You are on page 1of 28

AIR DIFFUSION COUNCIL

Manufacturers of Flexible Air Duct


ADC AIR DIFFUSION COUNCIL

Flexible Duct Performance


& Installation Standards
Fourth Edition

ADC AIR DIFFUSION COUNCIL, SCHAUMBURG, ILLINOIS


Flexible Duct
Performance and
Installation Standards

Fourth Edition
Copyright © 2003
Air Diffusion Council

AIR DIFFUSION COUNCIL


1000 E. Woodfield Rd. Suite 102
Schaumburg, IL 60173-5921
Telephone: (847) 706-6750 Fax: (847)706-6751
Email: info@flexibleduct.org Web: www.flexibleduct.org

Mission Statement of The Air Diffusion Council

The purpose for which the Air Diffusion Council was formed, as stated in its Certification of
Incorporation, is to promote and further the interests of manufacturers of air distribution equip-
ment, more specifically, flexible air ducts and related products, and the interests of the general
public in the areas of safety, quality, efficiency and energy conservation, and to this end,
develop programs approved and supported by the membership that legally promote and further
these interests, such as:

• To encourage, assist and support the maintenance and development of credible and
effective industry standards for the installation, use and performance of flexible duct
products; to promote the use of those standards by various code bodies, government
agencies; architects, engineers, heating and air conditioning contractors, etc. so that
the best interests of the public may be served.

• To collect and disseminate lawful information of value to members of the Council, the
general public and others and to act as a clearing house for all such information, as
well as providing a means by which the interests of the individual members of the
Council can be protected, defended, supported more vigorously and effectively in
legal association with others who share those interests.

ADC Bylaws, Article 1, Section 2 (1996)


Table of Contents
Foreword ......................................................................................... i

References ..................................................................................... i

Glossary of Terminology ................................................................ ii

1 Introduction ................................................................................... 4
1.1 Purpose ...................................................................... 4
1.2 Scope ......................................................................... 4
1.3 Units of Measurement ................................................ 4
1.4 Classification .............................................................. 4

2 Characteristics of Flexible Duct .................................................. 5


2.1 Description .................................................................. 5
2.2 Typical Styles - Figures 1-5 ......................................... 5

3 Testing, Listing, Reporting & Certifying ...................................... 6


3.1 General Requirements ................................................ 6
3.2 Listing Requirements - Table 1 ……............................ 6
3.3 Performance Values - Table 2 ……............................. 7
3.4 Performance Requirements .................................... 8, 9
3.5 Material Characteristics ............................................. 10
3.6 Methods of Test .........................................................10
3.7 Product Marking ........................................................ 11
3.8 Certification ............................................................... 11
3.9 Packaging ..…….……………......................................11

4 Installation Guidelines ................................................................ 12


4.1 Code Reference ........................................................ 12
4.2 General ......................................................................12
4.3 Installation and Usage - Figures 6-9 .......................... 12
4.4 Connecting, Joining and Splicing .............................. 13
4.5 Installation Instructions - Nonmetallic ….....................14
4.6 Alternate Installation Instructions - Nonmetallic …..... 15
4.7 Installation Instructions - Metallic ...............................16
4.8 Supporting Flexible Duct - Figures 10-16 ….........18, 19

5 Typical Accessories - Figures 17-27 ................................... 20, 21

6 General Commentary ................................................................. 22


6.1 Fire Safety ................................................................ 22
6.2 Installation Restrictions and Use Limitations …......... 22
6.3 Duct Sizing ................................................................ 23
6.4 Duct Leakage ............................................................ 23
6.5 Thermal Resistance (R-value Rating) …................... 24
6.6 Field Alterations ........................................................ 24
6.7 Exposure to UV Radiation and Sunlight …................ 24
Foreword
This standard was developed by the Air Diffusion Council. no responsibility nor accepts any liability for the
It is intended for use by the HVAC industry, including application or techniques contained in the
manufacturers, designers, installers, contractors, code standard.
bodies, inspectors and end users.
This standard is subject to review and revision as
The Flexible Duct Performance and Installation Standard the art of the industry advances or experience in
may be used as a comprehensive document in evaluating, the industry may dictate.
selecting, specifying and installing flexible duct in heating,
air conditioning and ventilating systems.
AIR DIFFUSION COUNCIL
Authorities considering adoption and/or reference of this 1000 E. Woodfield Rd., Suite 102
standard should review all federal, state, local and other Schaumburg, IL 60173-5921
applicable regulations. The Air Diffusion Council assumes Telephone (847)706-6750
Fax: (847) 706-6751
Email: info@flexibleduct.org
Web: www.flexibleduct.org

References
ACCA - Manuals D and Q

ADC Standard FD 72-R1 - Flexible Duct Test Code

ASHRAE Handbook - Fundamentals and Equipment Volumes

i ASTM E84 - Test for Surface Burning Characteristics of Building Materials

ASTM E96 - Water Vapor Transmission of Materials in Sheet Form


ADC Flexible Duct Performance & Installation Standards, 4th Edition

ASTM C167 - Thickness and Density of Blanket or Batt Thermal Insulations

ASTM C177 - Thermal Conductivity of Materials by Means of the Guarded Hot Plate

ASTM E477 - Duct Liner Materials and Prefabricated Silencers for Acoustical and Airflow Performance

ASTM C518 - Test Method for Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter

NFPA Standard 90A - Installation of Air Conditioning and Ventilating Systems

NFPA Standard 90B - Warm Air Heating and Air Conditioning Systems

NFPA Standard 255 - Method of Test of Surface Burning Characteristics of Building Materials

NAIMA - Fibrous Glass Duct Construction Standards

SMACNA - HVAC Duct Construction Standards, Metal and Flexible

UL Heating, Cooling, Ventilating and Cooking Equipment Directory

UL Standard 181 - Factory-Made Air Ducts and Air Connectors

UL Standard 181B - Closure Systems for Use With Flexible Air Ducts and Air Connectors

