Professional Documents
Culture Documents
Idronics 33 Na
Idronics 33 Na
CUTTING-EDGE
INNOVATION
IN TEMPERATURE MIXING
Caleffi mixing valves lead the way. From 3/8" under-sink scald protection valves to 3" flanged digital master
mixing valves, a full selection is available for residential and commercial plumbing and hydronic applications.
Over 60 years of innovation and global experience assure high quality and proven reliability. A wide
selection of double union connection types work with copper, iron, stainless steel and non-metallic pipes.
Approvals include compliance with U.S. and Canadian plumbing codes. CALEFFI GUARANTEED.
FROM THE GENERAL MANAGER & CEO
Caleffi ships products to 90 countries around the world. Caleffi North America collaborates
with its international colleagues in identifying and developing products that provide cutting
edge solutions for our customers as their needs evolve. Our many industry awards for
innovation testify to our collective efforts.
We hope you enjoy this issue of idronics and encourage you to send us any feedback by
emailing us at idronics@caleffi.com. An entire collection of the journal series can be found
at idronics.caleffi.com.
Mark Olson
3
TABLE OF CONTENTS
TABLE OF CONTENTS
SECTION PAGE
1 5 INTRODUCTION
5
33
Lowering water temperature in existing hydronic heating systems
2 7 Changing priorities
25
HEAT PUMP FUNDAMENTALS
Changes are needed
Refrigeration cycle Coefficient of performance
9 Why lower water temperatures are important
July 2023 Modulating/condensing boilers
July 2019 3 12 HEAT PUMP
Solar WATER
thermal HEATER INDUSTRY STATUS
collectors
Current replacement
Geothermal market
water-to-water-heat pumps Electrical service upgrades
Energy-efficiency
Air-to-water heatimprovement
pumps Equipment manufacturer
potential
Biomass boilers changes and requirements
Climate change impacts Electrical grid integration and demand
Future-proofing hydronics
Financial incentives systems response
Global trends in hydronics
16
4 16
Methods for reducing water temperature
EVALUATING WHEN A HEAT PUMP WATER HEATER MIGHT BE A GOOD FIT
Reducing building load
New construction
Partial installations
load vs design load considerationDomestic hot water recirculation
Water heater
Outdoor resetlocation Retrofit heat pump water heater
A Technical Journal
Source of absorbed heat installations
A Technical Journal Adding heat emitters
from Cold climate considerations
Adding more fin-tube baseboard
Water heater location
from Condensate management Airflow
CALEFFI NORTH AMERICA, INC. Adding the same type of fin-tube baseboard
Electrical power supply Condensate
CALEFFI NORTH AMERICA, INC Adding high output fin-tube baseboard Piping
Tank size
3883 W. Milwaukee Rd. Addingtemperature
other heat emitters
3883 W. Milwaukee Rd Storage and 120 VAC heat pump water heaters
Milwaukee, Wisconsin 53208 Fan-coils
point-of-distribution mixing Tank size
Milwaukee, Wisconsin 53208 Sizing supplemental heat emitters
valves Planning for future replacements
USA Thermal theperformance
USA Operating HPWH at of fan-coils
higher
Adding radiant
storage panels
temperature
Evaluating existing
Point-of-use cast iron radiators
mixing valves
Tel: 414-238-2360
Tel: 414-238-2360 1-pipe cast iron radiators
FAX: 414-238-2366 2-pipe cast iron radiators
FAX: 414-238-2366
5 34 Estimating heatTO
ALTERNATIVES output
HEAT from cast WATER
PUMP iron radiators
HEATERS
The effect of flow rate
Air-to-water heat pumps used on heat output Heat recovery applied to domestic water
E-mail: idronics@caleffi.com for domestic water heating heating
E-mail: idronics@caleffi.com
36 Piping
modifications
Water-to-water heat pumps
Website: www.caleffi.us
Website: www.caleffi.us Zoning possibilities
used for domestic water heating
Zoning with non-electric thermostatic radiator valves
Zoning with manifold valve actuators
To receiveTofuture idronics
futureissues
receive idronics issues 37 Boiler protection
SUMMARY
FREE, register Heat source configuration
FREE,online
register online
Design guildlines
idronics.caleffi.com
www.caleffi.us
38
47 APPENDIX A: CALEFFI HYDRONIC COMPONENTS
Example Systems
System #1
© Copyright 2023 2019
© Copyright System #2
Caleffi North America,
39 APPENDIX
System #3B: CALEFFI PLUMBING COMPONENTS
Caleffi North Inc.
America, Inc.
Printed: Milwaukee, WisconsinWisconsin
Printed: Milwaukee, 55 Appendix A: Generic piping symbol legend
USA USA 39 APPENDIX C: GENERIC COMPONENTS
56 Appendix B: Component Symbol legend
4 4 N° 55 giugno 2019
1. INTRODUCTION
The two primary objectives in a domestic hot water
plumbing system are: Figure 1-1
evaporator coil
• Heat the water in a cost-effective manner. expansion valve
• Deliver the water at an appropriate temperature to fan
the plumbing fixtures. compressor
cool &
There are many options to accomplish both objectives dry air
using a wide variety of energy sources. One approach room outlet
that is quickly gaining market share is based on heat air
pump technology. When applied properly, heat pump inlet
condensate
water heaters (HPWH) require approximately 60% drain
condenser
less energy than electric-resistance water heaters and coil
have the potential to reduce carbon emissions when
auxiliary
compared to gas water heaters, according to the
heating DHW
Pacific Northwest National Laboratory. element(s) outlet
There are many opportunities to integrate HPWHs pressure &
in both residential and commercial domestic water temperature
systems. Identifying those opportunities and planning relief valve
the installation accordingly will maximize energy insulation
efficiency without negatively affecting the comfort and
convenience consumers expect.
air-to-water
heat pump water heaters
P&TRV
DHW check
valve
mixing
valve
recirculation
storage tanks
5
In commercial systems, one or more modular HPWHs are When a building’s water heater fails and a replacement
connected to one or more thermal storage tanks. Figure is needed as soon as possible, the least complicated
1-2 shows the concept. Separating the storage tanks approach is a “like-for-like” replacement, since it restores
and heat pump units gives more flexibility to designers hot water service quickly. However, these ASAP swaps
and installers when matching load requirements. often omit consideration of new technology and energy-
saving options.
Using a standard refrigeration cycle, HPWHs transfer
heat from air surrounding them, or sometimes from Changing a standard water heater to a HPWH is
outside air, into the tank water. Because they mostly best evaluated before an emergency. By considering
move heat rather than create it, HPWHs can provide the potential for improvement, owners can achieve
the same amount of domestic hot water as an electric- highly energy-efficient domestic hot water heating using
resistance water heater using only 25 to 33% `of the HPWHs.
electrical energy input.
There are advantages and limitations to every type of
The U.S. Department of Energy and ENERGY STAR® water heating device. The underlying energy-efficiency
recommend replacing water heaters every ten years. potential of heat pump technology creates a high
Based on this, the opportunity to reassess the best water potential to save energy in the domestic water heating
heating system for a given building is a relatively frequent segment. This issue of idronics will assist in evaluating
recurring cycle. In the average North American home, HPWH technology in both retrofit and new construction
the original water heating system may be replaced many applications.
times throughout the life of the building.
