Prose Data Center Infrastructure

INTRODUCTION

Rosenberger Hochfrequenztechnik GmbH & Co. was founded in Germany in 1958 and ranks among the leading manufacturers of high-
speed interconnect solutions worldwide. With its long tradition of excellence and innovation, Rosenberger has excelled and earned an
outstanding reputation all over the world.

In early 2022 the Rosenberger Group announced the spinoff of its antenna and coverage solution product portfolio with a new brand entity
PROSE. The strategic focus of PROSE will be on the development of base station antennas, microwave antennas, indoor and outdoor
coverage solutions, Open RAN sub-systems, and related services.

As an independent entity, PROSE, with its lean, agile, and decentralized organizational structure, will be better placed to serve global
customers and manage growth by bringing new technologies and solutions, aligned with the changing needs of customers in the telecom
industry. The PROSE product portfolio will uphold Rosenberger’s tradition of the highest innovation and quality while delivering improved
technology expertise and enhanced local customer support around the globe.
A D

B E

A: Kunshan,Jiangsu, China
B: New Delhi, India
C: Pune, India
D: New Jersey, USA
E: Northmead, Australia

PROSE consists of more than 3500 people, with 25 subsidiaries sales/service offices, 3 factories, and 4 R&D centers covering mainly North
America, Europe, the Middle East, Africa, and Asia. It will continue to serve more than 100 operators/service providers worldwide including a
wide set of customized solutions for 5G deployments.

PROSE is an ISO 9001 quality system and ISO 14001 environmental system certified company. Equipped with advanced machinery,
automatically assembly, and testing centers supported by a large group of more than 300 R&D engineers, state-of-the-art production
assembly lines, and stringent product and quality control.

PROSE’s reliability and competitiveness are the cornerstones of this sustainable growth, which have resulted in long-term partnerships with
most of the leading companies in their respective industries. PROSE will continue to provide excellent product solutions and services for its
customers around the world.
PROSE MISSION
• Customer always comes first
• Drive innovation together with and for our customers
• Maintain a secure, humane and happy environment for our employees
• Develop our employees by investing in their education
• Take social responsibility
• Protect our environment with ecologically friendly products, production and processes

CORE VALUE
• Value Innovation
• Customer Focus
• Sustainable Growth
• Social Responsibility
PRODUCTS & SERVICES

Automatic Infrastructure Management System


Building Cabling System
Data Center Cabling System
Digital World Products
Edge Computing Data Center
Modular Data Center
Data Center Management System

Multi-Band Antennas
Multi-Beam Hybrid Antennas
TDD Beamforming Antennas
BTS Antennas
FDD+TDD Hybrid Antennas
5G Massive MIMO Antennas
Small Cell Antennas

Active DAS Products


Tetra DAS Products
Network Systems Passive DAS Products
Site RF Components
In-Cabinet RF Components

Class 3 Series
Class 4 Series
Microwave Products E-Band Series
Dual-Band Series
Microwave Components

Single-Band Portfolios
Multi-Band Portfolios
ORAN Radios Beamforming Portfolios
Massive MIMO Portfolios

Archer Feeder System


Cable Installation Products
Weatherproofting Products
Lightning Protection Products
Mechanical Parts and Mounting Brackets
Archer Site Accessories Fiber Solution
Hybrid cable solution
Enterprise
DC & Data Cable
Camouflaged Antennnas
CONTENTS
KhipuTM Micro Data Center ........................................................................................................................... 1
Khipu™ Micro Data Center ............................................................................................................................................... 2
Cabinet.............................................................................................................................................................................. 3
Power Distribution Box ...................................................................................................................................................... 4
Inverter Precision Air Conditioning .................................................................................................................................... 5
UPS(Uninterrupted Power Supply) ............................................................................................................................... 6
Dynamic Environment Monitoring System ........................................................................................................................ 7
Battery Pack ...................................................................................................................................................................... 8
PDU(Power Distribution Unit) ....................................................................................................................................... 8
Integrative Door Lock ........................................................................................................................................................ 9
Server-Rack Automatic Fire Suppression System (Option) ............................................................................................ 10
Micro Modular Data Center Solutions .................................................................................................... 12
Micro Modular Data Center Solutions ............................................................................................................................. 13
Server Cabinet ................................................................................................................................................................ 15
Power Distribution Unit.................................................................................................................................................... 17
Cooling Channel Product ................................................................................................................................................ 18
Power Distribution Cabinet .............................................................................................................................................. 22
UPS(Uninterrupted Power Supply) ............................................................................................................................. 23
Battery............................................................................................................................................................................. 25
Precision Air Conditioner ................................................................................................................................................. 26
Dynamic Environment Monitoring System ...................................................................................................................... 28
Khipu™ Micro Data Center

◼ Khipu™ Micro Data Center

◼ Cabinet

◼ Power Distribution Box

◼ Inverter Precision Air Conditioning

◼ UPS(Uninterrupted Power Supply)

◼ Dynamic Environment Monitoring System

◼ Battery Pack

◼ PDU(Power Distribution Unit)

◼ Integrative Door Lock

◼ Server-Rack Automatic Fire Suppression System(Option)

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
1
Khipu™ Micro Data Center
Product Introduction
From Germany and adhering to German quality, committed to providing customers with professional data center

infrastructure solutions. The integrated smart cabinet data center infrastructure solution transforms data center infrastructure

construction into customized products. The integrated design integrates the power supply and distribution system,

refrigeration system, cabinet system, fire control system, dynamic monitoring system, and security system, saving room

space. IT devices such as servers, KVM, routers, and switches can be installed.

Application Scenarios
Weak current room, monitoring room and small data room in government, finance, industry, communication,

transportation, power energy, medical care, education, Internet, and other industries. The room area is no more than 40

square meters.

Single cabinet Dual cabinet Triplex cabinet Quadruple cabinet

Five joint cabinet Six joint cabinet Eight joint cabinet

Certification System
Data center products strictly implement the

national and relevant industry standards, through

the corresponding national quality management

system, Theil certification, 3C certification, CE


certification and other authoritative certification,

with excellent quality and perfect service for most


users affirmed.

PROSE Technologies Inc.| www.prosetechnologies.com


2 The information contained in this document is subject to change without notice. info@prosetechnologies.com
Features of Khipu™ Micro Data Center
FC AC Energy Saving
Energy 30%
PUE Less Than 1.5

Saving Room Space 40%


Environment Quiet Operation Less-than 50dB
Cascading Available for Rack

Smart DCIM 24H Cloud


O&M
System Emergency Response Protection
Safety
Biometrics Authentication

Lower Investment by 25%


Cost
Fast Installation Only 2H

Cabinet

W600mm (or 800mm) * D1200mm * H2050mm (or 1340mm), 1 to 10 pcs of racks can be put in cascade configuration.