UL Standard 723 - Tests for Surface Burning Characteristics of Building Materials


Glossary of Terminology
Air Barrier The membrane of the flexible duct which Listing Mark/Label A printing, tag or other marking
actually contains the air volume. device of the listing agency permanently and promi-
Air Connector A category of flexible duct not meeting nently affixed to the listed product that certifies compli-
the requirements of an Air Duct per UL 181 Standard ance to the applicable Standard UL 181/UL 181B and
(not tested for flame penetration, puncture and impact) contains recommendations relating to installation and
and having limitations on use, length and location as maximum physical conditions of use.
defined by NFPA 90A and 90B. Air Connectors are Lot A collection of units of a product of a single cate-
identified by a “round shape” listing label of the listing gory, style, class and type manufactured under essen-
agency. tially the same conditions and from which a sample is
Air Duct A category of flexible duct tested and to be drawn and inspected for conformance to specifi-
classified as to the Surface Burning Characteristics in cation.
accordance with the UL 181 Standard and identified by Permeance The time rate of water vapor transmission
a “rectangular shape” listing label of the listing agency. through the vapor barrier expressed in U.S. perms
Authority Having Jurisdiction The organization, office [ng/(s·m2·Pa)].
or individual responsible for and having final approval Pressure The positive or negative static pressure
concerning use of flexible duct and its installation. expressed in inches of water gauge (in. w.g.) [Pa].
Classification For purposes of this standard, a Radiated Noise The sound power level transmitted
method of identifying, marking and specifying flexible through the duct wall, expressed in decibels (dB).
duct as related to listing category, physical style, Sag The distance deviation, expressed in inches per
positive pressure class and velocity type. lineal foot [mm/m] of flexible duct, from a horizontal or
Flexible Duct A preformed, flexible, tubular passage inclined plane between suspension points on installed
for supply, return and exhaust air in HVAC systems. flexible duct.
For purposes of this document, the terms designated Sound Attenuation (Insertion Loss) The extent to
Air Duct and Air Connector are used interchangeably, which sound power level is reduced (attenuated) as it ii
however not in their intended use and application. travels through a flexible duct, expressed in decibels
Friction Loss (Bends) The static pressure loss in (dB).

ADC Flexible Duct Performance & Installation Standards, 4th Edition


bends of flexible duct, expressed as a dimensionless Sound Generation The sound power level which is
coefficient (Co) at a specified bend radius ratio. Co is a generated by the movement of air through a flexible
dimensionless coefficient which represents the ratio of duct, expressed in decibels (dB).
the total pressure loss to the dynamic pressure in Thermal Conductivity (k) The time rate of heat flow
terms of velocity pressure. through unit thickness of an infinite slab of
Friction Loss (Straight) The static pressure loss in a homogeneous material in a direction perpendicular to
straight run of flexible duct, expressed in inches of the surface, induced by unit temperature difference.
water gauge (in. w.g.) per 100 feet [Pa/m]. Expressed in BTU-in./hr.-ft.2-°F [W/(m°- C)].
Inner Core/Liner That portion of insulated flexible duct Thermal Resistance (R) The mean temperature
which determines the internal dimensions and inner difference, at equilibrium, between two defined
physical form. surfaces of material or a construction that induces a
Installation Instructions A manufacturers printed unit heat flow rate through unit area. Expressed in
instructions in accordance with the terms of their listing hr.-ft.2-°F/BTU [(m2 -°C)/W].
which advises the method and materials to install the Ultraviolet (UV) Light Invisible radiation in the electro-
flexible duct. magnetic spectrum lying between visable light (380nm)
Leakage The time rate of air volume loss expressed in and x-rays (100nm). UV is arbitrarily categorized into
cubic feet per minute (cfm) [L/s]. short, medium and long wavelength bands: UV-A (315-
Listed A published list by a recognized approving 380nm), UV-B (280-315nm) and UV-C (100-280nm).
agency acceptable to the authority having jurisdiction UV radiation occurs naturally in sunlight or can be
stating that the flexible duct, tape, mastic, and clamp artificially generated.
have been tested to and comply with the applicable Vapor Barrier/Retarder The outer membrane of an
Standard UL 181/UL 181B and maintains periodic insulated flexible duct.
inspection to assure production of the listed products Velocity The average time rate of air flow expressed in
are in accordance with the listing. feet per minute (fpm) [m/s].
1
Introduction
1.1 Purpose 1.4 Classification

This standard sets forth specific methods of Flexible ducts shall be categorized as either Air Ducts
classifying, testing and marking flexible air ducts for or Air Connectors in accordance with testing and listing
indoor comfort heating, ventilating and air conditioning requirements in Table 1. Flexible ducts will appear in
applications. This standard sets forth guidelines for one of the following styles:
installing flexible ducts in air distribution systems.
M-UN Metallic, Uninsulated
1.2 Scope
M-I Metallic, Insulated
This standard includes requirements for both insulated
and non-insulated flexible ducts. No attempt is made in NM-UN Non Metallic, Uninsulated
this standard to designate a specific material or
construction. NM-IP Non Metallic, Insulated
with porous inner core
Special considerations not covered by this standard
may be required when flexible ducts are used in: NM-IL Non Metallic, Insulated lined
with nonporous inner core
a. Industrial applications; i.e. particulate
conveying, corrosive atmospheres, excessive
temperatures, etc. Flexible ducts, as part of this standard and for the
purpose of application use only, shall be one of the
b. Outdoor applications; i.e. continuous exposure following pressure classes and velocity types.
to direct sunlight, weathering elements etc.