6
2. HEAT PUMP FUNDAMENTALS
REFRIGERATION CYCLE the evaporator. At this point, the transfers heat to the “sink media,”
Nearly all current-generation heat refrigerant is colder than the air which is water in a HPWH. As it gives
pump water heaters operate on surrounding the evaporator. That up heat, the refrigerant changes from
a basic “vapor/compression” air is generically referred to as a high-pressure, high-temperature
refrigeration cycle. During this the “source media,” because it is vapor into a high-pressure, somewhat
cycle, a chemical compound called the source of the low-temperature cooler liquid (e.g., it condenses).
the refrigerant circulates around a heat. Because of the temperature
closed piping loop passing through difference between them, heat The high-pressure liquid refrigerant
all major components of the heat moves from the air into the lower- then flows through the thermal
pump. These major components temperature refrigerant. As the expansion valve at station (4), where
are named based on how they refrigerant absorbs this heat, it its pressure is greatly reduced.
affect the refrigerant passing changes from a liquid to a vapor The drop in pressure causes a
through them. They are as follows: (e.g., it evaporates). The vaporized corresponding drop in temperature,
refrigerant continues to absorb heat restoring the refrigerant to the same
• Evaporator until it is slightly warmer than the condition it was in when the cycle
• Compressor temperature at which it evaporates. began. The refrigerant is now ready
• Condenser to repeat the cycle.
• Thermal expansion valve (TXV) The vaporized refrigerant flows
on to the compressor, where its The refrigeration cycle remains in
The basic arrangement of these temperature and pressure are continuous operation whenever the
components to form a complete increased. The electrical energy compressor is running. In addition
refrigeration circuit are shown in used to operate the compressor is to heat pump water heaters, this
Figure 2-1. also converted to heat and added basic refrigeration cycle is used in
to the refrigerant. The temperature many other types of devices such as
To describe how this cycle works, a of the refrigerant gas leaving the refrigerators, freezers, water coolers,
quantity of refrigerant will be followed compressor is usually in the range dehumidifiers, air conditioners, deli
through the complete cycle. of 120º to 170ºF, depending on the cases, vending machines and many
operating conditions. types of heat pumps for specific
The cycle begins at station (1) HVAC applications.
as cold liquid refrigerant within The hot refrigerant gas flows into
the condenser at station (3). Here it Figure 2-2 shows the three primary
energy flows involved in the
refrigeration cycle. The first energy
Figure 2-1 input is low-temperature heat
refrigerant flow absorbed from the surrounding air
into the refrigerant at the evaporator.
medium temperature compressor high temperature The second energy input is electrical
low pressure high pressure
VAPOR energy flowing into the compressor
VAPOR
whenever it is operating. The third
energy flow is the heat output from
the condenser, which is transferred
to the water in the storage tank.
2
evaporator
condenser
SOURCE SINK
media 1 3 media The first law of thermodynamics
states that, under steady state
conditions, the total energy input
4 rate to the heat pump must equal
the total energy output rate. Thus,
low temperature thermal medium temperature the sum of the rate of heat absorbed
low pressure
expansion high pressure from the air surrounding the heat
LIQUID LIQUID pump water heater, added to the
valve
rate of electrical energy input to
(TXV)
the compressor, must equal the
rate of energy dissipation from the
7
refrigerant at the condenser. This is
Figure 2-2 electrical depicted by the arrows in Figure 2-2.
power input
(Q2) higher- The basic refrigeration components
low-
compressor temperature represented in Figures 2-1 and
temperature
heat 2-2 are present in all heat pump
heat
absorbed dissipated water heaters. There is also a fan
from source to load to blow air across the evaporator
(Q1) (Q3) coil. The size and placement of
evaporator
condenser
these components relative to each
other is determined based on the
“compartment” into which they must
fit, as well as the heating capacity of
the heat pump water heater.
thermal
expansion In a typical residential class heat pump
valve water heater, most of the refrigeration
(TXV) components are housed in a module
that’s attached to the top of a tank,
as shown in Figures 2-3a,b.
Q1 Q2 Q3
The condenser portion of the
refrigeration circuit consists of metal
tubing that is either immersed in the
tank water or wrapped around and
bonded to the outside of the steel
Figure 2-3a refrigerant circuit piping water tank. In either case, heat is
fan transferred from the hot refrigerant
compressor
gas passing through the tubing to
the water in the tank.
room air cool air Figure 2-3b
entering leaving
evaporator coil
condensate drain
expansion device
thermostat
hot water
element
T&P
relief
valve
Courtesy of True Blue Mechanical, Newark, DE
condenser
coil
insulation
cold
water
8
hot
Figure 2-4a
water
outlet
fan
evaporator air filter
cool air
leaving
room air
entering
temperature
sensor
drip pan
cold
condensate water
drain supply
compressor circulator
expansion valve condenser
storage tank
Figure 2-4b
DHW
charge
mixing
charge
valve
check
valves
thermocline
discharge
recirculation
discharge
discharge
charge
storage tanks
A small fan is used to move air surrounding the unit Commercial-scale heat pump water heaters have larger
through the evaporator coil. versions of the basic refrigerant system components but
typically do not have an integrated storage tank. The
Some heat pump water heaters also have serviceable air condenser is housed in the same compartment as the
filters to keep the surface of the evaporator coil as clean other refrigeration system components, and domestic
as possible. Most residential HPWHs also have one or two water is circulated between the heat pump and one or
electric-resistance heating elements that can provide auxiliary more storage tanks. Figure 2-4a shows the concept.
or backup heating if the refrigerant circuit requires servicing.
9
Figure 2-4c Figure 2-4c shows an example of a system piped in this
configuration and prefabricated on a skid so that it can be
placed as a single unit.
COEFFICIENT OF PERFORMANCE
The primary advantage of using a heat pump water heater
in comparison to an electric-resistance water heater, is
that the majority of the heat added to the water came
from the air surrounding the heat pump, rather than being
Figure 2-4b shows a configuration where two HPWHs created by an electric-resistance heating element (as it
supply three thermal storage tanks. The three tanks are would with a standard electric water heater).
piped in series. This helps create a “thermocline” region
that separates the hot and cold water within the tanks. This advantage can be expressed as the coefficient of
When the heat pumps are running and the flow through performance (COP), which in the case of a heat pump
them is greater than the demand for domestic hot water, water heater can be expressed as follows:
flow through the tanks is from left to right. This supplies
the heat pumps with the coolest water in the storage Formula 2-1:
system, which increases their coefficient of performance Formula 2-1a
(COP). When the heat pumps are off, or when flow to the Qw
building’s hot water distribution system is greater than COP =
the flow through the heat pumps, flow through the tank 3.413 ( Pe )
assembly will be from right to left.
Formula 2-1b
Btu
Figure 2-4d Qw 30,000
COP = = cold water supply
hr =
3.413 ( Pe ) Btu / hr
check
3.413 (2400 watt )
mixing valves watt
valve
Formula 4-1a
DHW recirculation loop
air-to-water
heat pump water heaters
Formula 4-1b
H = 8.33( v )(Ts − Tc )
Formula 4-2b
Formula 4-2c
Where:
COP = coefficient of performance (a unitless number) Figure 2-6
Qw = rate at which heat is added to water in storage tank
hot cold
(Btu/hr) water water
output supply
Pe = electrical power input to operate water heater (watts)
3.413 = conversion factor to change watts to Btu/hr hot
water
Formula 2-1a output
condenser
12
provide a major contribution. Merely
switching from gas water heaters Figure 3-3
to HPWHs will not decarbonize the
grid. For decarbonization efforts to
be meaningful, the electric utilities
must incorporate a larger portion of
renewable energy power plants into
the grid. Often, a regional electric
grid will still have a mix of fossil
fuels as part of the overall energy-
generation network. The regional-
scale decarbonization of the electrical
grid is a much bigger topic than can
be addressed in this journal.
