You are on page 1of 16

Section 6 - 6-248

DHAKA POWER DISTRIBUTION COMPANY LIMITED

BIDDING DOCUMENT
FOR
Design, Supply, Installation, Testing and Commissioning for RRA of 3 nos. 33/11kV Substation and
AIS breaker replacement with GIS breakers at different substations under DPDC including civil work
and related services on Turn-key Basis.

SCHEDULE A

BRIEF DESCRIPTION OF THE WORKS

The bidder shall be deemed to have visited site, inspected, gathered data and verified details of the as-built
system in order to design, supply and interface their new equipment. All necessary materials, adjustments,
dismantling, remedial and tiding-up work in order to complete the work specified shall be included in the
contract price. The contractor is responsible for ensuring that all and/or and any item(s) of work
required for the safe, efficient and satisfactory completion and functioning of the works, are included
in the Bid Price whether they be described in the specification or not.

During execution, the contractor will cooperate with the Cable Contractor and will not claim any damage due
to delay in execution of other related works for energisation of substation.

A1. RRA of Demra 33/11 kV Substation

The existing Demra 33/11 kV Substation located at Demra shall be upgraded by the proposed 33/11 KV
20/28 MVA Transformer. The existing substation shall be upgraded first maintaining the continuity of
electricity distribution with the cooperation of concerned Grid Divisions. The works to be covered under the
contract are to supply and install Plant and Equipment on turnkey basis as per following Scope of Works.

The scope of works include design, manufacture, quality assurance, inspection & testing, packing for export,
insurance & shipment to site, complete construction & installation etc as per Bill of Materials, but not limited
to, including all related civil works to complete the work in all respect up to the commercial operation.

The requirement is stated in the specification and as well as in the technical particulars and guarantee
schedules. The contractor is responsible for ensuring that all and any items of work required for the safe
efficient and satisfactory completion and functioning of the works are to be included in the tender price
whether they are described in the specification or not.

The following civil & electrical works are included in the scope of renovation works:

CIVIL WORKS:
It includes modification/construction of 33kV & 11kV Cable trench (Indoor & Outdoor) for installing
33kV GIS & Control Panel, 11kV AIS and cable connection; modification/construction of Indoor &
outdoor Gantry for cable & Line termination; recovery of all material & equipment (1 nos. 33/11kV,
33kV Breaker, Control Panel, Steel Structure, AC DB etc.) from existing 33/11kV substation and
returning them to DPDC store; dismantling of all existing foundation (1 nos. 33/11kV , steel structure,
outdoor equipment foundation, 33kV Breaker etc.).
Construction of the foundation & required blast wall for the 03 (Three) nos. Nitrogen Injection Fire
Protection System for 20/28 MVA Transformer; Oil pit and drainage system for 02 (Two) nos.
Nitrogen Injection Fire Protection System; Construction/modification of the foundation of the 01
(One) nos. Power Transformers and the foundation of the supporting structures for cable (33kV and
11kV) terminations on both sides of 01 (One) nos Power Transformers; Vertical Extension of
Existing Substation Building (One Raised floor for cable and another floor for 33kV switchgear);
Modification of 11kV switchgear room to accommodate new 11kV AIS in opposite trench of existing
11kV AIS.
Construction of Surface Drain, laying of gravels in the switchyard with associate works, Transformer
Blast Wall, all other miscellaneous civil works required (for FDA system, CCTV system, Internal
electrical works, earthing pit and others).
Internal electrical works for Building Lighting, Small Power, Air Conditioning & Ventilation; Outdoor
Switchyard Lighting, Small Power etc; Earthing & Lightning Protection.

Bidding Document for Package 2 - Renovation, Reinforcement and Augmentation (RRA) of 3 nos. 33/11kV Substation and AIS breaker replacement
with GIS breakers at different substations under DPDC.
Section 6 - 6-249

Installation of the Power Transformer & Aux. Transformer, 33 kV Gas Insulated Switchgear, 11 kV
Air Insulated Switchgear, Cables & Cable accessories and AC, DC Panel to the HV connections, LV
connections and grounding as required and all other electrical items as per BOQ including
relocations and transportation as indicated in the bid.
Installation of Fire Detection Alarm System & Fire extinguisher, Installation and Integration of
Substation Automation System (SAS) for 11kV Circuits and 33 kV Circuits along with UPS System
Installation, Construction of Steel Structure for Line and Cable Termination, Installation of Air
Conditioning Equipment, 33kV Surge Arrester including supporting steel structure and CCTV system
including necessary accessories.
Necessary Civil Modification including breaking of existing walls, floor etc. and all other allied civil
works deemed necessary for the aforesaid works & following electrical works are included in the bid.

ELECTRICAL WORKS:
The works will be done in phases. On completion of civil works of 1 no. of Transformer Foundations,
Control Building Civil Modification, Cable Trench, etc. 1 no. 33/11 kV 20/28 MVA Transformer, 13
nos. 33 kV GIS and 10 nos. 11 kV AIS panels and other associated equipment shall be placed and
commissioned.
1 (One) no. 33/11 kV, 20/28 MVA ONAN/ONAF Power Transformer with Vacuum type On Load Tap
Changer (OLTC), 1 (One) no. Remote Tap Changer Cubicles (RTCC) including Voltage regulating
relay for Power transformer and 03 (Three) sets Nitrogen Injection Fire Protection System for
33/11kV Transformer shall be installed within the Substation Building and connected to the 33 kV
switchgear and 11 kV switchgear panel by single core XPLE(Cu) cable of required voltage, size and
length. The transformers may have top bushing on both HV and LV sides.
33 kV GIS and 11 kV AIS panels shall be designed and installed in such a way that matches with the
existing 33 kV GIS and 11 kV AIS. Manufacturers of the existing 33kV GIS & 11kV AIS are ABB,
India
Control, Protection and Metering (CPM) with Substation Automation System (SAS) and metering
facilities for 33 kV GIS and 11 kV AIS (Required Control, Relay, Protection Devices (IEDs)
including 0.2S class programmable energy meter for all the existing 11kV switchgears in
order to integrate the breakers with SAS and Required Bus extension/truncking to install
11kV Switchgears in opposite trench of 11kV switchgear room) shall be designed, supplied and
installed. Automation should consider the future integration of Smart Grid and must be Compatible
with SCADA and Smart Grid Protocol.
Each transformer shall have to be provided with inter tripping and interlocking facilities between 33
kV and 11 kV switchgear. The conventional protections of transformer feeders, line feeders and
coupler are to be provided. Total protection scheme is to be implemented on approval from
Employer.
33 kV 1cx500 mm² XLPE (Cu) Cable for Source connection from existing source to 33 kV Incoming
Switchgear (1 run per phase); connection from 33 kV Switchgear to 33/11kV power transformer (1
run per phase) and Relocation of 33kV Outgoing feeder cable along with all requirements for these
items (33 kV GIS Plug in type termination, 33 kV Outdoor cable termination and 33 kV Straight
through joint etc.) are to be supplied and installed.
11 kV Cable 1cx500 mm² XLPE (Cu) for connection from power transformer to Switch Gear (3 run
per phase); 11 kV 3cx300 mm² XLPE (Cu) Cable for relocation of all 11 kV outgoing feeder for
existing substations & connection from power transformer to Auxiliary Transformer and 11kV
termination kits (Indoor and Outdoor) along with all requirements for these items are to be supplied
and installed.
All 33 kV & 11 kV feeders are to be provided with programmable energy meter of accuracy class
0.2S with FS > 5, for measuring import and export of energy.
Transportation, Procurement of all equipment and materials, all associated installations, connections
and testing are within the scope of the tender.
5 (Five) sets of As-built drawings together with operation and maintenance manual of the equipment
installed shall be submitted.