Ducts must be listed in conformance to NFPA


Positive Pressure Class Velocity Type
Standards 90A and 90B.
4
Pressure Velocity
a. They must be tested in accordance with (Up to and including) (Up to and including)
Underwriters Laboratories Standard for Factory-
ADC Flexible Duct Performance & Installation Standards, 4th Edition

Made Air Ducts and Air Connectors, UL 181. 1/2 in. w.g. [125 Pa] 1000 fpm [5.1 m/s]

b. Such ducts must be installed in accordance 1 in. w.g. [250 Pa] 2500 fpm [12.7 m/s]
with the conditions of their listing.

1.3 Units of Measurement 2 in. w.g. [500 Pa] 4000 fpm [20.3 m/s]

This standard is written in inch-pound (I-P) units 3 in. w.g. [750 Pa] Over 4000 fpm
followed by SI units in brackets [ ]. Metric symbols [20.3 m/s]
and units are consistent with SI policy, however some
4 in. w.g. [1000 Pa]
deviations have been taken in conversion values and
rules-of-rounding. Examples of some deviations are:
6 in. w.g. [1500 Pa]
Diameter conversions are based on 25 mm/in. dia.
A 12 in. duct diameter converts to 300 mm. 10 in. w.g. [2500 Pa]
Length conversions are rounded to the nearest 0.1 m.
A 14 ft. duct length converts to 4.3 m.
Linear dimensions are rounded to the nearest 1 mm.
A 1½ in. duct strap converts to 38 mm.
Pressure conversions use 250 Pa/inch w.g.
A pressure of 6 in. w.g. converts to 1500 Pa.

Note: When more precise conversions are required,


follow ASHRAE Policy on SI Units.
2
Characteristics
of Flexible Duct
2.1 Description

Flexible ducts usually are packaged in compressed


form in a variety of lengths with plain ends or as as-
semblies with special end fittings attached to either or
both ends. Diameters generally range from 2" [50 mm]
through 12" [300 mm] in 1 in. [25 mm] increments and
14" [350 mm] through 20" [500 mm] in 2 in. [50 mm]
increments. Most flexible ducts are slightly over-sized
in diameter to fit over standard sheet metal fittings (see
“Dimensions and Tolerances” in Section 3.5).

2.2 Typical Styles

Figure 3 Style NM-UN Nonmetallic, Uninsulated

ADC Flexible Duct Performance & Installation Standards, 4th Edition


Figure 1 Style M-UN - Metallic, Uninsulated

Figure 4 Style NM-IP - Nonmetallic Insulated,


Perforated (Porous Inner Core)

Figure 2 Style M-I - Metallic, Insulated


Figure 5 Style NM-IL - Nonmetallic, Insulated,
Lined (Non porous Inner Core)
3
Testing, Listing, Reporting
and Certifying
3.1 General Instructions 3.2 Listing Requirements

Flexible ducts conforming to this standard shall be Factory made air ducts and air connectors must be
tested, listed, reported and certified as applicable, in tested and listed in accordance with Underwriters
accordance with the requirements of this standard. Laboratories Standard for Factory-Made Air Ducts and
Testing requirements by category are shown in Table 1. Air Connectors, UL 181. The UL Heating, Cooling,
Ventilating and Cooking Equipment Directory
publishes such listings.

Table 1 Key to Table 1

Test Air Ducts Air Connectors X Test applicable


Surface Burning - Test not applicable
Characteristics 1 x x
a Applicable to parts of metals not inherently
Flame Penetration x - corrosion resistant.
Burning x x b Test applicable for flexible air ducts and air
connectors that incorporate vapor barriers
Corrosion a x x supported by grommets or other means of
field support.
Mold Growth
and Humidity x x
6 Footnote 1
Temperature x x Tests for surface burning characteristics are to be
ADC Flexible Duct Performance & Installation Standards, 4th Edition

conducted as specified for Surface Burning


Puncture x - Characteristics of Building Materials, UL 723 (ASTM
E84, NFPA 255).
Static Load xb xb
Class 0 Material: Shall have surface burning
Impact x - characteristics of zero (flame spread/smoke
developed).
Erosion 2 x x
Class 1 Material: Shall have flame spread rating of
Pressure 2 x x not over 25 without evidence of continued
progressive combustion and a smoke-developed
Collapse 2 x x rating of not over 50.
Tension x x Footnote 2
Torsion x x These three tests, Pressure, Erosion and Collapse,
are run at 2.5 times the manufacturer’s stated rating
Bending x x for that property. For the erosion test, the variable is
velocity; for the pressure test the variable is positive
Leakage x x pressure; for the collapse test, the variable is
negative pressure.
Listing
Label Shape Rectangular Round
Testing, Listing, Reporting and Certifying . . . continued

3.3 Performance Values

Table 2 lists the required tests and units of


measurement and recommended values of
minimum performance where applicable.

Table 2

For comparison purpose only. Not for design. For detailed design data, refer to manufacturer’s product engineering
data.

Property Recommended Performance Value

Thermal Loss* Test - Section 3.4 - Thermal Performance


All diameters R: hr- ft2 - °F/BTU [(m2·°C/W] 4.2 [0.74](minimum) @ 75°F [24°C] mean temperature

Friction Loss Test - Section 3.4 - Friction Loss


12" [300 mm]
diameter Straight:(in.w.g. per 100 ft. [Pa/m]
of duct @ 1000 fpm [5.1 m/s]) 0.3 [2.5] (maximum)
7
90° bend loss coefficient (Co)
@ R/D = 2 1.0 (maximum)

ADC Flexible Duct Performance & Installation Standards, 4th Edition


Acoustical Sound Attenuation Test - Section 3.4 - Acoustical Performance
(dB) Sound Generation Due to complexity of data, no recommended value of
Radiated Noise performance is stated. Refer to Manufacturer’s Data.

