Gas Heat Pump Air Conditioners GAS DRIVEN VRF

ELECTRIC VRF
K Series Specification Guide COMMERCIAL SPLIT SYSTEMS
ROOM AIR CONDITIONERS

SANYO Air Conditioners. The natural choice.


SANYO Gas Heat Pump Air Conditioners K Series
Contents

INTRODUCTION
SANYO Air Conditioners 4

Think GAIA - the environmental philosophy of SANYO 5

GHP OUTDOOR UNITS


SANYO GHP - the natural choice 6 Individual Control Systems Overview 60

Case Studies: Regione Lazio, Rome, Italy 8 Centralised Control Systems Overview 61

Case Studies: Sheraton Fota Island, Cork, Ireland 9 Individual Control Systems 62

Efficient, Powerful, Comfortable and Economical 10 Convenient System Control 64

SANYO 3-Way GHP for buildings requiring simultaneous Control Equipment Dimensional Drawings 67
cooling and heating 12
AMY Software 68
SANYO 2-Way GHP Comfort Air Conditioning 14

GHP Chiller 16 TECHNICAL INFORMATION


System Mixing Flexibility for 2 Way GHP 17
3 Way GHP Refrigerant Tubing Design 70

2 Way GHP Refrigerant Tubling Design 71


GHP INDOOR UNITS
Indoor Units Range Overview 18 Piping & Wiring diagram with GHP and Water Heat Exchanger 74

ECOi VRF Indoor Unit Key Features 20 Piping & Wiring diagram with Mix System 75

X Type Semi-Concealed Cassette 22 Piping & Wiring diagram with GHP 71kW with
2 Water Heat Exchanger 76-77
XM Type Mini Semi-Concealed Cassette 24
Terminal Block with Water Heat Exchanger 78-80
XMR Type 600 x 600 Semi-Concealed Cassette 26
Precautions 81
SR Type Semi-Concealed Cassette 28
Safety precautions and caution on installation and use 82
ADR Type Semi-Concealed Cassette 30
New System Design Software Program 83
LDR Type Semi-Concealed Slim Cassette 32

U Type Concealed Duct 34

UR Type Concealed Duct 36

DR Type Concealed Duct 38

US Type Concealed Duct 40

FUR Type Floor/Ceiling Slim Concealed Duct 42

UMR Type Concealed Duct 44

T Type Ceiling Mounted Units 46

FTR Type Floor/Ceiling Mounted Units 48

KR Type Wall Mounted Units 50

K Type Wall Mounted Units 52

FMR/FR Type Floor Standing Units 54

GU Type Total Heat Exchanger 56

Water Terminals 58

Fan-Coil Units 59
SANYO Air Conditioners
SANYO Air Conditioners - the natural choice
With almost 50 years’ experience in the industry, SANYO has earned its
reputation as an innovator in air conditioning, consistently delivering market-
leading technology and reliability. From the world’s first heat pump air
conditioners developed in 1960 to the first gas driven VRF systems in the
1980s and the first 3-pipe VRF system developed in 1989, our continuous
programme of research and development has ensured that SANYO’s
products remain at the forefront of innovation.

However, developing market-leading technology is only one part of the story. At


SANYO we are committed to delivering a complete service to all of our clients,
from customer service to ensuring we provide the most reliable products
in the industry.

Product Industry-leading
reliability technology

Excellent Environmentally
customer sustainable
service products

Extensive
range

2007 - a year of innovation


Here at SANYO we are excited about the future. 2006 was a breakthrough
year, with 53 new products launched across the whole range, and 2007
is set to be a landmark year, with plans to launch many revolutionary new
technologies including solar-powered air conditioning, the CO2 water heater
and the Virus Washer to name just a few.

If you would like to be the first to hear about our new products, register for
our newsletter via our website.
www.sanyoaircon.eu

SANYO’s Solar Ark, the world’s largest solar


power generator.

4
Think GAIA - the environmental philosophy of SANYO

Environmental sustainability and “Think GAIA”


In the latter part of the last century, mankind’s pursuit of convenience and
material comforts left indelible marks on the earth, such as global warming
and environmental destruction. SANYO has always had a strong environmental
focus. However, in 2005 we took that a stage further and based our whole
corporate philosophy on the concept of “Think GAIA”. Under this vision
SANYO has committed to using global resources and skills to develop
solutions for a sustainable coexistence on earth.
What is “Think GAIA”?
“GAIA”, originally the mythological goddess of the Earth, is a concept rapidly
gaining momentum today. Based around the belief that living organisms on the
earth affect the nature of their environment, the concept of “GAIA” was first
proposed in 1979 by the English scientist James Lovelock, who participated
in NASA’s Mars exploration programme during the 1960s. Lovelock proposed
the idea of earth as a living, green organism where mankind and all living
things live in harmony. His recent book “The Revenge of GAIA” serves as a
wake-up call and has sparked much public debate.

SANYO - committed to developing environmental technologies


At SANYO actions speak louder than words. We are dedicated to incorporating the “Think GAIA” ethos throughout our
business - an example of this is our Solar Ark, which is the world’s largest solar power generator with over 5000 cells,
used to supply one of our production plants.

“Think GAIA” has also been the driving force behind many environmentally sustainable products that are already
widely available, including:

• ECOi Electric VRF systems - we have developed some of the most energy-efficient and reliable products in the industry.

• Gas driven VRF system - providing an energy-efficient solution that delivers a reduced carbon footprint.

• Virus washer - suppresses 99% of airborne viruses from treated air including common cold, flu and avian flu. Now available as
a free-standing unit, it will soon be available in air conditioning systems.

• Solar powered air-conditioners - set to revolutionise the air conditioning industry.

World-leading innovators
The “Think GAIA” concept is driving environmentally sustainable product development throughout the whole SANYO corporation,
including the eneloop battery, which can be recharged 1000 times and has a solar charger, and the revolutionary AQUA washing
machine, which uses ozone rather than detergent as well as recycling its water.

The eneloop battery can be The revolutionary AQUA washing SANYO supplies the nickel-metal batteries
recharged 1000 times and has a machine uses ozone rather than used in hybrid cars such as Ford’s Escape
solar charger. detergent and recycles its water. Hybrid and Honda’s Accord Hybrid.

5
SANYO GHP - the natural choice

The SANYO GHP uses HFC-type refrigerant


and clean-burning natural gas for high-effi-
ciency operation. Since it is designed to work
with existing piping, the SANYO GHP offers
an easy way to renew old air-conditioning sys-
tems. It is a high-performance machine that is
economical to run and maintain.

The outdoor unit uses an


automobile engine for high
efficiency.

Environmental

High efficiency operation


All models are equipped with a high performance air
exchanger and a newly developed refrigerant/heat
exchanger for high efficiency operation.
Helps prevent global warming
High efficiency operation reduces emissions of carbon
dioxide (CO2), the major cause of global warming.
SANYO GHP uses the new R410A refrigerant

Up to 40% reduction of nitrogen oxide


(NOx) emissions
With a lean burn combustion system that relies on air-
fuel ratio feedback control, the SANYO GHP reduces NOx
emissions by as much as 40%.

6
Powerful Cooling and Heating

Power supply problems?


If you are short of electrical power, gas heat pumps
could be the perfect solution.
• Runs on gas and just needs single phase supply.
• Enables the building’s electrical power supply to be
used for other critical electrical demands.
• Reduces capital cost to upgrade power sub stations
to run heating and cooling systems.
• Reduces power loadings within a building especially
during peak periods.
• Electricity supply freed up for other uses such as IT
servers, commercial refrigeration, manufacturing,
lighting etc.

Economical Comfort

With high-efficiency operation, the SANYO GHP consumes Low operating noise and high heat capacity at low
less gas and electricity than conventional air conditioners, so it temperatures create a comfortable environment.
offers substantial savings on air conditioning costs.

Reduced gas consumption Outdoor unit has reduced noise and vibration
Gas consumption is significantly reduced by using a All our outdoor unit models have reduced noise and vibration
Miller-cycle engine. levels during normal operation, and in Quiet mode they are
Reduced electric power consumption levels even quieter. (Unit capacity drops by 10% in Quiet mode.)

Electric power consumption is significantly reduced by using


a DC motor and DC fan.
Outstanding durability for greater economical
efficiency
A maintenance interval of 10,000 hours helps make the Body rubber
SANYO GHP a cost-saving machine. (Converted to the Device
distance travelled by a car, 10,000 hours of operation is
equivalent to about 300,000 km!) Antifreeze

Orifice

Resin mount construction


As an industry first, we use a resin mount instead of anti-
vibration rubber to absorb engine vibration. The resin mount
suppresses engine startup vibration as well as reducing the
vibration transmitted to the unit structure while the engine is
running, so it helps reduce operating noise.

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 7
Case Studies: Regione Lazio, Rome, Italy
Famous Italian landmark is now Europe’s
largest GHP installation, with 81 outdoor and
1,390 indoor units. Energy savings
The HQ for the Lazio Region, is a building famous as the “What is special about this installation lies in the fact that
location for many Italian comedies over the years, and in its the outdoor units have multi-stage compressors driven by
own right part of cinematic history as Fantozzi’s office in the an endothermic motor powered by methane gas.” said
first episode of the popular series written by Paolo Villaggio. Engineer Gianpiero Pugliese, the Technical Manager of
As a result of refurbishment over the last two years, the Cedic 818, Srl, “This innovation has brought two benefits.
building is now the site of the largest Gas Heat Pump (GHP) The first is that we do not have to completely redesign the
installation in the whole of Europe. electrical supply for the building. A radical reworking would
have been required for the electrical supply sub-stations.
The second benefit is one of energy saving as a result of
the use of methane gas.”

Power problems overcome


Having been fitted with an old, energy-intensive centralised
system back in the 1960s, this iconic 12-storey property is
now a pleasure to occupy as it features SANYO’s innovative
Easy installation
gas-powered air conditioning system. The new system is Because the installation programme took a modular approach,
composed of 81 outdoor units located on the roof connected all offices could continue working as normal without undue
to an astonishing 1,390 internal units from SANYO’s disruption. All work was carried out without adversely affecting
pioneering gas-powered range. the air-conditioning of the offices during working hours, and
enabled the existing system to be kept running during the
The successful installation of a system this size however,
period of construction.
was only made possible as the system did not require
electrical power. With no capacity available from the existing Also, SANYO’s GHP system is of an extremely compact
electrical supply to the building, the owners were facing an design, requiring a smaller footprint than the previous
astronomical bill to re-develop the sub-station. However system. Therefore, although the new system serves
by opting for SANYO’s gas-powered system, not only are much of the 12-storey building, less plant space is actually
there impressive energy savings possible (it was estimated occupied. This has provided Regione Lazio with more free
that the new VRF system would achieve energy savings space, which is now home to the region’s archive files, which
of around 50%), but the installation only requires minimal were previously housed in rented space nearby, giving the
electricity for start-up and a single PC workstation. company even more cost savings.

8
Case Studies: Sheraton Fota Island, Cork, Ireland
SANYO GHP’S five-star showing at the Fota
Island resort, Cork. Many benefits
SANYO Gas Heat Pump (GHP) technology has been installed Alastair Howard of Mott MacDonald Pettit, Cork, explains:
at the new luxury five-star Sheraton Fota Island Hotel, “We reviewed a number of alternative solutions for hotel air
Golf Resort and Spa, Cork, Ireland. The resort includes a conditioning. A natural gas operated heat pump system was
championship golf course that has hosted events such as identified as providing energy-saving heat recovery, automatic
the Irish Open and the Irish PGA Championship. heating and cooling change-over, simultaneous heating and
cooling, BMS and reception desk controls interface, a low
running cost, as well as a short-term payback. The bedroom
units have been highly praised for their very low noise level
during night time operation. On the basis of our analysis for
this project, we recommended the natural gas heat pump
system from SANYO, which was installed.”

Gas or electric?
SANYO installer Kelly Refrigeration of Ennis, Co.Clare,
worked closely with the appointed consultant engineers
- Mott MacDonald Pettit - to devise the most appropriate
heating and cooling solution for this prestigious hotel. The
options of either a gas or electric air conditioning solution
were put forward, but it quickly became clear that a gas heat
Waste heat can provide hot water
pump (GHP) system was the most suitable, because of its
environmental benefits. The GHP system specified for the SANYO’s GHP range uses a new heat reclaim heat exchanger,
project provides 504kW cooling capacity via 139 concealed allowing a system in cooling to supply waste heat from the
indoor units with 9 rooftop GHP VRF outdoor condensing engine into the hot water system, improving overall efficiency
units providing simultaneous heating and cooling. and COP. The ECO G is the only GHP range in Europe to use
mains gas or LPG as its main power source, and single-phase
electricity for start-up and fan operation. It provides the ideal
solution for operators facing a shortfall in power. Due to its
advanced technology and design SANYO GHP requires no
defrost cycle, which enables it to provide continuous 100%
heating performance even in severe weather conditions with
an outside temperature as low as -20°C, while consuming
less gas and electricity than comparable air conditioning
systems. This was obviously a huge benefit when considering
the correct system for the hotel.
Sheraton Fota Island Hotel, Golf Resort and Spa, is twenty
minutes drive east from Cork, with 131 rooms, and a further
280 lodges are in development in the grounds. The spa’s
features include a pool and well-designed gym, 18 treatment
rooms and hydrotherapy suite. The nearby Fota Wildlife Park
offers visitors the experience of seeing giraffes roaming the
Irish landscape.

9
Efficient, Powerful, Comfortable and Economical
Speedy and powerful Always comfortable
The SANYO GHP provides quick and powerful The engine speed is computer-controlled
cooling/heating and the efficient recovery and is determined by the room temperature.
of waste heat. Defrosting operation is not The room temperature is therefore kept
required. comfortable at all times.
Not only is the gas used as the heat source but the waste A gas engine is used to drive the compressor. The speed
heat from combustion is also recovered and reused by highly of the engine is controlled efficiently by a microcomputer
efficient air-conditioning technology. This prevents energy according to the room temperature, so that there is no
loss enabling quick start operation and powerful heating. temperature loss.
In addition, a gas heat pump air conditioner requires Low running costs
no defrosting cycle and continuous heating is possible.
Very low consumption of electricity.
Comfortable heating is possible even in severe winter Low running costs and very economical.
conditions with an outside air temperature of -10˚C.
As a gas heat pump air conditioner uses gas as the heat
Comparison of the start times for heating source, it uses electricity only for auxiliary equipment like
operation fans etc. The electrical load is therefore reduced and the
Room temperature (˚C) electric power is used efficiently. The consumption of electric
power is equivalent to 8 PS, and as operation with 0.70 kW
20˚
(50 Hz at the time of cooling) is possible, comfortable air
15˚C
conditioning can be achieved even in locations with low
10˚C Gas heat pump
5˚C
electrical power capacity. By installing a gas heat pump air
0˚C conditioner, the running costs can be reduced by 20 - 40%
Electric heat pump in comparison with electric heat pumps. (Electrical power
consumption and running costs differ according to the
Time axis (in case of the same load) operating conditions.)

Consumption of electricity
Comparison of the heating capacity Approx
1/10
Heating capacity (%)

100

80
Gas heat pump
Gas heat pump Electric heat
60 pump

0
Electric heat pump Electric air conditioner (During cooling)
R410A R407C
Room
-20˚ -15˚C -10˚C -5˚C 0˚C 10˚C
Operation temperature Energy
Outside air temperature (˚C) Set
condition loss
temperature
(motor)

Gas heat pump air conditioner


OFF ON OFF ON OFF ON
Operation (Large electrical load at the time of start)
condition Room Set
temperature
(engine) temperature
High speed
Running costs
Approx
.
Low speed 60%
(with speed efficiently controlled by microcomputer)

Gas heat pump Electric heat


pump

10 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
1 Change to an air heat exchanger with high Exhaust
efficiency
A new hybrid heat exchanger is used, and the engine cooling
water piping has been separated. The condensation capacity
Fan
and the radiator performance is improved while keeping the
air resistance down, the efficiency drop during cooling is
improved, and a high COP rate is achieved.
2 Higher engine efficiency
The pumping loss at the time of the compression
Air
stroke is reduced by use of a Miller-cycle engine. As a result,
the expansion volume ratio increases and the exhaust loss
is reduced.
Miller cycle: This heat cycle has the characteristic that the
closing time for the suction valve in regard to the base
engine is late. As a result, the expansion stroke becomes
relatively longer in comparison to the compression stroke.
3 A newly developed refrigerant heat
exchanger is installed Accumulator

A new plate heat exchanger has been installed, and the Compressor
engine waste heat is recovered efficiently. In addition, a 3-way
change-over valve with proportional control is used for control
of the engine cooling water to realize high efficiency at the
time of heating operation.

Engine cooling water

Refrigerant
Explanation of the internal flow
Refrigerant and engine cooling water
flow alternately between the plates, and
the engine waste heat is recovered.

GHP mechanism

Cooling Heating
Refrigerant gas Refrigerant liquid

Refrigerant Cold air


Refrigerant
liquid gas
Outdoor unit Outdoor unit
Heat Heat Warm air
Warm air Cold air
Discharge of heat Hot water Engine waste heat
Absorption of heat
absorbed from the function from the outside air
inside of the room by evaporation of
by liquefaction of refrigerant.
refrigerant.
Compressor Gas engine Compressor Gas engine
Absorption of heat from the room by Discharge of heat generated by
liquefaction of refrigerant. condensation of refrigerant.

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 11
SANYO 3-Way GHP for buildings requiring
simultaneous cooling and heating
Excellent performance
SANYO 3 WAY multi system is capable of simultaneous heating/cooling as well as
independent operation of each indoor unit by only one outdoor unit. As a result, efficient
targeted individual air conditioning is possible in buildings demanding a diverse range of
room temperatures.
Improved maintenance intervals
The unit only needs to be serviced every 10,000 hours. This is the best in the industry.
Up to 35% energy saving (SANYO estimate)

Effective heat recovery system enables a maximum 35% energy saving


The waste heat removed from the cooled room is effectively used as a heat source for
Max. 28 indoor units the room to be heated. This reduces the load on the outdoor unit’s compressor and heat
3 WAY GHP MULTI exchanger, enabling excellent heat recovery.
enables simultaneous
heating and cooling
operation through each
solenoid valve kit.
Liquid pipe
medium-temperature
medium-pressure liquid pipe
Suction pipe
low-temperature
low-pressure gas pipe
Discharge pipe
high-temperature
high-pressure gas pipe
Stop
[Heating] [Cooling] [Heating] [Cooling] [Heating]

Flexible system design

120m piping allows effective system design


Allowable piping length is a maximum of 120m (actual length
of 145m). This allows flexible system design and installation.
Solenoid Valve Kit Up to 28 indoor units are capable of simultaneous heating/
ATK-RZP56BGWB, ATK-RZP160BGWB cooling operation.

SANYO 3 WAY GHP is ideal for the Solenoid valve kit


The industry’s smallest SVK
following applications: box: 166 x 147 x 217mm

• Office buildings with a diverse range of ATK-RZP56BGWB


(For 74 to 254 indoor unit)
room temperatures due to the differing
ATK-RZP160BGWB
amounts of sunshine. (For 364 to 604 indoor unit)
• Buildings with computer equipment rooms
requiring year-round cooling. * For conference rooms and other locations where low noise is required,installation location
should be carefully considered, eg, install in a corridor, etc.

Solenoid valve controller


ACC-3WAY-AG
(Distribution joint kits)
APR-RZP224BGB
(16.0 kW or less)
APR-RZP680BGB
(28.0 kW or less)
APR-RZP1350B
(More than 35 kW)

12 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Dimensional data
X
1000 (outer cover)

(for anchors)
1735 (outer cover) 1060
ø732 Fuel gas port: R3/4
(Anchor hole pitch)

4 -ø24
(148)
Wiring port

(Anchor hole pitch)


between units (ø28)

2253
Power inlet port (ø28)

1000
Discharge pipe: ø25.4
Suction pipe: ø31.75
4 - ø30

377
(Suspension hole)

104
394
1030 37

205
117
1754 (frame width) 160 Liquid pipe:
(suspension hole) 248 ø19.05 60 View in direction of arrow X
1106 (frame width) 261
Exhaust gas drain hose
(ø27 rubber hose)
Left side Front Rear Top

Outdoor unit specifications Main piping size after distribution


Model No. SGP-EZ190K1GU2 Main pipe size after distribution
Outdoor Outdoor unit
HP 20 Total capacity after branching (kW)
unit connection pipe
Cooling capacity
kW 56.0 35.6-112.0 28.1-35.5 16.1-28.0 9.0-16.0 Less than 9.0
STD kW 63.0 Suction pipe ø38.1 ø31.75 ø28.58 ø19.05 ø15.88
Capacity Heating capacity 560 type Discharge pipe ø25.4 ø22.22 ø19.05 ø15.88 ø12.7
Low* kW 67.0
Liquid pipe ø19.05 ø15.88 ø12.7 ø9.52 ø9.52
Hot water kW -
C Power kW 1.02
Electrical rating
H Power kW 1.13
C kW 39.0
Gas H-STD kW 43.0
consumption
H-LOW* kW 53.6 Distribution Solenoid valve kit connection piping
Cooling 1.4 <3 pipes>
COP Heating 1.43 Type 7 9 12 16 18 25 36 48 60
Indoor unit
AVE 1.41 Equivalent HP 0.8 1 1.3 1.6 2 2.5 4 5 6
Height mm 2,253 Suction pipe ø15.88 ø19.05
Size Width mm 1,735 Piping size Discharge pipe ø12.7 ø15.88
Depth mm 1000 (+106) Liquid pipe ø9.52
Weight kg 920
Starter current A 30
Fan motor power kW 0.45x2
Suction mm ø31.75
Discharge mm ø25.40 Solenoid valve kit Indoor unit connection piping
Pipe Liquid mm ø19.05 <2 pipes>
Fuel gas R3/4 (Male screw) Type 7 9 12 16 18 25 36 48 60
Drain water mm ø20 (ø27Rubber hose) Indoor unit
Equivalent HP 0.8 1 1.3 1.6 2 2.5 4 5 6
Operation sound† dB(A) 58 Gas pipe ø12.7 ø15.88 ø19.05
Piping size
Number of connections indoor* 28/ - Liquid pipe ø9.52
* Low temperature conditions (outdoor); 2CDB/1CWB.
† Sound values were obtained with the outdoor unit operator standing 1m in front of

the unit and operator height of 1.5m.