A2. RRA of Ullon Local 33/11 kV Substation

The existing Ullon Local 33/11 kV Substation located at Ullon shall be upgraded by the proposed 02 nos.
33/11 KV 20/28 MVA Transformer. The existing substation shall be upgraded first maintaining the continuity
of electricity distribution with the cooperation of concerned Grid Divisions. The works to be covered under the
contract are to supply and install Plant and Equipment on turnkey basis as per following Scope of Works.

Bidding Document for Package 2 - Renovation, Reinforcement and Augmentation (RRA) of 3 nos. 33/11kV Substation and AIS breaker replacement
with GIS breakers at different substations under DPDC.
Section 6 - 6-250

The scope of works include design, manufacture, quality assurance, inspection & testing, packing for export,
insurance & shipment to site, complete construction & installation etc as per Bill of Materials, but not limited
to, including all related civil works to complete the work in all respect up to the commercial operation.

The requirement is stated in the specification and as well as in the technical particulars and guarantee
schedules. The contractor is responsible for ensuring that all and any items of work required for the safe
efficient and satisfactory completion and functioning of the works are to be included in the tender price
whether they are described in the specification or not.

The following civil & electrical works are included in the scope of renovation works:

CIVIL WORKS:
It includes recovery of all material & equipment (33/11kV Transformer, 33kV switchgear, Control
Panel, AC DB, DC DB, Battery & Battery charger, SAS system etc.) from existing 33/11kV
substation and returning them to DPDC store; dismantling of all existing foundation (Transformer,
steel structure, outdoor equipment foundation, 33kV GIS etc.).
Construction of the foundation & required blast wall for the 02 (Two) nos. Nitrogen Injection Fire
Protection System for 20/28 MVA Transformer; Oil pit and drainage system for 02 (Two) nos.
Nitrogen Injection Fire Protection System; Construction/modification of the foundation of the 02
(Two) nos. Power Transformers and the foundation of the supporting structures for cable (33kV and
11kV) terminations on both sides of 02 (Two) nos. Power Transformers along with required Blast/
Fire wall of approved fire rating.
Construction of the foundation of 2 (two) Station Transformers and the supporting structures for
cable connections shall be on both side of the transformers.
Fencing outside periphery of Power Transformer & NIFPS; Modification / Construction of Cable
trench (Indoor and Outdoor); laying of gravels in the switchyard with associate works,
Modification/Construction of Indoor & outdoor Gantry for cable & Line termination, Construction of
Surface Drain and all other miscellaneous civil works required (for FDA system and others).
Internal electrical works for Earthing & Lightning Protection.
Installation of the Power Transformer & Aux. Transformer, 33 kV Gas Insulated Switchgear, 11 kV
Air Insulated Switchgear, Cables & Cable accessories, AC, DC Panel and Batteries & Chargers, to
the HV connections, LV connections and grounding as required and all other electrical items as per
BOQ including relocations and transportation as indicated in the bid.
Installation of Fire Detection Alarm System & Fire extinguisher, Installation and Integration of
Substation Automation System (SAS) for 11kV Circuits and 33 kV Circuits along with UPS System
Installation, Construction of Steel Structure for Line and Cable Termination, Installation of Air
Conditioning Equipment, 33kV Surge Arrester including supporting steel structure and including
necessary accessories and Indoor-outdoor lighting installation with associated civil works.
Necessary Civil Modification including breaking of existing walls, floor etc. and all other allied civil
works deemed necessary for the aforesaid works & following electrical works are included in the bid.

ELECTRICAL WORKS:
The works will be done in phases. On completion of civil works of 2 no. of Transformer Foundations,
Control Building, Civil Modification, Cable Trench, etc. 2 nos. 33/11 kV 20/28 MVA Transformer, 22
nos. 33 kV GIS and 22 nos. 11 kV AIS panels and other associated equipment shall be placed and
commissioned.
2 (Two) Nos. 33/11 kV, 20/28 MVA ONAN/ONAF Power Transformer with Vacuum type On Load
Tap Changer (OLTC), 02 (Two) nos. Remote Tap Changer Cubicles (RTCC) including Voltage
regulating relay for Power transformer and 02 (Two) sets Nitrogen Injection Fire Protection System
for 33/11kV Transformer shall be installed within the Substation Building and connected to the 33 kV
switchgear and 11 kV switchgear panel by single core XPLE(Cu) cable of required voltage, size and
length. The transformers may have top bushing on both HV and LV sides.
33 kV GIS and 11 kV AIS panels shall be designed and installed in such a way that matches with the
existing 33 kV GIS and 11 kV AIS. Manufacturers of the existing 33kV GIS & 11kV AIS are ABB,
India
Control, Relay, Protection with Substation Automation System (SAS) and metering facilities for 33
kV GIS and 11 kV AIS shall be designed, supplied and installed. Automation should consider the
future integration of Smart Grid and must be Compatible with SCADA and Smart Grid Protocol.

Bidding Document for Package 2 - Renovation, Reinforcement and Augmentation (RRA) of 3 nos. 33/11kV Substation and AIS breaker replacement
with GIS breakers at different substations under DPDC.
Section 6 - 6-251

Each transformer shall have to be provided with inter tripping and interlocking facilities between 33
kV and 11 kV switchgear. The conventional protections of transformer feeders, line feeders and
coupler are to be provided. Total protection scheme is to be implemented on approval from
Employer.
33 kV 1cx800 mm² XLPE (Cu) Cable for Source connection from 132/33kV Transformer to 33kV
incoming Switchgear (3 run per phase); connection from 33 kV Switchgear to 33/11kV power
transformer (1 run per phase) and 33 kV 1cx500 mm² or 1cx400 mm² (as per requirement of site and
XLPE (Cu) Cable for Relocation of 33kV Outgoing feeder along with all
requirements for these type of Cables (33 kV GIS Plug in type termination, 33 kV Outdoor cable
termination and 33 kV Straight through joint etc.) are to be supplied and installed.
11 kV Cable 1cx500 mm² XLPE (Cu) for connection from power transformer to Switch Gear (3 run
per phase); 11 kV 3cx300 mm²
XLPE (Cu) Cable for relocation of all 11 kV outgoing feeder for existing substations & connection
from power transformer to Auxiliary Transformer and 11kV termination kits (Indoor and Outdoor)
along with all requirements for these types of Cables are to be supplied and installed.
All 33 kV & 11 kV feeders are to be provided with programmable energy meter of accuracy class
0.2S with FS > 5, for measuring import and export of energy.
Transportation, Procurement of all equipment and materials, all associated installations, connections
and testing are within the scope of the tender.
5 (Five) sets of As-built drawings together with operation and maintenance manual of the equipment
installed shall be submitted.

