FOOTING DESIGN (SQUARE FOOTING):

DEAD LOAD: 300 KN


LIVE LOAD: 300 KN
Qa: 200 Kpa
COL. DIM. A 0.400 m
COL. DIM. B 0.400 m
f'c: 28.000 MPa
fy: 275.000 MPa

EFFECTIVE DEPTH OF FOOTING:


BASED ON WIDE-BEAM SHEAR:
d test: 191.82 mm
BASED ON PUNCHING SHEAR:
EQN. TO BE INPUT: 24.279 X² 10111.527 X -3450000
USE HIGHER D: 225 mm INPUT ONLY THE POSITIVE SIGN
p min: 0.00509090909
p: 0.00598995225
p max: 0.03783272727
Note: p min < p < p max . If p min is larger than p, use p min.
USE p: 0.005989952
BAR DIA. 16 mm

SUMMARY:
LENGTH OF FOOTING: 1.900 m
WIDTH OF FOOTING: 1.900 m
DEPTH OF FOOTING: 324 mm PLS. ROUND UP
LONGITUDINAL BARS: 13 pcs.
TRANSVERSE BARS: 13 pcs.
BAR DIA. 16 mm