Static Press./Temp Test - Section 3.4 - Static Press./Temp. Performance


12" [300 mm] At Recommended Operating 140° F [60° C] Continuous
diameter Positive Pressure (in. w.g.) [Pa] 180° F [82° C] Intermittent

Leakage Test - Section3.4 - Leakage (Duct Only)


All diameters cfm/in. (dia.)·ft. (length) 0.03
[L/s/mm (dia.)·m (length) [1.7 x 10¯4]

Leakage Test - Section 3.4 - Leakage (Including Connections)


All diameters cu.ft./hr. [L/s] 0.87 [1.1 x 10¯5] D2 (maximum) where D is
internal duct diameter in inches [mm].

Permeance* Test - Section 3.6


All diameters Water Vapor Transmission Rates of Vapor Barriers
U.S. Perms [ng/(s·m2·Pa)] 1.0 [57.5] (maximum)

* Not applicable to uninsulated ducts.


Testing, Listing, Reporting and Certifying . . . continued

3.4 Performance Requirements Friction Loss. Friction loss shall be determined in


accordance with the ADC Test Code FD 72-R1.
Thermal Performance. Thermal loss properties of Friction loss for straight runs shall be presented in
insulated flexible duct shall be based on flat sections of graphical form over the manufacturer’s rated velocity
insulation only at installed duct wall thickness and range and size range. Friction loss in 90° bends shall
excluding any air film resistance. be presented in graphical form at three different bend
radii.
The thermal resistance (R) shall be determined using
the relationship: R = th / k. Straight Runs:

Where: R = Thermal resistance (hr-ft2 - °F/Btu) Friction loss - inches of water gauge per 100 feet [Pa/
[(m2·°C)/W] rounded to the nearest 0.1 m] of duct, shall be plotted on the horizontal axis, and
“Air volume - CFM [L/s]” on the vertical axis. For
th = duct insulation wall thickness (in.) convenience of the user, corresponding velocities may
[mm] rounded to the nearest 1/16 also be plotted. For purposes of recommended
inch [2 mm]. performance values in Table 2, a 12" [300 mm]
nominal internal duct size, tested at 1000 fpm [5.1 m/s]
k = measured apparent thermal velocity shall be used.
conductivity (Btu-in/hr-ft2 - °F)
[W/(m·°C)] 90° Bends:

The insulation’s thermal conductivity is measured Friction loss coefficient (Co) - dimensionless coefficient,
according to ASTM C518 or ASTM C177 at 75°F [24° shall be plotted on the vertical axis, and the internal
8 C] mean temperature. Installed insulation thickness is duct diameter shall be plotted on the horizontal axis.
determined in the following manner (see note 1 and 2 Each R/D value tested shall be plotted. For purpose of
below). recommended performance values for 12" [300 mm]
ADC Flexible Duct Performance & Installation Standards, 4th Edition

nominal I.D. duct in Table 2, a loss coefficient of


R/D = 2 shall be used.
th =
{ Jacket Layflat Width x 2
3.14159 } - Nom. Core Dia.
The term Co is a dimensionless coefficient which
represents the ratio of the total pressure loss to the
2 dynamic pressure in terms of velocity pressure.

The jacket layflat width can be determined by


circumferentially cutting the jacket, removing it from
the duct, laying it on a flat surface and measuring the
width to the nearest 1/16 inch [2 mm].

Note 1 The out-of-package insulation thickness


meaured in accordance with ASTM C167 shall be
equal to or greater than the calculated installed duct
insulation wall thickness.

Note 2 Actual internal core diameter shall be within


the tolerances of +3/8, -0 in. [+9,-0 mm] of nominal
core diameter.
Testing, Listing, Reporting and Certifying . . . continued

Acoustical Performance. When acoustical properties Static Pressure/Temperature Performance. Flexible


are claimed, the duct shall be tested in accordance duct shall be tested under simultaneous temperature
with ASTM E477 and/or ADC Test Code FD 72-R1. and pressure conditions in accordance with ADC Test
Data shall be presented in the following form: Code FD 72-R1.

Attenuation: Test temperatures and times under this standard shall


be:
Sound attenuation test data shall be reported by
tabulation in either dB/lineal foot [dB/m] or as dB for Continuous Temperature/Time - 140° F [60° C] for 164
specified length (such as dB/3 ft. [1.0 m] or dB/12 ft. hours.
[3.7 m]). In either case, the table of values shall show Intermittent Temperature/Time - 180° F [82° C] for 4
attenuation at center frequencies of 125, 250, 500, hours.
1000, 2000, 4000 hertz. The table shall also indicate
whether determinations were made with or without air For purpose of recommended performance values in
flowing and the maximum velocity range to which data Table 2, a 12” [300 mm] nominal internal duct size
is applicable. shall be tested. In addition, the smallest and largest
size of the diameter range shall be tested for
Because this data is not necessarily linear, the limits of comparative performance verification.
linearity shall be stated. Notes must accompany data
explaining the limits of use. No additional attenuation Leakage - Duct Only. Leakage shall be determined in
may be claimed for lengths greater than the lengths accordance with ADC Test Code FD 72-R1. Duct
tested. leakage shall be reported as an average leakage rate
of air volume loss per unit internal diameter per unit
Sound Generation: length (CFM/in.dia./ft.) [L/s/mm dia./m]. 9
Sound generation test data shall be reported for at Leakage - Including Connections. Shall be deter-

ADC Flexible Duct Performance & Installation Standards, 4th Edition


least four different velocities selected from the mined in accordance with UL 181 requirements.
following range of velocities (must include maximum
rated velocity): 400, 800, 1000, 1500, 2000, 2500,
3000, 4000 and 6000 fpm. [2.0, 4.1, 5.1, 7.6, 10.2,
12.7, 15.2, 20.3 and 30.5 m/s]

Sound generation test data shall be reported by


tabulation in either dB/linear foot [dB/m] or dB for
specified length tested. Tabulated data shall show
sound generation at center frequencies of 125, 250,
500, 1000, 2000 and 4000 hertz.