Source: US EPA
carbon emissions are taxed at an
increasing rate, per ton of CO2
emissions. Vancouver is an example
of a city that is phasing out natural gas
service to new buildings. Essentially,
the status quo of consuming fossil tell if policy-driven decisions will While the Texas interconnect is
fuel-based energy for DHW will be push HPWHs to a similar adoption independent of the other states and
increasingly expensive. The policies trajectory. is able to determine the ideal power
currently in effect, or on the horizon, plant mix, there are significant strides
will require consumers to either pay Not all jurisdictions are pushing for to be taken at the grid level to
the carbon tax or pay to install more decarbonization. According to the accommodate HPWHs and electric
energy-efficient water heating systems. American Council for an Energy- cars if customer demand moves in
Efficient Economy, in some U.S. that direction.
From a policy perspective, there is States, consumers are discouraged
a parallel in the U.S. automotive from disconnecting their current gas For decarbonization to be an effective
industry. Federal and state energy- service. The rationale is often related long-term solution for water heating it
efficiency standards are pushing car to concerns that shifting gas water must dispel the concern that it will
and truck manufacturers to increase heaters to electric would increase overwhelm the grid. Modernization
the average miles-per-gallon of the potential for brownouts within an of the electrical grid is an important
gasoline efficiency in their fleets. Most already overloaded electrical grid. As step to reduce waste and improve
major car companies are phasing in an example, a utility company may reliability. Best practices in domestic
hybrid gas/electric and all electric be forbidden from providing financial hot water delivery will help deliver an
automobiles quickly, as a way to incentives to customers who want to energy-efficient and reliable future.
comply with these benchmarks. disconnect gas service and switch to
electric-resistance heating, cooling FINANCIAL INCENTIVES
While energy policy is likely not the and water heating technologies In the United States as of January
major decision point for automobile unless specific criteria are met. 2023, ENERGY STAR-eligible water
buyers, increased competition in the heaters purchased and installed
electric car segment has led to an There are three energy grids in between 2023 and 2032 are eligible
increased number of less-expensive the United States: western states, for a tax credit of 30% of the
options for electric vehicles, spurring eastern states and Texas. The eastern installation cost, up to $2,000. Local
competition. According to the Edison and western grids are able to share governments and utility companies
Electric Institute, in the U.S., “It took electricity regionally to better avoid may offer additional incentives.
eight years to sell 1 million electric brownouts and incorporate a large Verifying eligibility for financial
vehicles and fewer than three years mix of power plant technologies. incentives is an important factor
to sell the next million.” Time will Texas is an islanded electrical grid. for HPWH adoption and may help
13
offset some of the costs associated
with a changeout of a water heater. Figure 3-5
Depending on utility costs and usage off on off on off
rates, HPWHs might still have the peak peak peak peak peak
lowest lifetime costs without rebates.
DSIREUSA.org is a zip code-based 0.40
search engine to help find current
$/KWHR cost
rebate information. 0.30
2 PM
4 PM
6 PM
10 PM
midnight
8 AM
8 PM
4 AM
2 AM
noon
midnight
6 AM
10 AM
million households in the U.S. are
in this category. Smaller electric
service panel sizes and amperage
services worked fine with fossil fuel-
fired appliances. That may not be
the case as we switch the market an example, “low nitrous oxide (NOx)”
EQUIPMENT MANUFACTURER
to electrification of the buildings.” emissions were a benchmark for
CHANGES AND REQUIREMENTS
Upgrading the electrical service to gas appliances. Subsequently, “ultra-
The U.S. Department of Energy’s
buildings that are moving to HPWHs low NOx” emission requirements
ENERGY STAR ® program
may be a prerequisite to installation were enacted. In the future,
administers water heater energy-
and can be costly. Product selection, ENERGY STAR could adopt “zero
efficiency standards. Specific
related to input voltage requirements, NOx” requirements, which would
ENERGY STAR certification is
and water storage temperature set effectively exclude all gas appliances
required for products to qualify them
points are two variables that can from receiving the certification. In
for rebates or by the local authority
potentially reduce the electrical panel the current trajectory, water heater
having jurisdiction for use in new
upgrade requirement. These are manufacturers are working diligently
construction. There is enormous
discussed later in this journal. to ensure they have a wide range
leverage to steer the water heating
of HPWH product offerings to stay
market based on these standards. As
ahead of the curve.
Figure 3-4
14
Similar to charging an electric car overnight, HPWHs can specification. This is a unified communication technology
integrate with the grid and avoid heating water during that allows utility companies to react to demand trends
peak electrical demand periods. In many regions of the by sending a signal to CTA 2045-enabled water heaters,
world, demand for electricity is high in the morning and thus shedding some of the electrical load for a period.
throughout the late afternoon and evening. These are the
times when people are getting ready for work and arriving As an alternative, non-grid-connected option, water
back home. heaters can be scheduled with different setpoints during
the day to reduce the amount of water heating cycles
In the conceptual example shown in Figure 3-5, a utility during known peak times of day. Point-of-distribution
company charges different prices for electricity depending mixing valves can be used to ensure a consistent delivery
on the time of day. Essentially, if customers can avoid temperature to occupants in systems where the storage
using excess electricity during peak periods, they will pay temperature fluctuates, as detailed in the next section.
less for the same amount of energy. Scheduling electrical
appliances to start, operate or charge during the non-peak The HPWH industry is quickly evolving. Globally, the
times is possible and advisable with current technologies demand for more energy-efficient methods for heating
and consumer behavior changes. domestic water is rising. For a variety of reasons, HPWHs
will gain market share in the years to come. The next
Specific to water heating, industry stakeholders are section will describe the general evaluation process to
developing a load-shifting communication protocol determine how to best utilize HPWH technologies.
originally called EcoPort, now the CTA 2045 technical
15
4. EVALUATING WHEN A HEAT PUMP WATER HEATER MIGHT BE A GOOD FIT
Figure 4-1
vehicle
stop
16
Figure 4-2
Guidelines for space surrounding HPWHs (verify with specific manufacturer)
or as specified by manf.
ducted discharge air ducted intake & discharge air
min. free area of louvers 100 sq. inch
ducting ducting
upper louvered door
Figure 4-1 shows and lists several considerations when piping. Nearly all codes require gas-fired water heaters
planning the location of a typical residential heat pump that are located in garages to be on elevated platforms to
water heater. Always consult with the authority having prevent contact with gasoline or other fuels that might be
jurisdiction for local compliance, as well as equipment spilled on floors.
manufacturers for specific installation requirements
Electric-resistance water heaters and HPWHs do not have
Fuel type can also dictate location. Gas water heaters the constraints associated with fuel supply and venting
require access to a gas service line and the ability to for gas-fired water heaters. They have an installation
vent the products of combustion. Gas water heaters also advantage in that they can often be located in relatively
are constrained by the maximum allowed length for vent small closets or under sink vanities.