A3. RRA of Shyampur BSCIC 33/11 kV Substation

The existing Shympur BSCIC 33/11 kV Substation located at Shyampur BSCIC shall be upgraded by the
proposed 01 no. 33/11 KV 20/28 MVA Transformer. The existing substation shall be upgraded first
maintaining the continuity of electricity distribution with the cooperation of concerned Grid Divisions. The
works to be covered under the contract are to supply and install Plant and Equipment on turnkey basis as
per following Scope of Works.

The scope of works include design, manufacture, quality assurance, inspection & testing, packing for export,
insurance & shipment to site, complete construction & installation etc as per Bill of Materials, but not limited
to, including all related civil works to complete the work in all respect up to the commercial operation.

The requirement is stated in the specification and as well as in the technical particulars and guarantee
schedules. The contractor is responsible for ensuring that all and any items of work required for the safe
efficient and satisfactory completion and functioning of the works are to be included in the tender price
whether they are described in the specification or not.

The following civil & electrical works are included in the scope of renovation works:

CIVIL WORKS:
Modification/Construction of 33kV & 11kV Cable trench (Indoor & Outdoor) for installing 33kV GIS &
Control Panel, 11kV AIS and cable connection; Modification/Construction of Indoor & outdoor Gantry
for cable & Line termination; Dismantling of all existing foundation (steel structure, outdoor
equipment &1 nos. 33/11kV Transformer foundation), one storied building etc; Recovery of material
& equipment from existing 33/11kV substation (1 nos. 33/11kV Transformer, Breakers and others)
and returning them to DPDC store.
Construction of the foundation & required blast wall for the 03 (Three) nos. Nitrogen Injection Fire
Protection System for 20/28 MVA Transformer; Oil pit and drainage system for 03 (Three) nos.
Nitrogen Injection Fire Protection System; Construction of the foundation of the 33/11kV
Transformers including the foundation of the supporting structures for cable (33kV and 11kV)
terminations on both sides of the Power Transformers.
Modification of 33kV switchgear & CRP room including battery & Metering room to accommodate
33kV GIS in same trench (Rearrangement & reconstruction of Battery & Metering room is required)
Fencing for all the Transformers yard; Surface Drain; laying of gravels in the switchyard with
associate works, Transformer Blast Wall; Fire shield (seal) with associated fire rating for 33kV GIS

Bidding Document for Package 2 - Renovation, Reinforcement and Augmentation (RRA) of 3 nos. 33/11kV Substation and AIS breaker replacement
with GIS breakers at different substations under DPDC.
Section 6 - 6-252

room and 11kV Breaker room & cable and all other miscellaneous civil works required (for FDA
system and others).
Internal electrical works for Building Lighting, Small Power, Air Conditioning & Ventilation; Outdoor
Switchyard Lighting, Small Power etc and Earthing & Lightning Protection.
Installation of the Power Transformer, 33 kV Gas Insulated Switchgear, 11 kV Air Insulated
Switchgear, Cables & Cable accessories to the HV connections, LV connections and grounding as
required including relocations and transportation as indicated in the bid.
Installation of Fire Detection Alarm System & Fire extinguisher, Installation and Integration of
Substation Automation System (SAS) for 11kV Circuits and 33 kV Circuits along with UPS System
Installation, Construction of Steel Structure for Line and Cable Termination, Installation of Air
Conditioning Equipment, 33kV Surge Arrester including supporting steel structure and all other
electrical items as per BOQ including necessary accessories.
Necessary Civil Modification including breaking of existing walls, floor etc. and all other allied civil
works deemed necessary for the aforesaid works & following electrical works are included in the bid.

ELECTRICAL WORKS:
The works will be done in phases. On completion of civil works of 2 no. of Transformer Foundations,
Control Building, Civil Modification, Cable Trench, etc. 1(One) no. 33/11 kV 20/28 MVA Transformer,
04 nos. 33 kV GIS and 12 nos. 11 kV AIS panels and other associated equipment shall be placed
and commissioned.
01 (One) No. 33/11 kV, 20/28 MVA ONAN/ONAF Power Transformer with Vacuum type On Load
Tap Changer (OLTC), 01 (One) no. Remote Tap Changer Cubicles (RTCC) including Voltage
regulating relay for Power transformer and 03 (Three) sets Nitrogen Injection Fire Protection System
for 33/11kV Transformer shall be installed within the Substation Building and connected to the 33 kV
switchgear and 11 kV switchgear panel by single core XPLE(Cu) cable of required voltage, size and
length. The transformers may have top bushing on both HV and LV sides.
33 kV GIS and 11 kV AIS panels shall be designed and installed in such a way that matches with the
existing 33 kV GIS and 11 kV AIS. Manufacturers of the existing 33kV GIS & 11kV AIS are ABB,
India
Control, Protection and Metering (CPM) with Substation Automation System (SAS) and metering
facilities for 33 kV GIS and 11 kV AIS (Required Control, Relay, Protection Devices (IEDs)
including 0.2S class programmable energy meter for all the existing 11kV switchgears in
order to integrate the breakers with SAS and Required Bus extension/truncking to install
11kV Switchgears in opposite trench of 11kV switchgear room) shall be designed, supplied and
installed. Automation should consider the future integration of Smart Grid and must be Compatible
with SCADA and Smart Grid Protocol.
Each transformer shall have to be provided with inter tripping and interlocking facilities between 33
kV and 11 kV switchgear. The conventional protections of transformer feeders, line feeders and
coupler are to be provided. Total protection scheme is to be implemented on approval from
Employer.
33 kV 1cx500 mm² XLPE (Cu) Cable for Source connection from existing source to 33 kV Incoming
Switchgear (1 run per phase); connection from 33 kV Switchgear to 33/11kV power transformer (1
run per phase) and Relocation of 33kV Outgoing feeder cable along with all requirements for these
type of Cables (33 kV GIS Plug in type termination, 33 kV Outdoor cable termination and 33 kV
Straight through joint etc.) are to be supplied and installed.
11 kV Cable 1cx500 mm² XLPE (Cu) for connection from power transformer to Switch Gear (3 run
per phase); 11 kV 3cx300 mm² XLPE (Cu) Cable for relocation of all 11 kV outgoing feeder for
existing substations & connection from power transformer to Auxiliary Transformer and 11kV
termination kits (Indoor and Outdoor) along with all requirements for these types of Cables are to be
supplied and installed.
All 33 kV & 11 kV feeders are to be provided with programmable energy meter of accuracy class
0.2S with FS > 5, for measuring import and export of energy.
Transportation, Procurement of all equipment and materials, all associated installations, connections
and testing are within the scope of the tender.
5 (Five) sets of As-built drawings together with operation and maintenance manual of the equipment
installed shall be submitted.

Bidding Document for Package 2 - Renovation, Reinforcement and Augmentation (RRA) of 3 nos. 33/11kV Substation and AIS breaker replacement
with GIS breakers at different substations under DPDC.
Section 6 - 6-253

B1. Breaker Change of Khilgaon (Gulbag) 33/11 kV Substation

The existing Khilgaon (Gulbag) 33/11 kV Substation located at Khilgaon (Gulbag) shall be upgraded by
the required breaker change. The existing substation shall be upgraded first maintaining the continuity of
electricity distribution with the cooperation of concerned Grid Divisions. The works to be covered under the
contract are to supply and install Plant and Equipment on turnkey basis as per following Scope of Works.