Radiated Noise:

Radiated noise reduction shall be reported with 0 air


flow and at one flow of 2500 fpm [12.7 m/s] velocity or
the option of 4000 [20.3] or 6000 [30.5] fpm [m/s]
velocity for each duct diameter tested

Radiated noise reduction shall be reported as dB/


linear foot [db/m] or dB for a specified length at
center frequencies of 125, 250, 500, 1000, 2000 and
4000 hertz.
Testing, Listing, Reporting and Certifying . . . continued

3.5 Material Characteristics 3.6 Methods of Test

There are specifications external to this standard Water Vapor Transmission Rates of Vapor
based on specific properties of component materials. Barriers (Retarders). The water vapor transmission
When required, data should be determined and rate of vapor barriers shall be determined in
reported in accordance with the following procedure. accordance with ASTM E96, Procedure A. Specimens
for test shall be selected in the following manner. A
Permeance. Water vapor permeance of the jacketing sample of flexible duct shall be selected from
material is applicable only to insulated flexible duct. production material which has been stored in its
Permeance shall be tested and reported in accordance standard package a minimum of twenty-four (24)
with Section 3.6 “Water Vapor Transmission Rates of hours. Specimens 12 in. x 12 in. [300 mm x 300 mm]
Vapor Barriers.” shall be cut from each at the approximate center of the
sample duct.
Dimensions and Tolerances. Dimensions and
tolerances of flexible ducts shall be within the WVTR specimens will then be prepared and tested in
tolerance listed on the manufacturer’s data sheets. accordance with procedures outlined in ASTM E96,
Length shall not be less than advertised nominal when Procedure A.
measured fully extended in accordance with Section
3.6 “Length Measurement.” The permeance of the material shall be reported as the
average of the three determinations tested. The results
Sampling. Unless otherwise stated in the purchase are to be reported in U.S. perms [ng/(s·m2·Pa)].
document, quality records maintained by the
manufacturer will suffice in the relationship between Length Measurement. A length of flexible duct which
10 the purchaser and manufacturer. If they mutually agree has been packaged in compressed form shall be
to accepts lots on the basis of the quality control measured with a tape after fully extending the duct.
records, no further sampling is required. Measure while maintaining the tension.
ADC Flexible Duct Performance & Installation Standards, 4th Edition

For referee measurement: Apply an axial load of 25


lbs. [11.3 Kg], measured by a force gauge, to the
product for one minute. Measure the length with the
axial tension applied after the duct is fully extended.
Testing, Listing, Reporting and Certifying . . . continued

3.7 Product Marking 3.8 Certification

Listing Mark and Label Information. All ducts shall be Upon request, the manufacturer shall certify that its
marked, labeled or printed at maximum intervals of 10 product(s) conform to the requirements of this
ft. [3.0 m] or fraction thereof. Labels shall contain at standard.
least the following information.
Seal of Certification. A mark separate and distinct
a. Identifying mark of the listing agency from the ADC label. The seal signifies third-party
b. Manufacturer’s identification verification to particular performance requirements of
c. Maximum Positive and Negative pressure this standard by an ADC “Recognized Testing
rating Laboratory”.
d. Maximum Rated Velocity
e. R-Value (applicable to insulated ducts only)
f. Classification of Surface Burning
Characteristics (Class 0 or 1)
g. Identification as either an Air Duct or Air
Connector

Note 1 Air Connector identification shall further


state “Not to be installed in lengths greater than 14
ft [4.3 m].

Note 2 Air Duct labels shall be rectangular in


shape; Air Connector labels shall be round in 11
shape. Reference to listed installation instructions.

ADC Flexible Duct Performance & Installation Standards, 4th Edition


ADC Logo. A mark which is separate and distinct from
the listing mark and label containing the following
information and indicating compliance with this 3.9 Packaging
standard.
Unless otherwise agreed or specified between the
purchaser and the manufacturer, flexible duct shall be
packed in the manufacturer’s standard commercial
containers.

Unless otherwise specified, each container shall be


marked with the following information:

a. Manufacturer or Brand Name


b. Product designation product name (optional)
c. Size (internal diameter)
d. Nominal Length of duct section
e. Number of sections per container
f. Storage and/or stocking instructions (if any)
g. Production date or date code of the
manufacturer.

Each container shall contain the manufacturer’s


specific installation instruction. (Optionally, these
instructions may be printed on the container.)
4
Installation Guidelines
4.1 Code Reference 4.3 Installation and Usage

The “authority having jurisdiction” should be Install duct fully extended, do not install in the
referenced to determine what law, ordinance or code compressed state or use excess lengths. This will
shall apply in the use of flexible duct. noticeably increase friction losses.

Ducts conforming to NFPA 90A or 90B shall meet the


following requirements:

a. Shall be tested in accordance with Sections


5-21 of Underwriters Laboratories Standard
for Factory-Made Air Ducts and Air
Connectors, UL 181.
b. Shall be installed in accordance with the
conditions of their listing.
c. Shall be installed within the limitations of the
applicable NFPA 90A or 90B Standard.

4.2 General

The routing of flexible duct, the number of bends, the


number or degrees in each bend and the amount of
sag allowed between support joints will have serious
12 effects on system performance due to the increased Figure 6
resistance each introduces. Use the minimum length of
flexible duct to make connections. It is not
ADC Flexible Duct Performance & Installation Standards, 4th Edition

recommended that excess length of ducts be installed


to allow for possible future relocations of air terminal
devices.

Avoid installations where exposure to direct sunlight


can occur, e.g. turbine vents, sky lights, canopy
windows, etc. Prolonged exposure to sunlight will
cause degradation of the vapor barrier. Direct
exposure to UV light from a source lamp installed
within the HVAC system will cause degradation of
some inner core/liner materials.