Limitation of refrigerant piping length


Items Outdoor unit 560
Capacity ratio of indoor unit to outdoor unit 50-200%
Connectable indoor units 7(0.8HP)-60(6HP)
Max. number of connectable indoor units 28
Max. piping length 120m or less (actual length is 145m or less)
Difference between the max. length and the min. length from the first distribution point 30m or less
Max. length of main piping 30m or less
When outdoor unit is installed higher than indoor unit 50m or less
Allowable elevation difference 35m or less (30m or less in the case of cooling operation
When outdoor unit is installed lower than indoor unit
at outdoor temperature of -10˚C or less)
Max difference between indoor units 15m or less

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 13
SANYO 2-Way GHP Comfort Air Conditioning
The maximum number of indoor units that can be connected is 32 (240 type).
The capacities that can be connected to the indoor units range from 50% to 200%.

System example

Maximum number of
Cooling kW Heating kW
indoor units
8 HP SGP-E70K1GU2 22.4 25 20
10 HP SGP-E90K1GU2 28 31.5 24

Remote Remote Remote Remote Group


controller controller controller controller control
(Main) (Sub) (Main & Sub)

System example

Maximum number
Cooling kW Heating kW
of indoor units
13 HP SGP-E120K1GU2W 35.5 40 24
16 HP SGP-E150K1GU2W 45 50 24
20 HP SGP-E190K1GU2W 56 63 28
Remote Remote Remote Remote Remote Group
25 HP SGP-E240K1GU2W 71 80 32 controller controller controller controller controller control
(Main) (Sub) (Main & Sub)

Outdoor unit specifications

Model No. SGP-E70K1GU2 SGP-E90K1GU2 SGP-E120K1GU2W SGP-E150K1GU2W SGP-E190K1GU2W SGP-E240K1GU2W


Cooling capacity kW 22.40 28.0 35.50 45.0 56.0 71.0
STD kW 25.0 31.50 40.0 50.0 63.0 80.0
Heating capacity
Low ambient kW 26.50 33.50 42.50 53.0 67.0 75.0
Hot water supply capacity kW - 12.50 16.0 17.0 27.50
Power supply 220/230/240V Single Phase 50 Hz
Cooling kW 16.1 20.4 24.5 32.0 34.0 54.5
Gas consumption STD kW 17.2 21.7 27.5 34.0 40.9 58.6
Heating
LOW kW 20.9 26.9 33.5 42.1 53.3 58.6
Applicable gas type *Band P: propane gas (G31), Band H: natural gas (G20), Band L: natural gas (G25)
Air circulation m³/h 9,000 9,000 18,000 18,000 18,000 18,000
Cooling kW 0.55 0.55 0.96 0.96 1.13 1.60
Electrical consumption
Heating kW 0.58 0.58 1.06 1.06 1.24 1.70
Engine speed min-1 800-1,800 800-2,000 800-2,100 800-2,100 800-2,200 800-2,200
Operating sound† db (A) 56 56 57 57 58 62
Refrigerant tubing Narrow tube mm 12.7 12.7 15.88 19.05 19.05 19.05
Refrigerant tube outlet diameter Wide tube mm 22.22 25.4 28.58 28.58 31.75 31.75
Refrigerant R410A kg 9 9.5 10 10 21 20
Height mm 2,253
Depth mm 1,000 (+106)
Dimensions & weight
Width mm 1,290 1,735
Weight kg 620 640 875 920 940
Connectable indoor units 20 24 28 32
†Sound values were obtained with the outdoor unit operator standing 1m in front of the unit and operator height of 1.5m.
*Low temperature condition (outdoor); 2˚CDB/1˚CWB

14 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Dimensions of 2 way outdoor unit

(Anchor hole pitch)


1060
SGP-E70K1GU2 Top

SGP-E90K1GU2

1000
155 (Anchor hole pitch)
1000 (outer cover) 4 -ø24 (for anchors)
Fuel gas port: R3/4
ø732 1290 (outer cover)

(148)
2253
Wiring port
between units (ø28)
Power inlet port (ø28)

Gas pipe: E70K1: ø22.2


E90K1: ø25.4
104
394

Liquid pipe: 37 1030 (suspension hole)


140
220

156 ø12.7
60 1106 (frame width) 1310 (frame width)
217
Rear Left side Front
4 - ø30
Exhaust gas drain hose (Suspension hole)
(ø27 rubber hose)

SGP-E120K1GU2W

(Anchor hole pitch)


SGP-E150K1GU2W
SGP-E190K1GU2W Top

1060
SGP-E240K1GU2W

1000 4 -ø24
1000 (outer cover) 377 (Anchor hole pitch) (for anchors)
Fuel gas port: R3/4 1735 (outer cover)
ø732
(148)

Wiring port
between units (ø28)
2253

Power inlet port (ø28)

Hot water inlet : R ø3/4


Hot water outlet : R ø3/4
104

394

Liquid pipe: ø15.88, 19.05 1030 (suspension hole)


156 37
220
140

Gas pipe: ø28.58, 31.75


217 60 1754 (frame width)
1106 (frame width)
Exhaust gas drain hose
(ø27 rubber hose)
Rear Left side 4 - ø30 Front
(Suspension hole)

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 15
GHP Chiller
GHP Chiller available with outdoor unit
capacities from 20 kW to 71 kW
Fan Coil Unit
GHP Chiller Refer to page 59

Water Heat Exchanger

Duct
Water Piping

Outdoor unit

Refrigerant Piping Air Handling Unit

The GHP Chiller meets a wide range of • Can accommodate up to 120m of piping
temperature needs for all kinds of industrial
The system can accommodate up to 120m (actual length)
application, ranging from comfort air-
conditioning to food processing or the of piping between the outdoor unit and the water heat
replacement of boilers and other systems. exchanger, alllowing flexible installation locations.

• Reduced installation cost and circulating • Complies with “brine specifications”


pump power The system uses antifreeze coolant, so it can produce
The water heat exchanger is a split type, which reduces cold water even at -12˚C.
installation costs and allows the use of a less powerful • GHP Chiller remote controller is available
circulating pump.
• One-touch changeover between cooling
and heating operation
• Please ensure that the water loop volume
exceeds 3 litres per kW when designing a
chilled water system or alternatively install
a system buffer tank. RCS-WE170J

Water heat exchanger unit 4 -ø24 (for anchor holes)


(Anchor hole pitch)
677

Model No. SGP-WE80K1 SGP-WE170K1 Top


Power supply 220/230/240V Single Phase 50 Hz
Cooling capacity kW 25 50 1060
Standard kW 30 60 (Anchor hole pitch)
Heating capacity Electric box 1000 770
Low temperature kW 30 60 (outer cover)
Height mm 1,000 Cable connection
External opening
Width mm 770
dimensions 50 216 Liquid pipe
Depth mm
1000

1000 (+106)
Weight kg 185 200 Cold/hot Gas pipe
water inlet
Electrical Cooling power consumption kW 0.009 Rp2 female
( (
53
316

thread [50A]
221

consumption Heating power consumption kW 0.009


135

Can be discharged
from the front of the unit 1030 (suspension hole) 384
Standard cold/hot water flow rate m3/h 4.3 8.6
Hydrostatic loss kPa 12.6 6.3 515 124 1106 (frame width) 4 -ø30
Drain port suspension hole
Holding water quantity inside the unit m3 0.02 0.03 Cold/hot water outlet
(Rp3/4 female thread) [20A] (Rp2) [50A]
Minimum holding water quantity outside the unit m3 0.27 0.28
Rear Left side Front
Piping Gas pipe mm ø25.4 ø31.75
refrigerant Liquid pipe mm ø12.7 ø19.05 Heating Heating (low
Operating condition Cooling
Heat exchanger Plate type (standard) temperature)
Water circuit limit pressure MPa 0.686 (7kg/cm2) Water temperature of water heat exchanger unit Outlet 7˚C Outlet 45˚C Outlet 45˚C
Anti-freezing protection system Thermostat Outdoor side intake air temperature 35˚C DB 7˚C DB, 6˚C WB 2˚C DB, 1˚C WB
Data subject to change without notice.

Note: The gas consumption can be 110% of the specification value depending on the
operating conditions.

16 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
System Mixing Flexibility for 2 Way GHP
Combined with a water heat exchanger unit, The GHP Multi System can incorporate an
the SANYO 2 Way GHP can create a flexible indoor unit plus a GHP chiller. When the
system, the ideal replacement for existing two systems are operated independently,
chiller and boiler systems. an outdoor unit with a 200% capacity can be
connected.
Fan Coil Unit
System Example
GHP Chiller
Water Heat Exchanger
Refrigerant
Piping Water Piping

Duct

NOTE
Distance between units
must be less than 2m.
Outdoor Unit Air Handling Unit

Connectable indoor units


E70K1GU2 18 units
E90K1GU2 22 units
E120K1GU2W 22 units
E150K1GU2W 22 units
E190K1GU2W 28 units
E240K1GU2W 32 units

Note: The outdoor units operating mode is dependent on the water heat exchanger’s operating mode. The water pump is
not included in the water heat exchanger unit. For simultaneous operation, the maximum capacity is 130%. System
design details can be obtained from SANYO.

Hot Water Supply Function *Hot water capacity will vary depending on cooling load.
*Hot water is also available during heating when ambient temperature is
SGP-E120/150/190/240K1GU2W higher than 7˚C.
System Advantage
The engine waste heat, which is normally exhausted into
the atmosphere, is recovered via the heat exchanger and
effectively used as hot water, so the GHP Chiller acts as a
sub-system that alleviates the load on the client’s main hot GHP
water system and therefore offers ‘free’ hot water. SANYO
Water heating capacity SGP-E120: 12.5kW Hot water
(Cooling standard point) SGP-E150: 16kW
SGP-E190: 17kW
SGP-E240: 27.5kW
Hot water piping allowable pressure 0.7MPa
Hot water circulation rate 3.9m3/h
Hot water pipe size Rp3/4
Electric connection: 240AC, 3A
Water
tank Manometer
Expansion Tank
Boiler
Cold water Pump Valve
Electric Design
• All the items illustrated in this drawing (except outdoor unit)
are not supplied by SANYO.
• During start-up, set temperature value of the water in the
outdoor unit’s parameter.
Magnetic Relay *All water connections must be carried out in accordance with local
Pump regulations.

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 17
Indoor Units Range
Wide choice of models depending on the indoor requirements
Model size 7 9 12 16 18 22 25
Cooling 2.2 2.8 3.6 4.5 5.6 6.4 7.3
Capacity kW
Heating 2.5 3.2 4.2 5.0 6.3 7.0 8.0
Cooling 7,500 9,600 12,000 15,000 19,000 22,000 25,000
Capacity BTU/h
Page Heating 8,500 11,000 14,000 17,000 21,000 24,000 27,000
X Type SPW-X075XH SPW-X095XH SPW-X125XH SPW-X165XH SPW-X185XH SPW-X255XH
Semi-Concealed Panel Panel Panel Panel Panel Panel
Cassette 4-Way PNR-XD484GHAB PNR-XD484GHAB PNR-XD484GHAB PNR-XD484GHAB PNR-XD484GHAB PNR-XD484GHAB
22 Air Discharge
XM Type
Semi-Concealed SPW-XM075XH SPW-XM095XH SPW-XM125XH SPW-XM165XH SPW-XM185XH
4-Way PNR-XM185 PNR-XM185 PNR-XM185 PNR-XM185 PNR-XM185
24 Air Discharge
XMR Type SPW-XMR74EXH56B SPW-XMR94EXH56B SPW-XMR124EXH56B SPW-XMR164EXH56B SPW-XMR184EXH56B
600 x 600 Panel Panel Panel Panel Panel
Semi-Concealed PNR-XM184EHA PNR-XM184EHA PNR-XM184EHA PNR-XM184EHA PNR-XM184EHA
26 Cassette
SR Type SPW-SR74GXH56B SPW-SR95GXH56B SPW-SR125GXH56B SPW-SR165GXH56B SPW-SR185GXH56B SPW-SR254GXH56B
Semi-Concealed Panel Panel Panel Panel Panel Panel
Cassette 2-Way PNR-S124GHB PNR-S124GHB PNR-S124GHB PNR-S124GHB PNR-S124GHB PNR-S253GHANB
28 Air Discharge
ADR Type SPW-ADR74GXH56B SPW-ADR94GXH56B SPW-ADR124GXH56B
Semi-Concealed Panel Panel Panel
Cassette 1-Way PNR-AD124GHB PNR-AD124GHB PNR-AD124GHB
30 Air Discharge
LDR Type SPW-LDR94GXH56B SPW-LDR124GXH56B SPW-LDR164GXH56B SPW-LDR184GXH56B SPW-LDR254GXH56B
Semi-Concealed Panel Panel Panel Panel Panel
Slim Cassette PNR-LD254GHAB PNR-LD254GHAB PNR-LD254GHAB PNR-LD254GHAB PNR-LD254GHAB
32 1-Way Air Discharge

SPW-U075XH SPW-U095XH SPW-U125XH SPW-U165XH SPW-U185XH SPW-U255XH


U Type
34 Concealed Duct

SPW-UR74SXH56 SPW-UR94SXH56 SPW-UR124SXH56 SPW-UR164SXH56 SPW-UR184SXH56 SPW-UR254SXH56


UR Type
36 Concealed Duct
25,48 type
DR type
Concealed SPW-DR254GXH56B
Duct
38 High-Static Pressure 76,96 type

SPW-US075XH SPW-US095XH SPW-US125XH SPW-US165XH SPW-US185XH


US Type
40 Concealed Duct

FUR Type SPW-FUR74EXH56B SPW-FUR94EXH56B SPW-FUR124EXH56B SPW-FUR164EXH56B SPW-FUR184EXH56B SPW-FUR224EXH56B


Floor/Ceiling
42 Slim Concealed Duct

SPW-UMR74EXH56B SPW-UMR94EXH56B SPW-UMR124EXH56B SPW-UMR164EXH56B SPW-UMR184EXH56B SPW-UMR224EXH56B


UMR Type
44 Concealed Duct

SPW-T125XH SPW-T165XH SPW-T185XH SPW-T225XH


T Type Ceiling-
46 Mounted Units

FTR Type SPW-FTR74EXH56B SPW-FTR94EXH56B SPW-FTR124EXH56B SPW-FTR164EXH56B SPW-FTR184EXH56B SPW-FTR224EXH56B


Floor/Ceiling
48 Mounted Units

SPW-KR74GXH56B SPW-KR94GXH56B SPW-KR124GXH56B SPW-KR164GXH56B SPW-KR184GXH56B SPW-KR254GXH56B


KR Type
50 Wall-Mounted Units

SPW-K075XH SPW-K095XH SPW-K125XH


K Type
52 Wall Mounted Units

FMR Type SPW-FMR74GXH56B SPW-FMR94GXH56B SPW-FMR124GXH56B SPW-FMR164GXH56B SPW-FMR184GXH56B SPW-FMR254GXH56B


Concealed Floor
54 Standing Units

SPW-FR74GXH56B SPW-FR94GXH56B SPW-FR124GXH56B SPW-FR164GXH56B SPW-FR184GXH56B SPW-FR254GXH56B


FR Type Floor
54 Standing Units
GU Type
Total Heat SPW-GU055XH SPW-GU075XH SPW-GU105XH
Exchanger
56 with DX coil

18
30 36 48 60 76 96 Wireless remote control
9.0 10.6 14.0 16.0 22.4 28.0
10.0 11.4 16.0 18.0 25.0 31.5 Type with built- Type with sepa-
in reception rately installed Long-life Built-in drain Auto-flap Auto-swing
30,000 36,000 47,800 54,600 76,400 95,500 part reception part filter pump
34,000 39,000 54,600 61,500 85,300 107,500

SPW-X365XH SPW-X485XH SPW-X605XH


Panel Panel Panel • • • • •
PNR-XD484GHAB PNR-XD484GHAB PNR-XD484GHAB

• • • • • •

• • • • • •

• • • • • •

• • • • • •

• • • • • •

SPW-U365XH SPW-U485XH SPW-U605XH • •

SPW- SPW- SPW- SPW- • • •


UR304SXH56 UR364SXH56 UR484SXH56 UR604SXH56

SPW- SPW- SPW- SPW- •


DR364GXH56B DR484GXH56B DR764GXH56B DR964GXH56B

• • •

• •

• •

SPW-T365XH SPW-T485XH • • • • •

• • • • •

• • • •

• • • •

• •

• •

19
ECO VRF Indoor Unit Key Features
A wide range of quality indoor units with Control Options
many unique features
A wide choice of system controllers ranging from simple
• SANYO’s indoor unit range are compatible across all the remotes to more sophisticated web applications.
ECOi, GHP and PACi systems, enabling the system to
Controllers have flexibility to match across the range of
be designed without being restrained by the choice of
ECOi, GHP and PACi systems.
outdoor unit.
• Even wider range – 4 new models means a total choice of
19 models to suit every application.
• Expanded range includes 6 semi-concealed cassettes, 6
concealed ducted units, 4 wall / ceiling mounted units, 3
floor standing units and a total heat exchanger with DX coil.
• The highest quality design and manufacture to ensure
NEW
reliable, problem free operation.
PAC2 System Design Software for ECOi,
• Very efficient units with some of the best COPs in GHP and PACi systems
the industry.
• System design and selection has never been easier
• Indoor unit power consumption greatly reduced by use of
• Very user friendly interface with design wizards plus
high technology DC Fan Motors.
drag and drop icons
• Unique off coil temperature control to prevent cold
• AC Calc Lite included free
draughts available on ECOi and GHP ducted units.
• Auto piping and wiring features
• Very quiet operation ranging from just 22 db(A) for UR
Type ducted units. • Auto CAD (DXF) export
• All units carefully designed to ensure ease of installation • Plus much more… ask for free demo
and maintenance.

20 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
X Type Semi-Concealed Cassette
• By using turbo fans and heat exchanger fans in
recently designed shapes, the operating sound
levels can be reduced to a max. 6 dB (A)
dB(A)
45
40
35 42 39
37
30 33 31 31

Previous 4 series Previous 4 series Previous 4 series


model model model
9 type 18 type 36 type

• Power consumption is significantly reduced by • Fine adjustment of the body suspension height
using recently developed DC Fan motors with is easy
variable speed, and new heat exchangers.
The four corners
kW
0.25 of the ceiling panel
0.20 have removable
0.15 corner pockets fitted.
0.10
0.14 0.175 0.21
0.05
0.032 0.034 0.069 Even after installation, it is easy to make fine adjustment of
0 Previous 4 series Previous 4 series Previous 4 series
model model model the suspension height by removing the corner pockets
9 type 18 type 36 type

• Discharge opening and flap with new shape • Light, slim and attractive design with easy
The condensate and dirt that appears near the discharge installation
ports of conventional ceiling cassettes have been reduced. The direction of the air intake grille
can be changed.
A wireless remote control light
receiver can be installed by changing
the corner cover. The installation can
be done in a short time.
Previous New ceiling cassette • Easy servicing of the drain pan
The discharged air hits the Upward air flow is
ceiling and causes dirt. suppressed. The unit has a large diameter (45 mm) drain pan inspection
port and the drain pan and drain pump can be cleaned easily.
The flap can
be removed
easily for
45 mm
washing. Drain pan
inspection port

• Lighter and slimmer, easier installation


A lightweight unit at 26 kg (for type • A drain height of approx. 850 mm from the ceiling
Height 256 mm surface
36-60), the unit is also very slim with
Up to 300 mm
a height only 256 mm (7-25), making The drain height can be increased by
installation possible even in narrow ceilings. approx. 350 mm over the conventional
value by using a high-lift drain pump, and Up to 850 mm

long horizontal piping is possible.


Options
Air intake chamber
Timer remote controller Wireless remote controller Simplified remote controller Panel

RCS-SH80BG.WLB

Air intake plenum Air intake box


RCS-BH80AG.WLB CMB-GS140AGB
RCS-TM80BG (Transmitter, common part) CMB-FS140AGB
RCS-KR1AGB PNR-XD484GHAB
*Both Air intake plenum and Air intake box is necessary

22 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
SPW -
Model Name SPW-X075XH SPW-X125XH SPW-X165XH SPW-X185XH SPW-X255XH SPW-X365XH SPW-X485XH SPW-X605XH
X095XH
Power source 220/230/240V, 1 phase - 50, 60 Hz
Cooling kW 2.2 2.8 3.6 4.5 5.6 7.3 10.6 14 16
capacity BTU/h 7,500 9,600 12,000 15,000 19,000 25,000 36,000 47,800 54,600
Heating kW 2.5 3.2 4.2 5.0 6.3 8.0 11.4 16.0 18.0
capacity BTU/h 8,500 11,000 14,000 17,000 21,000 27,000 39,000 54,600 61,400
Power Cooling kW 0.033/0.032/0.032 0.033/0.032/0.032 0.035/0.034/0.034 0.042/0.041/0.041 0.070/0.069/0.069 0.099/0.097/0.097 0.107/0.105/0.105
input Heating kW 0.023/0.022/0.022 0.023/0.022/0.022 0.023/0.023/0.023 0.031/0.031/0.031 0.062/0.060/0.060 0.095/0.093/0.093 0.100/0.098/0.098
Running Cooling A 0.22/0.21/0.20 0.22/0.21/0.20 0.23/0.22/0.21 0.29/0.27/0.26 0.49/0.46/0.44 0.67/0.63/0.60 0.72/0.68/0.65
amperes Heating A 0.19/0.18/0.17 0.19/0.18/0.17 0.20/0.19/0.18 0.26/0.25/0.24 0.48/0.45/0.43 0.67/0.63/0.60 0.76/0.71/0.68
Type Turbo fan
Airflow rate
Fan motor 15.5/14/13 16/14/13 20/16/14 28/23/21 33/25/22 34/27/23
(H/M/L) m³/min
Output kW 0.05 0.09
Power sound level (H/M/L) db(A) 42/40/38 45/42/39 50/47/44 53/49/45 55/51/47
Pressure sound lev-
31/29/27 34/31/28 39/36/33 42/38/34 44/40/36
el (H/M/L) db(A)
Height mm 256 + <35> 319 + <35>
Dimensions Width mm 840 <950>
Depth mm 840 <950>
L i q u i d
6.35 9.52
Piping (flare) mm
connections Gas (flare) mm 12.7 15.88
Drain piping VP-25
Net weight kg 21+ <4.5> 26 + <4.5>
Rated conditions
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB Heating: Indoor air temperature 20˚C DB, outdoor air temperature 7˚C DB/6˚C WB.
The values in < > for external dimensions and net weight are the values for the optional ceiling panel. Data subject to change without notice.