The scope of works include design, manufacture, quality assurance, inspection & testing, packing for export,
insurance & shipment to site, complete construction & installation etc as per Bill of Materials, but not limited
to, including all related civil works to complete the work in all respect up to the commercial operation.

The requirement is stated in the specification and as well as in the technical particulars and guarantee
schedules. The contractor is responsible for ensuring that all and any items of work required for the safe
efficient and satisfactory completion and functioning of the works are to be included in the tender price
whether they are described in the specification or not.

The following civil & electrical works are included in the scope of renovation works:

CIVIL WORKS:
It includes modification/construction of 33kV & 11kV Cable trench (Indoor & Outdoor) for installing
33kV GIS & Control Panel; Recovery of all material & equipment (33kV VCB, Control Panel etc.) for
existing 33/11kV substation and returning them to DPDC store.
Construction of the foundation & required blast wall for the 02 (Two) nos. Nitrogen Injection Fire
Protection System for 20/28 MVA Transformer; Oil pit and drainage system for 02 (Two) nos.
Nitrogen Injection Fire Protection System; All other miscellaneous civil works required (for FDA
system and others).
Internal electrical works for Earthing & Lightning Protection.
Installation of Nitrogen Injection Fire Protection System and related accessories, 33 kV Gas
Insulated Switchgear, 11 kV Air Insulated Switchgear, Cables & Cable accessories as required and
all other electrical items as per BOQ including relocations and transportation as indicated in the bid.
Installation of fire Detection Alarm System & Fire extinguisher; Installation and Integration of
Substation Automation System (SAS) for 11kV Circuits and 33 kV Circuits along with UPS System
Installation and Air Conditioning Equipment Installation.
Necessary Civil Modification including breaking of existing walls, floor etc. and all other allied civil
works deemed necessary for the aforesaid works & following electrical works are included in the bid.

ELECTRICAL WORKS:
The works will be done in phases. On completion of civil works of 09 nos. 33 kV GIS and other
associated equipment shall be placed and commissioned.
02 (Two) sets Nitrogen Injection Fire Protection System for 33/11kV Transformer shall be installed
within the Substation Building and connected to the 33 kV switchgear and 11 kV switchgear panel by
single core XPLE(Cu) cable of required voltage, size and length. The transformers may have top
bushing on both HV and LV sides.
33 kV GIS panels shall be designed and installed in such a way that matches with the existing 33 kV
GIS. Manufacturers of the existing 33kV GIS ABB, India
Control, Protection and Metering (CPM) with Substation Automation System (SAS) and metering
facilities for 33 kV GIS shall be designed, supplied and installed. Automation should consider the
future integration of Smart Grid and must be Compatible with SCADA and Smart Grid Protocol.
33 kV 1cx500 mm² XLPE (Cu) Cable for Source connection from existing source to 33 kV Incoming
Switchgear (1 run per phase); connection from 33 kV Switchgear to 33/11kV power transformer (1
run per phase) and Relocation of 33kV Outgoing feeder cable along with all requirements for these
type of Cables (33 kV GIS Plug in type termination, 33 kV Outdoor cable termination and 33 kV
Straight through joint etc.) are to be supplied and installed.
All 33 kV & 11 kV feeders are to be provided with programmable energy meter of accuracy class
0.2S with FS > 5, for measuring import and export of energy.

Bidding Document for Package 2 - Renovation, Reinforcement and Augmentation (RRA) of 3 nos. 33/11kV Substation and AIS breaker replacement
with GIS breakers at different substations under DPDC.
Section 6 - 6-254

Transportation, Procurement of all equipment and materials, all associated installations, connections
and testing are within the scope of the tender.
5 (Five) sets of As-built drawings together with operation and maintenance manual of the equipment
installed shall be submitted.

B2. Breaker Change of Khanpur 33/11 kV Substation

The existing Khanpur 33/11 kV Substation located at Khanpur shall be upgraded by the required breaker
change. The existing substation shall be upgraded first maintaining the continuity of electricity distribution
with the cooperation of concerned Grid Divisions. The works to be covered under the contract are to supply
and install Plant and Equipment on turnkey basis as per following Scope of Works.

The scope of works include design, manufacture, quality assurance, inspection & testing, packing for export,
insurance & shipment to site, complete construction & installation etc as per Bill of Materials, but not limited
to, including all related civil works to complete the work in all respect up to the commercial operation.

The requirement is stated in the specification and as well as in the technical particulars and guarantee
schedules. The contractor is responsible for ensuring that all and any items of work required for the safe
efficient and satisfactory completion and functioning of the works are to be included in the tender price
whether they are described in the specification or not.

The following civil & electrical works are included in the scope of renovation works:

CIVIL WORKS:
It includes Recovery of all material & equipment (33kV breaker, Control Panel, AC DB, DC DB,
Battery & Battery charger, SAS system etc.) from existing 33/11kV substation and returning them to
DPDC store; Dismantling of all existing foundation (steel structure, outdoor equipment foundation,
cable trench etc.); modification/construction of 33kV Cable trench for installing 33kV GIS & Control
Panel; Modification/Construction of Indoor & outdoor Gantry for cable & Line termination and
Recovery of all material & equipment (33kV Breaker, Control Panel, Steel Structure, AC DB, DC DB,
Battery & Battery charger etc.) from existing 33/11kV substation and returning them to DPDC store.
Construction of the foundation & required blast wall for the 04 (Four) nos. Nitrogen Injection Fire
Protection System for 20/28 MVA Transformer; Oil pit and drainage system for 04 (Four) nos.
Nitrogen Injection Fire Protection System.
Construction of 01 storied control building (06 storied foundation) with 01 semi-basement along with
the facilities of passenger lift shaft for installing 8 persons capacity lift, main stair case, emergency
exit stair (if feasible), electricity, water supply, sewerage, guard house, boundary wall, septic tank,
soak well, water reservoir (underground & overhead) electricity, water supply, sewerage etc. All the
33kV switchgear are to be accommodated in this building and all 33 kV Control cum Relay panel
along with SAS, battery room etc. facilities might be accommodated in ground floor depending on
the final design approval or feasibility condition. Additionally, one toilet block (with provision of 02
individual toilets, urinal, basin, ablution etc.), one office room, one storage room, one Tea room
needs to be provided in Ground floor. The Plinth level/ Floor Finish level of the control building shall
be minimum 1000 mm considering the past flood level of the area and future development of road
top level.
Construction of Surface Drain and all other miscellaneous civil works required (for FDA system and
others).
Internal electrical works for Building Lighting, Small Power, Air Conditioning & Ventilation; Outdoor
Switchyard Lighting, Small Power etc. and Earthing & Lightning Protection. All metal work (such as
Window grill frames, metallic fences, Metallic gates etc.) within the project area which does not form
part of the electrical equipment shall be bonded to the Control building individual earthing system.
Installation of Nitrogen Injection Fire Protection System and related accessories, 33 kV Gas
Insulated Switchgear, 11 kV Air Insulated Switchgear, Cables & Cable accessories, AC, DC Panel,
Batteries, Chargers as required and all other electrical items as per BOQ including relocations and
transportation as indicated in the bid.
Installation of fire Detection Alarm System & Fire extinguisher; Installation and Integration of
Substation Automation System (SAS) for 11kV Circuits and 33 kV Circuits along with UPS System
Installation and Air Conditioning Equipment Installation.