Server-rack automatic fire suppression system(option)


Dynamic environment monitoring system

Power Distribution Box

Intelligent PDU

Battery pack

Intelligent door lock

Inverter precision air conditioning


Rack-mounted UPS

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
3
Item Standard Cabinet
Height unit (customizable) 27U 42U
Cabinet size (mm) 600(800) (W) x 1200(D) x 1340(H) 600(800) (W) x 1200(D) x 2050(H)
Weight About 150kg About 180kg
Static load Up to 1800kg Up to 2000kg
Color Black or Gray
Structure composition Welding framework, cabinet seal design as a whole
Meet standard ANSI/EIA RS-310-D, IEC297-2, DIN41491, DIN41494, GB/T3047.2-92
IP level IP5X
Display panel 10.1” Touch Panel LCD
Display languages English / Chinese
LED lighting BI-Color (Red & Blue)
Front door Toughened glass door with Mechanical lock or fingerprint lock (Support face detector)
Rear door Sheet metal door
Safety standard RoHS

Power Distribution Box

No. Parameter Value


1 Input rated voltage(V) 220VAC 380VAC
2 Input rated current(A) 32A~80A 32A~100A
3 Input switch 32A~80A /1P 32A~100A/3P
4 Output switch 3*32A/1P+16A/1P*4 7*32A/1P+16A/1P*12
5 Lightning protection level Class C lightning protection
6 Dimensions(mm) W*D*H,483*750*3U W*D*H,483*750*9U
7 Color Black, off-white or according to customer's specification
8 Ways to enter and exit Top-in and top-out or according to customer's designation
9 Installation 19" Rack mounted
10 Cooling Natural cooling

PROSE Technologies Inc.| www.prosetechnologies.com


4 The information contained in this document is subject to change without notice. info@prosetechnologies.com
Inverter Precision Air Conditioning

Rack-Type Air Condition Technical Specification


Type 3.5KW 6.5KW 12.5KW
Cooling Cooling capacity 3.6 6.7 12.6
Capacity Sensible heat ratio(SHR) 98% 98% 98%
Machine air volume (m³/h) 840 1540 2500
Energy efficiency ratio (EER) 3.36 3.22 3.10
Qty (PC) 1
Compressor
Type Enclosed inverter compressor
Fans type Hypokinesis EC centrifugal fan
Expansion valve type Electronic expansion valve
Air supply mode Upper, left, right and three side air supply
Evaporator Copper pipe+ Hydrophilic fin
Freezing medium R410A
Unit standard heating (W) 500 1000 2000
Input 220V/50Hz 220V/50Hz 220V/50Hz
Power Electric power supplying
7.8 15 22
parameter parameters FLA(A)
Recommended air switch
16A 25A 32A
model
Self-draining pipe (mm) Inner p16/Outer p21 Inner p16/Outer p21 Inner p16/Outer p21
Strong-Draining pipe (mm) Inner p5/Outer p7 Inner cp5/Outer p7 Inner p5/Outer cp7
Pipe type
Refrigerant air pipe (mm) 9.52 12.7 15.88
Refrigerant fluid pipe (mm) 6.35 9.52 9.52
Indoor machine size (mm) 440×700×217 440×717×350 440×717x440
Indoor machine weight (kg) 26 36 46
Outdoor machine size (mm) 844×286×604 882×396x803 932x440x1266
Outdoor machine weight (kg) 31 50 60

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
5
UPS(Uninterrupted Power Supply)

3-40KVA Technical Specification


Type 3KVA 6KVA 10KVA 15kVA 20kVA 25kVA 30kVA 40kVA
Capacity* 2400W 4800W 8000W 13.5kw 18kw 22.5kw 27kw 36kw
46Hz~54Hz@50HzSystem;5
Frequency 40Hz~70Hz 40-70Hz
6Hz~64Hz@60HzSystem
Single phase
Phase Single phase grounding type 3-phase+N-wire+ground wire
grounding type
200/208/220/230
Output voltage 208/220/230/240VAC 380/400/415VAC (Line Voltage)
/240VAC
Ambient
temperature<
35 °C:

105% to 110%:
UPS
automatically
shut down after
10 minutes in
battery mode

110% to 130%:
UPS
automatically
110%, Bypass after 1 hour;
shut down after 100%~110%:30 min;
125%, Bypass after 10 min;
Overload 1 minute in 110%~130%:5 min:
150%, Bypass after 1 min;
battery mode >130%:10 seconds
150%, Bypass after 200ms
>130%:
UPS
automatically
shut down after
3 seconds in
battery mode

In addition to the
above, the UPS
may switch to
bypass mode
when the input is
normal.
Battery voltage 96VDC 192VDC--240VDC ±240VDC(32~44 PCS Adjust)

PROSE Technologies Inc.| www.prosetechnologies.com


6 The information contained in this document is subject to change without notice. info@prosetechnologies.com
580x438x13
Size 410x438x88 530x438x88
3 485*790*130 485*723*174
(W*D*H) mm [2U] [2U]
[3U]
Weight(kg) 14.2 13 17 25 30 41
<50dB@1 < 55dB@1 <58dB@1
Noise(dB) 65dB@100% Load,62dB@45% Load
Meter Meter Meter
Operating
<1000m**
altitude **
Interface RS-232 or RS-485 RS-485
Operation
0-40℃
temperature
Storage
-40℃~70℃
temperature
Relative
0-95% (Noncondensing)
humidity

Dynamic Environment Monitoring System

Item Technical Specification


CPU ARM Cortex A9 Quad-core, Max Frequency 1.2GHz
Operating system Android 6.0
Memory DDR3L 2GB
Flash rom 8GB eMMC Flash
Standard serial port 2 Ports RS232
Standard serial port 2 Ports RS485
Debug port 1 Port Micro USB
Digital input port 2 Ports DI
Digital output port 2 Ports DO (for relay control)
USB port 3 Ports (1 Port USB Host, 2 Ports USB Device)
Debug port 1 Port Micro USB
Output supply 6 Ports 12V/1A
Wireless Reserved for 3G, 4G and Wi-Fi module expansion slot

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
7
Ethernet 1 Port RJ45 10M/100M/1000M
Operating voltage 12V DC
Max power 35W
Size 260 mm× 173 mm× 45 mm
ESD level Contact: 6KV; Air: 8KV
MTBF ≥100000H
Operating temperature -20~60℃
Operating humidity 10%~90%RH

Battery Pack

Battery Pack Valve Regulated Lead Acid Battery (VRLA)

Cabinet Power Backup Time Battery Type Quantity


3KVA 15 mins 5U Battery Pack (8pcs 18AH) 1set
6KVA 15 mins 5U Battery Pack (16pcs 18AH) 1set
10KVA 15 mins 5U Battery Pack (8pcs 38AH) 2set
15KVA 15 mins 5U Battery Pack (8pcs 38AH) 4set
20KVA 15 mins 5U Battery Pack (8pcs 38AH) 4set
25KVA 15 mins 5U Battery Pack (8pcs 24AH) 8set
30KVA 15 mins 5U Battery Pack (10pcs 24AH) 8set
40KVA 15 mins 5U Battery Pack (4pcs 65AH) 10set

PDU(Power Distribution Unit)

PROSE Technologies Inc.| www.prosetechnologies.com


8 The information contained in this document is subject to change without notice. info@prosetechnologies.com
Item Specification
Rated current 16A 32A
Rated voltage 110VAC/220VAC 50/60Hz 220VAC 50/60Hz
Output ports 8/12/16/20/24
Max power 5KW 10KW
Outline size 1217(Adjustable length) x 44 x 44 mm
Installation method Horizontal/Vertical installation
Safety certification UL/CE/CCC