Terminal devices shall be supported independently of


the flexible duct.

Repair torn or damaged vapor barrier/jacket with duct


tape listed and labeled to Standard UL 181B. If internal
Figure 7
core is penetrated, replace flexible duct or treat as a
connection.
Installation Guidelines . . . continued

Avoid bending ducts across sharp corners or incidental 4.4 Connecting, Joining and Splicing Flexible
contact with metal fixtures, pipes or conduits. Radius Ducts
at center line shall not be less than one duct diameter.
All connections, joints and splices shall be made in
accordance with the manufacturer’s installation
instructions.

For flexible ducts with plain ends, standardized


installation instructions conforming to this standard are
shown in Sections 4.5 “Nonmetallic With Plain
Ends” (uses tape and clamp to seal/secure the core to
the fitting), 4.6 “Alternate Nonmetallic With Plain
Ends” (uses mastic and clamp to seal/secure the core
to the fitting), and 4.7 “Metallic With Plain Ends
(optional use of tape or mastic and metal screws to
seal/secure the core to the fitting).

Figure 8 Due to the wide variety of ducts and duct assemblies


with special end treatments, e.g. factory installed
Do not install near hot equipment (e.g. furnaces, fittings, taped ends, crimped metal ends, etc., no
boilers, steam pipes, etc.) that is above the standardized installation instructions are shown.
recommended flexible duct use temperature. Reference manufacturer’s installation instructions.

All tapes, mastics, and nonmetallic clamps used for 13


field installation of flexible ducts shall be listed and
labeled to Standard UL 181B - Closure Systems for

ADC Flexible Duct Performance & Installation Standards, 4th Edition


Use With Flexible Air Ducts and Air Connectors.

Sheet metal fittings to which flexible ducts with plain


ends are attached shall be beaded and have a
minimum of 2 inches [50 mm] collar length. Beads are
optional for fittings when attaching metallic flexible
ducts.

Sheet metal sleeves used for joining two sections of


flexible duct with plain ends shall be a minimum of 4
inches [100 mm] in length and beaded on each end.
Beads are optional for sleeves when joining metallic
Figure 9 flexible ducts.

Flexible ducts secured with nonmetallic clamps shall


be limited to 6 inches w.g. [1500 Pa] positive pressure.
Installation Guidelines . . . continued
4.5 Installation Instructions for Air Ducts and Air Connectors - Nonmetallic with Plain Ends

Connections Splices

1. After desired length is determined, cut completely


around and through duct with knife or scissors. Cut 1. Fold back jacket and insulation from core. Butt two
wire with wire cutters. Fold back jacket and insulation. cores together on a 4" [100 mm] length metal sleeve.

2. Slide at least 1" [25 mm] of core over fitting and


past the bead. Seal core to collar with at least 2 wraps 2. Tape cores together with at least 2 wraps of duct
of duct tape. Secure connection with clamp placed tape. Secure connection with 2 clamps placed over the
over the core and tape and past the bead. taped core ends and past the beads.

14
ADC Flexible Duct Performance & Installation Standards, 4th Edition

3. Pull jacket and insulation back over core. Tape


jacket with at least 2 wraps of duct tape. A clamp may
be used in place of or in combination with the duct 3. Pull jacket and insulation back over cores. Tape
tape. jackets together with at least 2 wraps of duct tape.

NOTES:
1. For uninsulated air ducts and air connectors, disregard references to insulation and jacket.
2. Use beaded sheet metal fittings and sleeves.
3. Use tapes listed and labeled in accordance with Standard UL 181B and marked “181B-FX”.
4. Nonmetallic clamps shall be listed and labeled in accordance with Standard UL 181B and marked “181B-C”.
Use of nonmetallic clamps shall be limited to 6 in. w.g. [1500 Pa] positive pressure.
Installation Guidelines . . . continued
4.6 Alternate Installation Instructions for Air Ducts and Air Connectors -
Nonmetallic with Plain Ends

Connections and Splices

Step 1
After desired length is determined, cut completely around and
through duct with knife or scissors. Cut wire with wire cutters.
Pull back jacket and insulation from core.

Step 2
Apply mastic approximately 2" [50 mm] wide uniformly around
the collar of the metal fitting or over the ends of a 4" [100 mm]
metal sleeve. Reference data on mastic container for
application rate, application thickness, cure times and handling
information.

Step 3
Slide at least 2" [50 mm] of core over the fitting or sleeve ends
and past the bead.

15

ADC Flexible Duct Performance & Installation Standards, 4th Edition


Step 4
Secure core to collar with a clamp applied past the bead.
Secure cores to sleeve ends with 2 clamps applied past the
beads.

Step 5
Pull jacket and insulation back over core ends. Tape jacket(s)
with at least 2 wraps of duct tape. A clamp may be used in
place of or in combination with the duct tape.

NOTES:
1. For uninsulated air ducts and air connectors, disregard references to insulation and jacket.
2. Use beaded sheet metal fittings and sleeves.
3. Use mastics listed and labeled in accordance with Standard UL 181B and marked “181B-M” on container.
4. Use tapes listed and labeled in accordance with Standard UL 181B and marked “181B-FX”.
5. Nonmetallic clamps shall be listed and labeled in accordance with standard UL 181B and marked “181B-C”.
Use of nonmetallic clamps shall be limited to 6 in. w.g. [1500 Pa] positive pressure.
Installation Guidelines . . . continued
4.7 Installation Instruction for Air Ducts and Air Connectors - Metallic with Plain Ends

Connections and Splices


1. After cutting duct to desired length, fold back jacket 4. Secure to collar/sleeve using #8 sheet metal
and insulation exposing core. Trim core ends squarely screws spaced equally around circumference. Use 3
using suitable metal shears. Determine optional screws for diameters under 12" [300 mm] and 5
sealing method (Steps 2 or 5) before proceeding. screws for diameters 12" [300 mm] and over.