17
HPWHs need more space based HPWHs include the following: HPWH decreases when absorbing
on their airflow requirements. This heat generated by another device
is a major prerequisite for proper • A large space having a minimum for space heating.
performance. If a HPWH is installed volume determined by HPWH size
in the same space that would have and manufacturer, with unobstructed Examples of “surplus” heat include
been used for a similar-sized electric- airflow to the unit. low-grade heat in outdoor air,
resistance water heater, it could • A closet installation with a fully excess solar heat gains inside
drastically limit performance. louvered door or a combination a building, low-grade heat in an
of upper/lower louvers, per unconditioned basement or garage,
An ideal location for a HPWH would manufacturer requirements. or heat generated by equipment
be in the middle of a large interior • Inlet/outlet ducting to another or processes in a commercial
space that maintains itself at or space or outside, similar to a gas building. These sources of heat are
close to normal indoor temperatures. appliance. a byproduct of how the building
However, this is seldom possible is configured or used, rather than
because building space is expensive, Figure 4-2 shows some of these heat intentionally produced by the
and most occupants would much options. Different HPWHs have building’s heating system.
rather locate mechanical equipment specific airflow and placement
in the smallest and least usable requirements set by their Figure 4-3 shows the concept of
space within a building. manufacturers. Such requirements “cascading” heat pumps (e.g., where
take precedence over the conceptual the HPWH absorbs heat placed in its
In many cases, water heaters are guidelines shown Formula
in Figure 4-2.2-1a vicinity by another heat pump).
placed in minimally heated mechanical
spaces that are separated from SOURCE OF ABSORBED HEAT Heat pump Q1w is absorbing free heat
occupied spaces. These locations There are situations in which a COP =
from outside the building, combining
minimize noise transmission to HPWH placed in a conditioned space it 3.413
with heat ( Pe ) from electricity,
derived
occupied spaces and keep the absorbs heat supplied by a furnace, and sending that heat inside the
equipment out of sight. Most HPWHs boiler or heat pump used to heat that building. Heat pump 2 is a HPWH.
can be so located, provided that space. Effectively, the space heating It absorbs heat that was placed
adequate airflow and surrounding air Formula 2-1b
system is providing most (or all) of inside the building from heat pump
temperatures are ensured. the heat absorbed by the HPWH. 1, combines it with more electrical30,000 B
While the wire-to-water efficiency Qwsends combined energy
energy, and h
There are ways to provide for of the HPWH might be excellent COP =
into domestic = the tank.
water within
adequate airflow, while still partially based on absorbing “surplus” heat 3.413 ( P ) Btu / hr
enclosing the HPWH. Common not specifically generated for space The net COP of
e
this 3.413
cascading heat (
options for self-contained residential heating, the net efficiency of using a pump system can be determined: watt
Formula 4-1
Figure 4-3 Formula 4-1a
electric electric
energy energy
input 1 input 2
free
heat (space heat)
COP1 COP2 Where:
Formula 4-1b COP net = the overall COP of the two
heat cascaded heat pumps
heat pump 1
pump 2 COP1 = the COP of the space heating
(space heat)
(DHW) heat pump (must be > 1.0)
QDHW COP2 = the COP of the heat pump
water heater (must be > 1.0)
Formula 4-2a
18
H = 8.33( v )(Ts − Tc )
watt
Note: To use this formula, both COP 1 and COP 2 must may dislike the drone of a HPWH fan or gas appliance
be > 1.0 blower. Whenever possible, it is best to avoid placing any
mechanical equipment, including HPWHs, adjacent to
For example, if a heat pump provides space heating to bedrooms, offices or other spaces that are intended to
a building while operating at a COP of 4.0, and a heat remain quiet. Many hours of design and installation labor
pump water heater within that building only absorbed heat can be required to relocate or otherwise address mechanical
produced by the space heating heat pump while operating equipment after it has been installed without regard to the
at a COP of 3.0, the net COP, defined as the heat added sound it creates, which often leads to complaints from
to the domestic water divided by the total electrical input occupants. The ability to duct the airflow required by
to enable that heat placement, would be: HPWHs to and from locations away from occupied spaces
can help alleviate thermal discomfort and noise issues.
3.6
heat, and thus the long-term net COP will likely be higher
than the above calculation implies. Still, the concept of
20
= 8.33(60)(120 − 62) = 28,988 Btu
“cascading heat pumps” shown in the previous example
demonstrates that placing a HPWH within the heated
3.4
19
s
Ts − Tc
=
Figure 4-5
Courtesy of NEEA
The Northwest Energy Efficiency
Figure 4-6 Alliance (NEEA) provides guidance for
slope for HPWH installation locations, related
drainage
to International Energy Conservation
Condensation drainage options
Code (IECC) climate zones across
above
grade
the U.S. The map in Figure 4-5 is
useful to identify installation location
possibilities and should be used in
conjunction with HPWH manufacturer
guidelines and local building codes.
CONDENSATE MANAGEMENT
All HPWHs create condensate. It
condensate drainage tube
20
A floor drain in reasonable proximity
to the HPWH is ideal. If a floor Figure 4-7a
drain is not available, a small
automatically operated condensate
pump, such as used for residential
air conditioning systems, can be
used to route the condensate
to another drain or outside the
building. In the latter case, the
DHW
condensate drain tube should end
above grade and be sloped to temperature
avoid freezing in winter. sensor
recirculation
TANK SIZE
The volume of the storage tank in
a HPWH is an important selection
consideration. Larger storage
volumes typically increase the larger storage w/ lower capacity HPWH
amount of hot water the unit can
deliver, based on the unit’s first
hour rating. One downside to a
larger tank is increased standby vary by project. In Figure 4-7a, a
heat losses, which increase cost of STORAGE TEMPERATURE AND POINT-
system is designed with a larger heat OF-DISTRIBUTION MIXING VALVES
operation without providing a benefit pump and minimal storage. In Figure
for building occupants. Additionally, All HPWHs have an adjustable water
4-7b, a system is sized with larger temperature setting. Increasing the
larger storage can increase the storage but a smaller HPWH. Both
installed cost of the system. The storage temperature of a water
are acceptable designs. Consult heater increases its ability to deliver
balance between ideal water storage with heat pump manufacturers for
volume and heat pump output will hot water to the building. It may
specific sizing guidance.
21
HPWH operating cycles without regard to time-of-use electric rates
Figure 4-8
off-peak heat pump on cycles
power demand (KW) on-peak
4
2
0
4 PM
noon
10 PM
8 PM
midnight
2 PM
8 AM
6 PM
2 AM
6 AM
10 AM
midnight
4 AM
also allow for a smaller tank. In Point-of-distribution mixing valves temperature, the call for heat ends.
some installations, the minimum allow the tank temperature to be set The temperature of water delivered
storage tank temperature may also higher or for the tank temperature to to the building fluctuates slightly,
be mandated based on avoiding fluctuate while maintaining a consistent within the temperature differential
Legionella bacteria growth. and safe outlet temperature. of these on/off cycles. Often, the
differential is small and remains
Point-of-distribution mixing valves Here are three of the most common unnoticed by building occupants.
are highly recommended whenever design options for consideration: No point-of-distribution mixing valve
the temperature setting of the water is used, but point-of-use ASSE
heater is above 120ºF, or higher than 1. Baseline example, fixed 1070 may still be recommended
otherwise allowed by code or other temperature setpoint. No point-of- (or required) by local codes or
applicable regulations. distribution mixing valve. regulations.