Integrative Door Lock

Type of Device Specification


Rated operating voltage DC12V
Static standby: <250mA
Working current
Dynamic Electronically Controlled Unlocking: <500mA
Communication mode RS485,9600bit/s
Service life Above 500,000 times
Color Black
Operating temperature/humidity -20℃ ~50℃ / 20~90%
Storage temperature/humidity -30℃ ~60℃ / 20~90%
IP rate IP65
Remote unlocking by monitoring host control software
3 unlock modes Authorized card writes the card number and swipes card to unlock
Mechanicals unlock
Access control authorization 500 to 5000 fingerprints
Authorized entrance number Up to 5000
Software authorization Authorized by system software through network Communication
Event records Up to 1120 history records
Function Mechanical unlocking, password, card swiping, fingerprint, etc. are optional
RS485 networking real-time monitoring, door status, handle status, real-time clock
Communication interface
function

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
9
Server-Rack Automatic Fire Suppression System (Option)

Type of Device Specification


Model number JJQR-Q-W/C-4/1.2-WL/ZZ YF4C-W/1.2-N-Y-WL/ZZ
Control the number of cabinets Less than 4 set A maximum of five cabinets are configured
Size 483(W)*700(D)*2U(H)mm 483(W)*700(D)*2U(H)mm
Fire extinguishing agent HFC-ea. Per fluorinated hexanone
Storage pressure(20℃) 1.2MPa 1.2MPa
Injection time ≤10S ≤10S
Action temperature of fire
170 ℃ ±10 ℃ 170 ℃ ±10 ℃
detecting tube
Max. Length of fire detection tube 5m for each cabinet

PROSE Technologies Inc.| www.prosetechnologies.com


10 The information contained in this document is subject to change without notice. info@prosetechnologies.com
Ordering Information
MDC-XX XX-XX XX-XX XX-XX X X
① ② ③ ④ ⑤ ⑥ ⑦ ⑧⑨
① Cabinet Type and Quantity ⑤ PDU Standard and Quantity per cabinet

1: 27U*600mm*1200, Black 1: Single cabinet A:12 outlet PDU, 16A, IEC 320 C13 0:0ea
2: 27U*600mm*1200, Black 2: Dual cabinet B: 12 outlet PDU, 16A, IEC 320 C13 Smart 1:1ea
3: 27U*600mm*1200, Gray 3: Triplex cabinet C: 24 outlet PDU, 16A, IEC 320 C13 2:2ea
4: 27U*800mm*1200, Gray 4: Quadruple cabinet D: 24 outlet PDU, 16A, IEC 320 C13 Smart
5: 42U*600mm*1200, Black 5: Five joint cabinet E: 24 outlet PDU, 32A, IEC 320 20*C13+4*C19
6: 42U*800mm*1200, Black 6: Six joint cabinet F: 24 outlet PDU, 32A, IEC 320 20*C13+4*C19 Smart
7: 42U*600mm*1200, Gray 7: Seven joint cabinet G: 24 outlet PDU, 16A, IEC 320 20*C13+4*C19
8: 42U*800mm*1200, Gray 8: Eight joint cabinet H: 24 outlet PDU, 16A, IEC 320 20*C13+4*C19 Smart
9: 42U*600mm*800, Black 9: Nine joint cabinet J: 24 outlet PDU, 32A, IEC 320 C13
A: 27U*600mm*800, Black A: Ten joint cabinet K: 24 outlet PDU, 32A, IEC 320 C13 Smart

②UPS Capacity and Quantity L: 24 outlet PDU, 32A, IEC 320 C19

0: Without UPS 0: 0ea M: 24 outlet PDU, 32A, IEC 320 C19 Smart
1: Rack type 3KVA 1: 1ea N: 24 outlet PDU, 32A, IEC 320 18*C13+6*C19
2: Rack type 6KVA 2: 2ea O: 24 outlet PDU, 32A, IEC 320 18*C13+6*C19 Smart
3: Rack type 10KVA P: 12 outlet PDU, 32A, IEC 320 9*C13+3*C19
4: Rack type 15KVA Q: 12 outlet PDU, 32A, IEC 320 9*C13+3*C19 Smart
R: 8 outlet PDU, 16A, GB port, with surge protection
5: Rack type 20KVA
module
6: Rack type 25KVA ⑦Server-rack fire suppression unit and Quantity

7: Rack type 30KVA 0:None fire suppression unit 0:0 set


1:Four cabinets can be detected, but only one cabinet
8: Rack type 40KVA 1:1 set
can be detected at a time
2:One fire suppression unit controls five cabinet 2:2 set

③Uninterrupted Power Supply Time and Battery storage mode ⑧Lock Type 3:3 set

0: Without battery 1: Battery Pack 0: No Lock 4:4 set

1: 15 minutes 2: Lead-Acid Battery in cabinet 1: Mechanical lock 5:5 set

2: 30 minutes 3: Lead-Acid Battery in rack 2: Intelligent lock with keypad ⑨ Quantity of PDB
3: 60 minutes 3: Intelligent lock with Fingerprint 1:1ea
4: 120 minutes 4: Intelligent lock with IC card 2:2ea
5: Intelligent lock with Keypad +Fingerprint

④ Type of Precision Air Conditioning and Quantity 6: Intelligent lock with Keypad + IC card

1:Rack type 3.5kW air conditioning 0:Without Air Conditioner 7: Intelligent lock with Keypad + IC card +Fingerprint
2:Rack type 6.5kW air conditioning 1: One Air Conditioner 8: Intelligent lock and face detect with keypad
3:Rack type 12.5kW air conditioning 2: Two Air Conditioners 9: Intelligent lock and face detect with Fingerprint
4:Row rooms Class 12.5KW air
3: Three Air Conditioners A: Intelligent lock and face detect with IC card lock
conditioning
B: Intelligent lock and face detect with Keypad
5: Natural Ventilation 4: Four Air Conditioners
+Fingerprint
6: Fans Cooling 5: Five Air Conditioners C: Intelligent lock and face detect with Keypad + IC card
D: Intelligent lock and face detect with Keypad+ IC card
6: Six Air Conditioners
Fingerprint
⑥Dynamic environment monitoring system and Quantity
1: No display host, collects UPS, power distribution module, air conditioner, water leakage, temperature and humidity, smoke sensor,
0:None
access control, intelligent PDU, and northbound interface
2: No display host, collect UPS, power distribution module, air conditioner, water leakage, temperature and humidity, smoke sensor, and
1:1ea
northbound interface
3: Monitors the integrated screen, collecting the UPS, power distribution module, air conditioner, water leakage, temperature and
2:2ea
humidity, smoke sensor, access control, intelligent PDU, and northbound interface
4: Monitors the integrated screen, collecting the UPS, power distribution module, air conditioner, water leakage, temperature and
humidity, smoke sensor, and northbound interface

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
11
Micro Modular Data Center Solutions

◼ Micro Modular Data Center Solutions

◼ Server Cabinet

◼ PDU (Power Distribution Unit)

◼ Cooling Channel Product

◼ Power Distribution Cabinet

◼ UPS(Uninterrupted Power Supply)

◼ Battery

◼ Precision Air Conditioner

◼ Dynamic Environment Monitoring System

PROSE Technologies Inc.| www.prosetechnologies.com


12 The information contained in this document is subject to change without notice. info@prosetechnologies.com
Micro Modular Data Center Solutions
Product Introduction
Modular data center is to make the power distribution system, refrigeration system, dynamic environment monitoring

system, fire protection system, security system and cabinet cold aisle system into an intelligent platform, which further

improves the safety, reliability, and health of equipment, and is more green and energy-saving.