2. When mastics are required and for pressures 4"


w.g. [1000 Pa] and over, seal joint with mastic applied 5. For pressures under 4" w.g. [1000 Pa] seal joint
uniformly to the outside surface of collar/sleeve. using 2 wraps of duct tape applied over screw heads
(Disregard this step when not using mastics and pro- and spirally lapping tape to collar/sleeve. (Disregard
ceed to Step 3). this step when using mastics per Step 2).

16
ADC Flexible Duct Performance & Installation Standards, 4th Edition

3. Slide at least 1" [25 mm] of core over metal collar 6. Pull jacket and insulation back over core. Tape
for attaching duct to take off or over ends of a 4" [100 jacket with 2 wraps of duct tape. A clamp may be used
mm] metal sleeve for splicing 2 lengths of duct. in place of or in combination with the duct tape.

NOTES:
1. For uninsulated air ducts and air connectors, disregard references to insulation and jacket.
2. Use mastics listed and labeled to Standard UL 181B and marked”181B-M” on container.
3. Use tapes listed and labeled to Standard UL 181B and marked “181B-FX”.
4. Nonmetallic clamps shall be listed and labeled in accordance with Standard UL 181B and marked “181B-C”.
ADC Flexible Duct Performance & Installation Standards, 4th Edition
17
This page has been intentionally
left blank for future use.
Installation Guidelines . . . continued

4.8 Supporting Flexible Duct

Flexible duct shall be supported at manufacturer’s rec- Hanger or saddle material in contact with the flexible
ommended intervals, but at no greater distance than duct shall be of sufficient width to prevent any restric-
5’ [1.5 m]. Maximum permissible sag is ½ " per foot [42 tion of the internal diameter of the duct when the
mm per meter] of spacing between supports. weight of the supported section rests on the hanger
or saddle material. In no case will the material con-
A connection to rigid duct or equipment shall be con- tacting the flexible duct be less than 1½” [38 mm]
sidered a support joint. Long horizontal duct runs with wide.
sharp bends shall have additional supports before and
after the bend approximately one duct diameter from
the center line of the bend.

18
Figure 11
ADC Flexible Duct Performance & Installation Standards, 4th Edition

Figure 10

Figure 12
Installation Guidelines . . . continued

Factory installed suspension systems integral to the Support the duct between a metal connection and
flexible duct are an acceptable alternative hanging bend by allowing the duct to extend straight for a few
method when manufacturer’s recommended proce- Inches before making the bend. This will avoid possi-
dures are followed. ble damage of the flexible duct by the edge of the
metal collar.

Figure 13

Flexible ducts may rest on ceiling joists or truss


19
supports. Maximum spacing between supports shall
not exceed the maximum spacing per manufacturer’s Figure 15 Vertically installed duct
installation instruction. shall be stabilized by

ADC Flexible Duct Performance & Installation Standards, 4th Edition


support straps at a max.
of 6’ [1.8 m] on center.

Figure 14 Note:
Factory-made air ducts may not
be used for vertical risers in air
duct systems serving more than Figure 16
two stories.
5
Typical Accessories
5.1 Types

These figures depict typical accessories but do not


represent all available accessories. The designer
should select and approve accessories which are
acceptable for each application. The standard is not
intended to limit the selection or the development of
accessories for use with flexible duct.

Figure 19 Ductboard Collar (Spin-In)

20
Figure 17 Metal Duct Clamp
ADC Flexible Duct Performance & Installation Standards, 4th Edition

Figure 20 Sheet metal Collar (Dovetail)

Figure 18 Nonmetallic Duct Clamp

Figure 21 Sheet metal Collar (Spin-In-Straight)


Typical Accessories . . . continued

Figure 22 Conical Collar (Spin-In) Figure 25 Ductboard Collar (Tabbed)

21

ADC Flexible Duct Performance & Installation Standards, 4th Edition


Figure 23 4” [100 mm] length Sleeve/Coupling Figure 26 Insulated Box with Collar
(2" [50 mm] length min.)

Figure 24 45° Entry Fitting Figure 27 Flanged Fitting


6
General Commentary
6.1 Fire Safety 6.2 Installation Restrictions
and Use Limitations
Flexible ducts are not noncombustible, except metallic
uninsulated, but generally regarded as limited- There are specific restrictions and limitations related to
combustible. The UL 181 Safety Standard for “Factory- the use of flexible ducts. Some are due to NFPA Stan-
Made Air Ducts and Air Connectors” is used to dards, model codes and various state/local codes.
investigate safety performance as referenced in the Others are due to end use performance where the
applicable International Codes (ICC), Uniform product was not designed for that specific use. Some,
Mechanical Code (IAPMO), the applicable National but not all inclusive, are as follows:
Fire Protection Code/Standards (NFPA), and various
state and local codes. a. Cannot be used for vertical risers serving
more than two stories in height.
The UL 181 Standard has been used for over 40 years
for evaluating safety. The testing procedures were de- b. Cannot be used in systems with entering
veloped by taking a wide range of safety-related air temperature higher than 250°F[121°C].
installation situations into consideration, including
structural integrity and flammability characteristics. c. Must be installed in accordance with condi-
Four (4) fire tests are used to investigate the flamma- tions of listing.
bility and burning characteristics of flexible duct as
follows: d. When installed in a fire-rated floor/roof ceil-
ing assembly, ducts shall conform with the
a. The Surface Burning Characteristics (Flame design of the tested fire-resistive assembly.
Spread and Smoke Development) for both
interior and exterior of duct using the 25 ft. e. Should be interrupted at the immediate
[7.6 m] tunnel test method that is published in area of operation of electric, fossil fuel or
UL 723, the American Society of Testing and solar energy collection heat sources to
22 Materials (ASTM E84), the National Fire meet listed equipment clearances speci-
Protection Association (NFPA 255) and the fied.
American National Standards Institute (ANSI).
ADC Flexible Duct Performance & Installation Standards, 4th Edition