Dimensional data

X
Air intake grill 860 to 910 Dimensions: mm
(ceiling opening dimension)
Air outlet
790
Refrigerant piping (liquid pipes) (suspension bolt pitch)
Type 7 to 18: ø 6.35 (flared)
Type 25 to 60: ø 9.52 (flared)

97
88
(ceiling opening dimension)

Refrigerant piping (gas pipes)


(suspension bolt pitch)

Type 7 to 18: ø 12.7 (flared)


Type 25 to 60: ø 15.88 (flared) Panel centre
860 to 910

Drain outlet VP25 (outer ø 32)


88
723

Power supply entry 120


Discharge duct (ø 150) 480
382

(400)

Suspension bolt hole (4-12 x 37 slot)


Outside air inlet duct connection port (ø 100) X view

347

840
840 80 160
480 250 70
60
120

30
210

A
97
188

160
35
45
160

113

Within 35 Within 35
950
514
73
15

7 25 type 36 60 type

A 256 319
514
950

30

* Adjust the suspension bolt length so that the gap from the lower
ceiling surface becomes 30 mm or more (15 mm or more from the
lower surface of the body) as shown in the figure above. When the
suspension bolt length is long, it hits the ceiling panel and installation
is not possible.

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 23
XM Type Mini Semi-Concealed Cassette
• New turbo fans and heat exchanger fins with
improved design and the operating sound has
NEW
been reduced by up to 12 dB(A).
dB(A)
40

35

30
37 37 37 37

25
25 26 28 33

Previous Previous Previous Previous


model 5 series model 5 series model 5 series model 5 series
type 7-9 type 12 type 16 type 18

• Significant reduction of power consumption


by using newly developed DC fan motors with
variable speed, new heat exchangers, etc. • Lighter and slimmer, easier installation
kW
0.10 A light weight unit at 26 kg (for type
36-60), the unit is also very slim with Up to 256 mm

a height only 256 mm (7-25), making


installation possible even in narrow ceilings.
0.05
0.087 0.087 0.087 0.087

0.031 0.034 0.040 0.049

0 Previous Previous Previous Previous


model 5 series model 5 series model 5 series model 5 series
type 7-9 type 12 type 16 type 18

• Discharge opening and flap with new design • A drain height of approx. 850 mm from the ceiling
surface
The condensate and dirt that appears near the discharge
Up to 300 mm
ports of conventional ceiling cassettes have been reduced. The drain height can be increased by
approx. 350 mm over the conventional
value by using a high-lift drain pump, and Up to 850 mm

long horizontal piping is possible.

Previous New ceiling cassette


The discharged air hits the Upward air flow is
ceiling and causes dirt. suppressed.
The flap can
be removed
easily for
washing.

Options
Timer remote controller Simplified remote controller Panel
Wireless remote controller

RCS-BH80BG.WL

RCS-TM80BG RCS-KR1AGB PNR-XM185

24 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
Model Name SPW-XM075XH SPW-XM095XH SPW-XM125XH SPW-XM165XH SPW-XM185XH
Power source 220/230/240V, 1 phase - 50, 60Hz
Cooling kW 2.2 2.8 3.6 4.5 5.6
capacity BTU/h 7,500 9,600 12,000 15,000 19,000
Heating kW 2.5 3.2 4.2 5.0 6.3
capacity BTU/h 8,500 11,000 14,000 17,000 21,000
Cooling kW 0.034 / 0.031 / 0.030 0.037 / 0.034 / 0.031 0.044 / 0.040 / 0.037 0.055 / 0.049 / 0.040
Power input
Heating kW 0.024 / 0.021 / 0.020 0.027 / 0.024 / 0.021 0.034 / 0.030 / 0.027 0.045 / 0.039 / 0.030
Cooling A 0.26 / 0.23 / 0.21 0.29 / 0.26 / 0.23 0.37 / 0.33 / 0.29 0.47 / 0.42 / 0.33
Running amperes
Heating A 0.24 / 0.21 / 0.19 0.27 / 0.24 / 0.21 0.35 / 0.31 / 0.27 0.45 / 0.40 / 0.31
Type Centrifugal fan
Fan motor Airflow rate (H/M/L) m³/min 9/8/7 10 / 9 / 8 12 / 11 / 10 14 / 13 / 11
Output kW 0.030
Power sound level (H/M/L) db(A) 41 / 38 / 36 43 / 40 / 37 47 / 43 / 39 52 / 48 / 44
Pressure sound level (H/M/L) db(A) 30 / 27 / 25 32 / 29 / 26 36 / 32 / 28 41 / 37 / 33
Height mm 283
Dimensions Width mm 575 <625>
Depth mm 575 <625>
Liquid (flare) mm (inches) 6.35 (1/4)
Piping
Gas (flare) mm (inches) 12.7 (1/2)
connections
Drain piping VP-20
Net weight kg 19 + <2.7>
Rated conditions
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB. The values in < > for external dimensions and net weight are the values for the optional ceiling panel.
Heating: Indoor air temperature 20˚C DB, outdoor air temperature 7˚C DB/6˚C WB. Data subject to change without notice.

Dimensional data

Air intake
Dimensions: mm
Discharge outlet A

Refrigerant tubing (liquid tube) 7-18 type ø 6.35 (flared) 600


Ceiling opening dimensions
Refrigerant tubing (gas tube) 7-18 type ø 12.7 (flared) 534 Suspension bolt pitch
Drain tube connection port VP20 (outer dia. ø 26)
Power supply port
534 Suspension bolt pitch

Ceiling opening dimensions

Suspension bolt hole (4-12 x 30 hole) 195


Fresh air intake duct connection port (ø 100)
Centre of panel
600

125
316
327

A view

575 575
55 160 170
283
117 45

215
92

45

Less than 25 zLess than 25


30

625
358
30
17
79
334
625

The length of the suspension bolts should be selected so that there


is a gap of 30 mm from the ceiling (17 mm or more below the lower
surface of the main unit), as shown in the figure above. If the
suspension bolts are too long, it will contact the ceiling panel and
the unit cannot be installed.

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 25
XMR Type 600 x 600 Semi-Concealed Cassette
• New dimensions 600 x 600 mm suitable for
European ceiling standards

• Three-speed centrifugal fan

• Anti-mould and anti-bacteria washable filters

• Low operating sound

• Integral drain pump gives 250mm lift

575 mm
575 mm

Options
Timer remote controller Wireless remote controller Simplified remote controller Panel

RCS-TH80BG.WLB

RCS-BH80AG.WLB

RCS-TM80BG (Transmitter, common part) RCS-KR1AGB PNR-XM184EHA

26 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
Model Name SPW-XMR74EXH56B SPW-XMR94EXH56B SPW-XMR124EXH56B SPW-XMR164EXH56B SPW-XMR184EXH56B
Power source 220/230/240V, 1 phase - 50 Hz
kW 2.2 2.8 3.6 4.5 5.6
Cooling capacity
BTU/h 7,500 9,600 12,000 15,000 19,000
kW 2.5 3.2 4.2 5.0 6.3
Heating capacity
BTU/h 8,500 11,000 14,000 17,000 21,000
Cooling kW 0.087/0.087/0.087
Power input
Heating kW 0.087/0.087/0.087
Cooling A 0.41/0.41/0.41
Running amperes
Heating A 0.41/0.41/0.41
Type Centrifugal fan
Fan motor Airflow rate (H/M/L) m³/min 11.7/10/8.3 12.5/10.5/8.8
Output kW 0.06 0.06
Power sound level (H/M/L) db(A) 54/51/48 55/51/48
Pressure sound level (H/M/L) db(A) 43/40/37 44/40/37
Height mm 296 (41mm)
Dimensions Width mm 575 <730>
Depth mm 575 <730>
Liquid (flare) mm (inches) 6.35 (1/4)
Piping connections Gas (flare) mm (inches) 12.7 (1/2)
Drain piping VP-18
Net weight kg 16.5 + <2.5> 18 + <2.5>
Rated conditions
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB Heating: Indoor air temperature 20˚C DB, outdoor air temperature 7˚C DB/6˚C WB.
The values in < > for external dimensions and net weight are the values for the optional ceiling panel.. Data subject to change without notice.

Dimensional data

575
41 min.

Suspension Suspension 70 575 Dimensions:


bracket 506 bracket mm
544

Ceiling

273

296
259

233

183

23
135

133

41

600 600

730
544 544 Fresh air intake side
Suspension bracket 10

10
10

Electrical component
box side
506

506

730
41 min.

Suspension bolt

Ceiling
Refrigerant
Nuts and tubing side
Washers
25 25

ø2.9 I. D. 18mm
Fresh air intake port Refrigerant tubing side Condensate
ø90 drain piping

Refrigerant
tubing joint
narrow tube
ø70
Presplitting

Refrigerant tubing joint


90˚ wide tube

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 27
SR Type Semi-Concealed Cassette
• Slim, compact, and light weight units
Significant size and weight reductions have been achieved
by improving the design around the fan. In addition, the size
of the type 18 has been reduced compared to the current
model.
In case of the type 18
Body volume
Approx. 30% reduction
Weight (body + panel)
Reduction from 50 kg to 30 kg
(approx. 40% reduction)
• Excellent installation performance

Comparison with the current type The packing pad can be used for the ceiling opening
dimensions and for adjustment of the height of the
Type 9 Type 25
indoor unit.
Body volume Approx 14% reduction Approx 12% reduction
Weight 40 kg to 30 kg 50 kg to 39 kg First in the First in the
(body + panel) (approx 25% reduction) (approx 22% reduction) industry industry

• Quiet operation
Mark
Low operating sound levels have been achieved by using
high-efficiency fans.
String
Operational noise
Type 9 Type 12 Type 16-18 Type 25 M5xL40 Panel opening holes
33-26 34-28 35-29 38-33 (accessory black screw) and panel centre
High/low notch, dB/A Even large ceiling panels can be installed easily by
provisional fastening.
• Air flow adjusts for heating and cooling
The unit has both an automatic setting
to the most suitable flap angle for heating
and cooling and an auto-swing 3m

Fixed fitting side Movable fitting side


mechanism for increasing air flow.
• Uses a power up drain pump
auto flap section
F2 F4 Drain up is possible up to 500 mm from the drain port.
20˚
300 mm or less
F1
2.7m

F2 500 mm or less
F3
40˚ F4 F5 310 mm
Cooling/(Fan) Heating/(Hi,M)

• Simple maintenance
The drain pan is equipped with site wiring and can be Maintenance of the drain pump is possible from two sides,
removed. The fan case has a split construction, and the fan from the left (piping side) and from the inside of the unit.
motor and the fan can be removed easily when the lower
case is removed.

Options
Timer remote controller Wireless remote controller Simplified remote controller Panel

RCS-TH80BG.WLB

PNR-S253GHANB (For 254 type)


PNR-S124GHB (For 74-184 type)
RCS-TM80BG (Transmitter, common part) RCS-BH80AG.WLB
RCS-KR1AGB

28 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
Model Name SPW-SR74GXH56B SPW-SR95GXH56B SPW-SR125GXH56B SPW-SR165GXH56B SPW-SR185GXH56B SPW-SR254GXH56B
Power source 220/230/240V, 1 phase - 50, 60Hz
kW 2.2 2.8 3.6 4.5 5.6 7.3
Cooling capacity
BTU/h 7,500 9,600 12,000 15,000 19,000 25,000
kW 2.5 3.2 4.2 5 6.3 8
Heating capacity
BTU/h 8,500 11,000 14,000 17,000 21,000 27,000
Cooling kW 0.095 0.088/0.092/0.097 0.088/0.093/0.099 0.103/0.097/0.091 0.091/0.097/0.103 0.135/0.145/0.154
Power input
Heating kW 0.062 0.055/0.060/0.064 0.057/0.061/0.066 0.070/0.065/0.060 0.060/0.065/0.070 0.100/0.109/0.117
Running Cooling A 0.45 0.44/0.45/0.45 0.44/0.45/0.45 0.45/0.45/0.45 0.45/0.45/0.45 0.64/0.65/0.66
amperes Heating A 0.3 0.28/0.29/0.30 0.28/0.29/0.30 0.30/0.29/0.29 0.29/0.29/0.30 0.46/0.48/0.49
Type Sirocco
Fan motor Airflow rate (H/M/L) m³/min 480/420/360 9.0/8.0/7.0 9.6/8.6/7.6 11.0/9.0/8.0 19/16/14
Output kW 0.03 0.05
Power sound level (H/M/L) db(A) 49/46/44 44/40/37 45/42/39 46/44/40 49/46/44
Pressure sound level (H/M/L) db(A) 30/27/24 33/29/26 34/31/28 35/33/29 38/35/33
Height mm 358 350 + <8>
Dimensions Width mm 840 <1060> 1140 <1360>
Depth mm 600 <680>
Liquid (flare) mm 6.35 9.52
Piping
Gas (flare) mm 12.7 15.88
connections
Drain piping VP-26 VP-25
Net weight kg 30 23 + <7> 30 + <9>
Rated conditions
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB Heating: Indoor air temperature 20˚C DB, outdoor air temperature 7˚C DB/6˚C WB.
The values in < > for external dimensions and net weight are the values for the optional ceiling panel. Data subject to change without notice.

Dimensional data

Dimensions: mm

Air intake 7 18 type 25 type 36 48 type


Air outlet A 840 1,140 1,630
B 440 590 835
Ceiling opening dimensions
C 480 630 875
Suspension fitting (notch: 12 mm)
D 1,020 1,320 1,810
Refrigerant piping (liquid pipes) E 1,080 1,360 1,850
Refrigerant piping (gas pipes) Ceiling
Drain connection VP25 (outer diameter ø 32) opening 1,020x640 1,320x640 1,810x640
Inspection lid dimensions
Inlet for option cord between power supply 450 Refrigerant
and unit piping ø6.35 ø9.52
(liquid pipes)
20

Drain pan, drain pump inspection lid


300

Refrigerant
Drain pump inspection lid piping ø12.7 ø15.88
(gas pipes)
Round flange (field supply) mounting part
(fresh air inlet ø 125) Duct connection
port (only on the x 1 pc. x 2 pc. x 3 pc.
Discharge duct (field supply) mounting part right side)
530
600
640
680

Ceiling panel and ceiling


(installation possible only on the right side) opening centre
Wireless remote controller (option) signal
receiver installation part

40 A
70 B C
20 D
(230)
E
110
80
30 70 70
290
350
310
220
195

165

102 (55) 23
60
(105)
75

680

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 29
ADR Type Semi-Concealed Cassette
• Compact Size
The compact design keeps unit Unit width
600 mm Unit depth
width and height to a minimum 560 mm

and delivers the industry’s Unit height


300 mm
smallest panel width, allowing
Panel depth
plenty of leeway when selecting 620 mm Panel width
760 mm
an installation location.
• Lightweight Construction
With a maximum unit weight of 8.5 kg, installation is
easy.
Weight of Products (kg)
Unit weight (including Panel)
Type A type Current model
7 Type 17+(2.5) 23+(3)
9 Type 17+(2.5) 23+(3)
12 Type 17+(2.5) 25+(3)
• The hanging height of the unit can be
easily adjusted
• Quiet Operation Adjustable covers are equipped on both
With operating noise reduced by up to 3 dB(A) over sides of the ceiling panel so that the hanging
existing models, the unit creates a quiet, comfortable room height of the unit can be adjusted even after
environment. the panel has been installed.
Operation
Type noise dB(A) A type Current modeloperation)
(High/Low Adjustable covers on
7 Type 33/29 34/40 both sides of panel
9 Type 33/29 34/40
12 Type 36/31 39/33

• Greater freedom for installation


300 mm
The drain height has been or less
raised by 63 mm over
existing models.

850 mm
or less

• Auto Flap and Auto Swing Functions


The Auto Flap function lets you set the air direction by
remote control, and the Auto Swing function delivers a
uniform amount of air to every part of the room.

Options
Timer remote controller Wireless remote controller Simplified remote controller Panel

RCS-TRP80BG.WLB

RCS-TM80BG (Transmitter, common part) RCS-BH80AG.WLB RCS-KR1AGB PNR-AD124GHB

30 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
Model Name SPW-ADR74GXH56B SPW-ADR94GXH56B SPW-ADR124GXH56B
Power source 220/230/240V, 1 phase - 50, 60 Hz
kW 2.2 2.8 3.6
Cooling capacity
BTU/h 7,500 9,600 12,000
kW 2.5 3.2 4.2
Heating capacity
BTU/h 8,500 11,000 14,000
Cooling kW 0.064/0.064/0.067
Power input
Heating kW 0.039/0.039/0.04
Cooling A 0.25/0.24/0.24
Running amperes
Heating A 0.17/0.17/0.17
Type Sirocco fan
Fan motor Airflow rate (H/M/L) m³/min 8/7/6.0 9/8/7.0
Output kW 0.02
Power sound level (H/M/L) db(A) 44/42/40 47/45/42
Pressure sound level (H/M/L) db(A) 33/31/29 36/34/31
Height mm 300 + <30>
Dimensions Width mm 600 <760>
Depth mm 560 <620>
Liquid (flare) mm 6.35
Piping connections Gas (flare) mm 12.7
Drain piping VP-25
Net weight kg 17 + <2.5>
Rated conditions
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB Heating: Indoor air temperature 20˚C DB, outdoor air temperature 7˚C DB/6˚C WB.
The values in < > for external dimensions and net weight are the values for the optional ceiling panel.
Data subject to change without notice.

Dimensional data

Dimensions: mm

Air intake grille


Air outlet
730 Refrigerant piping (liquid pipes) ø6.35 (flared)
(ceiling opening dimensions)
Refrigerant piping (gas pipes) ø12.7 (flared)
659
36 (suspension bolt pitch) 36 Drain connection VP25 (outer ø32)
Power supply inlet
(ceiling opening dimensions)
95

Suspension holes (4-12 x 30 slot)


(suspension bolt pitch)

Wireless remote controller receiver (opening)


Discharge duct (ø150)
590
400
560
620

Fresh air intake (ø100)


<Dimensions of Filter>
Panel centre (350 x 241 x 12) x 1 piece
95

600
760

560
170 255
285

138 45
300
240
205

170
96

63

30

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 31
LDR Type Semi-Concealed Slim Cassette
Our slim model, which is only 200mm
in depth, can aircondition spaces with
ceiling heights up to 4.2m.
• Top industrial capacity*1 to handle ceiling heights
up to 4.2m
Attained height/ceiling height based on fan motor speed setting (m)
Indoor unit type 9 type-18 type 25 type
*2 Fan speed setting Attained height Ceiling height Attained height Ceiling height
Factory setting 3.2 3.5 3.5 3.8
High-ceiling setting 3.9 4.2 3.9 4.2
Ceiling-mounted installation 2.4 2.7 2.4 2.7

*1 With one-direction type for high ceilings (current as of November 2004)


*2 For setting method, refer to the installation instructions that came with
the ceiling panel.

• Lightweight, compact and quiet • Smudge-free operation


With a full model redesign, all units are some of the lightest Setting the flap in the smudge-free position suppresses
in the industry.* And with all models having coordinated soiling around the air outlet that occurs in conventional
dimensions between the unit and the panel, multi-unit ceiling cassettes, so the ceiling stays clean at all times.
installations have a smart, attractive appearance.
Product (unit + panel) weight (kg) • The hanging height of the unit can be easily
Current model New model Reduction
adjusted.
9/12 type 26+(8)kg 21+(5.5)kg 22%
16/18 type 27+(8)kg 21+(5.5)kg 24% The unit can be easily adjusted by simply
25 type 30+(9)kg 22+(5.5)kg 29%
removing the panel side covers, without
Operating noise [dB(A)] (High/Low operation)
having to remove the ceiling panel.
Current model New model
9/12 type 43/33 36/33
16 type 44/35 36/34
18 type 44/35 38/34
25 type 46/36 45/36

• With 3 types of air-blow systems, the units can be Separation distance from nearest obstacle Drain height
used in various ways.
1,000 mm or more 200 mm
1 One-direction down-blow system 2 Two-direction ceilling-mounted or more 300 mm
system or less

850 mm
or less
Powerful one-direction “down-blow” “Down-blow” and “front-blow” systems 200 mm 200 mm
or more or more
system reaches the floor even from high are combined in a ceiling-mounted unit to 1,000 mm or more
ceilings (up to 4.2m). blow air over a wide area.
.

3 One-direction ceilling-mounted
system

This powerful ceiling-mounted “front-blow”


system efficiently air-conditions the space
in front of the unit.