Modular infrastructure can meet the requirements of customers' special needs and usage, meet the requirements of

prefabricated production of all modular internal infrastructure and equipment, assemble, and deliver on site quickly, and truly

realize the one-stop solution of rapid deployment of IT equipment. It has the characteristics of modular integration, safety,

and reliability, saving room floor space and energy, saving time, labor and worry in installation, compatible architecture,

quick and flexible deployment, intelligent monitoring, efficient and stable refrigeration, etc. It is a new generation of intelligent

micro-module data center products.

Application Scenario
It is mainly used in small and medium data center scenarios. Its simple design, strong architectural adaptability, and

low requirements for computer room floor height and renovation meet the data center deployment requirements of corporate

headquarters or large branches, bank headquarters and secondary branches, government, operators, education, medical

care, energy, and other industries.

Certification System
Data center products strictly implement the

national and relevant industry standards, through

the corresponding national quality management

system, Theil certification, 3C certification, CE


certification and other authoritative certification,

with excellent quality and perfect service for most


users affirmed.

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
13
User Value of Modular Data Center Products
• 15% Increase In Reliability:High reliable scheme, high standard product design, improve system
reliability and ensure personnel safety.

• Energy Saving Increased By 30%:Green energy-saving design, high-efficiency equipment, the overall
PUE is lower than 1.3.

• Capacity Expansion Increased By 30%:Modular design, more intensive, increased capacity per unit
area online, more flexible.

• 50% Early Delivery:Quick matching scheme, all products are prefabricated and modularized, and the site is
simple, quick, and flexible to assemble.
• Operating Costs Are Reduced By 30%:365 * 7 * 24-hour intelligent monitoring, diversified alarm
modes, centralized management, and simple operation.
• The Occupied Space Is Reduced By 50%: The system is modular, highly integrated, and more
intensive; The integrated power distribution cabinet containing UPS integrates UPS and precision header cabinet,
increasing the out-of-cabinet rate per unit area.
• Reduce Power Consumption By 30%: Fully enclosed design concept with high efficiency and energy
saving air conditioner.

Architecture Diagram of Micro-Module System

Cooling channel

Cabinet
Power distribution cabinet

Battery Battery Rack

Dynamic environment
Air conditioner
Rack UPS Modular UPS Vertical UPS monitoring system
between columns

PROSE Technologies Inc.| www.prosetechnologies.com


14 The information contained in this document is subject to change without notice. info@prosetechnologies.com
Server Cabinet
Product Introduction
In order to adapt different application scenarios, PROSE provides 9-fold cold roll steel server cabinet, flagship server

cabinet and Network cabinet to meet different needs of customers in terms of cost, use space and portability.

9-fold cold roll steel server cabinet Flagship server cabinet Network Cabinet

Main Specifications
1. Rack Unit Mechanical Specifications
Flagship
9-Fold Cold Roll Steel Flagship Welded Detachable Network
Item
Server Cabinet Server Cabinet Server Cabinet
Cabinet
Cabinet type NCH FCH DCH TCH
Static load Up to1800kg Up to 2000kg Up to 1500kg Up to1000kg
Color Black or Gray
Compliance with EIA-310-E, IEC297-2, DIN41491; PART1, DIN41494; PART7,
Standard
GB/T3047.2-92 standard; Compatible with ETSI standard
Frame thickness(mm) 1.5mm 1.5mm 1.5mm 1.2mm
U-column thickness(mm) 2.0mm 2.0mm 2.0mm 2.0mm
Beam thickness(mm) 1.5mm 1.5mm 1.5mm 1.5mm
Thickness
1.2mm 1.2mm 1.2mm 1.2mm
(mm)
Front door
Yes Yes Yes
Removeable Yes& Tool-Free
& Tool-Free & Tool-Free & Tool-Free
Thickness
1.2mm 1.2mm 1.2mm 1.2mm
(mm)
Rear door
Yes Yes& Tool- Yes
Removeable Yes& Tool-Free
& Tool-Free Free & Tool-Free
Thickness
1.2mm 1.2mm 1.2mm 1.2mm
(mm)
Yes Yes Yes
Side door Removeable Yes& Tool-Free
& Tool-Free & Tool-Free & Tool-Free
Same door left
Yes No No Yes
& right

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
15
Thickness
1.2mm 1.2mm 1.2mm 1.2mm
Floorboard (mm)
Removeable No Yes Yes No
Thickness
Upper 1.2mm 1.2mm 1.2mm 1.2mm
(mm)
shield
Removeable No Yes No

2. Rack Unit Dimensions Specifications


Item Height(U) Width(mm) Depth(mm) Height(mm) Note
1 600 TCH Only
2 800 ALL
3 42 600 1000 2000(Without wheels) ALL
4 1100 ALL
5 1200 ALL
6 600 TCH Only
7 800 ALL
8 42 800 1000 2000(Without wheels) ALL
9 1100 ALL
10 1200 ALL
11 600 TCH Only
12 800 ALL
13 47 600 1000 2200(Without wheels) ALL
14 1100 ALL
15 1200 ALL
16 600 TCH Only
17 800 ALL
18 47 800 1000 2200(Without wheels) ALL
19 1100 ALL
20 1200 ALL

PROSE Technologies Inc.| www.prosetechnologies.com


16 The information contained in this document is subject to change without notice. info@prosetechnologies.com
Power Distribution Unit
Application
Prose PDU (Power Distribution Unit) provides various series of specifications with different functions, installation methods
and plug combinations. It can provide suitable rack power distribution solutions for different power environments. PDU can make
the power distribution in the cabinet more orderly, reliable, safe and professional.

Outline

Standard type Intelligent type Intelligent monitoring type

Socket Type

GB1002 10A GB1002 16A IEC320 C13 IEC320 C19

USA 15A USA 20A GER 16A UK 13A

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
17
Plug Type

GB1002 10A GB1002 16A IEC320 C14 IEC320 C20

GRE 16A UK 13A USA 15A USA 20A

IEC60309 16A/32A IEC60309 32A 380V 3P+N+E

Cooling Channel Product


The working principle of the closed cold channel is to isolate the cold air supply from the hot exhaust gas and
concentrate the cooling on the air inlet of the equipment. This process is called centralized cooling. This is achieved by
installing a server cabinet with the air inlet facing the cold channel. This cold channel containment prevents mixing of hot
and cold air, which means less energy is required to maintain the system at a controlled and consistent temperature. The
cold channel closure is composed of skylight, channel door, M-shaped trunking, cabinet back panel, etc.

Flip sunroof with a


M-type wire slot

width of 600mm

Fixed glass sunroof with

a width of 600mm

Fixed glass sunroof with a

width of 300mm

Cabinet rear baffle

Automatic sliding door


Fixed steel skylight with a width of 600mm
Reference Standard
Comply with EIA-310-E, IEC297-2 and DIN41491; PART1, DIN41494; PART7, GB/T3047.2-92 standard; Compatible
with ETSI standard.

PROSE Technologies Inc.| www.prosetechnologies.com


18 The information contained in this document is subject to change without notice. info@prosetechnologies.com
Components
1) Automatic Translation Door

No. Product Measurement Surface Treatment Remark


Automatic translation, aluminum alloy
Electrostatic spray wrapping and toughened glass,
1 Automatic Sliding Door 1200*2000
plastics Human body induction, lifting and fixing
without underground rail.

2) Manual Translation Door

No. Product Measurement Surface Treatment Remark


Manual translation, aluminum alloy wrapping
Electrostatic spray
1 Manual Sliding Door 1200*2000 and toughened glass, lifting and fixing without
plastics
underground rail.