f. Air connectors (does not apply to air ducts)


b. Ease of ignition/burning test using a Bunsen shall not be installed in lengths greater than
burner on both the inner core and outer jacket 14 ft. [4.3 m] for any given run; shall not
of the duct. pass through any wall, partition or enclo-
sure of a vertical shaft with a 1 hour or
c. Flame penetration test using a specially de- more fire resistive rating; shall not pass
signed test apparatus to evaluate the through floors.
retardation of flame passage from exterior to
interior of the duct. g. Should not penetrate walls where fire
dampers are required.
d. Component flame resistance test conducted
on tapes, fabrics, adhesives, and related h. Should not be used outdoors unless specifi-
components that are exposed directly to the cally designed to withstand exposure to
air system. direct sunlight and the weathering ele-
ments.

i. Should not be used to vent appliances for


cooking, heating and clothes drying unless
approved and recommended by the appli-
ance manufacturer.

j. Should not be installed in concrete, buried


below grade or in contact with the ground.
General Commentary . . . continued

6.3 Duct Sizing 6.4 Duct Leakage

The combined friction and dynamic pressure losses Flexible duct has inherently low leakage properties due
must be taken into consideration to properly size any to the impervious nature of the materials used as the
duct. Pressure losses caused by the roughness of the air barrier. These give the flexible duct itself leakage
duct wall resisting air movement are know as friction rates less than ½ of 1% of air volume when proper
losses. Pressure losses when air flow changes direc- connections are made to other system components.
tion, as caused by bends or when air flows across
other systems components, are known as dynamic A higher than expected leakage rate can occur at con-
losses. nections if improper materials or careless work
practices are used. To assure a low leakage rate for
To prevent undersizing or oversizing of flexible ducts flexible duct systems, the following is recommended:
and achieve the designed air delivery performance:
a Reference industry manuals (SMACNA,
a Have an understanding of and properly use NAIMA) for making round tap-ins into and
the air friction chart. sealing fitting joints to rigid ducts, plenums,
etc.
b. Use a proven method of duct sizing, one that
has taken into consideration both friction and b. Make flexible duct connections/splices in
dynamic losses. accordance with manufacturer’s
recommended installation instructions.
c. Use friction loss data characteristic of flexible
duct. Do not use data for round sheet metal c. Seal flexible duct connections with sealing
duct. materials listed and labeled to Standard UL
181B. Mechanically secure connections with
d. Since all flexible ducts are not alike, use the approved clamping material.
published data from the manufacturer of the
23
specific flexible duct being used. d. Repair any rip, tear or hole in the air barrier
using materials listed and labeled to Standard

ADC Flexible Duct Performance & Installation Standards, 4th Edition


UL 181B and methods recommended by the
manufacturer.
General Commentary . . . continued

6.5 Thermal Resistance (R-value Rating) 6.6 Field Alterations

The thermal resistance (R-value) requirements for air Flexible ducts complying with this standard are listed
distribution ducts can vary depending on the energy to the UL 181 Safety Standard for “Factory-Made Air
code being enforced. For insulated ducts, the minimum Ducts and Air Connectors” and must be installed per
value in conformance with this standard is R-4.2 [0.74]. the conditions of their listing.
Uninsulated ducts have no R-value rating. To
accommodate the varying levels of R-values, ADC Alterations made in the field, such as applying
manufacturers commonly offer insulated flexible duct additional overwraps of insulation/barriers, surface
with R-value ratings of 4.2 [0.74], 6.0 [1.06] and 8.0 paint, internal sanitizers, spray sealants, etc. may
[1.41]. compromise the fire safety performance of the duct
and void the manufacturer’s product warranty.
Thermal resistance (R-value) for this standard is
determined in accordance with Thermal Performance 6.7 Exposure to UV Radiation and Sunlight
in Section 3.4. The value, excluding any film
resistance, is determined on flat sections of insulation Some polymeric materials used to manufacture
only at installed duct wall thickness and in accordance nonmetallic flexible ducts will degrade with prolonged
with ASTM C518 at 75°F [24°C] mean temperature. R- exposure to ultraviolet (UV) radiation. UV radiation
values based on dynamic thermal tests are not part of occurs naturally in sunlight or can be artificially
this standard. generated by specialized lamps.

For credence, ADC initiated a third-party verification of The outer barrier (jacket) may degrade if ducts are
R-value ratings in accordance with Thermal installed outside in direct sunlight or within attics, crawl
Performance in Section 3.4 and Certification in spaces, etc. where direct sunlight enters, e.g. turbine
Section 3.8 of this standard. An adjunct testing and vents, sky lights, canopy windows, etc.
follow-up program was established with Underwriters
24 Laboratories Inc. for flexible ducts listed and labeled to The inner core (liner) may degrade if ducts are
Standard UL 181. The program includes testing, positioned near a bio-treatment lamp (UV emitter)
classifying, follow-up testing and labeling of R-values installed within the HVAC system.
ADC Flexible Duct Performance & Installation Standards, 4th Edition

at both the insulation manufacturer and flexible duct


manufacturer. Flexible duct members participating in Unless the product is specifically designed to
the thermal certification program are eligible to mark withstand the exposure to UV light, care should be
their product with the ADC Seal of Certification for taken to ensure the outer vapor barrier and inner core
Thermal Performance. material are shielded from direct sunlight and UV
radiation. Reference the manufacturer’s
recommendations for specific product information
related to UV exposure.

Thermal Performance
Notes
Notes