Two different types of mixing valves 2. Elevated fixed setpoint. Point-of- Figure 4-8 shows a conceptual
can be used in systems with elevated distribution mixing valve is added cycling pattern for the HPWH.
storage temperatures. Point-of- to lower the outlet temperature,
distribution (POD) mixing valves listed effectively adding heat storage The mathematical area of the black
to ASSE 1017 are designed to deliver capacity without increasing the size rectangles represents electrical
consistent water temperatures to the of the tank. energy input to the HPWH. Notice
building’s plumbing system by mixing that much of the energy input
hot and cold water. These devices 3. Variable setpoint. Scheduled to occurs during peak electrical rate
are designed for high flow rates. They avoid peak utility rates or coordinate periods. The length of the on-cycle is
are not scald protection devices. with real-time utility information. A determined primarily by the demand
Point-of-use (POU) mixing valves point-of-distribution mixing valve is for hot water at fixtures.
listed to ASSE 1070 are designed to added to lower the mixed outlet
prevent scalding at the fixtures. temperature, effectively adding An advantage of this control method
energy storage capacity without is that it is simple and requires the
Point-of-distribution mixing valves are increasing the size of the tank. minimum amount of components. A
a useful, adjustable part of a HPWH disadvantage is that it does not take
system. It is easier and typically less Design option 1 is typical in many advantage of time-of-use utility rates.
expensive to add a POD mixing water heater installations, especially Based on typical residential usage,
valve, or adjust the temperature new construction projects. A simple most of the electrical energy used by
setting of such a valve, than to aquastat or tank sensor calls for a HPWH falls within the peak time-of-
install a larger HPWH, especially if an heat when the water temperature in use utility rate windows. For utilities
electrical service upgrade is required the tanks drops slightly. When the offering time-of-use electrical rates,
for the latter. tank rises slightly above the setpoint the cost of electrical energy supplied
22
Figure 4-9a Conceptual variation in water temperature for HPWH operating cycles
using elevated storage temperature during off-peak periods combined
with point-of-distribution mixing.
130
water temperature (ºF)
125
temperature in storage (ºF)
120
115
temperature leaving point-of-distribution mixing valve (ºF)
110
Figure 4-9b
tight temperature control provided by electronic mixing valve
130
water temperature (ºF)
125
temperature in storage (ºF)
120
115
temperature leaving point-of-distribution mixing valve (ºF)
110
during peak demand periods is often substantially higher temperature increases the tank’s hot water delivery
than during off-peak times. capacity without increasing tank size. The mixing valve
provides a safe and consistent temperature to the fixtures
This type of loading is also a concern for utilities that are throughout the day. A disadvantage is that the COP of the
trying to decarbonize their energy offerings. For example, HPWH is slightly reduced when operating at higher water
if all the gas-fired water heaters were switched to HPWH temperatures.
systems operating primarily during peak demand times,
utilities would face major overloading, possibly leading to In Figure 4-9a, the HPWH setpoint is higher than the
brownouts or other large-scale grid reliability issues. temperature required at the fixtures. The difference
between these temperatures is constrained by the
Design option 2 adds a point-of-distribution mixing minimum temperature difference required between the hot
valve between the HPWH hot water outlet and the inlet and the mixed outlet of a mixing valve.
domestic hot water fixtures. The tank water is stored at
a higher temperature than the baseline design option 1. Some point-of-distribution mixing valves, typically
An advantage of this scenario is that the higher storage electronic mixing valves, do not have minimum temperature
23
3.413 ( P ) Qw
COP = e
Formula 2-1b = Btu / hr
Formula 2-1b 3.413 ( Pe ) 30,000Btu
Formula 2-1b COP =
Qw 3.413 Btu
30,000 hr
Q =
= 3.413w ( Pe ) =30,000
COP 4-1b Btu
Btu / hr hrwatt
FormulaQw 3.413 ( Pe ) 3.413 (2400 wat
Btu / hr
COP = = 3.413 hrwatt (2400 = 3.66
wat
3.413 ( Pe )stored in aBtutank-style
The heat / hr watt water
Figure 4-10 Formula 4-1aheater can be determined
3.413 using(2400 watt )
Formula
Formula 4-1a watt
4-2a.
Formula 4-1a
Formula 4-1a Formula
Formula 4-2a:
4-2a
H = 8.33( v )(Ts − Tc )
FormulaFormula
Where:4-2b
4-1b
Formula 4-1b
Formula H = heat stored in tank water (Btu)
4-1b
Formula 4-1b 8.33 = Btus required to raise 1 gallon of
H = 8.33(60)(120 − 62) = 28,988 Btu
water 1ºF 120
35º V = tank volume (gallons)
Ts = average temperature of stored hot
35º
37º
FormulaFormula
water 4-2c
4-2a (ºF)
37º
42º Formula 4-2a
Tc = cold-water inlet temperature (ºF)
47º Formula 4-2a H = 8.33( v )(T − T )
42º
47 º 52º
Formula 4-2aConsider
H = 8.33(H )(T= 8.33(60)(130
a v130
s
60-gallon
c − 62) =at33,986 Btu
− T )tank maintained
s c
an average temperature of 120ºF. The
52º 57º H = 8.33(
Formula 4-2bv )(Tstored
heat − Tc )in this tank’s water would be:
FormulaFormula
s 4-2d
57º 62º H = 8.33( v )(Ts − Tc )
4-2b
62 º
Formula 4-2b H130 33,986 Btu
67 º
67º
H120 = 8.33(60)(120
= 1.172 Btu
− 62) ==28,988 ≈ 17% increa
72º H120 28,988
H = 8.33(60)(120 Btu= 28,988 Btu
− 62)
72º
Formula 4-2b 120
35º H120 = 8.33(60)(120
If the average − 62) = 28,988
storage Btu
temperature was
Formula 4-2c increased from 120ºF to 130ºF, the heat
Formula
Formula 4-2c 4-3a
stored in the same tank would be:
Formula 4-2c H120 = 8.33(60)(120Hs Ts − T−c 62)−= 62) = 28,988 Btu
H130 = 8.33(60)(130 = 33,986 Btu
H130 = 8.33(60)(130
Hb Tb − Tc− 62) = 33,986 Btu
H130 =4-2d
Formula 8.33(60)(130 − 62) = 33,986 Btu
difference requirements between the hot inlet and mixed Formula 4-2c
Formula 4-2d 4-3b
Formula
outlet streams. An example of this would be a ball- The4-2d H130 33,986
percentage increase inHstored Btu
control, element style electronic mixing valve. This Formula
is H = 33,986 Theat
(Btu − Tcwould
) (140
s = 1.172
be:
≈ − 62)
17% increase
H120
130
= 28,988s
= Btu = =
1.172 ≈ 17% = 1.345 ≈ 34
increase
advantageous because the storage temperature does H130 33,986 H b (Btu Tb − Tc ) (120 − 62)
H Btu28,988
not necessarily have to be higher than the desired hot = H130 120 = 8.33(60)(130
= 1.172 ≈ 17% increase − 62) = 33,986 Btu
water delivery temperature. During periods of heavy DHW H 28,988
Formula Btu
5-1a
Formula 4-3a
120
demand, this approach can maintain a consistent delivery
Formula 4-3a
temperature while extracting more heat from the tank. Formula 4-2d
This increase canH s be approximated
Ts − Tc using the chart in
Formula 4-3a = TCOP = (2 × COPHP − 1)
Figure 4-11a. H − T
OPERATING THE HPWH AT HIGHER H−H Tbs − Tcc e
Tb33,986 Btu
s
b =
STORAGE TEMPERATURE H T H T − Tbec simplified
TheFormula
heat sstorage
130
b c = can
s formula
= 4-3b = 1.172
and ≈ 17% incr
generalized
How does the warmer storage temperature boost the H
to determine T H
Formula
the
Formula 4-3b120
b b
− Tratio
c
of28,988
5-1b stored heat Btu for any average
effective hot water delivery capacity of the system? As an storage temperature H s relative
(T −to Tc any
) baseline
(140 − 62) condition and
example, consider a project being designed for Atlanta, Formula
any4-3b
tank volume,H = (Ts by
as given TFormula
) = (140 4-3: = 1.345 ≈ 34.5% inc
H bs = (TbCOP −
s − Tce )= (2 × COP
(120 −
− 62)
62) −=1) = (2≈× 34.5%
3 − 1) =inc
5
Georgia. c = HP 1.345
Formula H s 4-3a
Formula 4-3: (T T
s H bc
− ) (T(140 − T−) 62)(120 − 62)
Formula = 5-1a = b c = 1.345 ≈ 34.5% increase
Start by determining the average groundwater temperature H b (Tb − Tc ) (120 − 62)
from the map in Figure 4-10. Formula 5-1a
Formula 5-1a
Hs Ts − Tc
For Atlanta, the average groundwater temperature is
=
COPe = (2 × COPHP − 1)
62ºF. Assume that this is the cold-water temperature
H COP T − Tc − 1)
b e = (2b × COP HP
supplied to the water heater. COPe = (2 × COPHP − 1)
Formula
Formula 4-3b
5-1b
Formula 5-1b
Formula 5-1b HCOP (T − Tc )HP − 1)
s e = (2s × COP (140= (2−× 362)
− 1) = 5
= = (2 × COPHP − 1) = (2 × 3 − 1) =
= = 51.345 ≈
24
HCOP e
(T − T ) (120 − 62)
COPe = (2 ×b COPHPb− 1) =c (2 × 3 − 1) = 5
Formula 2-1a
Qw
COP =
3.413 ( Pe )
This increase could also be
Figure 4-11a approximated using the chart in
Formula 2-1b
Btu Figure 4-11b.