3) Manual Sliding Door

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
19
No. Product Measurement Surface Treatment Remark
Manual door opening, consisting of metal frame
Electrostatic spray
1 Manual Sliding Door 1200*2000 and perspective window, supports door
plastics
opening limit and automatic closing function.

4) Fixed Steel Skylight

No. Product Measurement Surface Treatment Remark


All-steel plate design, with
1 600 Width fixed metal sunroof 600*1200 Electrostatic spray plastics
heightening plates on both sides
All-steel plate design, with
2 300 Width fixed metal sunroof 300*1200 Electrostatic spray plastics
heightening plates on both sides
All-steel plate design, with
3 800 Width fixed metal sunroof 800*1200 Electrostatic spray plastics
heightening plates on both sides

5) Fixed Glass Skylight

No. Product Measurement Surface Treatment Remark


All-steel+glass design, with
1 600-Width fixed glass skylight 600*1200 Electrostatic spray plastics
heightening plates on both sides.
All-steel+glass design, with
2 300 Width fixed glass skylight 300*1200 Electrostatic spray plastics
heightening plates on both sides.
All-steel+glass design, with
3 800-Width fixed glass skylight 800*1200 Electrostatic spray plastics
heightening plates on both sides.

6) Flip Sunroof

PROSE Technologies Inc.| www.prosetechnologies.com


20 The information contained in this document is subject to change without notice. info@prosetechnologies.com
No. Product Measurement Surface Treatment Remark
Electrostatic spray All-steel+glass design, with
1 600-Width single-turn glass skylight 600*1200
plastics heightening plates on both sides.
Electrostatic spray All-steel+glass design, with
2 600-Width double-turnover glass skylight 600*1200
plastics heightening plates on both sides.
Electrostatic spray All-steel+glass design, with
3 800-Width single-turn glass skylight 800*1200
plastics heightening plates on both sides.
Electrostatic spray All-steel+glass design, with
4 800-Width double-turnover glass skylight 800*1200
plastics heightening plates on both sides.

7) M-Type Wireway

No. Product Measurement Surface Treatment Remark


1 M-slot 300*300 Electrostatic spray plastics
2 M-slot 300*600 Electrostatic spray plastics
3 M-slot 300*800 Electrostatic spray plastics
4 Trapezoidal span bridge 300*600 Electrostatic spray plastics
5 Trapezoidal span bridge 300*800 Electrostatic spray plastics
6 Trapezoidal span bridge 300*1200 Electrostatic spray plastics
7 Trapezoidal span bridge 300*1800 Electrostatic spray plastics

8) Cabinet Rear Baffle

No. Product Measurement Surface Treatment Remark


1 Cabinet rear baffle 200*300 Electrostatic spray plastics
2 Cabinet rear baffle 200*600 Electrostatic spray plastics
3 Cabinet rear baffle 200*800 Electrostatic spray plastics
4 Cabinet rear baffle 300*300 Electrostatic spray plastics
5 Cabinet rear baffle 300*600 Electrostatic spray plastics
6 Cabinet rear baffle 300*800 Electrostatic spray plastics

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
21
Power Distribution Cabinet
Application
The precision column cabinet is an intelligent integrated power distribution cabinet, which mainly provides functions
such as power distribution, sub-item power consumption measurement, feeder output protection, station-level monitoring,
and other functional services for servers in computer rooms, data centers, base stations, and other places. It is used in the
field of uninterruptible power supply with high requirements on power supply reliability.
The precision column cabinet conforms to GB7251 "Low-voltage switchgear", GB50054 "Low-voltage power
distribution design code" and other standards.
Application scenarios: government, finance, education, medical care, energy, enterprise, Internet, and other data center
computer rooms.

Precision Column Cabinets Modular Rack-Mounted Column Cabinet

Technical Parameter
No. Parameter Precision Column Cabinets Modular Rack-Mounted Column Cabinet
Input rated
1 380VAC
voltage(V)
Input rated
2 2*(100A~630A) 2*(100A~400A)
current(A)
3 Input switch 2*(100A~630A) /3PMCCB 2*(100A~400A) /3PMCCB
2*(n*63A/321P+n*32A/321P+n*16A/321P+n 2*(n*63A/321P+n*32A/321P+n*16A/321P+n*1
4 Output switch
*10A/321P) MCB 0A/321P) MCB
Lightning
5 protection Class C lightning protection
level
Dimensions(m
6 W*D*H,according to the cabinet size W*D*H,483*750*24U
m)
7 Colors Black, off-white or according to customer's specification
Ways to enter
8 Top-in and top-out or according to customer's designation
and exit
9 Installation Vertical floor installation 19" rack mounted
10 Cooling Natural cooling

PROSE Technologies Inc.| www.prosetechnologies.com


22 The information contained in this document is subject to change without notice. info@prosetechnologies.com
UPS(Uninterrupted Power Supply)
PROSE introduces a new generation of three in and three out high-end UPS power supply, which adopts advanced
dual core DSP digital control technology, effectively improves product performance and system reliability, and achieves
higher power density integration and miniaturization.
Application
Finance, communication, security office, machine room power, network center, electronic medical equipment, industrial
control equipment and other fields.

VT Series High Frequency RTM Series High Frequency CM Series High Frequency

Online Vertical UPS Online Rack Modular UPS Online Modular UPS

Technical Parameter
VT series 3-Phase Input 3-Phase Output 10-200KVA Technical Specification
Model VT series
Rated capacity 10-30kVA 40-60kVA 80kVA 100-120kVA 160kVA 200kVA
Rated voltage 380VAC (3-phase +N)
Frequency range 40Hz-70Hz
Power factor ≥ 0.99@100% load; ≥ 0.98@50% load
Output voltage 380/400/415VAC(3-phase+N); 20/230/240VAC (single phase+N)
Power factor 0.9 (optional 1)
< 105%, long term;
< 110%, 60 minutes; 10-125% of rated load, with load for 10 minutes;
Overload capacity
> 125-150% rated load, with load for 1 minute;
> 150%, 200ms
Number of batteries Section 32 by default; 30 ~ 44 (15 ~ 22) knots (adjustable)
Dimension depth width x height (mm) 780*425*1200 800*600*1600 1010*600*2000
Net weight (kg) 116 141 166 230 320 460
Working temperature 0 ~ 40 C (the battery life will be shortened in the environment of > 25°C)
Relative humidity 0-95% without condensation.
1000 meters will not be derated, and every 100 meters above 1000 meters
Altitude
will be derated by 1%
Noise ≤ 60db (a) @ 1m ≤ 65db (a) @ 1m
Communication interface RS-232/RS-485