Bidding Document for Package 2 - Renovation, Reinforcement and Augmentation (RRA) of 3 nos. 33/11kV Substation and AIS breaker replacement
with GIS breakers at different substations under DPDC.
Section 6 - 6-255

Necessary Civil Modification including breaking of existing walls, floor etc. and all other allied civil
works deemed necessary for the aforesaid works & following electrical works are included in the bid.

ELECTRICAL WORKS:
The works will be done in phases. On completion of civil works of 04(Four) nos. Nitrogen Injection
Fire Protection System for 33/11kV Transformer, 13 nos. 33 kV GIS panels and other
associated equipment shall be placed and commissioned.
33 kV GIS panels shall be designed and installed in such a way that matches with the existing 33 kV
GIS. Manufacturers of the existing 33kV GIS are ABB, India
Control, Protection and Metering (CPM) with Substation Automation System (SAS) and metering
facilities for 33 kV GIS shall be designed, supplied and installed. Automation should consider the
future integration of Smart Grid and must be Compatible with SCADA and Smart Grid Protocol.
Required Control, Relay, Protection Devices (IEDs) including 0.2S class programmable energy
meter for all the existing 11kV switchgears in order to integrate the breakers with SAS shall be
supplied and installed.
33 kV 1cx500 mm² XLPE (Cu) Cable for Source connection from existing source to 33 kV Incoming
Switchgear (1 run per phase); connection from 33 kV Switchgear to 33/11kV power transformer (1
run per phase) and Relocation of 33kV Outgoing feeder cable along with all requirements for these
type of Cables (33 kV GIS Plug in type termination, 33 kV Outdoor cable termination and 33 kV
Straight through joint etc.) are to be supplied and installed.
Transportation, Procurement of all equipment and materials, all associated installations, connections
and testing are within the scope of the tender.
5 (Five) sets of As-built drawings together with operation and maintenance manual of the equipment
installed shall be submitted.

B3. Breaker Change of Green Road 33/11 kV Substation

The existing Green Road 33/11 kV Substation located at Green Road shall be upgraded by the required
breaker change. The existing substation shall be upgraded first maintaining the continuity of electricity
distribution with the cooperation of concerned Grid Divisions. The works to be covered under the contract are
to supply and install Plant and Equipment on turnkey basis as per following Scope of Works.

The scope of works include design, manufacture, quality assurance, inspection & testing, packing for export,
insurance & shipment to site, complete construction & installation etc as per Bill of Materials, but not limited
to, including all related civil works to complete the work in all respect up to the commercial operation.

The requirement is stated in the specification and as well as in the technical particulars and guarantee
schedules. The contractor is responsible for ensuring that all and any items of work required for the safe
efficient and satisfactory completion and functioning of the works are to be included in the tender price
whether they are described in the specification or not.

The following civil & electrical works are included in the scope of renovation works:

CIVIL WORKS:
It includes Modification/Construction of 33kV Cable trench for installing 33kV GIS & Control Panel;
Modification/Construction of Indoor & outdoor Gantry for cable & Line termination and Recovery of
all material & equipment (33kV Breaker, Control Panel, Steel Structure, AC DB, DC DB, Battery &
Battery charger etc.) from existing 33/11kV substation and returning them to DPDC store.
Construction of the foundation & required blast wall for the 02 (Two) nos. Nitrogen Injection Fire
Protection System for 33/11kV Transformer; Oil pit and drainage system for 02 (Two) nos. Nitrogen
Injection Fire Protection System.
All other miscellaneous civil works required (for FDA system and others).
Internal electrical works for Earthing & Lightning Protection.

Bidding Document for Package 2 - Renovation, Reinforcement and Augmentation (RRA) of 3 nos. 33/11kV Substation and AIS breaker replacement
with GIS breakers at different substations under DPDC.
Section 6 - 6-256

Installation of Nitrogen Injection Fire Protection System and related accessories, 33 kV Gas
Insulated Switchgear, 11 kV Air Insulated Switchgear, Cables & Cable accessories, AC, DC Panel,
Batteries, Chargers as required and all other electrical items as per BOQ including relocations and
transportation as indicated in the bid.
Installation of fire Detection Alarm System & Fire extinguisher; Installation and Integration of
Substation Automation System (SAS) for 11kV Circuits and 33 kV Circuits along with UPS System
Installation and Air Conditioning Equipment Installation.
Necessary Civil Modification including breaking of existing walls, floor etc. and all other allied civil
works deemed necessary for the aforesaid works & following electrical works are included in the bid.

ELECTRICAL WORKS:
The works will be done in phases. On completion of civil works of 02 (Two) nos. Nitrogen Injection
Fire Protection System for 33/11kV Transformer, 08 nos. 33 kV GIS panels and other
associated equipment shall be placed and commissioned.
33 kV GIS panels shall be designed and installed in such a way that matches with the existing 33 kV
GIS. Manufacturers of the existing 33kV GIS are ABB, India
Control, Relay, Protection with Substation Automation System (SAS) and metering facilities for 33
kV GIS shall be designed, supplied and installed. Automation should consider the future integration
of Smart Grid and must be Compatible with SCADA and Smart Grid Protocol.
Required Control, Relay, Protection Devices (IEDs) including 0.2S class programmable energy
meter for all the existing 11kV switchgears in order to integrate the breakers with SAS.shall be
supplied and installed.
33 kV 1cx500 mm² XLPE (Cu) Cable for Source connection from existing source to 33 kV Incoming
Switchgear (1 run per phase); connection from 33 kV Switchgear to 33/11kV power transformer (1
run per phase) and Relocation of 33kV Outgoing feeder cable along with all requirements for these
type of Cables (33 kV GIS Plug in type termination, 33 kV Outdoor cable termination and 33 kV
Straight through joint etc.) are to be supplied and installed.
Transportation, Procurement of all equipment and materials, all associated installations, connections
and testing are within the scope of the tender.
5 (Five) sets of As-built drawings together with operation and maintenance manual of the equipment
installed shall be submitted.

B4. Breaker Change of Kamrangirchar 132/3kV & 33/11 kV Substation

The existing Kamrangirchar 132/3kV & 33/11 kV Substation located at Kamrangirchar shall be upgraded
by the required breaker change. The existing substation shall be upgraded first maintaining the continuity of
electricity distribution with the cooperation of concerned Grid Divisions. The works to be covered under the
contract are to supply and install Plant and Equipment on turnkey basis as per following Scope of Works.

The scope of works include design, manufacture, quality assurance, inspection & testing, packing for export,
insurance & shipment to site, complete construction & installation etc as per Bill of Materials, but not limited
to, including all related civil works to complete the work in all respect up to the commercial operation.

The requirement is stated in the specification and as well as in the technical particulars and guarantee
schedules. The contractor is responsible for ensuring that all and any items of work required for the safe
efficient and satisfactory completion and functioning of the works are to be included in the tender price
whether they are described in the specification or not.

