1304.0551 Divyol Transformer oil sample – Inhibited insulating oil for Transformer
and Switchgears as per IEC 60296/ASTM D 3487 TYPE II
Interpretation of results
The tested parameters are according the requirements of the IEC 60296 Ed. 4.
Page 2 of 3
VCA** CERTIFIED
Sample: 1304.0551
Property Unit Test method Value
2 – Refining/stability
Potentially Corrosive sulfur IEC 62535 Non corrosive
Content of TTAA (= metal passivator IEC 60666 n.d.
Irgamet 39 ©) mg/kg
Content of TAA (= metal desactivator Laborelec UPLC-MS/MS n.d.
Irgamet 30 ©) mg/kg method
Content of metal passivators BTA and IEC 60666 n.d.
TTA mg/kg
Antioxidant additive (DBPC) % IEC 60666 0.294
2-Furfural content mg/kg IEC 61198 n.d.
Page 3 of 3