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
23
RTM series 3-Phase Input 3-Phase Output 20-150KVA Technical Specification
Model RTM series
Rated capacity 20KVA 30KVA 40KVA 40KVA 60KVA 80KVA 100kVA 120KVA 150kVA
Power module
10KVA 15KVA 20KVA 10KVA 15KVA 20KVA 25kVA 20KVA 25KVA
capacity
Wiring mode 3-phase +N-line +PE
Rated voltage 380/400/415Vac (line voltage)
304Vac ~478Vac (line voltage) full load;
Voltage range
304Vac ~228Vac (line voltage) load is derated linearly from 100%~80%
Frequency range 40Hz~70Hz
Battery voltage ±192Vdc(360~528Vdc; 30 ~ 44 batteries are adjustable, 32 batteries by default )
Power factor 1
Communication
RS232/RS485/SNMP card (option)/programmable dry contact (option)
interface
Working
Working temperature: 0 ~ 40℃; Relative humidity: 0~95% (no condensation)
environment
Cabinet type 2 module frames 4 module frames 6 module frames
Machine depth x 482.6 x 800 x 482.6 x 900 x
482.6 x 800 x 353(8U) 482.6 x 800 x 531(12U)
width x height (mm) 531(12U) 800(18U)
Module depth x
440 x 690 x 86(2U)
width x height (mm)
Altitude 1000m will not be derated, and every 100m above 1000m will be derated by 1%
Noise ≤ 60db (a) @ 1m < 58db (a) @ 1m
Machine (Kg) 35.5 37 37.5 45.5 46 47.5 47.5 72
Module (Kg) 23 23.5 25 23 23.5 25 30 25 30

CM series 3-Phase Input 3-Phase Output 80-300KVA Technical Specification


Model CM series
Rated capacity 80kVA 120kVA 140kVA 200KVA 240kVA 100kVA 175kVA 300kVA
Power module capacity 20kVA 25kVA
Wiring mode 3-phase +N-line +PE
Rated voltage 380/400/415Vac (line voltage)
Rated frequency 50/60Hz
Battery voltage ±192Vdc(360~480Vdc; 30 ~ 40 batteries are adjustable, 32 batteries by default)
Power factor 0.9
Line feeding mode Supports uplink and downlink
Communication function RS232/RS485/SNMP card (option)/programmable dry contact (option)
Working environment Working temperature: 0 ~ 40℃; Relative humidity: 0 ~ 95% (no condensation)
Noise < 60db @ 1m
Altitude 1000m without derating, > 1000m, power derating 1% for every 100m.
12
4Module 6 Module 7 Module 10 Module 12 Module 4 Module 7 Module
Cabinet type Module
cabinet cabinet cabinet cabinet cabinet cabinet cabinet
cabinet
600 x 600 x 600 x
Machine depth x width x 600 x 995 600 x 890 600 x 960
890 x 600 x 995 x 1600 1010 x 1010 x
height (mm) x 2000 x 1200 x 1600
1200 2000 2000
Module depth x width x
440 x 690 x 86(2U)
height (mm)
Machine (Kg) 140 124 185 207 270 150 195 270
Module (Kg) 26.5 30

PROSE Technologies Inc.| www.prosetechnologies.com


24 The information contained in this document is subject to change without notice. info@prosetechnologies.com
Battery
Lead-Acid Battery (DC12V 9Ah-200Ah)

PROSE Lead acid battery is floating charge batteries with a designed life of 10 years. It meets IEC standard. Adopt the
latest AGM valve control technology and high purity raw materials, the battery has a reliable standby life.

Application
UPS / EPS / Emergency light / Security System / Toy / Medical etc.

Technical Parameters
Rated Voltage Rated Capacity Dimensions(mm) Appr.Weight
No. Terminal Type
DC(V) AH/20HR L W H Total H (kg)
1 12 9 152 65 95 100 2.45 F2
2 12 12 152 100 97 102 3.5 F1/F2
3 12 18 181 77 167 167 5.4 F13
4 12 24 183 78 167 167 7.15 F14
5 12 26 177 167 126 126 9.08 F15
6 12 38 198 166 170 170 13.7 F3
7 12 55 229 138 210 228 15.2 F4
8 12 65 348 168 178 178 21.3 F4
9 12 75 260 168 209 214 22.5 F4
10 12 100 329 172 214 243 30 F4/F8
11 12 120 409 177 207 234 34.8 F9
12 12 150 483 170 240 240 42.4 F4/F10
13 12 200 522 240 218 244 60.6 F5/F11
14 2 100 171 72 205 210 5.6 F7
15 2 200 170 110 330 350 14.3 F7
16 2 300 171 151 330 366 20.3 F7
17 2 400 211 176 329 367 27 F7
18 2 500 241 172 330 365 32.1 F7
19 2 600 301 175 331 366 39.1 F7
20 2 800 410 176 330 365 48.1 F7
21 2 1000 475 175 327 365 64.2 F7
22 2 1200 475 175 327 365 71 F7
23 2 1500 401 351 342 378 101 F7
24 2 2000 491 351 343 383 132 F7
25 2 3000 712 353 341 382 192 F7

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
25
Precision Air Conditioner
Precision air conditioners are efficient, energy-saving, safe and reliable, intelligent management, compact structure, and

exquisite workmanship, which fully meet the cooling needs of modern data rooms.

F Series Room-Level Air- Cooled Precision Air Conditioner G Series In-Row Air-Cooled Precision Air Conditioner
Application Scenarios
Data center computer room, communication computer room, computer room, UPS battery room and industrial control

room in various industries such as finance, government, enterprise, energy, education, medical care, Internet, etc.

Indoor AC Technical Parameters


F Series Room-Level Air- Cooled Precision Air Conditioner
25 30 35 40 45 50 60 70 80 90 100
Parameter Model
KW KW KW KW KW KW KW KW KW KW KW
Parameter air
m³/h 7500 9000 10500 11500 12000 15000 18000 21000 23000 24000 25600
volume
Cooling
kW 26.4 31.5 36.1 38.1 45.7 52.7 62.9 72.3 76.1 91.6 100.2
capacity
Sensible
cooling kW 24.5 29.2 33.4 35.2 41.6 48.9 58.2 66.6 70.2 83.4 91.6
capacity
Electric
kW 6 6 6 6 6 9 9 9 9 9 9
heating
Humidification
kg/h 4.5 4.5 4.5 4.5 4.5 6.5 6.5 6.5 6.5 6.5 6.5
amount
Maximum
load current A 32.12 38.20 41.05 41.05 48.97 59.74 71.92 77.60 77.60 93.44 93.44
FLA
Width
900 900 900 900 900 1800 1800 1800 1800 1800 1800
(mm)
Depth
Unit size 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
(mm)
Height
1980 1980 1980 1980 1980 1980 1980 1980 1980 1980 1980
(mm)
Weight kg 355 370 375 380 390 665 695 705 715 735 755
OU OU OU OU OU OU OU OU OU OU OU
The outdoor model
-40 -50 -50 -50 -70 -40 -50 -50 -50 -70 -70
unit
quantity 1 1 1 1 1 2 2 2 2 2 2
Dimensions of a single
energy-saving module 650*300*950
(W*D*H) mm

PROSE Technologies Inc.| www.prosetechnologies.com


26 The information contained in this document is subject to change without notice. info@prosetechnologies.com
Indoor AC Technical Parameters
G Series In-Row Air-Cooled Precision Air Conditioner
Parameter Model 25KW 40KW 50KW
Air volume m³/h 5000 8500 10500
Cooling capacity kW 25.8 40 50
Sensible cooling capacity kW 25.8 40 50
Electric heating kW 3 6
Humidification amount kg/h 1.5 3 3
Maximum load current A 28.2 40
width mm 300 600 600
Unit size depth mm 1100 1100 1200
height mm 2000 2000 2000
Weight kg 240 330 340
The outdoor unit OU-40 OU-60 OU-70
Number of outdoor units 1 1 1

Outdoor AC Technical Parameters


Parameter Model OU-40 OU-50 OU-70 OU-80
Number of fans tower 1 1 2 2
width mm 1650 1650 2010 2860
Unit size depth mm 1100 1100 1100 1100
height mm 1150 1150 1150 1150
Full load current A 2.9 4.7 5.8 5.8
Weight kg 158 168 210 256
Noise db. 60 60 62 62

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
27
Dynamic Environment Monitoring System
DCIM System(Data Center Infrastructure Management)It monitors and manages the running status of assets and

resources in a data center and provides a comprehensive management platform for data centers by collecting, transmitting,

and managing devices. IT serves as a bridge between the equipment room infrastructure and IT devices. IT helps O&M

personnel manage data centers and improves the reliability of the equipment room and the security of communication

devices. In ordinary demand, if only do power, environmental equipment monitoring, we generally call it Dynamic

environmental monitoring system.