Qw 30,000
COP = = hr = 3.66 If the temperature were increased
3.413 ( Pe ) Btu / hr
3.413 (2400 watt ) to 140°F, it would add 34% to
watt the effective capacity. This would
essentially make a 60-gallon water
heater, storing water at 140°F,
Formula 4-1a
deliver the same amount of hot
water in a parallel drawdown as
an 80-gallon tank storing water
at 120°F. The space-saving and
cost-reducing potentials of this
approach are significant. It also can
allow for better demand response
Formula 4-1b scenarios with electrical rates.
25
COPe = (2 × COPHP − 1)
utility. The goal is to minimize
Figure 4-12 electrical demand during
on-peak times. This has the
HPWH operating cycles without regard to time-of-use electric rates combined effect of reducing
operating cost to the building
off-peak heat pump on cycles
on-peak owner, while also benefiting
power demand (KW)
relates to maintenance,
standby heat losses and the
0
4 PM
noon
10 PM
8 PM
midnight
2 PM
8 AM
6 PM
2 AM
6 AM
10 AM
midnight
4 AM
point-of-distribution mixing
130 valves, water heater
temperature in storage (ºF) manufacturers can design their
125 equipment with ASSE 1082 or
1084 compliant technologies
to limit the point-of-
120
distribution temperature. These
technologies can be used in
115 place of an ASSE 1017 point-
temperature leaving point-of-distribution mixing valve (ºF) of-distribution mixing valve.
110 ASSE 1070 point-of-use mixing
valves could still be required,
depending on the jurisdiction.
power demand (KW)
4
2
0
10 PM
8 PM
midnight
2 PM
8 AM
6 PM
2 AM
4 AM
6 AM
midnight
10 AM
26
POINT-OF-USE MIXING VALVES
Figure 4-14 ASSE 1070 valves are
temperature-limiting devices
designed to protect end-users
from hot water scalding. They
are also designed to prevent
the flow of water from the
mixed water outlet in the event
of the failure of hot or cold
supply. The size of the valve is
generally smaller than a point-
of-distribution valve because it
is required to stop the flow of
hot water quickly. Unlike a point-
of-distribution mixing valve, the
point-of-use valves are designed
to protect a single fixture or a
small group of fixtures.
Figure 4-15a
140 ºF
cold
water
27
Figure 4-15b
140 ºF
dishwasher
cold
water
codes or other regulations. Occupant DOMESTIC HOT WATER piping, reduces heat loss and the
safety is always the primary concern RECIRCULATION excessive cycling of the water heater.
upon which these codes or In an ideal domestic hot water However, omitting DHW recirculation
regulations are based. Scalding can delivery system, heated water systems may result in extended wait
occur quickly, as shown in Figure emerges from a faucet the moment times for hot water at fixtures, which
4-14. it is opened. There would be no wait is undesirable and also leads to
for cooler water to be purged from excessive water waste.
In some HPWH applications, a the piping ahead of heated water
point-of-distribution mixing valve is delivery. This desirable condition can Poorly designed or inadequately
not used. The temperature of the be closely approximated through use insulated hot water recirculation
stored water may be elevated above of a recirculating domestic hot water systems can create unnecessary
a desired (or mandated) maximum delivery system. cycling of water heaters, thus wasting
delivery temperature. In these energy. This effect is potentially more
situations, point-of-use mixing valves There is an important balance to noticeable in systems using HPWHs
should be used at each fixture or establish in recirculating domestic hot due to their reduced heating capacity/
small grouping of fixtures, as shown water systems: minimizing wait times recovery rate relative to gas-fired water
in Figure 4-15a. for hot water at the fixtures while not heaters. This is especially true during
wasting energy in the recirculation periods of high hot water demand or
It is also possible to send water at loop. In concept, DHW recirculation in systems with excessive heat loss
higher temperatures to a dedicated increases the total heat loss from the from a recirculating piping loop.
load, such as a dishwasher, while still hot water delivery system. Holding
using point-of-use mixing for all other the heated water in a well-insulated In some situations, hot water
fixtures, as shown in Figure 4-15b. storage tank, rather than distribution recirculation to all fixtures is not
28
Figure 4-16b
justified. As an example, if a warehouse has a single
mop sink located far from the water heater, a small,
dedicated point-of- use water heater at the sink would
save installation time and cost. It would also reduce
energy losses compared to circulating hot water over
long distances.
29
AIRFLOW The main decision points for ducting PIPING
HPWHs need an adequate supply of outside air to the HPWH relate to Installers should examine the piping
air to operate at peak performance. climate. In a high alpine environment, to an existing water heater to
In a retrofit application, this could the COP of the HPWH may be determine if improvements can be
mean “unboxing” the mechanical significantly lower if ~40°F air is the made at the same time as the water
space. When replacing existing water source of absorbed heat. Ducting heater replacement. The issue of
heaters that were installed in closets supply air from the outdoors in a wasteful DHW recirculation piping
or small mechanical spaces, verify the warm climate may lead to a higher in existing buildings will not be
minimum volume of the space with the COP, compared to absorbing heat remedied by replacing the existing
HPWH manufacturer’s requirements. from the cooler, conditioned air within water heater with a HPWH. A poor
If the minimum volume is not met, the building. DHW recirculation system may be
one possibility is to add louvers to the revealed when a HPWH is installed,
mechanical room doors. A few ideal Equipment service clearances should if not accounted for in the retrofit
locations for louvered doors would be also be checked. Avoid installing work. With any equipment upgrade,
in an adjacent exterior hallway/atrium HPWHs in areas that generate reassessing pipe insulation, mixing,
that has solar gains from windows considerable dust (e.g. a basement balancing and other componentry
or in a computer server room that woodshop). The dust will quickly is critical. Additionally, the cost and
may have a high cooling load. A accumulate on the filter screen. If complexity of making changes to
few undesirable location examples the screen is not frequently cleaned, the hot water distribution system will
would be louvered doors connecting the performance of the heat pump often be lower if done at the same
to bedrooms, offices or living spaces will decrease due to reduced airflow. time the water heater is replaced.
where occupants may be impacted If the screen is removed, the dust
by the cool air leaving the HPWH or will accumulate on the evaporator The heat loss of an existing recirculation
by the sounds of the equipment. coil where it would be difficult or loop should also be evaluated to
impossible to remove. determine next steps in a retrofit. This
Because it creates the potential is especially important with HPWHs
for condensation, avoid ducting a Installers should also ask owners because if the heat loss of the
HPWH system to an attic. A general about any issues related to their recirculation is similar to the output of
recommendation is to terminate current water heater when considering the HPWH when in heat pump only
the ductwork outside the building a HPWH. For example, does the mode (as opposed to hybrid mode,
envelope. current system create objectionable where electrical resistance heating
noises or does it take a long time for is also operating), the heat pump
When replacing a gas water heater hot water to reach certain fixtures might need to operate whenever the
with a HPWH, there may be existing when first used in the morning? recirculation pump is on.
ductwork for supplying combustion These insights help guide placement
air. That ducting may be reusable for of a replacement water heater in It is important to know the rate
a HPWH installation, depending on a way that minimizes or eliminates of heat loss from a recirculating
the diameter and total equivalent feet undesirable existing issues. DHW loop. The following example
of the ductwork. demonstrates that this is a relatively
CONDENSATE easy calculation.
