TEST REPORT

Report Version Number:1.0


CMEC

Customer Details CMEC

Ref Oil Transformer Oil


Location Laboratory
Job Number 1-Jan-00
Sampling Point NA
Tag No: 1
Equipment Name Transformer
Temperature ˚C 23.1 Humidity % 60
Running Hours NA
Release Date 4/3/2022 Sample Receiving Date: 2/3/2022 Sampling Date NA
OBSERVATIONS & RECOMMENDATION

RESULTS

Parameters Method/Principle FEB-2022 Ref.Value

External form Visual clear


*BDV , KV IEC 60156 78
*DDF @ 90˚C,% IEC 60247 0.00531
Water Content, ppm IEC60814 8.9
Total Acid Number,mgKOH/gm ASTMD664 0.0321
PH 5.2
Flash Point ISO 2719 169
Furan Analysis IEC-61198 0.08976
Resistivity,GΩm IEC 60247 76.67
Interface tension ,(mN/m) ASTMD3487 37
Sludge and sediment ,(%) Gravemetric 0.02456
0.0234
Gas content in oil (%) (volume fraction) IEC 60247
Particle size NAS 1638 3
Chromatographic analysis of dissolved
gas components in oil
Hydrogen, H2, ppm 0
Methane, CH4, ppm 0
Ethane, C2H6, ppm 0
Ethylene, C2H4, ppm 0
Acetylene, C2H2, PPM ASTM D3612 0
Carbon Monooxide, CO, ppm 76
Carbon Dioxide, CO2, ppm 2319
Nitrogen, N2, ppm 62077
Oxygen, O2, ppm 29943

Prepared By Reviewed & Approved By


Sr.Chemist Manager Laboratory

End of report-This is Computer generated report & Need no Signature