Northbound interface
Alarm record
Access control
Alarm Lighting Remote browsing

Integrated monitoring host

Video surveillance

UPS PDB Line Air Condition Battery Humiture Smoke Sensor Leakage Sensor

Application
Dynamic environmental monitoring system is a centralized monitoring of power equipment and environmental variables

in all kinds of computer rooms.


A set of perfect the distribution of the dynamic environment monitoring system can separate power equipment and

computer room environment, computer security monitoring objects such as signal acquisition, real-time monitoring system

and equipment running status, security, recording and processing the relevant data, detect the fault in time, and the

necessary remote control, remote regulating operation, timely notify ops staff on duty to deal with.

The purpose is to display the equipment room's few people, unattended, and centralized monitoring and maintenance

management of power supply and air conditioning and improve the reliability of the power supply system and the security of

communication equipment. It provides powerful technical support for the machine room management automation, intelligent
operation and scientific decision making.

PROSE Technologies Inc.| www.prosetechnologies.com


28 The information contained in this document is subject to change without notice. info@prosetechnologies.com
Monitoring Object Description:
Power load PUE meter Air condition load Humidity &temperature sensor

Smoke sensor

Lamp sensor

Door sensor

Leakages sensor

AFSS sensor

Battery sensor

Cable sensor

Air condition table Temperature/humidity table Alarm table

UPS: Collect the main circuit, bypass power quality such as voltage, current, power, frequency, and other information;
At the same time, the operating state of the equipment is also monitored, such as UPS on/off state, operation mode and

power supply mode, and the working state of its internal key electrical units.

Battery:Collect the voltage, internal resistance, temperature, and other information of a single battery. If the status
reaches the warning value, it pushes alarm information in time.

Cabinet:Collect the doors open/close status.


Air Condition:Collect the air supply/return air inlet temperature, compressor working status and temperature
and humidity level status.

Humidity &Temperature Sensor:Collect the humidity and temperature at cabinet, the system according
to it adjust such as fans status, air conditioning run and stop.

Smoke Sensor:Collect ambient smoke status.


Leakage Sensor:Collect environmental smoke Status. Place the device in a position with water leakage risk.
If water leakage occurs, the device detects and generates an alarm.

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
29
Application Scenarios
Finance, government, enterprise, energy, education, medical, Internet and other industries of the data center room,

communication room, computer room, UPS battery room and industrial control room.

Monitoring Host
The integrated monitoring screen is 10.1 inch capacitive screen, with good man-machine interface and touch

performance; A full set of configuration software development tools, a new style interface; Built-in AI/DI/RS232/RS485 port;

Fast data acquisition and processing; Cold aisle cabinet side plate embedded installation, beautiful; Support sliding operation,

pattern unlock, important data page encryption; A single device can manage multiple intelligent devices and environment

such as door status sensor smoke sensor and water leakage.

Item Technical Specification


CPU ARM Cortex A9 Quad-core, Max Frequency 1.2GHz
Operating system Android 6.0
Memory DDR3L 2GB
Flash rom 8GB eMMC Flash
Standard serial port 3 Ports RS232
Standard serial port 7 Ports RS485
Debug port 1 Port Micro USB
Digital input port 2 Ports DI
Digital output port 2 Ports DO (for relay control)
USB port 3 Ports (1 Port USB Host, 2 Ports USB Device)
Debug port 1 Port Micro USB
Output supply 6 Ports 12V/1A
Wireless Reserved for 3G, 4G and Wi-Fi module expansion slot
Ethernet 1 Ports RJ45 10M/100M/1000M
Operating voltage 12V DC
Max power 35W
Size 266 mm× 182 mm× 48.5 mm
ESD level Contact: 6KV; Air: 8KV
MTBF ≥100000H
Operating temperature -20~60℃
Operating humidity 10%~90%RH

PROSE Technologies Inc.| www.prosetechnologies.com


30 The information contained in this document is subject to change without notice. info@prosetechnologies.com
Technical parameters of micro module
Micromodule Data Center
Standard: Width:3600mm; Height 2000mm/2200mm; Length:15000mm;
Specification
Support other customization requirements
Number of IT cabinets Maximum support 48 cabinets
Average power of
Standard 3-5 kw, supporting other customization requirements
single cabinet
Recommended
Steel structure base or epoxy floor
installation method
Power supply support Two-way UPS, two-way commercial power, one-way commercial power and one-way UPS;
architecture Support other customization requirements.
Flip skylight Automatic turnover of glass skylight, supporting fire linkage control.
Intelligent Energy-saving LED lighting, supporting human body induction
Intelligent atmosphere
Intelligent atmosphere light, supporting alarm linkage color change.
lamp
Cabinet Size (W*D*H) 600/800*1200*2000/2200mm
Cabinet load bearing 1000KG/1500KG/2000KG
Enter UPS and battery system.
The maximum integrated UPS power distribution is 150KVA; Independent UPS can reach more
UPS rated capacity
than 200KVA; Single module 20KVA/25KVA/40KVA/50KVA; Adopt standard cabinet body.
Frequency range 40--70HZ
Input voltage range 300--460Vac
Output voltage 380/400/415VAC, 50--60Hz, 3Ph+N+PE
Input power factor ≥0.99
Output power factor 1
Battery cupboard Adopt cabinet battery cabinet with heat dissipation module.
Backup time Configure 15min, 30min or other customization according to the actual load.
Number of batteries A total of 16-40 12V lead-acid batteries can be installed in the battery cabinet unit.
Configure according to the actual UPS, and support to monitor the internal resistance, voltage
Battery monitoring
and temperature of each battery.
Into the precision column head cabinet
Input voltage range 360-415Vac
Distribution output The maximum support of input switch is 630A;
Input mode 1/2-way MCCB; PC/CB ATS
Output mode IT load power supply, air conditioning load power supply, other power load power supply, etc.
Examine Support measuring voltage, current, open state, real power, active power and electric energy;
Support main circuit overvoltage and undervoltage alarm, overcurrent alarm, frequency
Report an emergency
abnormality alarm, single-circuit power-off alarm, three-phase unbalance alarm, etc.
Interrow air conditioning
System cooling
25KW/40KW
capacity
Sensible heat ratio 0.99
Internal dimensions
300*1200*2000mm(25KW),600*1200*2000mm(40KW)
(W*D*H)
Refrigerant R410A
Monitoring unit
Man-machine interface 10.1/13.3/15.6/19/21-inch touch screen
Temperature and humidity, smoke, temperature, camera, sound and light alarm, SMS alarm,
Monitoring category
water leakage monitoring, etc.
Integrated monitoring screen/standard 1U rack monitoring host, supporting UPS, air conditioner,
battery and power distribution cabinet monitoring; Support environmental monitoring such as
temperature, humidity, smoke, input and output switching value; Support dual network ports and
Monitoring collection
data export; Support SD card/hard disk to expand storage capacity, support networking
monitoring through northbound interface, support access control system, video system
monitoring and dual power supply expansion.

