 0.82 Current & %VD is <2.6%
ACDB Hence Safe

FL Current<Derated
TELECOM
166 RTU PANELS LIGHT & HEATER 10.36 3 220 0.85 32.00 1 32.00 XLPE 4C 16 96 0.91 0.7 0.64 61.15 40 30 1.47 0.11 0.98 Current & %VD is <2.6%
ACDB Hence Safe

CE-113347, REV.01 18 of 21
85 C 2-CORE, PVC',
conductor current voltage R90 AC X
size rating mV/A/m
PVC 2C 1.5 PVC2CX1.5 21 21.22 15.19 0.165
PVC 2C 2.5 PVC2CX2.5 28 13.04 9.3 0.143
PVC 2C 4 PVC2CX4 33 8.16 5.79 0.132
PVC 2C 6 PVC2CX6 48 5.49 3.87 0.121
PVC 2C 10 PVC2CX10 66 3.3 2.3 0.109
PVC 2C 16 PVC2CX16 88 2.11 1.444 0.106
PVC 2C 25 PVC2CX25 118 1.37 0.913 0.103
PVC 2C 35 PVC2CX35 145 1.014 0.658 0.098
PVC 2C 50 PVC2CX50 177 0.777 0.487 0.098
PVC 2C 70 PVC2CX70 224 0.566 0.337 0.095
PVC 2C 95 PVC2CX95 274 0.435 0.244 0.093
PVC 2C 120 PVC2CX12 318 0.363 0.194 0.091
PVC 2C 150 PVC2CX15 365 0.314 0.158 0.091
PVC 2C 185 PVC2CX18 420 0.271 0.1272 0.091
PVC 2C 240 PVC2CX24 493 0.229 0.0978 0.09
PVC 2C 300 PVC2CX30 559 0.204 0.08 0.09
PVC 2C 400 PVC2CX40 653 0.179 0.0626 0.089
PVC 2C 500 PVC2CX500 0.161 0.0504 0.088
PVC 2C 630 PVC2CX630 0.149 0.0413 0.088
PVC PVCX
PVC PVCX
PVC PVCX current
PVC PVCX 3/4-CORE, PVC',
PVC 4C 1.5 PVC4CX1.5 21 21.22 15.19 0.165
PVC 4C 2.5 PVC4CX2.5 28 13.04 9.3 0.143
PVC 4C 4 PVC4CX4 33 8.16 5.79 0.132
PVC 4C 6 PVC4CX6 48 5.49 3.87 0.121
PVC 4C 10 PVC4CX10 66 3.3 2.3 0.109
PVC 4C 16 PVC4CX16 88 2.11 1.444 0.106
PVC 4C 25 PVC4CX25 118 1.37 0.913 0.103
PVC 4C 35 PVC4CX35 145 1.014 0.658 0.098
PVC 4C 50 PVC4CX50 177 0.777 0.487 0.098
PVC 4C 70 PVC4CX70 224 0.566 0.337 0.095
PVC 4C 95 PVC4CX95 274 0.435 0.244 0.093
PVC 4C 120 PVC4CX12 318 0.363 0.194 0.091
PVC 4C 150 PVC4CX15 365 0.314 0.158 0.091
PVC 4C 185 PVC4CX18 420 0.271 0.1272 0.091
PVC 4C 240 PVC4CX24 493 0.229 0.0978 0.09
PVC 4C 300 PVC4CX30 559 0.204 0.08 0.09
PVC 4C 400 PVC4CX40 653 0.179 0.0626 0.089
PVC 4C 500 PVC4CX500 0.161 0.0504 0.088
PVC 4C 630 PVC4CX630 0.149 0.0413 0.088
trefoil sysem
XLPE 1C 1.5 XLPE1CX1. 25 21.43 15.43 0.165
XLPE 1C 2.5 XLPE1CX2. 34 13.25 9.45 0.149
XLPE 1C 4 XLPE1CX4 44 8.3 5.88 0.143
XLPE 1C 6 XLPE1CX6 57 5.58 3.93 0.134
XLPE 1C 10 XLPE1CX10 77 3.37 2.33 0.132
XLPE 1C 16 XLPE1CX16 102 2.16 1.466 0.124