An advantage of using ducted outside Ideally, the condensate produced by a
air for a HPWH is that the absorbed HPWH would flow by gravity through Assume that an existing recirculation
heat is coming from outside the a pipe to a suitable drain. When this loop operates at an average
building envelope. This reduces the isn’t possible, one option is to install water temperature of 120ºF. The
possibility of thermal discomfort near a condensate pump that would recirculation piping has a total length
the equipment. A downside to outdoor collect and expel any condensate of 300 feet through an unconditioned
ducting is the added installation produced by the HPWH. There may crawl space where the air temperature
time and cost. It is also important to also be a possibility of connecting is 55°F. The entire recirculation loop
consider that if only the exhaust air the condensate drainage tube from is piped with bare ¾” copper tubing.
from the HPWH is ducted outside, a the HPWH to a condensate drainage Figure 4-16 can be used to estimate
negative air pressure could be created pipe or pump that serves an existing the rate of heat loss from each foot
in the space, drawing more outside air air conditioning system or other type of bare copper water tubing based
through the building envelope. of heat pump. on the difference in temperature
30
branches of the domestic hot water
Figure 4-17 system. The recirculation pump will
heat loss (Btu/hr/ft) for
bring water around the piping circuit
BARE COPPER TUBING
through the path of least resistance.
100 2" tube
This can create high velocity through
certain risers or laterals, which can
80 1.5" tube lead to pinhole leaks. In the service
heat loss (Btu/hr/ft)
31
Figure 4-19
30 amp
15 or 20 amp 15 or 20 amp
240 VAC
120 VAC 120 VAC other recepticles
dedicated circuit
dedicated circuit shared circuit
serviced by a dedicated 120V circuit. model designed for a dedicated 120V offset by operating them at higher
Recognizing this, some HPWH /15 amp circuit can provide 28 gallons storage temperatures in combination
manufacturers have developed 120V per hour with a 60ºF temperature rise. with an ASSE 1017 listed point-of-
models that could reuse this existing A similar model with the same tank distribution mixing valve to reduce
dedicated circuit. When possible, this size, but intended to be used on a supply water temperature, as shown
reduces installation cost, especially in 120V /15 amp shared circuit can only in Figure 4-20.
situations where a licensed electrician provide 12 gallons per hour across
would have to be hired to install a the same temperature rise. This is TANK SIZE
new dedicated 240V circuit. due to a smaller compressor in the When replacing a gas-fired or
model designed for a shared circuit. electric-resistance water heater
Some manufacturers also offer 120V Most HPWHs that are designed for with a heat pump water heater, it’s
HPWHs that can be plugged into a 240V /30 amp dedicated circuits, important to compare the first hour
shared (rather than dedicated) 120V and are equipped with auxiliary DHW production ratings. It may be
circuit. A retrofit example is shown in heating elements, can provide over necessary to increase the volume of
Figure 4-18. 40 gallons per hour across the 60ºF a HPWH to reasonably match the
temperature rise (see Figure 4-19). recovery rate of the existing water
120V heat pump water heaters have heater — especially if it’s a gas-
lower recovery rates than 240V The slower recovery rate associated fired unit. If a larger tank is selected
models. For example, one 50-gallon with 120V HPWHs can be partially to achieve the desired first hour
32
rating, be sure there is ample space
Figure 4-20 available — especially height — to
accommodate it. When a larger tank
15 or 20 amp 15 or 20 amp
is not possible, consider operating
120 VAC 120 VAC the HPWH at a slightly higher
dedicated circuit dedicated circuit
storage temperature, combined with
circuit
breaker
line circuit
breaker
line an ASSE 1017 rated thermostatic
cord cord
mixing valve to increase the amount
of hot water available during high
demand periods, as illustrated in
Figure 4-19.
33
5. ALTERNATIVES TO HEAT PUMP WATER HEATERS
Although dedicated heat pump water heaters are used for In a typical application, a motorized 3-way diverter valve
most domestic water heating applications and have been directs the flow of hot fluid from the heat pump to either
the primary focus of this issue, there are situations where the heat exchanger within the indirect water heater tank,
other types of heat pumps, primarily intended for space or to other parts of the system intended for space heating.
heating or cooling, can be adapted to domestic water
heating as an ancillary load. This section discusses some In this application, it is imperative to use an indirect water
of the possibilities. heater with a larger internal coil heat exchanger. The
greater the surface area of this heat exchanger, the lower
AIR-TO-WATER HEAT PUMPS USED the fluid temperature exiting the heat pump can be, while
FOR DOMESTIC WATER HEATING still transferring the heat pump’s full heat output to the
One of the fastest growing segments of the global heat water within the indirect water heater. Lower operating
pump market is based on units that extract heat from temperatures increase the heating capacity and COP of
outside air and transfer it to water or an antifreeze solution. the heat pump.
Although these heat pumps are generally intended for
space heating and cooling, they can also provide domestic If no suitable tank can be sourced, it is possible to use a
water heating as an ancillary load. Using them in this properly sized external stainless steel heat exchanger in
manner helps provide a more complete HVAC offering in combination with a standard thermal storage tank.
typical residential applications (e.g., space heating, cooling
and domestic water heating.) When domestic hot water temperatures of 130ºF or more
are required, the domestic hot water leaving the indirect
Figure 5-1 shows an example of a monobloc air-to-water tank can be routed through an auxiliary heater to boost its
heat pump connected to an indirect water heater tank. temperature as necessary.
A heat exchanger within the tank separates a non-toxic
antifreeze solution that passes through the heat pump Some air-to-water heat pumps have internal controls
from the potable water in the tank. that monitor the temperature of the indirect water heater,
cold
diverter water
valve check inlet
valve
space heating
to & from
SEP4
outside
inside
purging
monobloc valves
indirect water heater
air-to-water heat pump
34
and automatically operate the diverter valve and the heat WATER-TO-WATER HEAT PUMPS
pump’s refrigeration system whenever a call for domestic USED FOR DOMESTIC WATER HEATING
water heating is present. These controls can also be Geothermal water-to-water heat pumps can also be
configured to allow the domestic water heating load to configured to provide domestic water heating as an
have temporary “priority” over space heating (or cooling) ancillary load. The piping can be similar to that used for an
when there are simultaneous calls from both loads. air-to-water heat pump, as shown in Figure 5-2.
diverter cold
valve water
(DV1) check inlet
valve
space heating
water-to-water
to & from
heat pump
SEP4
diverter
valve
(DV2)
earth loop
35
valve (DV2) directs flow from the heat pump to either HEAT RECOVERY APPLIED TO DOMESTIC WATER HEATING
a heating load (e.g., space heating or domestic water Water-to-water heat pumps can also be applied in heat
heating) or to cooling. Diverter (DV1) directs heated water recovery applications. An ideal scenario is an industrial
to either the indirect water heater or to space heating. process where both chilled fluid and domestic hot water
are needed at approximately the same time. One example
Some geothermal water-to-water heat pumps can also be would be producing a product such as gelatin. This
equipped with “desuperheater” heat exchangers, which process requires both ice and hot water. The energy used
transfer heat from hot refrigerant leaving their compressor to produce the ice is reduced by any device or process that
to a circulating stream of domestic water. Figure 5-3 can cool incoming domestic water ahead of the icemaker.
shows the concept. Likewise, the energy required for hot water is reduced by
any device or process that can preheat the incoming cold
domestic water. A water-to-water heat pump can do both
of these processes simultaneously. The concept is shown
in Figure 5-4.