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
31
Ordering Information
MOC- XXX XX-XX XX- XX XX-XX XX
① ② ③ ④ ⑤ ⑥ ⑦ ⑧
①Cabinet Type and Quantity ⑤ Uninterrupted Power Supply Time and Battery installation

1:600*1000*2000,42U 01: Single cabinet 0: Without battery 1: battery pack

2: 600*1100*2000,42U 02: Dual cabinet 1: 15 minutes 2: Battery cabinet

3: 600*1200*2000,42U 03: Triplex cabinet 2: 30 minutes 3: Battery rack

4: 600*1000*2200,47U 04: Quadruple cabinet 3: 60 minutes

5: 600*1100*2200,47U … ... 4: 120 minutes

6: 600*1200*2200,47U 48: forty-eight cabinet

7: 800*1000*2000,42U ⑥ Type and quantity of air conditioner


1: 12.5KW air-cooled air conditioner between
8: 800*1100*2000,42U 0: 0
trains
2: 25KW air-cooled air conditioner between
9: 800*1200*2000,42U 1: 1
trains
3: 40KW air-cooled air conditioner between
A: 800*1000*2200,47U 2: 2
trains
4: 50KW air-cooled air conditioner between
B: 800*1100*2200,47U 3: 3
trains
C: 800*1200*2200,47U 5: Room-level 12.5KW air-cooled air conditioner 4: 4

②channel type 6: Room-level 20KW air-cooled air conditioner 6: 6


1: fixed skylights on both sides, inverted
skylights in the middle (single opening without
1: Single side cold passage automatic resetting), automatic sliding doors on 7: Room-level 25KW air-cooled air conditioner
both sides of access doors, wiring slots at the
top, and peripheral sealing plates at the top.
2: fixed skylight on both sides, inverted skylight
in the middle (double-opening without automatic
2: Two side cold passage resetting), automatic sliding doors on both sides 8: Room-level 30KW air-cooled air conditioner
of access doors, wiring trough at the top, and
peripheral sealing plate at the top.
3: fixed skylight on both sides, inverted skylight
in the middle (single opening without automatic
resetting), manual sliding doors on both sides of 9: Room-level 35KW air-cooled air conditioner
access doors, wiring trough at the top, and
peripheral sealing plate at the top.
4: fixed skylight on both sides, inverted skylight
in the middle (double-opening without automatic
resetting), manual sliding doors on both sides of A: Room-level 40KW air-cooled air conditioner
access doors, wiring trough at the top, and
peripheral sealing plate at the top.
5: fixed skylights on both sides, inverted
skylights in the middle (single-opening without
automatic resetting), double-opening revolving
B: Room-level 50KW air-cooled air conditioner
doors on both sides of access doors, wiring
ducts at the top, and peripheral sealing plates at
the top.
6: The fixed skylight on both sides, the inverted
skylight in the middle (double-opening without
automatic resetting), the double-opening
C: Room-level 60KW air-cooled air conditioner
revolving door on both sides of the access door,
the top with wiring trough, and the top peripheral
sealing plate.
D: Room-level 70KW air-cooled air conditioner

③Column header tank and Quantity E: Room-level 80KW air-cooled air conditioner

1. Ordinary type 0:0 set F: Room-class 90KW air-cooled air conditioner


2: Precision column head
1:1 set G: Room-class 100KW air-cooled air conditioner
cabinet
3: Integrated UPS cabinet 2:2 set

⑦PDU Standard and Quantity per cabinet

PROSE Technologies Inc.| www.prosetechnologies.com


32 The information contained in this document is subject to change without notice. info@prosetechnologies.com
④UPS Capacity and Quantity A:12 outlet intelligent PDU, 16A, IEC 320 C13 0:0 set

0: Without UPS 0:0 set B: 12 outlets intelligent PDU, 16A, IEC 320 C13 Smart 1:1 set

1: modular 30KVA 1:1 set C: 24 outlets intelligent PDU, 16A, IEC 320 C13 2:2 set

2: modular 40KVA 2:2 set D: 24 outlets intelligent PDU, 16A, IEC 320 C13 Smart

3: Modular 50KVA 3:3 set E: 12 outlet PDU, 16A, IEC 320 C13

4: Modular 60KVA 4:4 set F: 12 outlet PDU, 16A, IEC 320 C13 Smart

5: Modular 80KVA G: 24 outlet PDU, 16A, IEC 320 C13


H: 24 outlet PDU, 16A,
6: Modular 90KVA
IEC 320 C13 Smart
7: Modular 100KVA I: 24 outlet PDU, 32A, IEC 320 20*C13+4*C19
J: 24 outlet PDU, 32A,
8: Modular 120KVA
IEC 320 20*C13+4*C19 Smart
K: 24 outlet PDU, 16A,
9: Modular 150KVA
IEC 320 20*C13+4*C19
L: 24 outlet PDU, 16A,
A: modular 200KVA
IEC 320 20*C13+4*C19 Smart
M: 24 outlet PDU, 32A,
B: modular 300KVA
IEC 320 C13
C: high frequency tower N: 24 outlet PDU, 32A,
30KVA IEC 320 C13 Smart
D: High frequency tower O: 24 outlet PDU, 32A,
40KVA IEC 320 C19
E: high frequency tower P: 24 outlet PDU, 32A,
50KVA IEC 320 C19 Smart
F: high frequency tower Q: 24 outlet PDU, 32A,
60KVA IEC 320 18*C13+6*C19
G: high frequency tower R: 24 outlet PDU, 32A,
80KVA IEC 320 18*C13+6*C19 Smart
H: high frequency tower S: 12 outlet PDU, 32A,
100KVA IEC 320 9*C13+3*C19
I: high frequency tower
120KVA
J: high frequency tower
150KVA
K: high frequency tower
200KVA
L: high frequency tower
300KVA
⑧Dynamic environment monitoring system and Quantity
1: No display host, collects UPS, power distribution module, air conditioner, water leakage, temperature and humidity, smoke sensor, access 0:None
control, intelligent PDU, and northbound interface
2: No display host, collect UPS, power distribution module, air conditioner, water leakage, temperature and humidity, smoke sensor, and
1:1ea
northbound interface
3: Monitors the integrated screen, collecting the UPS, power distribution module, air conditioner, water leakage, temperature and humidity,
2:2ea
smoke sensor, access control, intelligent PDU, and northbound interface
4: Monitors the integrated screen, collecting the UPS, power distribution module, air conditioner, water leakage, temperature and humidity,
smoke sensor, and northbound interface

PROSE Technologies Inc.| www.prosetechnologies.com


The information contained in this document is subject to change without notice. info@prosetechnologies.com
33
PROSE SERVICE

Prose offers professional services that improve network design, reliability,


scalability and efficiency.

Our service core competences include:


• Network optimization
• Technical consultation
• Customized product design
• Installation & commissioning
• Onsite training & supervision
• System troubleshooting
• After-sales services

In addition, we also offer professional training, technical support and workshops for distributors and agents. We are committed to
offering exceptional services for our customers.

Prose is much more than just a supplier – Prose is a valued development partner and we will strive to meet new challenges in order
to scale to new heights.