The following civil & electrical works are included in the scope of renovation works:

CIVIL WORKS:
It includes Recovery of all material & equipment (11kV switchgear and other) from existing 33/11kV
substation and returning them to DPDC store, Modification / Construction of 11kV Cable trench
(Indoor and Outdoor); Modification/Construction of Indoor & outdoor Gantry for 11kV cable & Line
termination and all other miscellaneous civil works required (for FDA system and others).
Installation of 11 kV Air Insulated Switchgear, Cables & Cable accessories and Integration as
required including relocations and transportation as indicated in the bid.

Bidding Document for Package 2 - Renovation, Reinforcement and Augmentation (RRA) of 3 nos. 33/11kV Substation and AIS breaker replacement
with GIS breakers at different substations under DPDC.
Section 6 - 6-257

Installation and Integration of Substation Automation System (SAS) for 11kV Circuits and 33 kV
Circuits along with UPS System Installation and construction of Steel Structure for Line, Cable
Termination and all other electrical items as per BOQ.
Necessary Civil Modification including breaking of existing walls, floor etc. and all other allied civil
works deemed necessary for the aforesaid works & following electrical works are included in the bid.

ELECTRICAL WORKS:
The works will be done in phases. On completion of civil works 09 nos. 11 kV AIS panels and other
associated equipment shall be placed and commissioned.
11 kV AIS panels shall be designed and installed in such a way that matches with the existing 11 kV
AIS. Manufacturers of the existing 11 kV AIS are ABB, India
Control, Relay, Protection with Substation Automation System (SAS) and metering facilities for 11
kV AIS shall be designed, supplied and installed. Automation should consider the future integration
of Smart Grid and must be Compatible with SCADA and Smart Grid Protocol.
11 kV Cable 1cx500 mm² XLPE (Cu) for connection from power transformer to Switch Gear (3 run
per phase); 11 kV 3cx300 mm²
XLPE (Cu) Cable for relocation of all 11 kV outgoing feeder for existing substations & connection
from power transformer to Auxiliary Transformer and 11kV termination kits (Indoor and Outdoor)
along with all requirements for these types of Cables are to be supplied and installed.
UPS System for SAS Panels of 2000 VA shall be supplied and installed as per requirement.
Transportation, Procurement of all equipment and materials, all associated installations, connections
and testing are within the scope of the tender.
5 (Five) sets of As-built drawings together with operation and maintenance manual of the equipment
installed shall be submitted.

C. Vehicle for Transportation

The Contractor shall provide a vehicle (microbus) including driver, fuel, maintenance etc. for
transportation of DPDC officials during work implementation time. All the arrangements and
expenses of this vehicle will be borne by the contractor and the Cost shall be deemed included in
price schedule.

Bidding Document for Package 2 - Renovation, Reinforcement and Augmentation (RRA) of 3 nos. 33/11kV Substation and AIS breaker replacement
with GIS breakers at different substations under DPDC.
Section 6 - 6-258

PROJECT REQUIREMENT FOR EACH OF

Design, Supply, Installation, Testing and Commissioning for RRA of 3 nos. 33/11kV Substation and
AIS breaker replacement with GIS breakers at different substations under DPDC including civil work
and related services on Turn-key Basis.

Item Description Quantity


No.
Design manufacture, factory testing carrying and handling up to the port of loading and As per
shipment of: price
1 Transformer and RTCC schedule
1.01 33/11 kV, 20/28 MVA ONAN/ONAF Power Transformer with Vacuum type On Load
Tap Changer (OLTC) made by MR, Germany.
1.02 Remote Tap Changer Control (RTCC) Cubicles including Voltage regulating relay
made by MR, Germany for Power transformer.
1.03 Nitrogen Injection Fire Protection System for 20/28 MVA Transformer
2 33 kV Indoor Type Gas Insulated Switchgear
(GIS), 3000 Amps or 2000 Amps Single Bus System having segregated gas
chamber for each switchgear
2.01 33 kV, 3000A Incoming Feeder with Potential Transformer (PT) and Current
Transformer (CT)

CT Ratio: 1600-2400/1-1-1 A
Short Circit current capacity: 31.5 kA for 3 sec
2.02 33 kV, 2000A Incoming Feeder with Potential Transformer (PT) and Current
Transformer (CT)

CT Ratio: 900-1800/1-1-1 A
Short Circuit current capacity: 31.5 kA for 3 sec
2.03 33 kV, 3000A Bus Section Switchgear (Bus coupler and Bus Riser) having CT
(Current Transformer)
CT Ratio: 1600-2400/1-1-1 A
Short Circit current capacity: 31.5 kA for 3 sec
2.04 33 kV, 2000A Bus Section Switchgear (Bus coupler and Bus Riser) having CT
(Current Transformer)
CT Ratio: 900-1800/1-1 A
Short Circuit current capacity: 31.5 kA for 3 sec
2.05 33 kV, 2000A Outgoing Feeder for 33/11 kV Transformer with Potential Transformer
(PT) and Current Transformer (CT)
CT Ratio: 900-1800/1-1-1 A

Short Circit current capacity: 31.5 kA for 3 sec


2.06 33 kV 2000A Outgoing Feeder with Current Transformer (CT)
CT Ratio: 900-1800/1-1-1 A
Short Circit current capacity: 31.5 kA for 3 sec
2.07 33 kV, 3000A Bus with Bus PT

Short Circit current capacity: 31.5 kA for 3 sec


2.08 33 kV, 2000A Bus with Bus PT

Short Circuit current capacity: 31.5 kA for 3 sec


3 Control, Protection and Metering for 33 kV GIS compatible with Susbstation
Automation System (SAS)
3.01 For 33 kV, 3000A or 2000A Incoming Feeder
3.01.1 Control, Protection, Metering Panel with complete assembly
3.01.2 Measuring instruments (0.2s class Programmable energy meter, multifunction meter,
Ammeter etc) and others
3.01.3 Control & Protection IEDs
3.02 For 33 kV, 3000A or 2000A Bus Sectionalizer with Bus Riser
3.02.1 Control & Protection Panel with complete assembly
3.02.2 Control & Protection IEDs
3.03 For 33 kV, 2000A Transformer Feeder

Bidding Document for Package 2 - Renovation, Reinforcement and Augmentation (RRA) of 3 nos. 33/11kV Substation and AIS breaker replacement
with GIS breakers at different substations under DPDC.
Section 6 - 6-259

3.03.1 Control, Protection, Metering Panel with complete assembly


3.03.2 Measuring instruments (0.2s class Programmable energy meter, multifunction meter,
Ammeter etc) and others
3.03.3 Contyrol & Protection IEDs
3.04 For 33 kV, 2000A Outgoing Feeder
3.04.1 Control, Protection, Metering Panel with complete assembly
3.04.2 Measuring instruments (0.2s class Programmable energy meter, multifunction meter,
Ammeter etc) and others
3.04.3 Control & Protection IEDs
3.05 For 33 kV Bus with Three draw out type Bus PT
3.05.1 Control Panel
3.05.2 Measuring instruments (multifunction meter, Voltmeter etc) and others
4 11 kV Air insulated Switchgear including Control, Protection and Metering
compatible with Substation Automation System (SAS)
4.01 11 kV 2500A Bus with Three Bus PT

Short Circuit current capacity: 31.5 kA for 3 sec


This item includes Control, Relay, Protection with SAS facilities including 0.2S class
programmable energy meter.
4.02 11 kV, 2500A Incomer Switchgear with Potential Transformer (PT) and Current
Transformer (CT)