XLPE 1C 25 XLPE1CX25 139 1.41 0.927 0.121
XLPE 1C 35 XLPE1CX35 170 1.046 0.669 0.115
XLPE 1C 50 XLPE1CX50 208 0.8 0.494 0.111
XLPE 1C 70 XLPE1CX70 265 0.584 0.343 0.105
XLPE 1C 95 XLPE1CX95 326 0.451 0.248 0.103
XLPE 1C 120 XLPE1CX12 381 0.377 0.197 0.1
XLPE 1C 150 XLPE1CX15 438 0.326 0.16 0.1
XLPE 1C 185 XLPE1CX18 507 0.282 0.129 0.099
XLPE 1C 240 XLPE1CX24 606 0.238 0.0993 0.097
XLPE 1C 300 XLPE1CX30 697 0.212 0.0812 0.096
XLPE 1C 400 XLPE1CX40 816 0.186 0.0636 0.094
XLPE 1C 500 XLPE1CX50 933 0.167 0.0513 0.094
XLPE 1C 630 XLPE1CX63 1117 0.153 0.042 0.091
XLPE XLPEX
XLPE XLPEX
XLPE XLPEX
XLPE 2C 1.5 XLPE2CX1. 24 21.43 15.43 0.165
XLPE 2C 2.5 XLPE2CX2. 32 13.25 9.45 0.143
XLPE 2C 4 XLPE2CX4 42 8.3 5.88 0.132
XLPE 2C 6 XLPE2CX6 53 5.58 3.93 0.121
XLPE 2C 10 XLPE2CX10 73 3.37 2.333 0.109
XLPE 2C 16 XLPE2CX16 96 2.16 1.466 0.106
XLPE 2C 25 XLPE2CX25 130 1.41 0.927 0.103
XLPE 2C 35 XLPE2CX35 160 1.046 0.669 0.098
XLPE 2C 50 XLPE2CX50 195 0.8 0.494 0.098
XLPE 2C 70 XLPE2CX70 247 0.584 0.343 0.095
XLPE 2C 95 XLPE2CX95 305 0.451 0.248 0.093
XLPE 2C 120 XLPE2CX12 355 0.377 0.197 0.091
XLPE 2C 150 XLPE2CX15 407 0.326 0.16 0.091
XLPE 2C 185 XLPE2CX18 469 0.282 0.129 0.091
XLPE 2C 240 XLPE2CX24 551 0.238 0.0993 0.09
XLPE 2C 300 XLPE2CX30 638 0.212 0.0812 0.09
XLPE 2C 400 XLPE2CX40 746 0.186 0.0636 0.089
XLPE 2C 500 XLPE2CX500 0.167 0.0513 0.088
XLPE 2C 630 XLPE2CX630 0.153 0.042 0.088
XLPE XLPEX
XLPE 4C 1.5 XLPE4CX1. 24 21.55 15.43 0.165
XLPE 4C 2.5 XLPE4CX2. 32 13.24 9.45 0.143
XLPE 4C 4 XLPE4CX4 42 8.28 5.88 0.132
XLPE 4C 6 XLPE4CX6 53 5.57 3.93 0.121
XLPE 4C 10 XLPE4CX10 73 3.35 2.333 0.109
XLPE 4C 16 XLPE4CX16 96 2.14 1.466 0.106
XLPE 4C 25 XLPE4CX25 130 1.39 0.927 0.103
XLPE 4C 35 XLPE4CX35 160 1.03 0.669 0.098
XLPE 4C 50 XLPE4CX50 195 0.786 0.494 0.098
XLPE 4C 70 XLPE4CX70 247 0.574 0.343 0.095
XLPE 4C 95 XLPE4CX95 305 0.44 0.248 0.093
XLPE 4C 120 XLPE4CX12 355 0.37 0.197 0.091
XLPE 4C 150 XLPE4CX15 407 0.316 0.16 0.091
XLPE 4C 185 XLPE4CX18 469 0.273 0.129 0.091
XLPE 4C 240 XLPE4CX24 551 0.231 0.0993 0.09
XLPE 4C 300 XLPE4CX30 638 0.206 0.0812 0.09
XLPE 4C 400 XLPE4CX40 746 0.181 0.0636 0.089
XLPE 4C 500 XLPE4CX500 0.163 0.0513 0.088
XLPE 4C 630 XLPE4CX630 0.15 0.042 0.088