Options
Timer remote controller Wireless remote controller Simplified remote controller Panel

RCS-TRP80BG.WLB

RCS-TM80BG (Transmitter, common part) RCS-BH80AG.WLB RCS-KR1AGB PNR-LD254GHAB

32 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
Model Name SPW-LDR94GXH56B SPW-LDR124GXH56B
SPW-LDR164GXH56B SPW-LDR184GXH56B SPW-LDR254GXH56B
Power source 220/230/240V, 1 phase - 50, 60 Hz
kW 2.8 3.6 4.5 5.6 7.3
Cooling capacity
BTU/h 9,600 12,000 15,000 19,000 25,000
kW 3.2 4.2 5.0 6.3 8.0
Heating capacity
BTU/h 11,000 14,000 17,000 21,000 27,000
Power Cooling kW 0.105/0.110/0.115 0.105/0.110/0.115 0.105/0.110/0.115 0.110/0.115/0.120 0.115/0.120/0.125
input Heating kW 0.075/0.080/0.085 0.075/0.080/0.085 0.075/0.080/0.085 0.080/0.085/0.090 0.085/0.090/0.095
Running Cooling A 0.50/0.50/0.51 0.50/0.50/0.51 0.50/0.50/0.51 0.53/0.53/0.54 0.55/0.55/0.56
amperes Heating A 0.36/0.37/0.38 0.36/0.37/0.38 0.36/0.37/0.38 0.38/0.39/0.40 0.40/0.41/0.42
Type Sirocco fan
Fan
Airflow rate (H/M/L) m³min 12/10/9.0 12/11/10.0 13/11.5/10 18/15/13
motor
Output kW 0.05
Power sound level (H/M/L) db(A) 47/45/44 47/46/45 49/47/45 56/51/47
Pressure sound level (H/M/L) db(A) 36/34/33 36/35/34 38/36/34 45/40/36
Height mm 200 + <20>
Dimensions Width mm 1,000 <1,230>
Depth mm 710 <800>
Liquid (flare) mm 6.35 9.52
Piping
Gas (flare) mm 12.7 15.88
connections
Drain piping VP-25
Net weight kg 21 + <5.5> 22 + <5.5>
Rated conditions
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB. Heating: Indoor air temperature 20˚C DB, outdoor air temperature 7˚C DB/6˚C WB.
The values in < > for external dimensions and net weight are the values for the optional ceiling panel. Data subject to change without notice.

Dimensional data

Dimensions: mm

Air intake grille


Air outlet
Refrigerant piping 9 18 ø 6.35 (flared)
(liquid pipes) 25 ø 9.52 (flared)
Refrigerant piping 9 18 ø 12.7 (flared)
(gas pipes) 25 ø 15.88 (flared)
20

1060 (suspension bolt pitch)


Drain connection VP25 (outer diameter ø 32)
(ceiling opening dimension)

Power supply entry


Discharge duct connection port
(Suspension bolt pitch)

9 5 (for descending ceiling)


255

60

Wireless remote control receiver (option)


710
475
760

4 Suspension mounting (4-12 x 30 slot)


216 80
220

Panel centre
Fresh air intake (ø 100)
3
135

25

20

1000
20 1190 (ceiling opening dimension) 20

230 7 61
154

41
94
112

200
92

20

2 6

8
800

1230

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 33
U Type Concealed Duct
• Comfortable environment achieved by dispersed
arrangement of discharge ports

• System examples
An inspection port (450 mm x 450 mm or more) is required
at the lower side of the indoor unit body.

Canvas Duct (field supply) Flange Canvas duct


Flexible duct
• Lowest noise levels in the industry
• The static pressure outside the unit can be Inspection port Intake grille
(450 x 450 mm or more)
increased
High-Performance Filter Long-life filter (field supply)
By using the booster cable, the static pressure outside the
unit can be increased. (Pa)
type 7-9-12 16-18 25 36 48
Inspection port
standard 49 40 50 79 78 (450 x 450 mm or more)
with booster cable
Distributor (field supply)
69 62 92 122 113
use

• More powerful drain pump Inspection port


(450 x 450 mm or more)
By adoption of a high-lift Up to 300mm
Up to
drain pump, the drain piping 500mm
• Unified body height of approx. 310 mm for
rise height can be increased 285mm
all models
to 785 mm from the lower
surface of the body. Even models with different capacities can be installed
smoothly in the ceiling.
• External electrical equipment box makes
maintenance easy

7-22˚C Air off temperature control as standard


• Able to control air off temperature
• Reduces cold drafts
• Accurate room temperature controls
Electrical equipment box
23°C

Options
Timer remote controller Wireless remote controller Simplified remote controller

RCS-TM80BG RCS-BH80AG.WLB RCS-KR1AGB


12°C Coil sensor

34 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
Model Name SPW-U075XH SPW-U 095XH SPW-U125XH SPW-U165XH SPW-U185XH SPW-U255XH SPW-U365XH SPW-U485XH SPW-U605XH
Power source 220/230/240V, 1 phase - 50, 60 Hz
kW 2.2 2.8 3.6 4.5 5.6 7.3 10.6 14.0 16.0
Cooling capacity
BTU/h 7,500 9,600 12,000 15,000 19,000 25,000 36,000 47,800 54,600
kW 2.5 3.2 4.2 5.0 6.3 8.0 11.4 16.0 18.0
Heating capacity
BTU/h 8,500 11,000 14,000 17,000 21,000 27,000 39,000 54,600 61,500
Cooling kW 0.094/0.100/0.106 0.109/0.102/0.096 0.096/0.102/0.109 0.180/0.195/0.210 0.312/0.327/0.342 0.308/0.325/0.341 0.341
Power input
Heating kW 0.082/0.088/0.094 0.097/0.090/0.084 0.084/0.090/0.097 0.168/0.183/0.198 0.300/0.315/0.330 0.296/0.313.0.329 0.329
Running Cooling A 0.45/0.46/0.47 0.46/0.45/0.44 0.44/0.45/0.46 0.83/0.86/0.89 1.44/1.45/1.46 1.42/1.43/1.44 1.44
amperes Heating A 0.40/0.41/0.42 0.41/0.40/0.39 0.39/0.40/0.41 0.78/0.81/0.84 1.39/1.40/1.41 1.36/1.37/1.38 1.38
Type Sirocco fan
Airflow rate (H/M/L) m³/min 10/8.5/7 12/10.5/9 18/15/13 30/26/21 33/30/25 19800/1800/1500
Fan motor
Output kW 0.05 0.07 0.14
External static pressure Pa 49(69) 40(62) 50(92) 79(122) 78(113) 78(113)
Power sound level (H/M/L) db(A) 40/37/33 41/39/36 45/41/38 49/44/42 51/48/44 51/48/44
Pressure sound level (H/M/L) db(A) (32)/29/26/22 (33)/30/28/25 (38)/34/30/27 (42)/38/33/31 (44)/40/37/33 40/37/33
Height mm 310
Dimensions Width mm 700 1000 1480
Depth mm 630
Liquid (flare) mm 6.35 9.52
Piping
Gas (flare) mm 12.7 15.88
connections
Drain piping VP-25 VP-26
Net weight kg 24 25 32 47
Rated conditions
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB. Heating: Indoor air temperature 20˚C DB, outdoor air temperature 7˚C DB/6˚C WB.
The values in ( ) for the external static pressure and operating sound are for use of booster cable. Data subject to change without notice.

Dimensional data
75-185 Type 255 Type
Flange external
Dimensions:
Flange external

260

dimension mm
dimension
260

24

962 19
24

662 19
Flange external dimension
Flange external dimension 310
31 180P x 5 = 900 31 16-ø 3.3 hole 310
31 200Px3=600 31 12-Ø3.3 hole 25 210 25 25 210 25
90 200 90 Inspection port 450 175
25

Inspection port 450 175 10


10

25
180 (field supply)
(field supply)
185

185
(Suspension bolt pitch)

(Suspension bolt pitch)


630
580

580

630
160

160
70 30

30
190

190
70
85

25
25

25

85

35
25

700 40 1000 40 35
70 130
780 (Suspension bolt pitch) (150) 1080 (Suspension bolt pitch) (150) 70 130
285 100
290 262 75 290 290 272 75
285

65 65
115
115

Inspection port 450


(field supply)

365-485 Type
Flange external

Refrigerant piping 9 18 ø 6.35 (flared)


dimension
260

(liquid pipes) 25 48 ø 9.52 (flared)


Refrigerant piping 9 18 ø 12.7 (flared)
1442
24

19
Flange external dimension
(gas pipes) 25 48 ø 15.88 (flared)
310 Drain piping connection port VP25 (outer ø 32)
31 230P x 6 =1380 31 18-Ø3.3 hole 25 210 25
230 175 200 flexible hose accessory
10

Inspection port 450


25

90
(field supply)
Lower drain port VP25 (outer ø 32)
185

(Suspension bolt pitch)

Suspension fitting (4-12 x 37 slot)


Power supply inlet (2-ø 30)
630
580

Outside air inlet (ø 150 irregular opening)


160
30

190

Discharge around duct adapter flange (3-ø 200)


70
25

25

40
Inspection lid
1480 35
85

1560 (150) 70 130 Electric equipment box


(Suspension bolt pitch)
285
335 335 335 310 75 Wind shielding panel
65 Inspection port 450
(field supply) Suction angle duct flange (field supply)
115

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 35
UR Type Concealed Duct
• The static pressure outside the unit can be
increased
NEW
By using the booster cable, the static pressure outside the
unit can be increased. (Pa)

type 7-9-12 16-18 25 36 46-60


standard 49 40 50 79 78
with booster cable use 69 62 92 122 113

• Drain pump with increased power • Unified body height of approx. 310 mm for all
Up to 300mm
models
By adoption of a high-lift
drain pump, the drain piping Up to
Even models with different capacities can be installed
rise height can be increased 500mm smoothly in the ceiling.
to 785 mm from the lower 285mm
• Lowest noise levels in the industry
surface of the body.
• Anti-mould washable filters included

• Easy maintenance by external installation of the


electric equipment box! 7-22˚C Air off temperature control as standard

• System example • Able to control air off temperature


• Reduces cold drafts
• Accurate room temperature controls

23°C

Body electric equipment box

An inspection port (450 mm x 450 mm or more) is


required at the lower side of the indoor unit body. 12°C Coil sensor

Rectangle duct Canvas duct

Inspection port Intake grille


(450 x 450 mm or more)

Options
Timer remote controller Wireless remote controller Simplified remote controller

RCS-BH80AG.WLB

RCS-TM80BG RCS-KR1AGB

36 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
SPW- SPW- SPW- SPW- SPW- SPW- SPW- SPW- SPW- SPW-
Model Name
UR74SXH56 UR94SXH56 UR124SXH56 UR164SXH56 UR184SXH56 UR254SXH56 UR304SXH56 UR364SXH56 UR484SXH56 UR604SXH56
Power source 220/230/240V, 1 phase - 50Hz
kW 2.2 2.8 3.6 4.5 5.6 7.3 9.0 10.6 14.0 16.0
Cooling capacity BTU/
7,500 9,600 12,000 15,000 19,000 25,000 30,000 36,000 47,800 54,600
h
kW 2.5 3.2 4.2 5.0 6.3 8.0 10.0 11.4 16.0 18.0
Heating capacity BTU/
8,500 11,000 14,000 17,000 21,000 27,000 34,000 39,000 54,600 61,400
h
Cooling kW 0.094/0.100/0.106 0.109/0.102/0.096 0.096/0.102/0.109 0.180/0.195/0.210 0.312/0.327/0.342 0.308/0.325/0.341 0.308/0.325/0.341
Power input
Heating kW 0.082/0.088/0.094 0.097/0.090/0.084 0.084/0.090/0.097 0.168/0.183/0.198 0.300/0.315/0.330 0.296/0.313/0.329 0.296/0.313/0.329
Running Cooling A 0.45/0.46/0.47 0.46/0.45/0.44 0.44/0.45/0.46 0.83/0.86/0.89 1.44/1.45/1.46 1.42/1.43/1.44 1.42/ 1.4/1.44
amperes Heating A 0.40/0.41/0.42 0.41/0.40/0.39 0.39/0.40/0.41 0.78/0.81/0.84 1.39/1.40/1.41 1.36/1.37/1.38 1.36/1.37/1.38
Type Sirocco fan
Airflow rate (H/M/L)
10/8.5/7 12/10.5/9 18/15/13 30/26/21 33/30/25 33/30/25
m³/min
Fan motor
Output kW 0.05 0.07 0.14 0.14
External static
49(69) 40(62) 50(92) 79(122) 78(113) 78(113)
pressure Pa
Power sound level (H/M/L) db(A) 40/37/33 41/39/36 45/41/38 49/44/42 51/48/44 51/48/44
Pressure sound level (H/M/L) db(A) (32)/29/26/22 (33)/30/28/25 (38)/34/30/27 (42)/38/33/31 (44)/40/37/33 (44)/40/37/33
Height mm 310
Dimensions Width mm 700 1000 1480
Depth mm 630
Liquid (flare) mm
6.35 (1/4) 9.52 (3/8)
Piping (inches)
connections Gas (flare) mm (inches) 12.7 (1/2) 15.88 (5/8)
Drain piping VP-25
Net weight kg 24 25 32 47
Rated conditions
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB. The values in ( ) for the external static pressure and operating sound are for use of booster cable.
Heating: Indoor air temperature 20˚C DB, outdoor air temperature 7˚C DB/6˚C WB. Data subject to change without notice.

Dimensional data
Filter(437x241)x2 Dimensions:
75 - 185 Filter(608x241)x1 255 - 305
mm

Flange external
dimension
Flange external
dimension

262
262

Suction side
310 310
Suction side
24

262 262
(Flange external dimension)
24

Flange external dimension 31 31 27 31 31


27 946
646 100Px2=200
23 23 100Px2=200
73 100Px5=500 73 100Px9=900
90 175 90 100 Inspection port 450 175
100
31

Inspection port 450 31


(field supply)
(field supply)
185

185

18-ø3.1 hole 26-ø3.1 hole


(Suspension bolt pitch)

(Suspension bolt pitch)


580

630

630
580
160

160

12-ø3.3 hole
70 30

70 30

20-ø3.3 hole
190

190
25
25

25

25

96 100Px3=300 96 35 41 100Px7=700 41 35
43 100 43 43 100 43
25

25

492 161 40 782(Flange external dimension) 171 40


186 Flange external dimension 70 130 186 75
70 130
75 1000
700 285 (150) 285
Flange external 780 1080
dimension (Suspension bolt pitch) (150) Flange external (Suspension bolt pitch)
65 dimension 65
115

115
186

186

Discharge side Discharge side

Filter(677x241)x2
365 - 605
Flange external
dimension
262

Suction side 310


262 Piping connection (Liquid) ø 6.35 Flared
(Flange external dimension) 27 31 31
1426 Piping connection (Gas) ø 12.7 Flared
100Px2=200
63 100Px13=1300 63
90 100 175 Drain piping connection port VP25 (outer ø 32)
31

Inspection port 450


(field supply) 200 flexible hose accessory
185

Lower drain port VP25 (outer ø 32)


(Suspension bolt pitch)

26-ø3.1 hole

Suspension fitting (4-12 x 37 slot)


630
580

Power supply inlet (2- ø 30)


160

28-ø3.3 hole
70 30

Outside air inlet (ø 150 irregular opening)


190
25

Discharge angle duct adapter flange


25

43 100 43 81 100Px11=1100 81 35
25

186 1262(Flange external dimension) 182 40 70 130 Inspection lid


Flange external 1480 75 285 Electric equipment box
dimension
1560 (Suspension bolt pitch) (150)
Wind shielding panel
65
Suction angle duct adapter flange
115

Discharge angle duct adapter flange


186

Discharge side

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 37
DR Type Concealed Duct
• High static pressure, low-noise design
25-48 Type 76-96 Type
Embedded ceiling type with high static pressure and
excellent low operating sound features. As the discharge
port also can be set freely, it is suitable for office space.
• RAP valve kit
Except for use as a single system, two Rap valve kits are
required for each unit for the type 76 and the type 96.

Single system • “Short duct” use of the DR Type


When the DR Type is used with a short duct (duct length of
4 to 5 m, external static pressure around 49 Pa (5 mm Aq),
the air volume and the operating sound may be too high
and an air volume damper or similar should be installed. The
external static pressure for this model is 147 Pa (15 mm Aq)
Double system or more. In such a case, we recommend that you consider
an alternative indoor unit.

ATK-RX160AGB ATK-RX160AGB

Mixed system

ATK-RX160AGB

Distribution joint kit (APR-RP160AG/APR-P160 for type 76)


(APR-RP680AG/APR-P680 for type 96)

Options
Timer remote controller Wireless remote controller Simplified remote controller Rap valve kit
The types 76 and 96 require
two rap valve kits for each unit.

RCS-TM80BG RCS-BH80AG.WLB RCS-KR1AGB ATK-RX160AGB

38 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
Model Name SPW-DR254GXH56B SPW-DR364GXH56B SPW-DR484GXH56B SPW-DR764GXH56B SPW-DR964GXH56B
Power source 220/230/240V, 1 phase - 50, 60 Hz
kW 7.3 10.6 14.0 22.4 28.0
Cooling capacity
BTU/h 25,000 36,000 47,800 76,400 95,500
kW 8 11.4 16.0 25.0 31.5
Heating capacity
BTU/h 27,000 39,000 54,600 85,300 107,500
Power Cooling kW 0.480/0.505/0.530 0.520/0.545/0.570 0.600/0.660/0.710 0.870/0.900/0.930 1.270/1.330/1.390
input Heating kW 0.480/0.505/0.530 0.520/0.545/0.570 0.600/0.660/0.710 0.870/0.900/0.930 1.270/1.330/1.390
Running Cooling A 2.29/2.30/2.31 2.46/2.46/2.47 2.80/2.90/3.00 4.05/4.06/4.07 6.04/6.06/6.07
amperes Heating A 2.29/2.30/2.31 2.46/2.46/2.47 2.80/2.90/3.00 4.05/4.06/4.07 6.04/6.06/6.07
Type Sirocco fan
Airflow rate (H/M/L) m³/min 23/22/21 30/28/25 36/35/33 56/53.1/49.6 72/70/66
Fan motor
Output kW 0.2 0.35 0.2*2 0.4*2
External static pressure Pa 186 176 167 176 216
Power sound level (H/M/L) db(A) 55/54/53 56/55/53 58/57/55 59/58/57 62/61/60
Pressure sound level (H/M/L) db(A) 44/43/42 45/44/42 47/46/44 48/47/46 51/50/49
Height mm 420 450 467
Dimensions Width mm 1065 1428
Depth mm 620 1230
Liquid (flare) mm 9.52
Piping connections Gas (flare) mm 15.88 19.05 22.22
Drain piping VP-25
Net weight kg 47 50 54 110 120
Rated conditions
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB. Heating: Indoor air temperature 20˚C DB , outdoor air temperature 7˚C DB/6˚C WB.
Data subject to change without notice.

Dimensional data
940
25-48 Type 793 Dimensions: mm
7 x 100 =700
55 20
22-ø3.2 holes 40 90
26, 36 type 48 type (entire circumference) 60 Refrigerant piping (liquid pipes)
48
A 420 450
Refrigerant piping (gas pipes)
128

B 395 425
Power supply inlet
130

C 68 98
(Suspension

Drain 25A or VP25


bolt pitch)
290

Electric equipment box Duct connection for suction


80

Duct connection for discharge


4-ø20 (for suspension bolts)
46
16-ø3.2 holes
(entire circumference)
4x100=400
500
15 980 15
(Suspension bolt pitch)
620
50 500 70 1010
10 10 35 940 35
100
55
25

55
50

(274)
100 100

81
100 100
310

300

55
A

C
B
55

23

Drain pan
479

467

76-96 Type
55

Refrigerant piping (liquid pipes), ø9.52


Refrigerant piping (gas pipes)
97

42
View in direction of arrow X
Type 224: ø19.05, type 280: ø22.22
X
800 or more
479 (service space) 1310 28-ø3.5holes Power supply outlet
467
23
300
178 100 100
41
50 106
1070 (entirecir umfer nce) (ø25 grommet, rubber)
44 10 x 100 pitch = 1000
51
45 40

Power supply outlet (spare) (ø30 knock-out)


209

(Suspension bolt pitch)

180 Drain port 25A, male thread


344

Duct connection for suction


(service space)

1100
1170
1222
1230

1138
1100 or more

Duct connection for discharge


4-37 x 12 holes
(for suspension bolts)

. 200
100 100 60
71

9 x 100 pitch = 900 423


320 43 964 26-ø3.5 holes
Inspection port 600 67 67 (entire circumference)
435 1200 (Suspension bolt pitch)
1310

364 (236) 364


1334
1428

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 39
US Type Concealed Duct
• Ultra-slim profile: 200 mm for all models NEW
• Anti-mould washable filters included

200mm

• DC Fan Motor reduces power consumption • Easy maintenance and service by external
• Ideal for hotel application with very narrow electrical box
false ceilings • Three-speed centrifugal fan through wired
• Extremely quiet: 26 dB(A) at low speed or wireless remote controller
(Class 7, 9, 12)

Options
Timer remote controller Wireless remote controller Simplified remote controller

RCS-TM80BG RCS-BH80AG.WLB RCS-KR1AGB

40 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
Model Name SPW -US075XH SPW-US095XH SPW-US125XH SPW-US165XH SPW-US185XH
Power source 220/230/240V, 1 phase - 50, 60Hz
kW 2.2 2.8 3.6 4.5 5.6
Cooling capacity
BTU/h 7,500 9,600 12,000 15,000 19,000
kW 2.5 3.2 4.2 5.0 6.3
Heating capacity
BTU/h 8,500 11,000 14,000 17,000 21,000
Cooling kW 0.022/0.022/0.022 0.027/0.027/0.027 0.028/0.028/0.028 0.037/0.037/0.037 0.32/0.32/0.32
Power input
Heating kW 0.022/0.022/0.022 0.027/0.027/0.027 0.028/0.028/0.028 0.037/0.037/0.037 0.32/0.32/0.32
Cooling A 0.22/0.22/0.22 0.23/0.23/0.23 0.25/0.25/0.25 0.32/0.32/0.32 0.41/0.41/0.41
Running amperes
Heating A 0.22/0.22/0.22 0.23/0.23/0.23 0.25/0.25/0.25 0.32/0.32/0.32 0.41/0.41/0.41
Type Sirocco fan
Airflow rate (H/M/L) m³/min 8/7/6 8.5 / 7.5 / 6.5 9/8/7 10.5/9.5/8 12.5/11.5/10
Fan motor
Output kW 0.05
External static pressure Pa 10--30 15 - 30 15 - 40
Power sound level (H/M/L) db(A) 42/41/39 43/42/40 44/42/40 45/43/41 46/44/42
Pressure sound level (H/M/L) db(A) 31/30/28 32/31/29 33/31/29 34/32/30 35/33/31
Height mm 200
Dimensions Width mm 750
Depth mm 640
Liquid (flare) mm (inches) 6.35 (1/4)
Piping
Gas (flare) mm (inches) 12.7 (1/2)
connections
Drain piping VP-21
Net weight kg 21
Rated conditions
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB. Heating: Indoor air temperature 20˚C DB, outdoor air temperature 7˚C DB/6˚C WB.
Data subject to change without notice.