See idronics #9 for more information on The effective COP of the heat pump in this type of
geothermal heat pump systems and idronics #13 application can be very high. The reason is that both the
for more information on chilled water cooling. chilled water and preheated domestic water are useful
cold
water
inlet
desuperheater
heat exchanger
stainless steel
circulator
space heating
or cooling
to & from
36
H = 8.33( v )(Ts − Tc )
Formula 4-2b
Formula 4-2a
H120v=)(8.33(60)(120
H = 8.33( Ts − Tc ) − 62) = 28,988 Btu
Figure 5-4
H s (Ts − Tc ) (140 − 62) As is the case with any mechanical equipment, proper
= COPe = (2=× COPHP − 1)= 1.345 ≈ 34.5% increase
application and installation leads to optimal results. HPWHs
H b (Tb − Tc ) (120 − 62)
selected and installed in ways that maximize their COP
Where: have the potential to reshape the domestic water heating
Formula 5-1a effective
Formula
COPe = 5-1b COP of the heat pump system in this market while increasing the use of renewably generated
application electricity. They help building owners by lowering utility
COPHP = COP of the heat pump at the operating bills, while also benefiting utilities with decarbonization and
COP
COPeimposed
conditions COP
= (2 e×=by COP
(2the×HPtwo 1)HP − 1)water
− entering = (2streams
× 3 − 1) = 5 load management strategies.
COPe = (2 × COPHP − 1) = (2 × 3 − 1) = 5
37
APPENDIXHYDRONIC
CALEFFI A: CALEFFI HYDRONIC COMPONENTS
COMPONENTS
NA551 Discal NA551 Discal
5517 ASME / CRN ASME / CRN 5020 5023 501
Discal 551 Minical Valcal Maxcal
551 Discal 553 5350
rotating Discal
collar Compact AutoFill AutoFill 573
AutoFill
Combo
NA5453 DirtMag NA5465M DirtMag NA5465M DirtMag NA546 DiscalDirt NA546M DiscalDirtMag
rotating Collar ASME / CRN ASME / CRN ASME / CRN ASME / CRN Z2 Z-one Z3 Z-one 6762 TwistTop
2-way 3-way Zone Valve 574
AutoFill
Combo
221 220
Radiator Radiator 472 Thermostatic
Valve Valve Control Head 142
Flo-Set 130
NA546 NA546M 3 3 Flo-Set
DiscalDirt DiscalDirtMag 5461
ASME / CRN ASME / CRN DiscalDirtMag
546 5461
DiscalDirt DiscalDirtMag
132 132
127 FlowCal 127 FlowCal+ 121 FlowCal QuickSetter QuickSetter
NA548 Hydro Separator NA549 SEP4
ASME / CRN ASME / CRN
NA548 NA549
548 Hydro Separator SEP4
Hydro 5495 ASME / CRN ASME / CRN 668S1 TwistFlow Manifold Assembly 172 Manifold Mixing Station
Separator SEP4
5599 HydroLink
5599 HydroLink
38
APPENDIX B: CALEFFI PLUMBING COMPONENTS
CALEFFI PLUMBING COMPONENTS
5213
521 MixCal 520 AngleMix 521 MixCal 5212 Point-of-Use 5231 5231 6000 LegioMix 6000 LegioMix 6000 LegioMix
w/ Gauge w/ Gauge w/ Checks SinkMixer Mix Valve MixCal MixCal+
520 TankMixer Control
574 RPZ
130 142 NA5026 Backflow
Flo-Set Flo-Set PlumbVent Preventer
127 FlowCal 127 FlowCal+ 132 QuickSetter+
circulator w/
internal check
valve 4-way motorized
& isolation mixing valve
flanges
union
variable-speed
pressure-regulated
circulator pressure
gauge
condenser
spring-loaded
check valve TXV
panel radiator
w/ isolation valve
purging valve & TRV
diaphragm
expansion
tank
brazed-plate
heat exchanger
indirect water heater
39
520 SERIES TANKMIXER
TM
CODE
CONNECTION CONNECTION WITHOUT MIXED WITH MIXED
TO TANK TO SYSTEM OUTLET OUTLET
TEMPERATURE TEMPERATURE
GAUGE GAUGE
520500AX 520510AX
520506AX 520516AX
520509AX 520519AX
*Kit includes AngleMix mixing valve, cold water cross with check valve,
PRODUCT FEATURES
42º
37º
47º
42º
47 º 52º
57º
57º
62º
62º
0.5 GPM minimum flow for stable control for 67º
67º
72º
today’s high efficiency fixtures. 72º
35º
PERFORMANCE
MAX. OPERATING PRESSURE 150 psi (10 bar)
600060A
2½” 105 17 288 470 -- --
flanged
600080A
3” 120 22 329 537 -- --
Meets requirements of NSF/ANSI 372-2011
flanged
and complies with ASSE 1017, CSA
B125.3, UPC, IPC, Low Lead Laws and *To ensure stable operation and accurate temperature control. Minimum flow is 0 gpm when recirculation flow rate is ≥ the valve’s minimum flow rating.
listed by ICC-ES for use in accordance with
the U.S. and Canadian plumbing codes. **Suggested maximum flow rate for optimum modulating control (at 7.5 psid pressure drop).
Meets requirements of CSA Z317.1 Special ***Maximum recommended differential pressure is 20 psid for smooth and quiet operation.
Requirements For Plumbing Installations In
Health Care Facilities. Inlet port check valves are available for field installation, code NA10366 (1”, 1¼”) and NA10367 (1½”, 2”).
PRODUCT FEATURES
All configuration, set points, temperatures, Calender based programs for scheduling
run status, alarms and datalogging functions thermal disinfection to control Legionella in
are available at the user interface without the recirculation circuit.
need for a laptop.
3
THURSDAY 10/12/2017
+
-
TM127• F TR120 • F
ADJUSTMENT
RUNNING
7
4 2
40
110 13060
20
90 150
F
700 170
80
50 190
°C
30 210
6
8
60
40 80
°C
20 100
0 120
THERMOSETTER
THERMAL BALANCING
SET IT AND FORGET IT
ThermoSetter™ thermal balancing valves maintain precise temperature in recirculation return piping using
state-of-the-art modulating control. Setup is simple and safe with an easy-to-read, lockable temperature
adjustment dial. Enjoy ease of maintenance with serviceable cartridge. Models with bypass cartridges
available for systems that provide thermal disinfection to control Legionella bacteria. Factory assemblies
with isolation and check valves are available. Approvals include compliance with the U.S. and Canadian
plumbing codes. CALEFFI GUARANTEED.