You are on page 1of 1

THIS SHOP DRAWINGS ARE FOR THE ANCHOR BOLTS ONLY.

SEPARATE DOCUMENTS SHALL BE SUBMITTED FOR THE


BASE PLATES AND ALONG WITH THE BALANCE OF THE
1 2 3 4 5 6 7 8 STRUCTURE.

379

320

282

242

202
431
HEA240 HEA240 HEA240 HEA240
C HEA240

HEA240

1538
438
IPE300 IPE300

57

IPE300 IPE300

1816
HEA240 HEA240 HEA240 HEA240 HEA360 HEA360
B

2322
HEA220

HEA240

338
246

562
HEA240

419
114
HEA240 HEA240
A HEA360 HEA360

REMOVE PEDESTALS
DIMENSIONS FROM THE SPECIFY THESE WELDS. WE
REMOVE PEDESTALS ANCHORS SHOP DRAWINGS. REMOVE PEDESTALS HAVE NO WELDED ANCHORS.
DIMENSIONS FROM THE THESE DIMENSIONS ARE NOT DIMENSIONS FROM THE
ANCHORS SHOP DRAWINGS. CORRECT FOR MANY ANCHORS SHOP DRAWINGS.
Plan 0.00
THESE DIMENSIONS ARE NOT LOCATIONS. THESE DIMENSIONS ARE NOT USE 8.8 ANCHORS OR
CORRECT FOR MANY CORRECT FOR MANY EQUIVALENT. THE ANCHOR
LOCATIONS. LOCATIONS. ANCHORS LENGTHS SHALL BE
GRADE IS NOT CORRECT.
550 RE CALCULATED
550 75 400 75 CONSIDERING ALL THE SUBMITTAL
125 300 125 COMMENTS.
REV . ESPECIALLY
DATE BY . THE
DESCRIPTION CHKD . APPD .

400 GROUT THICKNESS.


00 20-08-2023 SAR ISSUED FOR APPROVAL AHMED

30 340 30
85

85
125

125

110

110 45 90 45 110
120 COORDINATION
80

PREPARED BY ENGINEERING DEPT . DRAWN BY :

CHECKED BY: ARCHITECTURAL STRUCTURAL ELECTRICAL MECHANICAL SECURITY SYSTEM


550

300

550

380

400
140

140

180
SIGNATURE :

POSITION NAME SIGNATURE


80

120

DEPARTMENT HEAD ENG.AHMED ELSHERBINY

110
TECHNICAL MANAGER ENG.AHMED HAMDY OMAR
125

125

PROJECT MANAGER ENG.MAHMOUD HANAFY


85

85

30 110 120 20 90 30 KEY PLAN

125 100 100 100 125


USE 30mm GROUT THICKNESS 75 120 160 120 75 USE 30mm GROUT THICKNESS USE VALID NUT AND WASHER
USE 30mm GROUT THICKNESS AS USED IN THE DESIGN. THREADED LENGTH IS
AS USED IN THE DESIGN. GRADES. A36 IS NOT VALID
AS USED IN THE DESIGN. MOST PROBABLY 15mm WILL MISSING.
MOST PROBABLY 15mm WILL FOR WASHERS AND NUTS.
PROJECT :

MOST PROBABLY 15mm WILL NOT BE ENOUGH BASED ON NOT BE ENOUGH BASED ON MOC Warehouse Project (SAL)
RIYADH, KINGDOM OF SAUDI ARABIA
NOT BE ENOUGH BASED ON SITE CONDITION. REVISE THE SITE CONDITION. REVISE THE
HEA360

CLIENT
SITE CONDITION. REVISE THE ANCHOR LENGTH ANCHOR LENGTH
ANCHOR LENGTH ACCORDINGLY. ACCORDINGLY.

IPE300
ACCORDINGLY. HEA240
400
300
120 160 120

X
100 100 100
90 160 90 CONSULTANT :
KINDLY RECTIFY. THESE
50

50

50

NON NON NUMBERS ARE NOT

1
SHRINKAGE SHRINKAGE READABLE.
20

20

20
15

15

15

NON
PROVIDE SHRINKAGE
MAXIMUM
450

450

450
365

CONTRACTOR:
365

365

D20 EMBEDDED PROVIDE


DEPTH. TYP. MAXIMUM RIYADH 11474
D20 PROVIDE PO BOX 16934
D20 EMBEDDED www.metco-sa.com

DEPTH. TYP. MAXIMUM


EMBEDDED 40 80 40 SUB CONTRACTOR:

DEPTH. TYP.
3 FLT10*80 FOURTH PYRAMID
TEMPLATE TEMPLATE TEMPLATE
PLATES ARE PLATES ARE

40 80 40
PLATES ARE
MISSING. MISSING. WHY 3 IS USED? PLEASE
MISSING. REFERENCES
CLARIFY.
CONTRACT DRAWING

SHOP DRAWING

DISCIPLINE :

DRAWING TITLE :
MOC WAREHOUSE (SAL)
MEZZANINE ANCHOR DETAILS
DRAWN SARFRAS SCALE: DATE 20-08-2023
CHECKED ENG.AHMED ELSHERBINY APPROVED
PROJECT SAL-MOC-STR-SD-042 REV.

SAL 01