CT Ratio: 1200-2400/1-1-1A
Short Circuit current capacity: 31.5 kA for 3 sec
This item includes Control, Relay, Protection with SAS facilities including 0.2S class
programmable energy meter.
4.03 11 kV 2500A Bus Sectionalizer Switchgear with Current Transformer (CT)
CT Ratio: 1200-2400/1-1A
Short Circuit current capacity: 31.5 kA for 3 sec
This includes Control, Relay, Protection with SAS facilities.
4.04 11 KV 800A Bus Outgoing Feeder Switchgear with Current Transformer (CT)
CT Ratio: 600-300/1-1A
Short Circuit current capacity: 31.5 kA for 3 sec As per
This item includes Control, Relay, Protection with SAS facilities including 0.2S class price
programmable energy meter. schedule
5 33 kV Underground Cable and accessories As per
5.01 33 kV, 1cx800 mm² XLPE (Cu) Cable for price
i. Source connection from 132/33kV Transformer to 33kV incoming schedule
Switchgear (3 run per phase) As per
ii. connection from 33 kV Switchgear to 33/11kV power transformer (1 run price
per phase) schedule
5.02 33 kV, 1cx500 mm² or 1cx400 mm² (as per requirement of site and
approval) XLPE (Cu) Cable for
i. Source connection from existing source to 33 kV Incoming Switchgear (1
run per phase)
ii. connection from 33 kV Switchgear to 33/11kV power transformer (1 run
per phase)
iii. Relocation of 33kV Outgoing feeder cable
5.03 33 kV Cable termination (GIS Plug in type termination including dummy plug
compatible with 33 kV switchgear, Cable Size 1cx800 mm² XLPE (Cu))
5.04 33 kV Cable termination (GIS Plug in type termination including dummy plug
compatible with 33 kV switchgear, Cable Size 1cx500 mm² or 1cx400 mm² (as per
XLPE (Cu))
5.05 33 kV outdoor Cable termination (Cable Size 1cx800 mm² XLPE (Cu))
(final quantity to be delivered as per requirement of site)
5.06 33 kV Straight through joint with all requirements for Cable Size 1cx800 mm² XLPE
(Cu)
5.07 33 kV Straight through joint with all requirements for Cable Size 1cx500 mm² or
XLPE (Cu)
6 11 kV Underground Cable and accessories
6.01 11 kV Cable 1cx500 mm² XLPE (Cu) for connection from power transformer to
Switch Gear (3 run per phase) .

Bidding Document for Package 2 - Renovation, Reinforcement and Augmentation (RRA) of 3 nos. 33/11kV Substation and AIS breaker replacement
with GIS breakers at different substations under DPDC.
Section 6 - 6-260

6.02 11 kV 3C*300mm2
approval)Cable for
i. relocation of all 11kV outgoing feeder of existing Substation.
ii. connection from power transformer to Auxiliary Transformer.
6.03 11kV termination (Indoor) along with all requirements for Cable 1cx500 mm² XLPE
(Cu)
6.04 11kV termination (Outdoor) along with all requirements for Cable 1cx500 mm² XLPE
(Cu)
6.05 11kV termination (Indoor) along with all requirements for Cable 3Cx300 mm² or
XLPE (Cu)
6.06 11kV termination (Outdoor) along with all requirements for Cable 3Cx300 mm² or
XLPE (Cu)
6.07 11kV straight through joint along with all requirements for relocation of feeders cable
7 AC, DC Panel
7.01 AC Distribution Panel with mechanical and electrical interlocking and Bus Tie
Scheme
7.02 DC Distribution Panel with interlocking and Bus Tie Scheme
8 LV Control & Power Cable
9 Battery and Battery Charger 110V
9.01 110 V Battery (350Ah Ni-Cd) with accessories
9.02 110 V Battery Charger with accessories
10 Supply necessary grounding cable, Cu rod etc. for Earthing System. Earthing
resistance should be obtained below 0.5 ohm
11 Fire Extinguishing Equipment
11.01 Fire Detection Alarm System for substation building
11.02 Trolly mounted fire extinguisher with dry type chemical for A, B and C type fire (15
kg.)
11.03 Wall mounted fire extinguisher with dry type chemical for A, B and C type fire (5 kg.)
11.04 Trolly mounted fire extinguisher with dry type chemical for A, B and C type fire (2 kg.)
11.05 Wall mounted fire extinguisher with CO2 type chemical for A, B and C type fire (5 kg.) As per
11.06 Small portable type fire extinguisher with dry type chemical for A, B and C type fire (2 price
kg.) schedule
12 Substation Automation System (Automation Should Consider the future As per
integration of Smart Grid and Must be Compatible with SCADA and Smart Grid price
Protocol) schedule
12.01 Substation Automation System (SAS) for both 33 kV and 11 kV voltage level
Substation Automation System including RTU's, Data Hub, GPS, Communication
Cable/Fiber Optic, Workstation, Graphical User Software, network switching device
etc for Incoming line circuit, Transformer circuit, outgoing circuits, Bus-coupler and
spare bay circuit etc.
12.02 Online UPS System for SAS Panels 2000 VA
13 Steel Structure, Conductor, Insulator, Connector
13.01 Steel Structure for Line and Cable Termination
14 Indoor & Outdoor lighting
14.01 Indoor & Outdoor lighting
15 Air Conditioning Equipment
15.01 Split air conditioner
Capacity: 5 ton
Brand: General (Thailand)/Daikin(Japan)
16 Testing/Maintenance Equipments for 33/11 kV Grid Substations
16.01 GIS Test Probe (100A, 100 kV) Compatible with Supplied GIS
16.02 SF6 Gas Analyzer
16.03 SF6 gas recovery and refilling plant
16.04 SF 6 optical Gas Imaging Camera (See flir catalogue)
17 Surge Arrester for Complete 33/11 kV GIS Based Substation
17.01 33kV Surge Arrester including supporting steel structure (1 Set = 3 Nos.)
17.02 11kV Surge Arrester including supporting steel structure (1 Set = 3 Nos.)
Recovery & Modification of Existing 33/11 kV old Substation and 33 kV
18 Switchyard
Dismantling of all existing foundation (Transformer, steel structure, outdoor
18.01 equipment foundation, 33kV GIS etc.)