Dimensional data
Dimensions:
mm
(Air intake)
155

704 (Air intake)


200
149

Electric
549 (Suspension bolt pitch)

equipment box
640

Lower drain port

Drain port
50

30

750 40

824 (Suspension bolt pitch)

874
(Air outlet)
139

690 (Air outlet) 65


27

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 41
FUR Type Floor / Ceiling Slim Concealed Duct
• Ultra-slim profile: 190 mm for all models

190mm

• Suitable for horizontal and vertical installation • Ideal for hotel applications or projects with
very shallow ceilings
Options • Extremely quiet: 29 dB(A) at low speed
Timer remote controller Wireless remote controller Simplified remote controller
(Class 7, 9, 12)
• Anti-mould washable filters included
• Easy maintenance and service through air
suction port
RCS-BH80AG.WLB RCS-KR1AGB
• Three-speed centrifugal fan through wired
RCS-TM80BG
or wireless remote controller

42 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
Model Name SPW-FUR74EXH56B SPW-FUR94EXH56B SPW-FUR124EXH56B SPW-FUR164EXH56B SPW-FUR184EXH56B SPW-FUR224EXH56B
Power source 220/230/240V, 1 phase - 50Hz
kW 2.2 2.8 3.6 4.5 5.6 6.4
Cooling capacity
BTU/h 7,500 9,600 12,000 15,000 19,000 22,000
kW 2.5 3.2 4.2 5.0 6.3 7.0
Heating capacity
BTU/h 8,500 11,000 14,000 17,000 21,000 24,000
Cooling kW 0.037/0.037/0.037 0.065/0.065/0.065 0.088/0.088/0.088
Power input
Heating kW 0.037/0.037/0.037 0.065/0.065/0.065 0.088/0.088/0.088
Running Cooling A 0.17/0.17/0.17 0.29/0.29/0.29 0.41/0.41/0.41
amperes Heating A 0.17/0.17/0.17 0.29/0.29/0.29 0.41/0.41/0.41
Type Sirocco fan
Airflow rate (H/M/L) m³/min 7.8/6.3/5.6 10.3/9/7.5 11.3/10/8.7
Fan motor
Output kW 0.04 0.07 0.09
External static pressure Pa 7.5 10
Power sound level (H/M/L) db(A) 48/41/37 56/52/44 60/56/51
Pressure sound level (H/M/L) db(A) 37/30/26 45/41/33 49/45/40
Height mm 190
Dimensions Width mm 890
Depth mm 614
Liquid (flare) mm (inches) 6.35 (1/4)
Piping
Gas (flare) mm (inches) 12.7 (1/2)
connections
Drain piping VP-26
Net weight kg 25
Rated conditions
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB. Heating: Indoor air temperature 20˚C DB, outdoor air temperature 7˚C DB/6˚C WB.
Data subject to change without notice.

Dimensional data

ø7
5 33 4
ø3
Dimensions: mm
86 70

190 752 58

44.5 116.5 752 69


890
29 38.5 692.5 159 58
29

44
165

221
476

498

140
265

828
585

40
274.5

30.5 833 26.5

870

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 43
UMR Type Concealed Duct
• Integrated condensate pump for condensate
discharge
• Fresh air intake
• Reduced dimensions
• Anti-mould and anti-bacterial washable filters
• High static option

Options
Timer remote controller Wireless remote controller Simplified remote controller

RCS-TM80BG RCS-BH80AG.WLB RCS-KR1AGB

44 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
Model Name SPW-UMR74EXH56B SPW-UMR94EXH56B SPW-UMR124EXH56B SPW-UMR164EXH56B SPW-UMR184EXH56B SPW-UMR224EXH56B
Power source 220/230/240V, 1 phase - 50 Hz
kW 2.2 2.8 3.6 4.5 5.6 6.4
Cooling capacity
BTU/h 7,500 9,600 12,000 15,000 19,000 22,000
kW 2.5 3.2 4.2 5.0 6.3 7.0
Heating capacity
BTU/h 8,500 11,000 14,000 17,000 21,000 24,000
Cooling kW 0.11/0.11/0.11 0.138/0.138/0.138 0.136/0.136/0.136
Power input
Heating kW 0.11/0.11/0.11 0.138/0.138/0.138 0.136/0.136/0.136
Running Cooling A 0.45/0.45/0.45 0.60/0.60/0.60 0.57/0.57/0.57
amperes Heating A 0.45/0.45/0.45 0.60/0.60/0.60 0.57/0.57/0.57
Type Sirocco fan
Airflow rate (H/M/L) m³/min 10/8.5/7.3 14.6/10/6.7 16.7/11.7/10
Fan motor
Output kW 0.11 0.14
External static pressure Pa 49 (70)
Power sound level (H/M/L) db(A) 54/52/49 54/47/42 57/49/46
Pressure sound level (H/M/L) db(A) 43/41/38 43/36/31 46/38/35
Height mm 266
Dimensions Width mm 852 1,058
Depth mm 572
Liquid (flare) mm (inches) 6.35 (1/4)
Piping
Gas (flare) mm (inches) 12.7 (1/2)
connections
Drain piping VP-18
Net weight kg 30 35
Rated conditions
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB. Heating: Indoor air temperature 20˚C DB, outdoor air temperature 7˚C DB/6˚C WB.
The values in ( ) for the external static pressure and operating sound are for use of booster cable. Data subject to change without notice.

Dimensional data

74-124 Type Top view Air conveyor (Optional part) Dimensions:


0 mm
3
ø1
250

ø120

228.5 228.5 ø3.1


435
572
636

801 90˚
200

25 25
900 I. D. 18mm
Condensate
drain piping
ø200 ø200
Refrigerant
782 70 782 tubing joint
narrow tube
207

207
266

101

Refrigerant tubing joint


wide tube
Front view Rear view Refrigerant tubing side

164-224 Type Top view Air conveyor (Optional part)


30
ø1
ø120
250

290 290 ø3.1


962 90˚
435
572
636

200

25 25
I. D. 18mm
1106 Condensate
ø200 ø200 ø200 drain piping
943 70 943 Refrigerant
tubing joint
narrow tube
207

207
101

Refrigerant tubing joint


wide tube
Front view Rear view Refrigerant tubing side

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 45
T Type Ceiling Mounted Units
• Newly developed DC fan motor with
variable speed
Significant reduction of the power input by using a Sirocco
fan with a new design, a heat exchanger, etc.

kW

0.088 0.21
• Realisation of the most suitable air flow for
0.032 0.074 heating and for cooling
P r ev i o us P re v i o u s
m od el 4 series model 4 series
18 type 36 type
F1
• Weight reduction for all models
All models are lightweight and the installation also has been F2 60˚
improved. Unit height and depth have been unified for all F3
models, and functional design allows attractive installation.
Heating: F1 to F3
kg F4
40 Cooling: F1 to F3
F5
30
Automatic setting of the air flow angle according to heating
20 or cooling. In case of swing operation, the flap moves
23 21 38 33 automatically and seamlessly in the range from F1 to F5,
10 independent of the mode.
• Further comfort improvement
Previous Previous
model 4 series model 4 series The wide air discharge opening widens the air flow to the left
12, 16, 18 type 36, 48 type and the right, so that a comfortable temperature is obtained
in the entire room. The unpleasant feeling caused when
the air flow directly hits the human body is prevented by
• New design with lower operating sound the “Draft prevention position”, which changes the swing
The operating sound levels have been reduced by max. 2 dB width, so that the degree of comfort is increased.
(A) through using heat exchanger fins and Sirocco fans with
a new design and reduced wind path resistance.
Model 25 type 48 type
Operation noise (H/L) 38/33dB(A) 43/37dB(A)

4m

Correspondence to ceiling height of


up to 4m

Options
Timer remote controller Wireless remote controller Simplified remote controller

RCS-TRP80BG.WLB

RCS-TM80BG (Transmitter, common part) RCS-BH80AG.WLB RCS-KR1AGB

46 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
Model Name SPW-T125XH SPW-T165XH SPW-T185XH SPW-T225XH SPW-T365XH SPW-T485XH
Power source 220/230/240V, 1 phase - 50, 60 Hz
kW 3.6 4.5 5.6 7.3 10.6 14.0
Cooling capacity
BTU/h 12,000 15,000 19,000 25,000 36,000 47,800
kW 4.2 5.0 6.3 8.0 11.4 16.0
Heating capacity
BTU/h 14,000 17,000 21,000 27,000 39,000 54,600
Power Cooling kW 0.028/0.029/0.029 0.039/0.029/0.028 0.031/0.032/0.032 0.043/0.043/0.044 0.073/0.074/0.075 0.085/0.086/0.088
input Heating kW 0.028/0.029/0.029 0.029/0.029/0.028 0.031/0.032/0.032 0.042/0.042/0.043 0.072/0.073/0.074 0.084/0.085/0.086
Running Cooling A 0.26/0.24/0.23 0.26/0.24/0.23 0.28/0.26/0.24 0.38/0.35/0.33 0.62/0.57/0.53 0.69/0.63/0.60
amperes Heating A 0.26/0.24/0.23 0.26/0.24/0.23 0.28/0.26/0.25 0.38/0.35/0.34 0.62/0.57/0.55 0.69/0.63/0.62
Type Sirocco fan
Fan motor Airflow rate (H/M/L) m³/min 12/10/9.0 13/11/9.0 18.5/15/14 27.5/23/20 30/26/22
Output kW 0.03 0.04 0.08
Power sound level (H/M/L) db(A) 46/43/41 47/44/41 49/47/44 52/49/46 54/51/48
Pressure sound level (H/M/L) db(A) 35/32/30 36/33/30 38/36/33 41/38/35 43/40/37
Height mm 210
Dimensions Width mm 910 1180 1595
Depth mm 680
Liquid (flare) mm z6.35 9.52
Piping
Gas (flare) mm 12.7 15.88
connections
Drain piping VP-20
Net weight kg 21 25 33
Rated conditions
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB. Heating: Indoor air temperature 20˚C DB, outdoor air temperature 7˚C DB/6˚C WB.
Data subject to change without notice.

Dimensional data

Drain port VP20 (inner ø26, hose accessory) Dimensions: mm


Drain for left piping
Upper piping outlet port (knock-out hole)
Right piping outlet port (knock-out hole)
123 216
Drain left piping outlet port (knock-out hole)
53

70

50

Power supply entry port (knock-out hole ø40)


Remote controller wiring inlet port
170

Wireless remote control receiver mounting part


130

12~18 25 36~48
Suspension

type type type


bolt pitch
320

A (body) 910 1180 1595 110 76


B (suspension bolt pitch) 855 1125 1540
Refrigerant piping
(gas pipes) ø12.7 ø15.88 ø15.88
Refrigerant piping ø6.35 ø9.52 ø9.52
(liquid pipes)
B 27.5
Suspension bolt pitch 680
217
105
171
210

251 Air outlet 90 161


A
500 or more 250 or more 250 or more
(Service space)
Front (Service space)
Air intake

97
84 75
146

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 47
FTR Type Floor/Ceiling Mounted Units
• Three-speed centrifugal fan
• Anti-mould and anti-bacterial washable filters
• Low operating sound
• Horizontal flap swinging or set on a fixed
position
• Shallow design

Options
Timer remote controller Wireless remote controller Simplified remote controller

RCS-TH80BG.WLB
RCS-BH80AG.WLB

RCS-TM80BG (Transmitter, common part) RCS-KR1AGB

48 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
Model Name SPW-FTR74EXH56B SPW-FTR94EXH56B SPW-FTR124EXH56B SPW-FTR164EXH56B SPW-FTR184EXH56B SPW-FTR224EXH56B
Power source 220/230/240V, 1 phase-50 Hz
kW 2.2 2.8 3.6 4.5 5.6 6.4
Cooling capacity
BTU/h 7,500 9,600 12,000 15,000 19,000 22,000
kW 2.5 3.2 4.2 5.0 6.3 7.0
Heating capacity
BTU/h 8,500 11,000 14,000 17,000 21,000 24,000
Cooling kW 0.65/0.65/0.65 0.88/0.88/0.88
Power input
Heating kW 0.65/0.65/0.65 0.88/0.88/0.88
Running Cooling A 0.29/0.29/0.29 0.41/0.41/0.41
amperes Heating A 0.29/0.29/0.29 0.41/0.41/0.41
Type Sirocco fan
Fan motor Airflow rate (H/M/L) m³/min 10.5/9/7.5 12/10.8/9.7 15/13.5/12
Output kW 0.07 0.09
Power sound level (H/M/L) db(A) 60/54/49 62/58/54 63/60/57
Pressure sound level (H/M/L) db(A) 49/43/38 51/47/43 52/49/46
Height mm 680
Dimensions Width mm 900
Depth mm 190
Liquid (flare) mm (inches) 6.35 (1/4)
Piping
Gas (flare) mm (inches) 12.7 (1/2)
connections
Drain piping VP-26
Net weight kg 23.5
Rated conditions
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB. Heating: Indoor air temperature 20˚C DB, outdoor air temperature 7˚C DB/6˚C WB.
Data subject to change without notice.

Dimensional data

Wide tube Dimensions: mm

Narrow tube
900 190
Drain hose ø26
680
41

41

74 74
86

86

74 Center of tubing hole 74


ø75 (4 places)

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 49
KR Type Wall Mounted Units
• More variations
With addition of the new types 7, 16 and 25 to the existing
types 9, 12, and 18, the line-up now consists of six types
of unit.
• Closed discharge port
When the unit is turned off, the flap closes completely to
prevent dust and dirt entering the unit and thereby keeping
it clean.
• Lighter and smaller units make the installation • Attractive colour and rounded design, adoption
easy of horizontal stripes
The unit height has been reduced by approx. 20%, and is an The compact and attractive design means that the unit can
extremely slim design. easily be installed even in a small space.
• Washable front panel

NEW
The indoor unit’s front panel can be easily removed and
285 mm washed for trouble-free cleaning.
(Current 360mm)

NEW
995 mm
(Current 1000mm)

• Quiet design
One of the quietest units in the industry making these
models suitable for hotels and hospitals.
dB(A)
50 • Piping outlet in three directions
45 Piping is possible in the three directions: the rear, right, and
left, making the installation easier.
40
35 • Anti-mould filters are standard
38 36 40 36 46 39

Previous Previous Previous Important


model 4 series model 4 series model 4 series
9 type 12 type 18 type When an indoor unit is installed in a quiet place such as a hotel meeting
room, bedroom or VIP room, the Electronic Expansion Valve may be
noisey during cooling and heating operation.
In order to prevent the noise, an optional External Electronic Expansion
Valve Kit (ATK-SVRK160AGB) can be installed at narrow tube 5 to 15m
away from the indoor unit.

Options
Timer remote controller Wireless remote controller Simplified remote controller

RCS-TM80BG RCS-SH1BGB RCS-BH80AG.WLB RCS-KR1AGB

50 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
Model Name SPW-KR74GXH56B SPW-KR94GXH56B SPW-KR124GXH56B SPW-KR164GXH56B SPW-KR184GXH56B SPW-KR254GXH56B
Power source 220/230/240V, 1 phase - 50, 60 Hz
kW 2.2 2.8 3.6 4.5 5.6 7.3
Cooling capacity
BTU/h 7,500 9,600 12,000 15,000 19,000 25,000
kW 2.5 3.2 4.2 5.0 6.3 8.0
Heating capacity
BTU/h 8,500 11,000 14,000 17,000 21,000 27,000
Cooling kW 0.031/0.033/0.035 0.049/0.052/0.055
Power input
Heating kW 0.031/0.033/0.035 0.049/0.052/0.055
Running Cooling A 0.15/0.15/0.15 0.23/0.23/0.24
amperes Heating A 0.15/0.15/0.15 0.23/0.23/0.24
Type Cross flow fan
Fan motor Airflow rate (H/M/L) m³/min 10/8/6.0 12/10/8.0 16/14/10
Output kW 0.011 0.015 0.023
Power sound level (H/M/L) db(A) 47/43/39 53/49/46
Pressure sound level (H/M/L) db(A) 36/32/28 42/35/38
Height mm 285 330
Dimensions Width mm 995 1140
Depth mm 203 228
Liquid (flare) mm 6.35 9.52
Piping
Gas (flare) mm 12.7 15.88
connections
Drain piping VP-13
Net weight kg 14 21
Rated conditions
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB. Heating: Indoor air temperature 20˚C DB, outdoor air temperature 7˚C DB/6˚C WB.
Data subject to change without notice.

Dimensional data

74-184 Type 254 Type Dimensions: mm

Liquid pipe ø6.35 (Length: Approx. 470 mm) Liquid pipe ø9.52 (Length: Approx. 570 mm)
Gas pipe ø12.7 (Length: Approx. 400 mm) Gas pipe ø15.88 (Length: Approx. 500 mm)
Drain hose VP13 (Length: Approx. 450 mm) Drain hose VP13 (Length: Approx. 450 mm)
Installation fitting Installation fitting
Fitting fixing hole (ø5 hole or 5 x 13 slot) Fitting fixing hole (ø5 hole or 5 x 13 slot)
Installation fitting piping, wiring inlet (ø80) Installation fitting piping, wiring inlet (ø80)
3

228
200

1140
995
285

330

Z Z

Receiver Receiver

53.5 151 68 450 68 151 53.5 45 105 229 71 240 210 120 70 50
64 90 90 47 30 30 34
40 30 60 30 40 90 75 60 75 90
19.5

20
17
17
55

55 55
(4x27.5P)

(5x27.5P)
110

137.5

48
46

147.5 147.5 174 135


ø8

ø 80

ø 80

0
0

ø8

View in direction of arrow Z View in direction of arrow Z

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 51
K Type Wall Mounted Units
• Closed discharge port NEW
When the unit is turned off, the flap closes completely
to prevent entry of dust into the unit and to keep the
equipment clean.
• Lighter and smaller units make the installation
easy
The width has been removed by 17% and the units
are lighter.

NEW • Washable front panel


255mm
(Current 285mm) The indoor unit’s front panel can be easily removed and
washed for trouble-free cleaning.

NEW
82 mm
(Current 995mm)

• Quiet operation
These units are among the quietest in the industry, making
them ideal for hotels and hospitals.
dB(A)
50
• Piping outlet in three directions
45
Piping outlet is possible in the three directions of rear, right,
40
and left, making the installation work easier.
35 38 36 40 36 46 39
• Anti-mould filters are standard
Previous Previous Previous
model 4 series model 4 series model 4 series
Important
9 type 12 type 18 type
When an indoor unit is installed in a quiet place such as a hotel meeting
• Smooth and hardwaring design room, bedroom or VIP room, the Electronic Expansion Valve may be
noisey during cooling and heating operation.
The smooth cover means these units match most modern
In order to prevent the noise, an optional External Electronic Expansion
interiors. Their compact size enables them to blend in, even Valve Kit (ATK-SVRK160AGB) can be installed at narrow tube 5 to 15m
in small spaces. away from the indoor unit.

Options
Timer remote controller Wireless remote controller Simplified remote controller

RCS-TM80BG RCS-SH1BGB RCS-BH80AG.WLB RCS-KR1AGB

52 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
Indoor Unit SPW-K075XH SPW-K095XH SPW-K125XH
Power Source 220/230/240V, 1 phase - 50, 60Hz
kW 2.20 2.80 3.60
Cooling capacity
BTU/h 7,500 9,600 12,000
kW 2.50 3.20 4.20
Heating capacity
BTU/h 8,500 11,000 14,000
Cooling kW 0.018/0.019/0.019 0.021/0.022/0.023
Power input
Heating kW 0.019/0.019/0.020 0.022/0.023/0.023
Cooling A 0.16/0.16/0.16 0.19/0.19/0.20
Running amperes
Heating A 0.17/0.17/0.18 0.20/0.20/0.20
Power sound level (H/M/L) dB(A) 46/43/39 48/44/40
Sound pressure Level (H/M/L) dB(A) 35/32/28 37/33/29
Type Sirroco fan
Fan motor Airflow rate (H/M/L) m3/min 9/7.5/6 10/8.5/6.5
Output kW 0.047
Air circulation (H/M/L) m3/hr 540/450/360 540/450/360 600/510/390
Dimensions (HxWxD) mm 285x825x217 285x825x217 285x825x217
Liquid (flare) mm (inches) 6.35 (1/4)
Piping connections Gas (flare) mm (inches) 12.7 (1/2)
Drain piping VP-13
Net weight kg 10
Rated conditions Data subject to change without notice.
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB.
Heating: Indoor air temperature 20˚C DB, outdoor air temperature 7˚C DB/6˚C WB.

Dimensional data

Dimensions: mm

Refrigerant tubing (liquid tube) ø6.35 (flared)


5 815 5 Refrigerant tubing (gas tube) ø12.7 (flared)
FILTER SIZE
Drain hose VP13 (outer dia. ø18)
(316 x 311 x 2) x 2pcs.
Rear panel (PL BACK)
Rear panel fixing holes (5ø holes or 5 x 13 oval holes)
Piping & coiring holes (ø65)

187 450 187


825
45
285

56

87

87
7

47 179 179
Gas tube
217 (1)
Liquid tube Drain hose ÿ18
825
187.5 450 187.5
24.5
45

122.5 92.5
815 70
285

65 65
40

15cm
40

360 308

5cm 5cm

Front view

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 53
FMR Type Concealed FR Type Floor Standing
Floor Standing Units Units

• Perimeter air conditioning with stylish interior • Effective perimeter air conditioning with simple
design installation is possible
Compact and effective air conditioning can be achieved by The perimeter zone is handled effectively, with indoor units
embedding it in room perimeters. The units are particularly of a multi-system.
suitable for hotel applications

• Large window space can be used


The compact units make it ideal for installlation in a large
window space (unit height: 615 mm). Particularly suitable
for perimeter air conditioning in hotels etc.

A wired remote controller


can be installed in the body.

Options
Timer remote controller Wireless remote controller Simplified remote controller

RCS-TM80BG RCS-BH80AG.WLB RCS-KR1AGB

54 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
Concealed Floor Standing type
Model Name SPW-FMR74GXH56B SPW-FMR94GXH56B SPW-FMR124GXH56B SPW-FMR164GXH56B SPW-FMR184GXH56B SPW-FMR254GXH56B
Power source 220/230/240 1 phase - 50, 60 Hz
kW 2.2 2.8 3.6 4.5 5.6 7.1
Cooling capacity
BTU/h 7,500 9,800 12,000 15,000 19,000 24,000
kW 2.5 3.2 4.2 5.0 6.3 8.0
Heating capacity
BTU/h 8,500 11,000 14,000 17,000 21,000 27,000
Cooling kW 0.051/0.056/0.061 0.079/0.085/0.091 0.136/0.126/0.116 0.116/0.126/0.136 0.150/0.160/0.170
Power input
Heating kW 0.036/0.040/0.045 0.064/0.070/0.076 0.101/0.091/0.079 0.079/0.091/0.101 0.110/0.120/0.130
Running Cooling A 0.24/0.25/0.26 0.37/0.38/0.39 0.58/0.56/0.54 0.54/0.56/0.58 0.70/0.72/0.73
amperes Heating A 0.17/0.18/0.19 0.30/0.31/0.32 0.43/0.41/0.37 0.37/0.41/0.43 0.52/0.54/0.56
Type Sirocco fan
Fan motor Airflow rate (H/M/L) m³/min 7/6/5.0 9/7/6.0 12/9/8.0 15/13/11 17/14/12
Output kW 0.01 0.02 0.02 0.03 0.06
Power sound level (H/M/L) db(A) 44/41/39 50/46/40 49/46/42 49/46/42 52/49/46
Pressure sound level (H/M/L) db(A) 33/30/28 39/35/29 38/35/31 39/36/31 41/38/35
Dimensions (HxWxD) mm 616x904x229 616x1219x229
Liquid (flare) mm 6.35 9.52
Piping
Gas (flare) mm 12.7 15.88
connections
Drain piping VP-20
Net weight kg 21 28
Floor Standing type
Model Name SPW - FR74GXH56B SPW - FR94GXH56B SPW - FR124GXH56B SPW - FR164GXH56B SPW - FR184GXH56B SPW - FR254GXH56B
Power source 220/230/240 1 phase - 50, 60 Hz
kW 2.2 2.8 3.6 4.5 5.6 7.1
Cooling capacity
BTU/h 7,500 9,800 12,000 15,000 19,000 24,000
kW 2.5 3.2 4.2 5.0 6.3 8.0
Heating capacity
BTU/h 8,500 11,000 14,000 17,000 21,000 27,000
Cooling 0.051/0.056/0.061 kW 0.079/0.085/0.091 0.136/0.126/0.116 0.116/0.126/0.136 0.150/0.160/0.170
Power input
Heating 0.036/0.040/0.045 kW 0.064/0.070/0.076 0.101/0.091/0.079 0.079/0.091/0.101 0.110/0.120/0.130
Running Cooling 0.24/0.25/0.26 A 0.37/0.38/0.39 0.58/0.56/0.54 0.54/0.56/0.58 0.70/0.72/0.73
amperes Heating 0.17/0.18/0.19 A 0.30/0.31/0.32 0.43/0.41/0.37 0.37/0.41/0.43 0.52/0.54/0.56
Type Sirocco fan
Fan motor Airflow rate (H/M/L) m³/min 7/6/5.0 15/13/11 9/7/6.0
17/14/12 12/9/8.0
Output kW 0.01 0.03 0.02
0.06 0.02
Power sound level (H/M/L) db(A) 44/41/39 50/47/42 50/46/40
52/49/46 49/46/42
Pressure sound level (H/M/L) db(A) 33/30/28 39/36/31 39/35/29
41/38/35 38/35/31
Dimensions (HxWxD) mm 615x1065x230 615x1380x230
Liquid (flare) mm 6.35 9.52
Piping
Gas (flare) mm 12.7 15.88
connections
Drain piping VP-20
Net weight kg 29 39
Rated conditions. Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB. Heating: Indoor air temperature 20˚C DB, outdoor air temperature 7˚C DB/6˚C WB.
Data subject to change without notice.
Dimensional data
FMR Type Concealed Floor Standing FR Type Floor Standing type
4 x ø12 holes (for floor fixing)
Indoor Liquid Gas 4 x ø12 holes (for floor fixing) Indoor Liquid Gas Power supply outlet
unit A B C D E F pipes pipes unit A B C pipes pipes Air filter
Electric equipment box
74 124 Power supply outlet 74 124 Refrigerant piping (liquid pipes)
type 904 692 672 665 500 86 type 1,065 665 632
Air filter Refrigerant piping (gas pipes)
164 164 Level adjustment bolt
type 797 782 770 700 41 ø6.35 ø12.7 Discharge duct connection flange type 770 737 ø6.35 ø12.7
Drain outlet VP20 (with vinyl hose)
184 1219 Refrigerant connection 184 1380
type outlet (liquid pipes) type Refrigerant piping connection port
1007 1002 980 900 51 980 947 (bottom or rear)
254 ø9.52 ø15.88 Refrigerant connection 254 ø9.52 ø15.88
type type Operation switch (remote controller
outlet (gas pipes) RCS-SH80AG) mounting part
Drain filter Electric equipment box
Drain pan Accessory copper pipe for gas pipe connection
100 56

2 9
(60.5)
170

Level adjustment bolt 161 26


15
57

Drain outlet VP20 (with vinyl hose)


177

184.5 D
100

230

1
109

A 229
125 61
166 B 46 (inner dimension) 156
155 C
60.5

C(inner dimension) 66 B 1 138


F E (hole pitch = 100) F 5 20 85 20 A 67
10

20

20
10

10
5
7
374

615

4
616

6
539

539
402
402

11
8
255
260

70 110
70
10

2
147

3 9
6
40
10 147 107 (110)
4 2 3 7
30 B 60 30 205 8 50 Knock-out hole 205
11

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 55
GU Type Total Heat Exchanger
• A powerful fresh air intake which matches the
necessary temperature and humidity required
in medium-sized commercial spaces
• Integration of heat recovery ventilation and
DX coil technology for optimum air
temperature control
• Highly efficient temperature and humidity control
• Compact and quiet design
Installation example

• High static pressure available


Humidification DX coil Heat exchanger
(optional)
• Standard spigots ensure simple connection
to ductwork
Exhaust air
Supply air
• Easy-to-clean filter prevents mould or bacteria
from occurring
• Easy service and maintenance through the
Return air Fresh air
external installation of the electrical box
• Humidifier function available as option

Options
Timer remote controller Wireless remote controller Simplified remote controller • 3 Way: Solenoid valve kit is required for each unit.
• 2 Way: RAP kit is required for each unit.

RCS-TM80BG RCS-BH80AG.WLB RCS-KR1AGB

56 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Indoor unit specifications
Model Name SPW-GU055XH SPW-GU075XH SPW-GU105XH
Air circulation (H) m³/h 500 750 1,000
Power source 220/230/240V, 1 phase - 50 Hz
Fresh air load Cooling kW 5.3 (1.7)*¹ 8.2 (2.6)*¹ 10.7 (3.4)*¹
treatment capacity Heating kW 6.5 (2.3)*¹ 9.8 (3.5)*¹ 12.6 (4.6)*¹
Enthalpy Exchange Cooling % 59
Efficiency Heating % 67
Temp exchange efficiency 75
kW 3.6 5.6 7.3
Equivalent cooling capacity
BTU/h 12,000 19,000 25,000
Cooling kW 0.532/0.532/0.532 0.737/0.737/0.737 0.798/0.798/0.798
Power input
Heating kW 0.532/0.532/0.532 0.737/0.737/0.737 0.798/0.798/0.798
Cooling A 2.4/2.4/2.4 3.2/3.2/3.2 3.5/3.5/3.5
Running amperes
Heating A 2.4/2.4/2.4 3.2/3.2/3.2 3.5/3.5/3.5
Type Sirocco fan
External static pressure-return air Pa 183 (170) 221 (188)
135 (88)
Fan motor
External static pressure-supply air Pa 205 (182) 264 (218)
176 (137)
Output kW 0.28 (4P)x2 0.35 (4P)x2
Power sound level (C/H) db(A) 57 (Cooling), 58 (Heating) 58 (Cooling), 59 (Heating) 59 (Cooling), 60 (Heating)
Pressure sound level (C/H) db(A) 46 (Cooling), 47 (Heating) 47 (Cooling), 48 (Heating) 48 (Cooling), 49 (Heating)
Height mm 425 450
Dimensions Width mm 1785 1903
Depth mm 1000 1120 1220
Liquid (flare) mm (inches) 6.35 (1/4)
Piping connections Gas (flare) mm (inches) 12.7 (1/2)
Drain piping VP-25
Connection duct diameter mm 250 300
Net weight kg 155 180 200
Rated conditions
Cooling: Indoor air temperature 27˚C DB/19˚C WB, outdoor air temperature 35˚C DB. Heating: Indoor air temperature 20˚C DB outdoor air temperature 7˚C DB/6˚C WB.
The values in ( ) for the external static pressure and operating sound are for use of booster cable. *1: Heat recovery capacity by heat exchanger. Data subject to change without notice.

Dimensional data
Dimensions: mm
(Service space)

H
700

150

G
G
55

F
F
RA

OA

RA OA
(Suspension bolt pitch)

I
E
E

2-ø
A
C

2-ø I
SA

EA

SA EA
380

380
55
(Service space)

150
150
800

Refrigerant piping (liquid pipes)


200 Refrigerant piping (gas pipes)
25 B 25
Suspension bolt pitch (4-15 x 52 holes: M12 bolts)
Electric equipment box
D
(Suspension bolt pitch) Power supply inlet
314 30 Communication line inlet
Drain VP25A male thread
70

Humidifier (Option)
100 or more

Total heat exchanger


Long life Filter
J

Highly efficient filter (Option)


35

183
Air filter

Model A B C D E F G H I J
GU055 1,000 1,785 890 1,835 426 194 205 425 250 175
GU075 1,120 1,903 1,010 1,953 526 214 225 450 250 200
GU105 1,220 1,903 1,110 1,953 611 229 225 450 300 200

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 57
Water Terminals

FW-X FW-K FW-FT


Ceiling Cassette Wall Mounted Unit Floor/Ceiling Unit

• Wide model range for 2-pipe and • X, K and FT also available with • 3-way valve kit features precise
4-pipe design system (X type size infrared remote controller temperature control in the room
031 and 051) • Quiet operation ensures maxi- • Cleanable air filter included as
• Suitable for any commercial mum comfort standard
buildings and even for hotels and
residential applications
FW-X Type Ceiling Cassette
Performance FW-X031EH5 FW-X051EH5 FW-X061EH5 FW-X081EH5 FW-X101EH5
Main power supply V/Ph/Hz 230/1+N/50
Total cooling capacity Max/Med/Min* kW 2.60/2.35/2.15 4.70/4.10/3.60 6.00/5.00/4.20 7.60/6.00/5.00 9.92/8.09/6.23
Sensible cooling capacity Max/Med/Min* kW 2.31/2.09/1.91 3.72/3.21/2.80 4.70/3.80/3.20 6.00/4.70/3.80 7.60/6.22/4.62
Heating capacity Max/Med/Min* kW 3.49/3.11/2.83 5.70/4.85/4.35 7.70/6.40/5.40 9.00/7.70/6.40 13.00/10.60/8.16
Air flow Max/Med/Min* m³/h 520/400/600 750/630/530 1300/1060/850 1470/1300/1060 2300/1700/1200
Absorbed power Max/Med/Min* W 60/50/40 90/70/50 120/90/80 150/120/90 180/130/110
Water flow Max/Med/Min* l/h 430/395/360 790/690/600 1030/860/720 1300/1030/860 1700/1400/1070
Sound power level (Lw) Max/Med/Min* dB(A) 46/44/41 56/51/48 51/44/40 55/51/44 57/49/43
Sound pressure level (Lp) Max/Med/Min* dB(A) 37/35/32 47/42/39 42/35/31 46/42/35 48/40/34
Water connections inch 1/2"female 3/4" female
Dimensions & Weights
body mm 296x575x575 296x575x575 310x760x760 310x760x1050 310x760x1050
Dimensions (H/W/D)
grille panel mm 41x730x730 41x730x730 30x860x860 30x860x1150 30x860x1150
Weight (with grille panel) kg 21 23 28 32 36
(*) Fan speed

FW-K Type Wall Mounted Units


Performance FW-K011EH5 FW-K021EH5 FW-K031EH5 FW-K041EH5
Main power supply V/Ph/Hz 230/1+N/50
Total cooling capacity Max/Min* kW 1.24/0.80 1.67/0.96 2.90/1.57 3.50/2.35
Sensible cooling capacity Max/Min* kW 0.94/0.58 1.30/0.74 2.20/1.20 2.70/1.80
Heating capacity Max/Min* kW 1.72/1.11 2.38/1.49 3.90/2.45 5.40/3.60
Air flow Max/Min* m³/h 220/150 270/180 585/360 720/470
Absorbed power Max/Min* W 24/19 20/16 75/57 86/57
Water flow Max/Min* l/h 215/135 290/165 500/274 615/415
Sound power level (Lw) Max/Min* dB(A) 44/37 45/35 50/46 55/48
Sound pressure level (Lp) Max/Min* dB(A) 35/28 36/26 41/37 46/39
Water connections inch 1/2" female
Dimensions & Weights
Dimensions (H/W/D) mm 270x805x177 270x805x177 285x995x206 285x995x206
Weight kg 8 8 12 12
(*) Fan speed
FW-FT Type Floor/Ceiling Units
Performance FW-FT021EH5 FW-FT031EH5 FW-FT04EH5
Main power supply V/Ph/Hz 230/1+N/50
Total cooling capacity Max/Med/Min* kW 2.10/1.20/0.90 3.19/2.10/0.90 3.90/3.10/1.65
Sensible cooling capacity Max/Med/Min* kW 1.50/1.00/0.70 2.47/1.50/0.70 3.00/2.50/1.25
Heating capacity Max/Med/Min* kW 3.10/2.00/1.60 4.07/3.00/1.60 5.00/4.40/2.10
Air flow Max/Med/Min* m³/h 430/300/210 520/430/210 675/570/327
Absorbed power Max/Med/Min* W 40/30/26 46/37/26 70/53/35
Water flow Max/Med/Min* l/h 360/206/160 550/360/160 670/530/285
Sound power level (Lw) Max/Med/Min* dB(A) 48/43/35 50/45/35 54/51/40
Sound pressure level (Lp) Max/Med/Min* dB(A) 40/35/27 42/37/27 46/43/32
Water connections (inches) 1/2" female
Dimensions & Weights
Dimensions (H/W/D) mm 680x900x190
Weight kg 23.5
(*) Fan speed
Nominal conditions
Cooling Heating Sound pressure level
Entering air temperature 27˚C (db) 19˚C (wb) 20˚C At 2m distance in closed environment
Entering water temperature 7˚C 50˚C (at same water flow as for cooling) 100m³ volume with 0.5 sec reverberation time
Leaving water temperature 12˚C 60˚C (maximum water entering temperature)

58
Fan-Coil Units

S-VM S-HM S-VH


Floor Standing Unit Ceiling Unit Concealed Unit

• Very wide and complete range: • Cleanable air filter included • Electronic controllers available
centrifugal or Cross Flow Fan, 2- • Easy to install and very simple to for unit mounting and remote
pipe or 4-pipe design maintain installation ensure precise control
• Stylish units can match any kind of the room temperature
of interior decor • Large choice of accessories,
either separately supplied or
Cross Flow S-VMT/HMT/VHT factory mounted
Performance 151 251 351
Main power supply V/Ph/Hz 230/1+N/50
Total cooling capacity Max/Med/Min* kW 1.40/1.20/1.04 2.40/2.08/1.70 3.40/2.80/2.30
Sensible cooling capacity Max/Med/Min* kW 1.17/0.92/0.78 2.02/1.62/1.31 2.87/2.30/1.89
Heating capacity (standard coil) Max/Med/Min* kW 2.08/1.66/1.46 3.10/2.70/2.30 4.30/3.60/2.90
Heating capacity (add. 1 row coil) Max/Med/Min* kW 1.65/1.35/1.20 2.60/2.25/1.95 3.50/3.00/2.45
Air flow Max/Med/Min* m³/h 300/240/190 450/360/290 600/480/380
Absorbed power Max/Med/Min* W 40/30/27 50/45/37 65/50/42
Water flow cooling Max/Med/Min* litres/h 240/210/180 240/210/180 585/485/400
Water pressure drop heating Max/Med/Min* kPa 4.0/3.2/2.4 14.7/11.8/8.5 13.2/10.0/7.0
Water flow heating Max/Med/Min* litres/h 145/120/105 225/195/170 300/260/210
Water pressure drop heating Max/Med/Min* kPa 2.5/1.9/1.5 8.9/6.9/5.4 2.9/2.3/1.7
Sound power level (Lw) Max/Med/Min* dB(A) 48/40/34 47/42/36 48/43/39
Sound pressure level (Lp) Max/Med/Min* dB(A) 39/31/25 38/33/27 39/34/30
Dimensions & Weights
Dimensions (H/W/D) S-VMT mm 530x775x225 530x990x225 530x1205x225
Dimensions (H/W/D) S-HMT mm 225x775x530 225x990x530 225x1205x530
Dimensions (H/W/D) S-VHT mm 530x567x218 530x782x218 530x1007x218
Weight S-VMT kg 18 26 29
Weight S-HMT kg 18 26 29
Weight S-VHT kg 17 25 28
(*) Fan speed

Centrifugal S-VMC/HMC/VHC
Performance 151 251 351 401 501 601 701
Main power supply V/Ph/Hz 230/1+N/50
Total cooling capacity Max/Med/Min* kW 1.50/1.30/1.10 2.50/2.15/1.80 3.50/2.90/2.47 4.00/3.44/2.90 4.80/4.15/3.60 5.95/5.08/4.30 6.60/5.50/4.60
Sensible cooling capacity Max/Med/Min* kW 1.25/1.00/0.83 2.10/1.68/1.39 2.95/2.35/1.95 3.35/2.68/2.21 4.05/3.24/2.67 5.00/4.00/3.30 5.50/4.40/3.64
Heating capacity (standard coil) Max/Med/Min* kW 2.06/1.70/1.40 3.30/2.70/2.30 4.45/3.70/3.00 5.20/4.35/3.65 6.60/5.50/4.70 8.00/6.70/5.50 8.80/7.30/6.00
Heating capacity (add. 1 row coil) Max/Med/Min* kW 1.75/1.35/1.25 2.70/2.35/2.05 3.60/3.10/2.65 3.69/3.31/2.65 5.30/4.50/3.90 5.50/5.00/4.20 5.50/5.00/4.20
Air flow Max/Med/Min* m³/h 300/240/190 450/360/290 600/480/380 750/600/480 1000/800/650 1200/950/750 1200/950/750
Absorbed power Max/Med/Min* W 50/37/25 60/50/45 87/80/60 95/80/65 130/85/65 180/145/120 180/145/120
Water flow cooling Max/Med/Min* litres/h 260/225/190 430/370/310 600/500/425 690/590/500 825/715/620 1020/875/740 1135/950/795
Water pressure drop heating Max/Med/Min* kPa 5.7/4.3/3.2 14.1/10.6/7.9 12.3/9.2/7.0 17.9/13.5/10.0 27.8/20.5/16.8 21.1/16.0/12.0 4.5/3.3/2.4
Water flow heating Max/Med/Min* litres/h 150/120/110 235/205/180 310/270/230 315/285/250 460/390/340 475/435/365 475/435/365
Water pressure drop heating Max/Med/Min* kPa 3.7/2.8/2.2 8.6/6.7/5.3 2.8/2.3/1.7 3.7/2,9/2.3 7.3/5.7/4.3 6.9/5.8/4.3 6.9/5.8/4.3
Sound power level (Lw) Max/Med/Min* dB(A) 51/45/40 54/50/42 51/42/37 54/48/45 59/54/48 60/55/48 60/55/48
Sound pressure level (Lp) Max/Med/Min* dB(A) 42/36/31 45/41/33 42/33/28 45/39/36 50/45/39 51/46/39 51/46/39
Dimensions & Weights
Dimensions (H/W/D) S-VMC mm 530x775x225 530x990x225 530x1205x225 530x1205x225 530x1420x225 530x1420x255 530x1420x255
Dimensions (H/W/D) S-HMC mm 225x775x530 225x990x530 225x1205x530 225x1205x530 225x1420x530 255x1420x530 255x1420x530
Dimensions (H/W/D) S-VHC mm 530x510x218 530x725x218 530x940x218 530x940x218 530x1155x218 530x1155x248 530x1155x248
Weight kg 17 24 27 28 33 43 48
Weight kg 17 24 27 28 33 43 48
Weight S-VHC kg 16 23 26 27 31 40 45
(*) Fan speed

Nominal conditions
Cooling Heating additional 1-row coil Heating standard coil Sound pressure level
Entering air temperature 27˚C(db) 19˚C (wb) 20˚C 20˚C At 2m distance in closed environment
Entering water temperature 7˚C 70˚C 50˚C (at same water flow as for cooling) 100m³ volume with 0.5 sec reverberation time
Leaving water temperature 12˚C 60˚C

59
Individual Control Systems Overview
A wide variety of control options to meet the needs of different customers.
Operation system Individual control systems Timer operation

Normal Operation from Quick and Daily and


Needs
operation each seat easy operation weekly programme

NEW

External appearance

Wireless remote
controller
Timer wired RCS-SH80BG.WLB Simplified remote controller Schedule timer
Type, model name remote controller RCS-TH80BG.WLB
RCS-KR1AGB SHA-TM64AGB
RCS-TM80BG RCS-BH80AG.WLB
RCS-TRP80BG.WLB
RCS-SH1BGB

Number of indoor units which can be 64 groups,


1 group, 8 units 1 group, 8 units 1 group, 8 units
controlled max. 64 units

Power supply from the system


controller.
Up to 2 units can be Up to 2 units can be Up to 2 units can be When there is no system controller,
Use limitations
connected per group. connected per group. connected per group. connection is possible to the T10
terminal of an
indoor unit.