Bidding Document for Package 2 - Renovation, Reinforcement and Augmentation (RRA) of 3 nos. 33/11kV Substation and AIS breaker replacement
with GIS breakers at different substations under DPDC.
Section 6 - 6-261

Modification/Construction of 33kV & 11kV Cable trench (Indoor & Outdoor) for
18.02 installing 33kV GIS & Control Panel, 11kV AIS and cable connection.
18.03 Modification/Construction of Indoor & outdoor Gantry for cable & Line termination.
Recovery of all material & equipments (33/11kV Transformer, 33kV switchgear,
Control Panel, AC DB, DC DB, Battery & Battery charger, SAS system etc.) from
18.04 existing 33/11kV substation and returning them to DPDC store.
19 Substation Building, Foundation & Civil works for NIFPS and others etc.
Construction of the foundation & required blast wall for the Nitrogen Injection Fire
19.01 protection System for 20/28 MVA Transformer
Oil pit and drainage system for 02 (Two) nos. Nitrogen Injection Fire protection
19.02 System
Construction of the foundation of the 33/11kV Transformers including the foundation
of the supporting structures for cable (33kV and 11kV) terminations on both sides of
19.03 the Power Transformers.
Construction of the foundation of the Auxiliary Transformers including the foundation
19.04 of the supporting structures for cable terminations on both sides of the Transformers.
19.05 Fencing outside periphery of Power Transformer & NIFPS
19.06 Surface Drain
19.07 Laying of gravels in the switchyard with associate works
19.08 Transformer Blast Wall
20 Internal Electrical Works, Earthing & Lightning Protection
Upgradation of existing Earthing system to maintain S/S earth resistance below 0.5
20.01 ohm and supply necessary grounding cable, Cu rod etc. for this purpose
20.02 Lighting Protection System for complete substation (as required)
20.03 Internal electrical works for Air Conditioning
Installation work including testing and commissioning and complete in all
21 respect
21.01 Power Transformer with OLTC, RTCC Panels
21.02 Nitrogen Injection Fire protection System and related accessories
11/.415kV, 250 kVA, three phase Station transformer along with structure
21.03 (Recovered & Reuse)
21.04 33 kv Gas Insulated Switchgear
Complete 33 KV GIS Panels, comprising with 3 Incomers, 2 Transformer Feeders, 15
i) Outgoing Feeders, 2 Bus Sectionalizer with Bus coupler & Bus Riser, 3 Bus PT etc.
ii) Control, Protection, metering panel for all 33kV GIS
Complete 11kV AIS Panels comprising with 2 Incomers, 19 Outgoing Feeders, 1 Bus
21.05 Sectionalizer with Bus coupler & Bus Riser etc.
21.06 Cables & Cable accessories
i) Complete 33kV XLPE cable with cable accessories
ii) LV Control Cable
iii) LV Power Cable
iv) Complete 11kV XLPE cable with cable accessories
21.07 AC, DC Panel
AC Distribution Panel with mechanical and electrical interlocking and Bus Tie
i) Scheme
ii) DC Distribution Panel with interlocking and Bus Tie Scheme
21.08 Batteries, Chargers
i) 110kV Ni-cd Battery
ii) 110kV Battery Charger
21.09 Fire Detection Alarm System & Fire extinguisher
Installation & Integration of Substation Automation System (SAS) for 33 kV & 11 kV
21.10 voltage level along with UPS
21.11 Steel Structure for Line and Cable Termination
21.12 Air Conditioning Equipment
21.13 33kV & 11kV Surge Arrester including supporting steel structure
All other miscellaneous Civil, Internal Electrical & Installation works required (FDA
21.14 system, indoor & outdoor lighting etc).

Bidding Document for Package 2 - Renovation, Reinforcement and Augmentation (RRA) of 3 nos. 33/11kV Substation and AIS breaker replacement
with GIS breakers at different substations under DPDC.
Section 6 - 6-262

SCHEDULE B

PRICE SCHEDULES

PREAMBLE
General
1. The Price Schedules are divided into separate Schedules as follows:
Schedule No. B1 :Plant (including Mandatory Spare Parts) Supplied from Abroad
Schedule No. B2
Country
Schedule No.B3 :Design Services
Schedule No. B4 :Installation and Other Services
Schedule No.B5 :Grand Summary
Schedule No. B6 :Recommended Spare Parts

2. The Schedules do not generally give a full description of the plant to be supplied and the services
to be performed under each
Requirements and other sections of the Bidding Document and reviewed the Drawings to
ascertain the full scope of the requirements included in each item prior to filling in the rates and
prices. The entered rates and prices shall be deemed to cover the full scope as aforesaid,
including overheads and profit.

3. If bidders are unclear or uncertain as to the scope of any item, they shall seek clarification in
accordance with ITB 7 prior to submitting their bid.
Pricing
4. Prices shall be filled in indelible ink, and any alterations necessary due to errors, etc., shall be
initialed by the Bidder.
As specified in the Bid Data Sheet and Special Conditions of Contract, prices shall be fixed and
firm for the duration of the Contract, or prices shall be subject to adjustment in accordance with
the corresponding Appendix (Price Adjustment) to the Contract Agreement.

5. Bid prices shall be quoted in the manner indicated and in the currencies specified in the
Instructions to Bidders in the Bidding Document.
For each item, bidders shall complete each appropriate column in the respective Schedules,
giving the price breakdown as indicated in the Schedules.
Prices given in the Schedules against each item shall be for the scope covered by that item as

6. Payments will be made to the Contractor in the currency or currencies indicated under each
respective item.

7. When requested by the Employer for the purposes of making payments or partial payments,
valuing variations or evaluating claims, or for such other purposes as the Employer may
reasonably require, the Contractor shall provide the Employer with a breakdown of any
composite or lump sum items included in the Schedules.

Please refer to Schedule B: Schedule of Prices, Scetion-4: Bidding Forms, Volume 1 of 2 of the
Bidding Document.

Bidding Document for Package 2 - Renovation, Reinforcement and Augmentation (RRA) of 3 nos. 33/11kV Substation and AIS breaker replacement
with GIS breakers at different substations under DPDC.
Section 6 - 6-263

DHAKA POWER DISTRIBUTION COMPANY LTD.

BIDDING DOCUMENT

PACKAGE 2: Design, Supply, Installation, Testing and Commissioning for RRA of 3 nos. 33/11kV
Substation and AIS breaker replacement with GIS breakers at different substations under DPDC
including civil work and related services on Turn-key Basis.

SCHEDULE C

TIMES FOR DELIVERY AND COMPLETION

The individual dates are all contractually binding.

The times given under Column D are the commissioning target dates at present planned to be achieved and
may be the subject of mutual adjustment.

Column A details the earliest dates by which access to site can be given for storage purposes. The times
entered under column B are to be the dates guaranteed for arrival at Site of the first shipment of parts for the
circuits in question being also the dates when the contract requires access to the Site for plant erection, to
the extent necessary to enable him to proceed with work to meet the dates under column C guaranteed for
complete delivery, erection and commissioning of the shipment.

The times include all necessary control, relay, metering, auxiliary power ancillary equipment to enable the
respective circuit or item of plant to be completely commissioned and put into commercial operation, together
with such other associated equipment, e.g., etc as will ensure that subsequent shutdown are unnecessary or
at least only of a temporary or short time nature.

The dates assume an order is placed by . . . . . . . . . . . . . . . . . . . . .


(to be advised or stated by Bidder)

A* B* C* D*
Latest Guaranteed Guaranteed Target
Site
Access Arrival of first Completion Completion
Permitted Shipment
a) DEMRA
b) ULLON LOCAL
7 days from
c) SHYMPUR BSCIC
the date of
d) KAMRANGIRCHAR
signing of the 18 months
e) GREEN ROAD (OLD)
Contract
f) KHANPUR
g) KHILGAON (GULBAG)
* Time in days, from contract effective date.

Preliminary building drawings as called for in Section 10 of the Technical Specification shall be provided
within 2.0 months of the contract commencing date with final drawings following one month later.

Bidding Document for Package 2 - Renovation, Reinforcement and Augmentation (RRA) of 3 nos. 33/11kV Substation and AIS breaker replacement
with GIS breakers at different substations under DPDC.

You might also like