Connectable
4 series indoor unit 4 series indoor unit 4 series indoor unit 4 series indoor unit
indoor unit

Function

ON/OFF • • • -

Mode setting • • • -

Fan speed setting • • • -

Temperature setting • *1
• *1
• *1 -

Air flow direction • • • -

Permit/Prohibit switching - - - -

Weekly programme • - - •
*1 Setting is not possible when a remote control unit is present. (Use the remote control for setting.)

60
Centralised Control Systems Overview

Centralised control systems

Simplified charge ratio for each tenant


Operation with various function Only ON/OFF operation from
from central station central station Personal computer
Touch screen panel
(field supply)

External appearance

Web
application

System controller ON/OFF controller Intelligent controller Communication adaptor


Type, model name
SHA-KC64AGB SHA-KC16KAGB SHA-KT256BG SHA-KA128AGB

Number of indoor units which can be 64 groups, 16 groups, 64 units x 4 systems, 2 systems,
controlled max. 64 units max. 64 units max. 256 units max. 128 units

Up to 10 units, can be connected to


one system. Up to 8 units (4 main units + 4 sub
units) can be connected to one A communication adaptor (SHA-
Main unit/sub unit (1 main unit + 1 system. Maximum 500 indoor units (128 per
Use limitations KA128AGB) must be installed for
sub unit) connection is possible. communication adaptor)
Use without remote controller is three or more systems.
Use without remote controller is impossible.
possible.

Connectable
4 series indoor unit 4 series indoor unit 4 series indoor unit 4 series indoor unit
indoor unit

Function

ON/OFF • • • •
Mode setting • - • •
Fan speed setting • - • •
Temperature setting • - • •
Air flow direction • *1 - • *1
• *1

Permit/Prohibit switching • • • •
Weekly programme • - • •

61
Individual Control Systems
Remote controller (Wired remote controller/Wireless remote controller)
Control contents Part name, model No. Quantity
Timer remote controller
Standard Control
RCS-TM80BG
• Control of the various operations of the indoor unit
System example by wired or wireless controller.
Wireless remote controller
RCS-SH80BG.WLB
• Cooling or heating mode of the outdoor unit is decided by the 1 unit each
RCS-TH80BG.WLB
first priority of the remote controller.
RCS-BH80AG.WLB
• Switching between remote controller sensor and body
RCS-TRP80BG.WLB
sensor is possible.
RCS-SH1BGB
(1) Group control
• Batch remote control on all indoor units.
• Operation of all indoor cells in the same mode.
Timer remote controller
• Up to 8 units can be connected. 1 unit
RCS-TM80BG
• The sensor is the body sensor, and thermostat ON/OFF
setting in regard to the temperature set by the remote
controller is possible for each indoor unit.
Main or sub
Timer remote controller
(2) Main/sub remote control RCS-TM80BG
Remote controller Main Sub Main Sub
• Max 2 remote controllers per indoor unit. Wireless remote controller
(Main remote controller can be connected) RCS-SH80BG.WLB As required
Standard control (2) Main/sub (1) Group control
remote control • The button pressed last has priority. RCS-TH80BG.WLB
• Timer setting is possible even with the sub remote controller. RCS-BH80AG.WLB
RCS-TRP80BG.WLB
RCS-SH1BGB

Timer remote controller (RCS-TM80BG)


• Basic remote controller ON/OFF

NEW • Operation mode changeover (Cooling, Heating, Dry, Auto, Fan)


• Temperature setting (Cooling/Dry: 18-30 deg Heating: 16-30 deg)
• Air volume adjustment (HH, H, LL, Auto).
• Air flow direction adjustment.
• Time Function
• 24 hours real time clock.
• Day of the week indicator.
• Weekly Programme Function
A maximum of 6 action can be programmed for each day.
• Outing Function
• This function can prevent the room temperature from dropping or rising when
the occupants are out for a long time.
• Sleeping Function
• This function controls the room temperature for comfortable sleeping.
• Max. 8 indoor units can be controlled from one remote controller.
(Dimensions: H 120 x W 120 x D 16 mm)
• Remote control by main remote controller and sub controller is possible.
Max. 2 remote controllers (main remote controller and sub controller) can be
installed for one indoor unit.

Wireless remote controller


• Ventilation independent operation is possible.
When commercial ventilation fans or heat-exchange ventilation
fans have been installed, they can be operated with this remote
control (interlocked operation with the indoor unit
or independent ventilation ON/OFF).
• Easy installation for the 4-way cassette type simply by
replacing the corner part.
• Timer setting is up to 72 hours (in easy 30 minutes).
• Remote control by main remote controller and sub
type X type T, L, A type K
controller is possible.
RCS-SH80BG.WLB RCS-TRP80BG.WLB RCS-SH1BGB
• Max. 2 remote controllers (main remote controller and sub
controller) can be installed for one indoor unit.
• Do not perform group control for 3 Series indoor unit and
4 Series indoor unit together.
• When RCS-BH80BG.WLB is used, wireless control becomes
possible for all indoor units.
• When a separate receiver is set up in a different room, control
from that room also becomes possible.
• Automatic operation by means of the emergency operation
button is possible even when the remote controller has been
lost or the batteries have been exhausted.
• In addition, there are other functions like temperature
type S, SL, XMR, FTR, FUR, UR For all indoor units setting, operation switching, wind direction/fan speed
RCS-TH80BG.WLB RCS-BH80AG.WLB setting, etc.

62 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Simplified remote controller (RCS-KR1AGB)
• A remote controller with simple functions and basic operation.
• Suitable for open rooms or hotels where detailed functions are not required.
• ON/OFF, operation mode switching, temperature setting, wind velocity
switching, wind direction setting, alarm display, and remote controller
self-diagnosis can be performed.
• Batch group control for up to 8 indoor units.
• Remote control by main remote controller and sub controller is possible with
a simplified remote controller or a wired remote controller (up to two units).

(Dimensions: H 120 x W 70 x D 16 mm)

Schedule timer (RCS-TM64AGB)


* As operation mode and temperature settings are not possible with the schedule
timer, it must be used together with a remote controller, a system controller, an
intelligent controller, etc. Also, as it does not have an address setting function,
the control function of a system controller etc. must be used for address setting.
• Up to 64 groups (max. 64 indoor units) can be controlled divided into
8 timer groups.
• Six programme operations (Operation/Stop/Local permission/Local
prohibition) per day can be set in a programme for one week.
• Only operation or stop, remote controller local permission or remote controller
local prohibition, and their respective combinations are possible. (Operation +
local permission, stop + local prohibition, only local permission, etc.)
• Local prohibition and the combination of the three items of temperature
(Dimensions: H 120 x W 120 x D 16 mm) setting, mode change, and operation/stop can be set at the time of installation.
• A function for pausing the timer in case of national holidays has been
* The Power supply for the schedule timer is taken from added, and timer operation also can be stopped for a long time.
one of the following.
1 Control circuit board (T10) of a nearby indoor unit • By setting holidays or operation stop within one week, the timer can be
(power supply wiring length: Within 200 m from the paused just for that week.
indoor unit) • All timer settings can be stopped with the timer “ON/OFF effective” button.
2 System controller (Power supply wiring length: Within (Return to timer operation is made by pressing the button again.)
100 m from the indoor unit) Connection example 2 (power supply from the central controller)
* When the power supply for the schedule timer is taken
from the control circuit board of the indoor unit, that
indoor unit cannot be used with other control devices
using the T10 terminal. Indoor/outdoor
operation wire
System controller Schedule timer
Connection example 1(Power supply from the indoor unit)

Zone 1
1 2 8 9 10 16
Centralised addresses
1 to 16
Timer group 1: Centralised addresses 1 to 8 Timer group 2: Centralised addresses 9 to 16

Zone 2
17 18 24 25 26 32
Centralised addresses
17 to 32

Timer group 3: Centralised addresses 17 to 24 Timer group 4: Centralised addresses 25 to 32

Zone 3
33 34 40 41 42 48
Centralised addresses
33 to 48

Timer group 5: Centralised addresses 33 to 40 Timer group 6: Centralised addresses 41 to 48

Remote controller Schedule timer

Zone 4
49 50 56 57 58 64
Centralised addresses
49 to 64

Timer group 7: Centralised addresses 49 to 56 Timer group 8: Centralised addresses 57 to 64

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 63
Convenient System Control
System controller (SHA-KC64AGB)
• Individual control is possible for max. 64 groups, 64 indoor units.
Control of 64 indoor units divided into 4 zones. (One zone can have up
to 16 groups, and one group can have up to 8 units.)
Control is possible for ON/OFF, operation mode, fan speed, air flow
direction (only when used without a remote controller), operation
monitoring, alarm monitoring, ventilation, remote controller local
operation prohibition, etc.

Individual All operations are possible also from the remote


controller. However, the contents will be changed to
the contents of the controller operated last.
Central: 1 The remote controller cannot be used for ON/OFF.
(Dimensions: H 160 x W 160 x D 21 + 69 (embedding dimension) mm) (All other operations are possible from the remote
* Power supply AC 220 to 240 V controller.)
* I/O part Remote input (effective voltage: DC 24 V): Central: 2 The remote controller cannot be used for ON/OFF,
All ON/All OF mode change, and temperature setting. (All other
Remote output (voltage-free contact): operations are possible from the remote controller.)
All ON/All OFF Central: 3 The remote controller cannot be used for mode
(external Power supply within DC 30 V) change or temperature setting change. (All other
* Total wiring length 1km operations are possible from the remote controller.)
Central: 4 The remote controller cannot be used for operation
mode change. (All other operations are possible from
the remote controller.)

• A control mode corresponding to the use condition can be • Joint use with a remote controller, an intelligent controller, a
selected from 10 patterns. schedule timer, etc. is possible.
A Operation mode: Central control mode or remote control (The maximum number of connectable system controllers is 10,
mode can be selected. including other central controllers on the same circuit.)
Central control mode: The system controller is used as centralised (In case of joint use with a wireless remote controller, there are
control device. (Setting from a remote controller can be prohibited by limitations for the control mode. Please use only with “Individual” and
prohibiting local operation from the system controller.) “Central 1”.)
• Control of systems without a remote controller and of main/sub
Remote control mode: The system controller is used as a remote
systems (a total of up to two units) is possible.
controller. (Setting from the system controller can be prohibited by
prohibiting local operation from another central control unit.)
B Controlled unit number mode: All mode or zone 1, 2, 3, 4 mode
can be selected.
All mode: All, zone, or group unit can be selected.
Zone 1, 2, 3, 4 mode: Setting is possible only for the indoor units of Connection example
zone 1, 2, 3, or 4.

A Operation mode
Central control mode Remote control mode
All central control System controller
All mode All remote control
*Example Individual
Zone 1 central control (Control mode example 2: Central control for zone 1) remote controller
Zone 1 mode Zone 1 remote control
*Example 2
Zone 2 remote control
Zone 2 mode Zone 2 central control
*Example 3
B Controlled unit
number mode

Zone 3 central control


Zone 3 mode Zone 3 remote control System controller
*Example 4
Group control
Zone 4 remote control
Zone 4 mode Zone 4 central control (Control mode example 3: Remote control for zone 2)
*Example 5

System controller

(Control mode example 4: Central control for zone 3) Individual remote controller

System controller

System without a remote controller Control of a group


without remote controller
(Control mode example 5: Remote control for zone 4)

System controller

(Control mode example 1:


All central control)

64 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Intelligent controller (SHA-KT256BG)
• Max. 256 indoor units (4 systems x 64 units) can be controlled. In
case of three or more systems, a communication adapter SHA-
KA128AG must be installed on the outside.
• Operation is possible as batch, in zone units, in tenant units and in
Touch group units.
panel • ON/OFF, operation mode setting, temperature setting, for speed
setting, air flow direction setting (when used without a remote
controller), and remote controller local operation prohibition
(prohibition 1, 2, 3, 4) can be done.
• A system without a remote controller is possible. Joint use with a
remote controller or a system controller is also possible.
• Use of a schedule timer and holiday setting also can be done.
• Proportional distribution of the air-conditioning energy is possible.
*In case of joint use with a wireless remote control system, there are limitations for
(Dimensions: H 240 x W 280 x D 20 + 130 mm) the control mode. Please use only with “Permission” and “Prohibition 1”.
* Power supply AC 100 to 240 V (50 Hz), 20 W
(separate power supply)
* I/O part Remote input (voltage-free contact):
All on/off
Remote output (voltage-free contact):
All ON, All alarm
(external power supply within DC 30 V) *Display sample
* Total wiring length 1 km for each system
* Only for embedding in the panel

• Limitation contents for prohibited operation


Prohibition means limitation of the operation contents from the remote Web
controller. It is also possible to change application
the prohibition items.

Linked system No. 1


Limitation contents Intelligent
controller
Individual There is no limitation for the operation of the remote SHA-KT256BG
controller. However, the contents will be changed to
the contents of the controller operated last. (Last-
pressed priority.) System signal x 4
Linked system No. 2
Prohibition: 1 The remote controller cannot be used for ON/OFF.
(All other operations are possible from the remote
controller.) RS 485
(Polarity shield wire)
Prohibition: 2 The remote controller cannot be used for ON/OFF,
operation mode change and temperature setting. Linked system No. 3
(All other operations are possible from the remote
controller.)
Prohibition: 3 The remote controller cannot be used for operation
mode change and temperature setting. (All other Communication
operations are possible from the remote controller.) adapter Linked system No. 4
SHA-KA128AGB
Prohibition: 4 The remote controller cannot be used for operation
mode change. (All other operations are possible
from the remote controller.) System signal x 4

Note: Avoid joint use of the AMY system and the intelligent
Max. 4 links can be connected for the indoor/outdoor
controller on the same indoor/outdoor operation line. operation line = Max. 64 indoor units x 4 (256 units)
Max. 30 outdoor units x 4 (120 units)

For more information on how to connect please see installation manual.

Communication adaptor (SHA-KA128AGB)


• Required to connect three or more linked wiring systems
(indoor/outdoor operation lines) to the intelligent controller.
• Also required for connection of the AMY software.
* For more detail, please take a look at page 61.
• Two linked wiring systems can be connected to one SHA-
KA128AG, but max. 4 systems can be connected for the entire
intelligent controllers.
*As this is not a splash-proof design, it must be installed indoors
or in the control panel etc.

(Dimensions: H 260 x W 200 x D 68 mm)


*Power supply: AC 100 to 240 V (50 Hz),
3 W (separate power supply)

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 65
Seri-Para I/O Unit (ACC-SP16TAG)
• This is the interface for connecting signals from the central control
device with the SANYO air conditioner unit control network.
• This unit can control and monitor the status up to 16 groups of
indoor units (Max 64 indoor units).
• Up to 4 seri-para units can be connected in one system.
• From the central control device, it is possible to set the temperature
and to monitor the room temperature or intake air temperature.

System example

Input Output
Seri-para I/O
On/Off (Pulse DC24V) On/Alarm/Answer back/Filter sign

Central Control Device


Local prohibit (Continuous DC24V) Room temp (Analog DC4-20mA)
Temp setting (Analog DC1~5V) All On/Off
All On/Off (Pulse DC24V)
All local prohibit & emergency stop
(Continuous DC24V)

LonWorks Interface (SHA-LN16UGB) • This interface is a communications converter for connecting


LonWorks to the SANYO air conditioner unit (PAC • GHP) control
network.
• From the host connected to LonWorks, basic settings and status
monitoring is possible for up to 16 groups of A/C units.

Functions
Start/stop
Temp. setting
Settings for each group
A/C unit settings from the of indoor units Operation mode
LonWorks communicator Option 1 settings(*)
System example
Option 2 settings(*)
Settings for all units Emergency stop
Start/stop
Temp setting
Operation mode
Option 1 settings(*)
A/C unit status notifications made to
Option 2 settings(*)
the LonWorks communicator
Alarm status
Indoor/outdoor unit Indoor units with active alarms
control line LonWorks interface Room temp.
A/C unit status
LON LON
Transmission intervals settings
Configuration properties
System Controller Minimum time secured for transmission
LonWorks Centre Control
communication line Device * Select two of the following: remote controller prohibit, fan speed setting, air direction
setting, filter sign reset.

Remote sensor (ART-K45A6GB) ON/OFF controller (SHA-KC16KAGB)

Dimensions: H 121 x W 122 x D 14 + 52


(embedding dimension mm)
*Power supply: AC 220 to 240 V
*I/O part: Remote input (effective
voltage: within DC
240V) : All ON/OFF.
Remote output (allowable
voltage: within DC 30V) :
All ON, All alarm

• 16 groups of indoor units can be controlled.


• Collective control and individual group (unit) control can also be
• This is a remote sensor which can be used with 4 series indoor performed.
unit. Please use it to detect the room temperature when no remote • Up to 8 on/off controller (4 main, 4 sub) can be installed in one link
controller sensor or body sensor is used. (Correspondence to a system.
system without a remote controller is possible.) • The operation status can be determined immediately.
• For joint use with a remote control switch, use the remote control * As operation mode and temperature settings are not possible with the ON/OFF controller, it
switch as main remote controller. must be used together with a remote controller a system controller etc.

66 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Control Equipment Dimensional Drawings

Simplified remote
controller
(RCS-KR1AGB)
Timer remote controller Wireless remote controller Remote sensor
(RCS-TM80BG) (ART-K45AGB)
4 Separate receiver for
2.7
58 19.5
wireless remote controller 70
4.4 x 9.4 slot

120
177

83.5
120

3
4.4 x 5.4 slot 35
70 13

13
120
61
16

System controller Intelligent controller Communication adapter


(SHA-KC64AGB) (SHA-KT256BG) (SHA-KA128AGB)
116
47 280 200
238 20 130
240
220

220
160 21 69

260
121
160

115

68
121

ON/OFF controller Seri-Para I/O unit for 16 groups indoor unit Seri-Para I/O unit for each indoor unit
(SHA-KC16KAGB) (ACC-SP16TAG) 4-ø0.5 hole (ACC-SP1AGB)
116 7.5
47 256
320
305

116.4
136.0
126

160 14 69
7.5
420
50 50 204.0
520
160

115
121

18-ø31.0 hole, opposite side included


63.8

15
9.2
160

122 10

LonWorks interface Seri-Para I /O unit for outdoor unit


(SHA-LN16UGB) (ACC-XSP4U1GB)
500
460 270
10 360
28.5

28.5

255
ø5
24

24
115
115

220

260 ø 10
180
24

24

6
le

4-ø

4 10
0 ho

5h

.5
ole

Potbellied hole (4 locations)


3-ø3

R2

80 ø5
30
80

290 Magnified view


90 50
R5

Detail of the potbellied hole

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 67
AMY Software

AMY software is an air conditioner (A/C) central control system for buildings

RS485/RS232C Communication
Adaptor adaptor
(Field supply)

(RS-232C) (RS-485)
Max. 64 I/D

Outdoor unit
Group control Remote controller

Outdoor unit
Remote Group control
controller

Max. 64 I/D
Outdoor unit
Remote Group control
controller

Outdoor unit

Max. 16 system Remote


Connectable I/D units: Max. 512 controller

Software environment
Functions
Unit ON/OFF OS: Windows 2000, Windows NT 4.0
Mode-change Service Pack 6 or above
Room temperature setting Browser: Internet Explorer 4.0
Fan speed setting or above
A/C unit settings
Flap setting
Central control setting
Filter-sign clear
Alarm reset
Unit ON/OFF status
Operation mode
Setting temperature
Fan speed status
A/C unit status Flap status
Central control setting
Filter-sign situation
Correct/incorrect status
Alarm code

68 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
TECHNICAL INFORMATION
3 Way GHP Refrigerant Tubing Design

The maximum number of indoor units that can be connected is 24. The capacities that can be connected
to the indoor units are 50 - 200%.
Outdoor unit
3-piping line (discharge gas tube, suction gas tube, and liquid tube) line CAUTION 1.Each indoor unit requires a solenoid valve kit.
2-piping line (gas tube and liquid tube) line 2.Never branch the tube between solenoid valve kit
and indoor unit.
3.Never branch the tube again after header branching.

Indoor unit Solenoid valve kit


d21 d22 d23
20 cm or more if indoor Branch tube (purchased separately)
unit is installed in a lower
Solenoid valve kit position than the header. Ball valve (purchased separately)

T-tee (provided by installator)


Dn d24
Maximum length of each Closed (pinch) weld
D1 branch tube
d < 30 m Header tube
Header tube

H2 (height difference between indoor units)


<15 m
First branch
L3 (Minimum length after the first branch)

Maximum tubing length L1 <120 m


(Branch line)
L2 (Maximum length after the first branch)
D2
L5
D3 L4
Solenoid
valve kit

d1 d2 d4 d5

d3
Indoor unit

Height difference between indoor units after the fast branch must be less than 4 m. If height difference between indoor units after the last branch cannot be less than 4 m, divide
the height difference between upper and lower units (2 to 1).

2X (m) or
4m or less more
Height difference exceeding 4 m

X(m)

Length of Refrigerant Tubing


Main tube (level) Closed weld Main tube (vertical)

Outdoor
Indoor
Indoor
Indoor
L3 < 2 m Indoor

Indoor
Closed weld
Level Use Vertical Use
Outdoor
Arrangement of Solenoid valve Kit.
Please attach Solenoid vaive kit to a less than 30m place from an indoor unit.
For conference rooms and other locations where low noise is required, pay attention to the installation
location and install on a corridor etc.
Please prepare the check place for service near a kit.
Sorenoid Valve Kit Room Room Room Room

Indoor unit Indoor unit Indoor unit Indoor unit


ATK-RZP56BG
(For 74 to 184 indoor unit)
Solenoid valve kit
Solenoid valve kit
ATK-RZP160BG
corridor corridor
(For 254 to 604 indoor unit)

70 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
2 Way GHP Refrigerant Tubling Design
In regard to the refrigerant tubing length

The maximum number of indoor units that can be connected is 24. The capacities that can be connected
to the indoor units are from 50% to 200%.
System example : Header tube (purchased separately)

: Branch tube (purchased separately)


: T-tee (provided by installer)
Outdoor unit
: Closed (pinch) weld

Distance (cm) from flammable materials

L1
LA L2

LB LC LG 8

L4
1 2 3

L2
L3
LA
H1
L4 T-tee
1 2 branch tube

7 8
Indoor unit
Unit main tube
(between unit branch tubes)
L2
Unit main tube

No. 1 branch
1 6 7 8
Unit branch tube

4 m or less

Over 2X
Over 4 m

X
*Limit of elevation difference between
indoor units after the final branch

Item Symbol Details Actual length (m)

L1 Maximum allowable tubing length 160


(equivalent length 185)
Difference between longest and
Allowable tubing length L(L2 L4) shortest tubing lengths after the 30
No. 1 branch (first branching point)
1, 2, 8 Maximum length of each branch tube 30
If outdoor unit is above 50
H1
Allowable elevation If outdoor unit is below 35 (*1)
difference
H2 Maximum difference between
indoor units 15 (*2)
Allowable header Maximum length from the first
tubing length L3 tees to the front seal 2

(*1) If cooling mode is expected to be used when the external temperature is 10˚C or below, install so the maximum length is 30 m.
(*2) Install so that the height difference between indoor units after the final branch is within the limits shown in the figure.

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 71
Optional Parts
(Ball Valve and Distribution Joint Kit)
Distribution joint kit
Position Part A Part B Part C Part D Part E Part F Part G Part H Part I Part J

Dimension ø38.1 ø31.75 ø28.58 ø25.4 ø22.22 ø19.05 ø15.88 ø12.7 ø9.52 ø6.35

APR-P160BG (for indoor units) (Capacity after distribution joint is 22.4 kW or less.)
Gas pipe 110 Liquid pipe 110
97 97
G
G I H H I J
F G F
H
G
Distribution Distribution

72

72
Joint Joint
H I
J

Insulator Insulator

APR-P680BG (for indoor units) APR-P1350BG (For indoor units)


(Capacity after distribution joint is greater than 22.4 kW and (Capacity after distribution joint is greater than 68.0 kW and
no more than 68.0 kW)) no more than 135.0 kW))
Gas pipe 175
Gas pipe 175 Distribution
135
135 Joint
B A

C C D E F GH
114

F E D

114
A B C D
Distribution C B
Joint D C
Insulator D
E C
F D
Reducing Insulator Reducing
G
H Joints E Joints
F

G
110 H
Liquid pipe
97
Liquid pipe 110
G HI J
97 G F
72

I H G F
G
H

72
Distribution G
Joint H Distribution G
I
J Reducing Joint
Joints Insulator H
Insulator I
Reducing
J Joints

APR-CHP680BG (for outdoor units) (Capacity after distribution joint is 68.0 kW or less)
175 175
Gas pipe 135 Liquid pipe B
A 135
A B
B C
114

C D
114

C DE F
D

B
Distribution C
Joint Distribution
Joint
C D
D E E
F
F
Reducing Reducing
Joints Joints
Insulator Insulator

APR-CHP1350BG (for outdoor units) (Capacity after distribution joint is greater than 68.0 kW and no more than 135.0 kW))
Gas pipe 175 Liquid pipe
110
135 97 HI
A
A B
B
F G
114

C D
72

E F F

B G
Distribution I H
Joint H
Distribution I
C Joint
D E
F
Reducing
Reducing Joints
Joints
Insulator
Insulator

72 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Connection dimensions of the parts ** Example: In the drawing, F indicates an inner diameter dimension, indicates an outer diameter dimension. (mm)

Position Part A Part B Part C Part D Part E Part F Part G Part H Part I Part J

Dimension ø38.1 ø31.75 ø28.58 ø25.4 ø22.22 ø19.05 ø15.88 ø12.7 ø9.52 ø6.35

APR-RZP224BGB (for indoor units) (Capacity after distribution joint is 22.4 kW or less.)

Suction pipe Discharge pipe Liquid pipe


210 186
235
12

7
G F F F F
G H H H H G I
H
GH
55 40 H
F I H HI

69
77
F H
92

G G
H
55

145 136

Insulator Insulator Insulator

APR-RZP680BGB (for indoor units) (Capacity after distribution joint is greater than 22.4 kW and no more than 68.0 kW))
Suction pipe Discharge pipe Liquid pipe
300 300 I
16

16
C C DE F D D EF G
FED C C FED C C G
F

130
112
126

126
E
112 G GF E EFG G
C D
C
D I H HI
D
74

E E 340 50
F F
F
F G
G H
230
55

230
55

Insulator Insulator Insulator

APR-RZP1350BGB (for indoor units) (Capacity after distribution joint is greater than 68.0 kW and no more than 135.0 kW))
I
H
Suction pipe G F Liquid pipe H G
F E
Discharge pipe D
G
55

F
130

C E
C G G F E EFG G
A
B I H HI
F E D C C A B B BA C CDE F 340 50
B B
45

90 105 112

Insulator Insulator

Check the room limit concentration


With a multi-type system, the total length of refrigerant tubing is longer, and more additional refrigerant charge is
required. For this reason, there is a danger that refrigerant leaking into a small room may cause persons in the room
WARNING to be asphyxiated. The room limit concentration is determined as follows according to the “Installation Standards
for Refrigeration and Air Conditioning Equipment (KHK-S0010)” voluntary standards created by the High Pressure
Gas Safety institute of Japan.
Total amount of refrigerant charge (kg) for the system Limit concentration 0.44 kg/m3
Smallest room volume (m3) where an indoor unit is installed
No special measures are required if the concentration is below 0.41 km/m3 (EN378).
However, special measures are required if the concentration is above 0.44 km/m3.

“Maintenance and inspection” is a must for gas heat pump air conditioning systems.
Just like an automobile, a heat pump air-conditioning system requires periodic servicing so that it can perform efficiently.
Main maintenance and inspection items
Maintenance and inspection Since a heat pump air-conditioning system
uses a gas engine as its power source, it 1 Changing the engine oil
should be periodically inspected to keep 2 Checking the coolant level
it running efficiently. We recommend a 3 Inspecting the engine system
Fixing problems Efficient operation 4 Checking the safety protection system
maintenance contract for your SANYO
Gas Heat Pump, which is great value 5 Checking and adjusting the running
since it not only ensures that problems conditions, collecting operating data, etc.
Preserving durability Safe and reliable
operation will be fixed, but it helps reduce running
costs and improves comfort.

Energy saving

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 73
Piping & Wiring diagram with GHP
and Water Heat Exchanger

Electric Outdoor unit


box

RCS-
WE170J

Water heat exchanger

Electric magnetic
Inlet Outlet
contactor water water

Differential
pressure switch

Pump* Water buffer tank

Charging
valve
Manometer

Electric line Outlet water pipe


Remote control line Inlet water pipe
Pump/switch line Refrigerant pipe gas side
Comunication line O.U./W.H.E Refrigerant pipe liquid side
Comunication line O.U/I.U.

*Please refer to page 16

Outdoor unit

Electric connection

HEAT /COOL STATE


ALARM
ALARM/OIL
OPERATION STATE

Connection with BUS


Line to U1, U2 of
GHP outdoor unit

Connect with control system


(Capacity AC 240 V, 0.8 A)
OPERATION SIG

ALARM
COMMON

OIL

Contactor
START

COOL
STOP

HEAT

Pump
In this design only outdoor unit, water RCS-WE170J
heat exchanger and remote controller
Differential
are supplied by SANYO. pressure switch These designs are only examples of installation.

74 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Piping & Wiring diagram with Mix System

Electric Outdoor unit


box

RCS-
WE170J

Water heat exchanger

Electric magnetic
contactor Inlet Outlet
water water

Differential
pressure switch

Pump* Water
buffer tank
Charging
valve
Manometer
Indoor units direct expantion
Electric line Outlet water pipe
Remote control line Inlet water pipe
Pump/switch line Refrigerant pipe gas side
Comunication line O.U./W.H.E Refrigerant pipe liquid side
Comunication line O.U/I.U.
*Please refer to page 16

Outdoor unit

Electric connection

HEAT /COOL STATE


ALARM
ALARM/OIL
OPERATION STATE

Connection with
BUS Line to U1,
U2 of GHP
outdoor unit

Connect with control system


(Capacity AC 240 V, 0.8 A)
OPERATION SIG

ALARM

OLIO
COMMON

Contactor
START

COOL
STOP

HEAT

Pump
RCS-WE170J
Differential
pressure switch
In this design only outdoor unit, water These designs are only examples of installation.
heat exchanger and remote controller.
are supplied by SANYO.

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 75
Piping & Wiring diagram with
GHP 71kW with 2 Water Heat Exchanger

Electric SGP-E240K1GU2W
box

RCS- RCS-
WE170J WE170J

SGP-
SGP-WE80K1 WE170K1

Electric magnetic
Electric magnetic Inlet Outlet Inlet Outlet
water water contactor water water Water buffer tank
contactor

Differential Differential
pressure switch pressure switch
Charging Pump*
valve Pump*

Manometer Electric line Outlet water pipe


Remote control line Inlet water pipe
Pump/switch line Refrigerant pipe gas side
*Please refer to page 16 Comunication line O.U./W.H.E Refrigerant pipe liquid side
HEAT /COOL STATE
ALARM
Electric connection
ALARM/OIL
OPERATION STATE

Connection with BUS


Line to U1, U2 of
GHP outdoor unit

Connect with control system


(Capacity AC 240 V, 0.8 A)

Outdoor unit
OPERATION SIG

ALARM
COMMON

START

COOL

Contactor
STOP

HEAT

HEAT /COOL STATE Pump RCS-WE170J


ALARM
ALARM/OIL
Differential
OPERATION STATE
pressure switch

Connection with
Connect with control system BUS Line to U1, U2
(Capacity AC 240 V, 0.8 A) of GHP outdoor unit
OPERATION

ALARM
STATE
COMMON

START

COOL
STOP

HEAT

These designs are only Contactor In this design only outdoor


examples of installation. unit, water heat exchanger
and remote controller are
Pump supplied by SANYO.
RCS-WE170J

Pressure switch

76 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Electric
box SGP-E240K1GU2W

RCS-
WE170J

SGP-
SGP-WE80K1 WE170K1

Electric magnetic
Outlet Inlet
water contactor water Water buffer tank

Differential Differential
pressure switch pressure switch

Charging
valve

Manometer Pump*
Electric line Outlet water pipe
Remote control line Inlet water pipe
HEAT /COOL STATE Pump/switch line Refrigerant pipe gas side
ALARM Comunication line O.U./W.H.E Refrigerant pipe liquid side *Please refer to page 16
ALARM/OIL
OPERATION STATE Electric connection

Connection with BUS


Line to U1, U2 of
GHP outdoor unit

Outdoor unit

Connect with control system


(Capacity AC 240 V, 0.8 A)

HEAT /COOL STATE


ALARM
ALARM/OIL
OPERATION STATE

Connection with BUS


Line to U1, U2 of
GHP outdoor unit

Connect with control system


(Capacity AC 240 V, 0.8 A)

These designs are only


examples of installation.
OPERATION

ALARM
STATE
COMMON

In this design only outdoor


OIL

Contactor
START

COOL
STOP

HEAT

unit, water heat exchanger


and remote controller are
Pump supplied by SANYO.

RCS-WE170J

Pressure switch Pressure switch

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 77
Terminal Block with Water Heat Exchanger

OPERATION STATE

ALARM OIL

ALARM

HEAT /COOL STATE

Pump
Connect with control system
(Capacity AC 240 V, 0.8 A)

Magnet Switch

Differential
COMMON
pressure switch
START
These diagrams are only
installation examples.

STOP

HEAT

RCS-WE170J
COOL

OPERATION Outdoor unit


STATE

ALARM

OIL

In this design only outdoor unit, water heat exchanger and


remote controller are supplied by SANYO.

Connection with BUS


Line to U1, U2 of
GHP outdoor unit.

78 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
It shall set "STATIC" side in the SW1 of PCB of
Water heat exchanger. STATIC
PULSE

OPERATION STATE

ALARM OIL

ALARM
Pump

HEAT/COOL STATE

Magnet Switch

Connect with control system


(Capacity AC 240 V, 0.8 A)

Differential
pressure switch

COMMON

Weekly Timer

These designs are only


START examples of installation.

ON/OFF switch STOP

HEAT

COOL Outdoor unit


RCS-WE170J

OPERATION
STATE

ALARM

OIL

In this design only outdoor unit, water heat exchanger Connection with BUS
and remote controller are supplied by SANYO. Line to U1, U2 of
GHP outdoor unit

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 79
OPERATION STATE OPERATION STATE OPERATION STATE

ALARM OIL ALARM OIL ALARM OIL


Connect with control system
(Capacity AC 240 V, 0.8 A) ALARM ALARM ALARM

HEAT/COOL STATE HEAT/COOL STATE HEAT/COOL STATE

Differential Differential Differential


pressure pressure pressure
switch switch switch

COMMON COMMON COMMON

START/STOP HEAT/COOL START/STOP START/STOP

HEAT/COOL HEAT/COOL

Connection with Connection with Connection with


BUS Line to U1, BUS Line to U1, BUS Line to U1,
U2 of GHP U2 of GHP U2 of GHP
outdoor unit outdoor unit outdoor unit
START

START

START
STOP

STOP

STOP

COOL
HEAT

STATIC

CENTRAL SYSTEM
PULSE

This designs are only


examples of installation.

In this design only outdoor unit, water heat exchanger It shall set "STATIC" side in the SW1 of PCB
and remote controller are supplied by SANYO. of water heat exchanger.

80 These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer.
Precautions
Securing adequate space for servicing
Several units can be installed in series Installing 8 or more outdoor units in series
Install the outdoor unit in a well-ventilated location that will When installing eight or more outdoor units in series, or
help the heat exchanger work at its optimum level. Be sure when installing units near a wall or other location where air
to secure enough space for maintenance work, referring to circulation may be inadequate, give sufficient consideration
the diagram below for minimum clearances. When installing to the possibility of the units shorting out.
up to three units in series, provide a passageway between
units for servicing.
Unit: mm

At least 600
When installing one unit At least 2000 Refrigerant piping side
A passageway for servicing can
be provided on either the left or
right side of the unit.
Be sure to secure an installation * At least 350 as passageway for servicing.
Front side
space with the following
At least 100
clearances. At least 1000

Installation space needed for servicing Unit: mm


When installing more than For series installation For dispersed installation At least 100
At least 1000 on both the refrigerant
one unit in series At least 350 piping side and the front side
Refrigerant piping side At least 600
A passageway for servicing can
be provided on either the left or
At least 600 on the At least 600 on the
right side of the unit. refrigerant piping side refrigerant piping side
At least 1000 on the At least 1000 on the
Be sure to secure an installation At least 1000 front side
At least 100 At least 100 front side * At least 350 as passageway for servicing
space with the following
At least 100
clearances.
Overhead clearance Distance from flammable material †Distance from the exhaust tube

†At least 150 †At least 150 At least 600


At least 1000 At least 2000

†At least 150


At least 10
At least 10 At least 10

At least 10 At least 10

(Top View) (Top View) (Front View)


SGP-E70K2GU2/E90K2GU2 SGP-E120K2GU2W/E150K2GU2
SGP-E190K2GU2W/E190K2GU2W

Avoid the following installation


locations
Install the unit safely and securely in a place where
it will be adequately protected and be able to
perform at its designed specifications.
• A place that has no space for servicing • Near a street lamp or tree
Maintenance work can require a large number of instruments and Insects attracted by street lamps in large numbers and leaves from
tools. Lack of sufficient space for servicing may prevent the unit from trees can get sucked into the unit and cause it to malfunction.
being properly maintained and cared for. • Other locations to avoid:
• A place that is unsafe for maintenance work * Places where chemicals are used.
If the unit is installed on the roof of a building (even if the spot is * Places where the unit will disturb others.
level) and there is no guard rail or similar safe guard, not only will * Near a chimney or exhaust outlet.
maintenance work become impossible but the unit may fall or another * Places exposed to strong winds.
accident may occur. * An installation that has no vibration-proof pad.
• A place where a ladder must be used to access the unit * Near a wall other than a soundproof wall.
An installation that requires maintenance workers to go up and down * Places where salt damage may occur and no preventive
a ladder or stairs makes safe and reliable maintenance work not only measures are taken.
difficult but dangerous as well. * Places with no protection from snow.
• A poorly ventilated location In addition, if the area below the outdoor unit is to be used, make sure
If the top, side or front of the unit is close to a wall or other obstruction, the installation pad is constructed so that water drops and oily or greasy
poor ventilation and lack of sufficient air circulation may not only cause dirt will not drip down into the area below. Do not use a pad fabricated by
trouble but also prevent the unit from operating normally. metal punching or similar process.

These diagrams and illustrations are for guidance only. Actual design should be undertaken by a qualified HVAC engineer. 81
Safety precautions and caution on installation and use

Safety Precautions
• Usage • Installation
The air conditioners listed herein are only for cooling/heating areas Request a sales agent or a technician from the store to install the
used by people. Do not use the unit for foods, animals, plants, air conditioner. Improper installation by yourself may result in water
precision machines, works of art or other objects. Doing so may leakage, electric shock or fire.
cause damage to the unit. Do not use the unit for vehicles or vessels. When installing in a small room, take measures to keep refrigerant
Doing so may cause unit water leakage and short circuiting. leakage within acceptable density limits.
• Before Using • Location
Please read the Operating Instructions carefully and use the air Do not install where inflammable gas may leak or inflammable objects
conditioner properly. exist. Do not install where there is any inflammable gas emission,
inflow or leftover, or where carbon fibres are in the air. This could be
the cause of fire.

Caution On Installation and Use


• Location • Noise Emissions
Blocking air intake or outlet can be the cause of trouble including the The noise emission rate indicated in the catalogue shows values
loss of air flow power, or short-cycled air emission drawn into the (A scale) measured in an anechoic chamber. In actual installation
intake. Be sure to install in an airy place. conditions, noise emission is generally greater than the indicated rate
• Avoid Installation in Highly Humid Locations due to surrounding noise and echoing.
1 Avoid installation where the humidity is excessive. This causes • Odour Emissions
condensation during cooling. Even though an air conditioner does not contain odour-emitting parts,
2 Installation in a room where the temperature and humidity are high discharged air can in certain conditions have an unpleasant odour. This
around the ceiling due to sunlight will result in condensation. Use is the result of odourous particles such as from smoke, cosmetics and
insulation or take other preventive measures to block the sunlight. foods affixing themselves to the air conditioner. Although the odour
• Exposure to Oil does not affect performance, cleaning the air filter and the inside of
Avoid installation where there is exposure to oil or soot (such as in the air conditioner is recommended.
kitchens or machinery plants). Oil will adhere to the heat exchanger. • Noise Caused by Electromagnetic Waves
This will lower heat exchange performance, emit mist, or deform or When installing near equipment that emits electromagnetic waves, be
damage synthetic resin parts. sure that the air conditioner does not suffer noise damage.
• Cleaning • Remote Control Wiring
After using the air conditioner for several seasons, the insides For remote control wiring and control wiring between indoor units, do
becomes dirty and this results in low performance. In addition to not install along side of power wiring (220/240V) in the same tube nor
regular cleaning, a maintenance contract with a service person is wherever power wiring exists. Doing so may cause a malfunction.
recommended.
• Features of Heat Pump Heating
Heating power (kW) indicated in the catalogue is based on the
following conditions: outdoor temperature of 7˚C and indoor
temperature of 20˚C, as specified by JIS. Heating capacity decreases
as outdoor temperature drops. Therefore, if heating power is
insufficient due to low outdoor temperature, use the air conditioner
together with other heating equipment. When heated air rises and
collects in a room with a high ceiling, install an air circulator as well.

Do not install an air conditioner in a room where the limit density will be exceeded if refrigerant
leaks. The refrigerant used by this system is itself a safe refrigerant; however, if for some reason the
refrigerant leaks and the limit density is exceeded, there is a risk of injury to persons due to a lack of
oxygen. For further information, ask your dealer or consult references such as an engineering manual
and install the airconditioner correctly.

82
New System Design Software Program

SANYO have identified the importance and The design package utilises system wizards and
ever increasing demands for fast and accurate imports tools to enable both simple and complex
responses to customer requests in our industry. systems to be created. In addition the system will
More and more emphasis is being placed upon allow outdoor and indoor units to be dragged and
energy efficiency in our marketplace and the dropped on an interactive desktop, allowing users
ability to calculate cooling/heating loads and to create realistic floor plans with detailed piping
produce information of actual design conditions and wiring schematics to send out with quotations,
is a major advantage to any architect, consultant, through to installation guidance drawings.
contractor or end user.
The new PAC2 system software can be used for
SANYO understands the ever changing and all SANYO ECOi, GHP and PACi systems.
demanding industry we are in and are pleased to
announce the launch of the next generation of our Features include
system design software program.
• AC Calc Lite (included in the package)
The new advanced PAC2 system design software
has been customised to make any selection and • Easy to use system wizards
design process as quick and easy as possible. The • Auto piping and wiring features
software features an AC Calc Lite (produced by click
• Converted duties for conditions and pipe work
software). This facilitates small building loadings to
be accurately calculated and directly imported into • Auto CAD (DXF) export
the PAC2 software. • Detailed wiring and pipe work diagram

System design software

83
Indicates conformation ISO 9001: 2001 ISO 14001: 2001
with EC Directives Certificate Number: JQ116B Certificate Number: ECOOJ0303-33

SANYO reserves the right to make any variation in specification to the equipment described or to withdraw or replace
products without prior notification or public announcement. All descriptions, illustrations, drawings and specifications in
this publication are given in good faith, but are intended to present only general particulars and shall not form any part
of the contract. For full installation details, please contact your SANYO distributor.

Rating Conditions
The cooling and heating capacities are based on the following conditions:
Cooling: Indoor temperature 27˚C DB / 19˚C WB, Outdoor temperature 35˚C DB / 24˚ C WB.
Heating: Indoor temperature 20˚C DB, Outdoor Temperature 7˚C DB 6˚C WB.

Printed uasing paper produced from 50% recycled material and 50% from sustainable forestr

www.sanyoaircon.eu